aldes 16 330 MR Modulo User Guide

June 13, 2024
aldes

aldes 16 330 MR Modulo User Guide
aldes 16 330 MR Modulo

SETTING THE AIRFLOW

Twist the rotating adjustment ring until the desired airflow is reached. Reference the correlation table at right and printed on the device. No tools required

SETTING THE AIRFLOW
SETTING THE AIRFLOW

CORRELA TION TABLE†

11016307 Ø 3″ (80 mm)

| |
---|---|---
m 3 /h| CFM| m 3 /h| CFM
K| 20| 12| –| –
J| 25| 15| –| –
H| 30| 18| –| –
G| 35| 21| 45| 26
F| 40| 24| 50| 29
B| 45| 26| 60| 35

P/N: 11016308 Ø 4″ (100 mm)

| |
---|---|---
m3/h| CFM| m3/h| CFM
L| 15| 9| –| –
J| 20| 12| –| –
H| 25| 15| –| –
F| 30| 18| –| –
E| 35| 21| 70| 41
D| 40| 24| 75| 44
C| 45| 26| 80| 47
A| 55| 32| 90| 53

P/N: 11016309 Ø 5″ (125 mm) 10-50 CFM (15-90 m3 /h)

| |
---|---|---
m3/h| CFM| m3/h| CFM
L| 15| 9| –| –
H| 25| 15| 60| 35
F| 30| 18| 65| 38
E| | | 70| 41
D| 45| 26| 75| 44
B| 50| 29| 80| 47
Q| –| –| 85| 50

P/N: 11016310 Ø 5″ (125 mm) 60-110 CFM (100-190 m3 /h)

| m3/h| CFM
---|---|---
K| 100| 59
J| 110| 65
I| 120| 71
H| 130| 76
G| 140| 82
E| 150| 88
C| 160| 94
ct| 190| 112

† Certain letters correspond to two setpoints: one with the clip, and one without the clip.

P/N: 11016311 Ø 6″ (150 mm)

| m 3 /h| CFM
---|---|---
R| 100| 60
P| 110| 65
O| 120| 70
M| 130| 75
L| 140| 80
K| 150| 90
J| 160| 95
H| 170| 100
G| 180| 105
F| 190| 110
E| 200| 120
D| 210| 125
A| 240| 140

P/N: 11016313 Ø 8″ (200 mm)

**** m3 /h CFM
U 225 132
S 250 147
Q 275 160
N 300 177
M 325 191
J 350 206
D 400 235

P/N: 11016314 Ø 10″ (250 mm)

| m 3 /h| CFM
---|---|---
U| 300| 175
R| 355| 205
O| 400| 235
L| 450| 265
I| 500| 295
G| 550| 325
A| 650| 385

INSTALLATION

  • The MR Modulo will push-fit into circular ducts in close proximity to a take-off or terminal.

  • Orient the MR Modulo according to the airflow direction indicated on the device.

  • Horizontal or vertical mounting is acceptable.

  • To avoid acoustic and aeraulic disturbance, provide the following distance between the device and the terminal (grille / diffuser / inlet):
    INSTALLATION

    • Exhaust Air: 1x the device diameter Ø
      INSTALLATION

    • Supply Air: 3x the device diameter Ø
      INSTALLATION

MAINTENANCE

  • MR Modulo performance is not altered by clogging, therefore it requires practically no special maintenance.
  • If the intended application includes air heavily loaded with grease or dust, a fitting with an access panel or door, such as that used for flame dampers, should be used.
  • Clean with soaped water. When cleaning, plug the hole on the plastic body, at the base of the bulb, to prevent any obstruction and any penetration of liquid or foreign body inside the bulb.
    MAINTENANCE
    Write the diameter and airflow setting on the provided sticker and place it directly onto the duct to show where the MR Modulo has been installed.

TYPICAL APPLICATIONS

  • Duct System
    TYPICAL APPLICATIONS

  • Exhaust/Return Air
    TYPICAL APPLICATIONS
    TYPICAL APPLICATIONS
    TYPICAL APPLICATIONS

  • Supply Air
    TYPICAL APPLICATIONS
    TYPICAL APPLICATIONS
    TYPICAL APPLICATIONS

For more information, contact your Aldes sales advisor, visit aldes-na.com, call 1.800.255.7749.

© 2020 Aldes North America. EN-Aldes-MRModuloIOM-Inst-Corp-012023. Aldes reserves the right to modify its products at any time to introduce new technologies.

Company Logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals