legrand LE13954AB Light Up Advanced Multisensor DALI Detector Installation Guide

May 15, 2024
Legrand

legrand LE13954AB Light Up Advanced Multisensor DALI Detector

legrand LE13954AB Light Up Advanced Multisensor DALI
Detector

Parts Description

Parts Description

  • Technical documentation available in your language => Scan the QR code

Legrand Close Up

QR Code

App Store Icon| Google Play Icon
---|---

Product Specification

| 110 – 230 V~
---|---
| 50 / 60 Hz
| 2 x 1.5 mm² ou/or 1 x 2.5 mm²


| +5°C / +30°C
| Thermal image
| 300 lux
| 15 mn
|

  • Mode Passage

Bluetooth| 5.0 compatible 4.2|

  • Reach: 10 m

Radio| 2.4 – 2.483 GHz
| Guaranteed
16 V
100 mA| Maximum 16 V
130 mA

  • Standby consumption:

| Charge/Load OFF 1.6 W| Charge/Load ON 2.3 W

  • Thermal image sensor

| Installation height → 2,5 à 4 m / 8.2 to 13.1 ft| Surface/ max. 8 m x 8 m

  • Daylight sensor

| 5 →| 1275 lux

  • Humidity sensor

| 20 % →| 80 %

  • Sound sensor

| 38 →| 120 dB spl

  • Temperature sensor

| +0°C / +50°C

  •  VOCT sensor

| 0 →10 000 ppb

  • IAQ level

| 1.0 →| 5.0

  • Estimated CO2 level

| 400 →| 5000 ppm

  • F (Frequency) : 2.4 to 2.483 GHz
  • P (Power) : <100 mW
  • LEGRAND declares that radio equipment of the type Cat. no. 0 485 72 complies with
    Directive 2014/53/EU. The full text of the EU declaration of conformity can be found at: www.legrandoc.com

Parts List

Parts List

  • 1 – Incandescent and halogen lamps
  • 2 – Halogen lamp with separate ferromagnetic or electronic transformer
  • 3 – Fluorescent tubes
  • 4 – Compact fluorescent lamp with integrated ballast
  • 5 – Compact fluorescent lamps with separate ferromagnetic or electronic transformer
  • 6 – LED lamp
  • 7 – Contactor

Parts Description

Parts Description

Installation Instruction

  • Installation and wiring must be carried out with the power off. Please follow the Safety Instructions carefully.
    Installation Instruction

Safety Precautions

Safety Precautions

Wiring

Wiring

  • (*) This product can be controlled by:

    • A wireless battery less control (ON/OFF without dimming)
      Or

    • A wired control (ON/OFF and dimming) And it can control (in wireless mode) a connected outlet.
      Wiring

D ****
≤ 100 m 0.5 mm²
≤ 150 m 0.75 mm²
≤ 300 m 1.5 mm²
  • The maximum distance from the control to the auxiliary input is 50 m.

  • To associate this product with a control point and/or outlet, please follow the procedures described in the Light Up Technical Guide.

  • Type of load “DIMMING”
    Wiring

  • The relay is dedicated to powering the ballast to reduce energy consumption, and there is a 5 minute delay before the ballasts switch off.
    Wiring

  • The maximum distance from the control to the auxiliary input is 50 m.

  • Type de charge “NON DIMMABLE”
    Wiring

  • Type of load “NO DIMMING”
    Wiring

  • The 0 485 72 detector is configured to control dimmable DALI ballasts; it is possible to link DALI actuators (ON/OFF) to it. To do this, use the “Legrand Close Up” application on your smartphone to change the type of load used, in this case “No Dimming”.

  • Auxiliary parallel input
    Wiring

  • Ne pas connecter les sorties DALI ensemble.

  • Do not connect 2 DALI outputs together.
    Wiring

  • The maximum distance from the control to the auxiliary inputs 50 m.

  • Master/Slave

  • The product is configured as Master by default.
    To change it to Slave, follow the description in the Light Up Technical Guide.
    Wiring

  • The slave extends the detection area. No load will be associated with it.

  • If used in “Master/Slave” mode, the push-button should only be connected to the “Master” detector.

Installation precautions

  • Maximum installation height 4 m. Make sure that the thermal imager’s field of vision is not obstructed by high objects or devices that could conceal one or more persons.
    Wiring

  • Avoid direct airflow over product vents. Place the detector at a distance of over 1.5m from a glass surface to avoid infra-red reflection.
    Installation Precautions

Detection zone

Detection zone

  • Up to 6 configurable Zones of Interest and/or Exclusion can be monitored.
    Detection zone
    Detection zone

First commissioning:

The product is operational after 5 minutes. The device self-calibrates in 20 minutes. To calibrate it immediately, start calibration from Close Up, making sure that no-one is in the area covered by the product.

First commissioning

  • In large areas that require the installation of several devices, it is recommended to install them in a row and facing in the same direction.
    First commissioning