MITSUBISHI ELECTRIC TPLA0A0361EA70B Ceiling Cassette Instruction Manual
- May 15, 2024
- Mitsubishi Electric
Table of Contents
MITSUBISHI ELECTRIC TPLA0A0361EA70B Ceiling Cassette
Product Usage Instructions
Installation
- Ensure proper electrical supply and wiring before installation.
- Mount the indoor unit in the ceiling cassette according to the provided dimensions.
- Connect the refrigerant piping following the specified pipe sizes and guidelines.
Operation
- Power on the unit using the remote controller or control interface.
- Select the desired cooling or heating mode and set the temperature accordingly.
- Adjust fan speed and airflow direction for optimal comfort.
Maintenance
- Regularly clean the air filters to ensure efficient operation.
- Check for any leaks in the refrigerant piping and repair if necessary.
- Schedule annual professional maintenance to keep the unit in top condition.
FAQ
- Q: Can I use a wireless remote controller with this indoor unit?
- A: No, the indoor unit is compatible only with the wired remote controller provided (PAC-SF40RM-E).
- Q: What is the recommended ceiling height for installation?
- A: The ceiling height should be at least 70-7/8 inches (1800mm) or more from the floor for proper installation.
- Q: How often should I clean the air filters?
- A: It is recommended to clean the air filters every 2-4 weeks depending on usage to maintain optimal performance.
GENERAL FEATURES
- Space-efficient ductless installation
- Equipped with 3D i-see Sensor® for enhanced comfort and energy efficiency
- Airflow settings for high and low-ceiling applications
- Individual vane settings for direct/indirect airflow control or variable airflow patterns
- Knockouts for outside-air intake and branch-duct run
- Filter indicator signal
- Easy-to-clean, washable filter (optional high-efficiency filter available – requires multi-function casement)
- Built-in condensate lift mechanism
- Ideal for retail shops, classrooms, office spaces, conference centres, building lobbies, and more
- Multiple control options available:
- Kumo cloud® smart device app for remote access
- Third-party interface options
- Wired or wireless controllers
Specifications
Specifications | System |
---|---|
Unit Type | TPLA0A0361EA70B |
Cooling Capacity1, 3 | BTU/H |
Heating Capacity2, 3 | BTU/H |
Electrical
| Voltage, Phase, Frequency| 208/230, 1, 60
Guaranteed Voltage Range| V AC| 198- 253V
Voltage: Indoor – Outdoor, S1-S2| V AC| 208/230
Voltage: Indoor – Outdoor, S2-S3| V DC| 24
Short-circuit Current Rating [SCCR]| kA| 5
Indoor Unit
| MCA| A| 2.0
Fan Motor Full Load Amperage| A| 0.95
Airflow Rate at Cooling, Dry| CFM| 670–850–1,020–1,200
Airflow Rate at Cooling, Wet| CFM| 630–810–980–1,160
Airflow Rate at Heating, Dry| CFM| 670–850–1,020–1,200
Sound Pressure Level [Cooling]| dB[A]| 32–37–41–44
Sound Pressure Level [Heating]| dB[A]| 32–37–41–44
Drain Pipe Size| In. [mm]| 1-1/4 [32]
Condensate Lift Mechanism, Maximum Distance| In. [mm]| 33-7/16 [849]
Coating on Heat Exchanger| —
External Finish Color| White Munsell 6.4Y 8.9/0.4
Unit Dimensions| W x D x H: In. [mm]| 33-1/16 // 37-13/32 x 33-1/16 //
37-13/32 x 11-3/4 // 1-9/16 [840 // 950 x 840 //
950 x 298 // 40]
Package Dimensions| W x D x H: In. [mm]| 35-9/16 // 39-6/16 x 34-5/16 // 38-3/16 x 16-9/16 // 4-12/16 [903 // 1,000 x 871
// 970 x 421 // 121]
Unit Weight| Lbs. [kg]| 56 // 11 [25 // 5]
Package Weight| Lbs. [kg]| 77 [35]
Refrigerant| Type| R410A
Piping
| Gas Pipe Size O.D. [Flared]| In.[mm]| 5/8 [15.88]
Liquid Pipe Size O.D. [Flared]| In.[mm]| 3/8 [9.52]
NOTES
Conditions 1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
3Capacity varies based on the number of indoor units operating and the model
of the Multi-zone Outdoor Unit. For reference to connected capacity charts,
please refer Multi-zone Outdoor Unit Operational Performance.
