aldes L225 Smoke And Heat Exhaust System

Product Information: The product is a smoke and heat exhaust unit designed for non-residential buildings (such as public buildings, high-rises, commercial & industrial plants) and multi-family housing. It is available in 9 different sizes ranging from 225 to 560, delivering an airflow from 1000 to 40,000 m3/h. The unit has a galvanized steel casing and features a forward with an aluminum hub and backward curve impeller. It is equipped with a belt & pulley drive and a motor with IP 55 class F on a mount that allows easy adjustment of the belt tension. The motor can be single-speed or two-speed.

The product complies with the EU standard EN 12101-3 and has a fire resistance class of F400 with a fire resistance time of 120 minutes.

Product Usage Instructions

  1. Before servicing the fan unit, always disconnect the power and ensure that it cannot be turned on accidentally during the intervention.
  2. Do not perform any servicing until the fan is fully stopped.
  3. Follow the installation and maintenance tutorials available on Aldes.com for proper installation and maintenance of the product.
  4. Refer to the sizing chart to select the appropriate size (225, 250, 280, 315, 355, 400, 450, 500, or 560) based on the required airflow.
  5. Ensure that the unit is installed with the correct orientation for horizontal or vertical discharge as indicated in the outlet flange section.
  6. If using a backdraft damper, install it according to the provided instructions to prevent reverse airflow.
  7. For horizontal air intake, refer to the aspiration horizontale section for the recommended dimensions.
  8. For any servicing or maintenance, always refer to the installation and maintenance tutorials and follow the recommended procedures.

GENERAL INFORMATION

Related reference documents

Documents Aldes.com
Guide de démarrage rapide / Quick Start Guide
Documentation commerciale / Sales brochure
Documentation technique / Technical documentation
PV F400 120° Certificat CE, DOP
 Installation & maintenance tutorials

WEEE recycling compliant:
Smoke and heat exhaust for non-residential buildings (public buildings, high- rises, commercial & industrial plants, etc.) and multi-family housing (mainly type 3B and type 4 dwellings).

Description

  • Smoke and heat exhaust fan unit CE-certified as per the European Construction Products Directive 305/2011/EU and tested as per standard EN 12101-3 – Fire resistance class: F400 – 120 min.
  • 9 sizes of unit: 225, 250, 280, 315, 355, 400, 450, 500, 560 delivering an airflow from 1000 to 40,000 m3/h.
  • Galvanised steel casing.
  • Forward with aluminium hub and backward curve impeller.
  • Belt & pulley drive.
  • IP 55 class F motor on a mount designed to allow easy adjustment of the belt tension.
  • Single-speed or two-speed motor (Dahlander coupling or independent winding coupling).

Exploded view

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(2\)

  1. Casing
  2. Engine
  3. Proximity switch
  4. Housing

Dimensions

Horizontal discharge

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(3\)

Vertical discharge

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(4\)

 |  | **Horizontal discharge| ****Vertical discharge| ****Outlet flange
---|---|---|---|---
A| B| C| D| E| F| GxG| H| I| J| M| N| O| A.R| B.R
L225| 1047| 712| 757| 619| 214| 153| 550| 290| 242| 474| –| –| –| 350| 43
–| –| –| 288| 288| 141| –| –
L250| 1152| 792| 791| 619| 319| 145| 600| 324| 269| 481| –| –| –| 400| 43
–| –| –| 322| 322| 160| –| –
L280| 1257| 872| 871| 619| 424| 135| 700| 363| 302| 528| –| –| –| 450| 43
–| –| –| 361| 361| 170| –| –
L315| 1362| 972| 971| 794| 325| 135| 800| 406| 339| 591| –| –| –| 500| 43
–| –| –| 404| 404| 172| –| –
L355| 1467| 1092| 1011| 794| 430| 155| 800| 455| 382| 588| –| –| –| 550| 43
–| –| –| 453| 453| 163| –| –
L400| 1608| 1213| 1141| 954| 411| 145| 950| 509| 431| 669| –| –| –| 600| 43
–| –| –| 507| 507| 180| –| –
L450| 1758| 1373| 1211| 954| 561| 155| 1000| 571| 485| 685| –| –| –| 650| 43
–| –| –| 569| 569| 200| –| –
L500| 1918| 1503| 1281| 1034| 641| 140| 1100| 640| 538| 702| –| –| –| 700| 43
–| –|  | 638| 638| 227| –| –
L560**| 2093| 1683| 1381| 1114| 736| 140| 1200| 717| 603| 737| –| –| –| 800| 43
–| –| –| 715| 715| 248| –| –

GENERAL DESCRIPTION

Unloading

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(5\)

Optional list

  • Discharge duct position (horizontal or vertical),
  • Casing fitted with thermo-acoustic insulation.
  • Connected pressure switch (two switches are required for 2-speed smoke extraction).
  • Rain hood / anti-volatile mesh (supplied with unit but not fitted).
  • “All-in-one“: hard-wired safety box (this option includes the switch and connected pressure switches).
  • Adjustable drive pulley.
  • ProtectONE® Adapt (airflow adjustment damper) / connection flange / rain hood.

