RMF-CMX100-V1 Commax Interface Instruction Manual
- May 15, 2024
- COMMAX
Table of Contents
RMF-CMX100-V1 Commax Interface
Product Information
Specifications :
- Model: RMF-CMX100-V1
- Interface: Commax
- Firmware Version: 1.0.0
Product Usage Instructions
Safety Precautions
- Attention: Incorrect handling can result in electrical injury, device malfunction, and damage. Thoroughly read the following safety precautions before each use of this product.
- Warning: Power supply to the indoor unit must be removed when configuring DIP switch settings and when connecting/disconnecting CN105 connector to the indoor unit board.
Setting Up the Device
- Prior to connecting the RMF-CMX100-V1 to other devices, set the DIP switch positions by removing the four screws on the back of RMF-CMX100-V1.
- Address setting is required for communication with the Commax controller. Refer to Table 4.2 for DIP switch positions SW1-1 to 4 for device address setting of the interface board.
Wiring Instructions
Note: Do not proceed to wiring section until DIP switch settings
have been set and power to the indoor unit is removed.
- Step 1: Connect the interface board (B) to the Commax controller (C) using an RS-485 wire.
FAQ
Q: What should I do if I encounter difficulties during installation?
A: If you encounter difficulties during installation, please refer to the
troubleshooting section of the manual or contact our customer support for
assistance.
RMF-CMX100-V1 Commax Interface
INSTALLATION / INSTRUCTION MANUAL
Please read prior to installing/operating device. Keep this manual for future
reference.
Supplied Parts
- RMF-CMX100-V1 (Quantity – 1)
- Installation Manual (Quantity – 1)
Amendment Register
Document version | Firmware Version | Date | Author | Notes |
---|---|---|---|---|
1.0.0 | 1.0.0 | 1/9/2020 | FM | Initial version of firmware V1.0.0 |
1.0.1 | 1.0.0 | 10/9/2022 | MD | -Added compatibility and mode setting charts for |
SEZ-KD & SUZ-KA
1.0.2| 2.3| 8/23/2023| FM| Revised instance number order; changed HEX address
setting
Compatibility
Firmware Version| Indoor Unit (Model Number)| Outdoor Unit (Model Number)|
Notes
---|---|---|---
1.0.0|
- PVFY-P-NAMU-E (& later versions)
- PEFY-P-NMAU-E (& later versions)
| Not Applicable|
SEZ-KD(NA4)| SUZ-KA(NA/NAHZ)|
2.3| Unchanged| Unchanged|
Safety Precautions
ATTENTION – INCORRECT HANDLING CAN RESULT IN ELECTRICAL INJURY, DEVICE MALFUNCTION AND DAMAGE
THOROUGHLY READ THE FOLLOWING SAFETY PRECAUTIONS BEFORE EACH USE OF THIS PRODUCT (THE “DEVICE”).
- Do not expose the device to, or immerse the device in, water. Doing so could lead to electrical shock to a person, device malfunction or device damage.
- Do not install the device in a bathroom, kitchen, or any room where high humidity or steam could form. Condensation could develop on or around the device and cause electrical shock to a person, device malfunction and device damage.
- Do not install the device in a location where a gas leak could occur.
- Do not expose the device to heat or radiation, including direct sunlight, or install the device in a location where the temperature could be greater than 40°C (104°F) or less than 0°C (32°F). This could result in device deformation or device malfunction.
- Always ensure the device is installed in an area without exposure to high frequency noise.
- Power generators, inverters, and high-frequency or radio communication equipment may interfere with the operation of this device.
- All electrical work should be performed by a qualified technician and in accordance with applicable laws and instructions outlined in this manual.
- Use standard wiring with the proper current capacity to avoid current leak, excessive heat, and fire.
- Use only specified cables and wiring; securely connect each so that the terminals do not bear any weight.
- Include slack in the power supply wiring. Tension in the wiring may cause it to excessively heat up and break, which could result in a fire.
- Improperly connected or short-circuited cables or wiring may produce heat and cause device malfunction, device damage, and fire.
- Capacity shortage to the power supply circuit or improper installation may result in electrical shock or fire.
- Do not modify or alter this device or cable in any manner whatsoever.
Warning:
- To avoid danger or suffocation, safely dispose of the packing materials and keep away from children.
- Packing materials, such as nails and other metal or wooden parts, may cause injuries.
Configuration Instructions
- Note: Power supply to indoor unit must be removed when configuring DIP switch settings and when connecting/disconnecting CN105 connector to the indoor unit board.
- Prior to connecting the RMF-CMX100-V1 to the other devices, set the DIP switch positions by removing the four screws on the back of RMF-CMX100-V1.
Address setting is required for communication with the Commax controller. Please reference table 4.2 below for DIP switch positions SW1-1 to 4 for device address setting of the interface board.
Table 4.1
Wiring Instructions
Note: Do not proceed to wiring section of this manual until DIP switch settings have been set and power to indoor unit is removed.
- Step 1: Connect the interface board (B) to the Commax controller (C) using a RS-485 wire <200ft.
- Step 2: Connect the interface board (A) to the indoor unit control board (D) using the 4-foot CN105 cable.
Legend
Symbol| Connector / Terminal| Location of Connector
A| CN105-1| RMF-CMX100-V1 (Interface board)
B| RS-485| RMF-CMX100-V1 (Interface board)
C| LAN| Commax Controller
D| CN105| Mitsubishi Electric Indoor Unit Control Board
- Step 3: Supply power to the indoor unit and confirm green LED is flashing at the rate of approximately 0.5Hz. If the LED does not flash, power down the indoor unit, disconnect interface board from the system and repeat steps 1 and 2. If LED does not light, replace the Interface board.
Mode Settings Chart
- Note: MA/PAR Mitsubishi Controller must be connected to the indoor unit for accessing the settings. Function settings must be properly configured prior to system start-up.
- For more information on mode settings procedures visit www.mitsubishitechinfo.ca
SEZ UNIT FUNCTION SETTINGS
Definition| Mode| Setting #| Setting Description
Power Failure Auto Restart| 1| 1| Disabled
| 2| Enabled
Static Settings| 08 & 10| | See Static Pressure Settings Below
Frost Prevention Temp| 15| 1| 2°C (36°F)
2| 3°C (37°F)
Heater Control| 23| 1| Set Temp-2.5°C ON
2| Set Temp-2.5°C ON & Enable Heater During Defrost/Error
Heating Height Offset 4°C| 24| 1| Available (ON) 4°C (7.2°F) UP
2| Not Available (OFF)
Fan Speed Thermal-Off (Heating)| 25| 1| Extra Low
2| Stop
3| RC Setting
Fan Speed Thermal-Off (Cooling)| 27| 1| RC Setting
2| Stop
Abnormal Pipe Temperature Detection (P8)| 28| 1*| Available (ON)
2| Not Available (OFF)
*Factory Default Setting
External Static Pressure Setting for SEZ
External Static Pressure| Setting No. of Mode 08| Setting No. of
Mode 10
---|---|---
0.02 in. WG [5Pa]| 1| 2
0.06 in. WG [15Pa]| 1| 1
0.14 in. WG [35Pa]| 2| 1
0.20 in. WG [50Pa]| 3| 1
RMF-CMX100-V1_1.0.2
© Mitsubishi Electric Sales Canada Inc. All rights reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>