INDOOR UNIT ACCESSORIES
INDOOR UNIT ACCESSORIES: TPLA0A0361EA70B
Control Interface
| 3-Pin Connector| □ PAC-715AD
---|---|---
Airline ZBS Wired Blueface Principal Controller White| □ AZZBSBLUEFACECB
Airline ZBS Wired Lite Controller White| □ AZZBSLITECB
Airline ZBS Wireless Lite Controller White| □ AZZBSLITERB
Airline ZBS Wireless Think Controller White| □ AZZBSTHINKRB
BACnet® and Modbus® Interface| □ PAC-UKPRC001-CN-1
CN24 Relay Kit| □ CN24RELAY-KIT-CM3
IT Extender| □ PAC-WHS01IE-E
Kumo station® for kumo cloud®| □ TAC-WHS01HC-E
Remote Operation Adapter‡| □ PAC-SF40RM-E
Thermostat Interface| □ PAC-US445CN-1
USNAP Adapter| □ PAC-WHS01UP-E
Wireless Interface for Kumo cloud®| □ PAC-USWHS002-WF-2
Remote Sensor
| Flush Mount Remote Temperature Sensor| □ PAC-USSEN002-FM-1
Flush Mount Temperature Sensor| □ PAC-USSEN001-FM-1
Remote Temperature Sensor| □ PAC-SE41TS-E
Wireless temperature and humidity sensor for Kumo cloud®| □ PAC-USWHS003-TH-1
Wired Remote Controller
| Deluxe Wired MA Remote Controller†| □ TAR-40MAAU
Simple MA Remote Controller†| □ TAC-YT53CRAU-J
Touch MA Controller†| □ TAR-CT01MAU-SB
Wireless Remote Controller
| Kumo touch™ RedLINK™ Wireless Controller| □ MHK2
Lockdown bracket for remote controller| □ RCMKP1CB
Wireless MA Receiver| □ PAR-SR32MA-E
Wireless MA Remote Controller| □ TAR-FL32MA-E
Wireless Remote Contoller| □ PAR-SL101A-E
Wireless Signal Receiver Panel| □ PAR-SR4LU-E
Casement| Multi-function Casement| □ PAC-SJ41TM-E
Condensate
| Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor
(208/230V) [recommended]| □ X87-721
Blue Diamond (MegaBlue Advanced) Condensate Pump w/ Reservoir & Sensor| □
X87-835
Blue Diamond Sensor Extension Cable — 15 Ft.| □ C13-103
Refco Condensate Pump (100-240 VAC) up to 120,000 BTU/H| □ COMBI
Disconnect Switch
| (30A/600V/UL) [fits 2” X 4” utility box] – Black| □ TAZ-MS303
(30A/600V/UL) [fits 2” X 4” utility box] – White| □ TAZ-MS303W
Filter| High Efficiency Filter Element**| □ PAC-SH59KF-E
i-see Sensor® Panel| Grille with 3D i-see Sensor® (required)| □ TLP-41EAEU
Lineset
| 10’ x 3/8” x 10’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-10
100’ x 3/8” x 100’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-100
15’ x 3/8” x 15’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-15
30’ x 3/8” x 30’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-30
50’ x 3/8” x 50’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-50
65’ x 3/8” x 65’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-65
Shutter Plate| Shutter Plate| □ PAC-SJ37SP-E
Space Panel| Space Panel| □ PAC-SJ38AS-E
NOTES
‡PAC-SF40RM-E (Unable to use with wireless remote controller)
DIMENSIONS
INDOOR UNIT DIMENSIONS: TPLA0A0361EA70B
NOTE
-
CHOOSE THE GRILLE AMONG THE DEDICATED GRILLES.
-
REINFORCE THE SUSPENSION BOLT FOR EARTHQUAKE RESISTANCE AS NEEDED.
-
FOR THE SUSPENSION BOLT, USE M10 OR W3/8. (PROCURED AT THE LOCAL SITE.)
-
FOR DRAIN PIPE, USE VP-25(O.D. n1-1/4″(( 32) PVC TUBE). DRAIN PUMP INCLUSION.
RAISE IS-MAX 33-7/16″(850mm) FROM THE CEILING. -
ELECTRICAL BOX MAY BE REMOVED FOR THE SERVICE PURPOSE. MAKE SURE TO SLACK THE ELECTRICAL WIRE A LITTLE BIT FOR THE CONTROL/POWER WIRE CONNECTION.
-
THE HEIGHT OF THE INDOOR UNIT CAN BE ADJUSTED WITH THE GRILLE ATTACHED.
-
REQUIRES “E” OR MORE SPACE BETWEEN THE TRANSOM AND CEILING FOR THE INSTALLATION.
-
WHEN INSTALLING THE BRANCH DUCTS, BE SURE TO INSULATE ADEQUATELY. OTHERWISE CONDENSATION AND DRIPPING MAY OCCUR. (IT BECOMES THE CAUSE OF DROPLET OR DROPLET DRIPPING.)
-
AS FOR NECESSARY INSTALLATION/SERVICE SPACE, PLEASE REFER TO THE RIGHT AT FIGURE.
-
FOR THE INSTALLATION OF THE OPTIONAL HIGH-EFFICIENCY FILTER OR MULTI-FUNCTIONAL CASEMENT, REFER TO SPECIAL DRAWING.
© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>