List of tools, equipment and consumables

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(6\)

Unpacking

Open the casing, read the installation instructions

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(7\)

Accessories

  • Axone (assembly) relay box if option «all in one»

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(8\)

Axone assembly Assembly
Taille / Size (mm) A.M (mm)
T0 335
T1 435
T2 540

Outlet flange


Rejet vertical / Horizontal discharge
 | A.R| B.R| V
L225 RV| 350| 43| 114
L280 RV| 400| 43| 125
L400 RV| 450| 43| 130
L450 RV| 500| 43| 128
L500 RV| 550| 43| 119
L560 RV| 600| 43| 138
L450 RV| 650| 43| 163
L500 RV| 700| 43| 200
L560 RV| 800| 43| 209

Rain screen


Rejet horizontal / Horizontal discharge
 | A.G| B.G| C.G
L225 RH| 374| 322| 152
L250 RH| 408| 349| 174
L280 RH| 447| 382| 200
L315 RH| 490| 419| 205
L355 RH| 539| 462| 233
L400 RH| 593| 511| 263
L450 RH| 655| 565| 291
L500 RH| 724| 618| 318
L560 RH| 801| 683| 366

Backdraft damper


Rejet vertical / Vertical discharge
 | A.C| B.C| T
L225 RV| 305| 50| 138
L250 RV| 340| 50| 157
L280 RV| 380| 50| 167
L315 RV| 420| 50| 169
L355 RV| 470| 50| 160
L400 RV| 525| 50| 177
L450 RV| 585| 50| 196
L500 RV| 655| 50| 223
L560 RV| 730| 50| 244

Square-round adapter


Aspiration horizontale/ Horizontal air intake
 | T.C| Ø
L225| 550| 400
L250| 600| 400
L280| 700| 500
L315| 800| 560
L355| 800| 630
L400| 950| 710
L450| 1000| 800
L500| 1100| 800
L560| 1200| 800

RECOMMENDATIONS PRIOR TO ASSEMBLY

Safety instructions

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(14\)

RECOMMANDATIONS

ATTENTION: check the direction of rotation of the turbine If it is rotating in the wrong direction (3-phase power supply), inverse the two power phases on the motor terminal unit to ensure it rotates in the correct direction.

Precautions

IMPORTANT: disconnect the power before servicing a fan unit (using the proximity switch) and ensure that it cannot be turned on accidentally during the intervention. Do not perform any servicing until the fan is fully stopped. All work on electrical equipment must be done by qualified personnel.

  • The electrical connection must be made according to industry best practices and in accordance with standards NF C 15-100 and NF S 61.932 “Installation rules.” The power cable must be dimensioned according to principle 471-1-2 of standard NF C 15-100: “the cross-section of channel conductors is determined by an admissible current equal to 1.5 times the rated motor current.”
  • The “FITTED SWITCH» and «ALL-IN-ONE» options enable customers to receive the CYCLONE F400 smoke and heat exhaust unit ready for use. Simply connect the power supply cable(s) from the LV distribution panel to the switch or the safety box.

IMPORTANT: remember to connect the Earth connection to the circuit bar at the location indicated by the symbol .

Pulley alignment
If you need to adjust a variable pulley, change a pulley or change a motor, check that the pulleys are correctly aligned and that the belt tension is correct before starting the unit.

ASSEMBLY

Horizontal installation

We recommend that you use anti-vibration mountings.

  • We strongly recommend that you connect the unit to the air ducts using flexible sleeves to avoid the transmission of vibrations.
  • Leave a gap (L) of at least 700 mm on the transmission side for technical work.
  • Avoid blocking the vents on either side of the unit.
Wiring

PROXIMITY SWITCH WIRING (Except All-In-One option)

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(18\)

ALL-IN-ONE OPTION: RELAY BOX WIRING
Voir notice d’installation Axone • See Axone installation instruction

Electrical connections

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(19\)

Uniquement 1V 4,7A et 16,7A / Only 1V 4.7A and 16.7A

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(20\)

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(21\)

ACTIVATION

Adjusting the ProtectONE® Adapt airflow adjustment damper

Remove the screw. Lower the arm to reduce the airflow.

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(22\)

Airflow adjusting with the variable pulley

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(24\)

The pulley is delivered at the maximum diameter. Unscrew the hexagonnal screws on each flanges. Spread the flanges (by 1/4 turn rotation). Screw in the hexagonnal screws, apply a threadlock to ensure proper tightening of the screws.

  • Release the lock nut
  • Belt tension

aldes-L225-Smoke-And-Heat-Exhaust-System-FIG- \(25\)

  • Using a 19 wrench (under the proposed ProtectONE® F400 model) move the motor along his rail.
  • The length of the belt between the 2 orange lines must be equal at the value indicated on the belt.

Tests and trials

Symptom 1 Symptom 2 Verifications Action
The fan unit will not start   – Check all wiring

– Check the motor: 400V AC direct supply

| Replace the faulty part
The fan unit starts and then stops|  | – Check all wiring.|

The fan unit does not work at the specified operating set point

|

Too weak

| – Check that the impeller is not rubbing against the casing

– Check that the ProtectONE® adapter is not set to a minimum

– Check the motor: 400V AC direct supply

|

Replace the faulty part

Too strong

| – Actuate the damper (if ProtectONE® Adapt option included).

– Change the impeller gear (if variable pulley)

| Contact After- sales
The fan rotates in the wrong direction|  |

– Check the wiring in the motor terminal unit

| Swap 2 phases on the power supply cable

MAINTENANCE

IMPORTANT: Maintenance must be carried out by qualified personnel. After commissioning the ProtectONE® F400, it is important to regularly check that it is operating correctly.
Since April 1997, Appendix A of the new standard NF 61.933 requires that smoke and heat exhaust fans be checked via their safety boxes every three months.
The motors installed do not require any specific maintenance. They are equipped with sealed bearings that are lubricated for their whole service life.

OTHER COUNTRIES
Need after sales technical support?
Visit our website for more information: https://www.aldes- international.com/fr/contact/

www.aldes.com
20, boulevard Irène Joliot-Curie 69694 Vénissieux Cedex – France

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals