legrand LE13954AB Light Up Advanced Multisensor DALI Detector Installation Guide
- May 15, 2024
- Legrand
Table of Contents
legrand LE13954AB Light Up Advanced Multisensor DALI Detector
Parts Description
Legrand Close Up
Product Specification
| 110 – 230 V~
---|---
| 50 / 60 Hz
| 2 x 1.5 mm² ou/or 1 x 2.5 mm²
| +5°C / +30°C
| Thermal image
| 300 lux
| 15 mn
|
- Mode Passage
Bluetooth| 5.0 compatible 4.2|
- Reach: 10 m
Radio| 2.4 – 2.483 GHz
| Guaranteed
16 V
100 mA| Maximum 16 V
130 mA
- Standby consumption:
| Charge/Load OFF 1.6 W| Charge/Load ON 2.3 W
- Thermal image sensor
| Installation height → 2,5 à 4 m / 8.2 to 13.1 ft| Surface/ max. 8 m x 8 m
- Daylight sensor
| 5 →| 1275 lux
- Humidity sensor
| 20 % →| 80 %
- Sound sensor
| 38 →| 120 dB spl
- Temperature sensor
| +0°C / +50°C
- VOCT sensor
| 0 →10 000 ppb
- IAQ level
| 1.0 →| 5.0
- Estimated CO2 level
| 400 →| 5000 ppm
- F (Frequency) : 2.4 to 2.483 GHz
- P (Power) : <100 mW
- LEGRAND declares that radio equipment of the type Cat. no. 0 485 72 complies with
Directive 2014/53/EU. The full text of the EU declaration of conformity can be found at: www.legrandoc.com
Parts List
- 1 – Incandescent and halogen lamps
- 2 – Halogen lamp with separate ferromagnetic or electronic transformer
- 3 – Fluorescent tubes
- 4 – Compact fluorescent lamp with integrated ballast
- 5 – Compact fluorescent lamps with separate ferromagnetic or electronic transformer
- 6 – LED lamp
- 7 – Contactor
Parts Description
Installation Instruction
- Installation and wiring must be carried out with the power off. Please follow the Safety Instructions carefully.
Safety Precautions
Wiring
-
(*) This product can be controlled by:
-
A wireless battery less control (ON/OFF without dimming)
Or -
A wired control (ON/OFF and dimming) And it can control (in wireless mode) a connected outlet.
-
D | **** |
---|---|
≤ 100 m | 0.5 mm² |
≤ 150 m | 0.75 mm² |
≤ 300 m | 1.5 mm² |
-
The maximum distance from the control to the auxiliary input is 50 m.
-
To associate this product with a control point and/or outlet, please follow the procedures described in the Light Up Technical Guide.
-
Type of load “DIMMING”
-
The relay is dedicated to powering the ballast to reduce energy consumption, and there is a 5 minute delay before the ballasts switch off.
-
The maximum distance from the control to the auxiliary input is 50 m.
-
Type de charge “NON DIMMABLE”
-
Type of load “NO DIMMING”
-
The 0 485 72 detector is configured to control dimmable DALI ballasts; it is possible to link DALI actuators (ON/OFF) to it. To do this, use the “Legrand Close Up” application on your smartphone to change the type of load used, in this case “No Dimming”.
-
Auxiliary parallel input
-
Ne pas connecter les sorties DALI ensemble.
-
Do not connect 2 DALI outputs together.
-
The maximum distance from the control to the auxiliary inputs 50 m.
-
Master/Slave
-
The product is configured as Master by default.
To change it to Slave, follow the description in the Light Up Technical Guide.
-
The slave extends the detection area. No load will be associated with it.
-
If used in “Master/Slave” mode, the push-button should only be connected to the “Master” detector.
Installation precautions
-
Maximum installation height 4 m. Make sure that the thermal imager’s field of vision is not obstructed by high objects or devices that could conceal one or more persons.
-
Avoid direct airflow over product vents. Place the detector at a distance of over 1.5m from a glass surface to avoid infra-red reflection.
Detection zone
- Up to 6 configurable Zones of Interest and/or Exclusion can be monitored.
First commissioning:
The product is operational after 5 minutes. The device self-calibrates in 20 minutes. To calibrate it immediately, start calibration from Close Up, making sure that no-one is in the area covered by the product.
- In large areas that require the installation of several devices, it is recommended to install them in a row and facing in the same direction.
References