Model F3SG-SR-K
Safety Light Curtain
Instruction Sheet
Thank you for purchasing the F3SG-SR Series Safety Light Curtain (hereinafter
referred to as the “F3SG-SR”). Be sure to have F3SG-SR be handled by a
“Responsible Person” who is well aware of and familiar with the machine to be
installed. The term Responsible Person” used in this document means the
person qualified, authorized and responsible to secure “safety” in each
process of the design, installation, operation, maintenance services and
disposition of the machine. It is assumed that F3SG-SR will be used properly
according to the installation environment, performance and function of the
machine.
Responsible Person should conduct risk assessment on the machine and determine
the suitability of this product before installation. Read this document and
reference manuals for F3SG-SR thoroughly to understand and make good use of
the descriptions before installing and operating the product. Keep this
document at the place where the operator can refer to whenever necessary.
This device is electro-sensitive protective equipment for the purpose of
protecting the human body.
Instructions in the EU languages and a signed EU Declaration of Conformity are
available on our website at
www.industrial.omron.eu/safety.
Declaration of Conformity
OMRON declares that the F3SG-SR is in conformity with the requirements of
following
EU Directives and UK Legislations:
EU: Machinery Directive 2006/42/EC, EMC Directive 2014/30/EU, RoHS Directive
2011/65/EU,
UK: 2008 No 1597 Machinery (Safety) , 2016 No 1091 EMC, 2012 No 3032 RoHS
Safety Standards
- The F3SG-SR is designed and manufactured according to the following standards.
EN61496-1 (Type 4 and Type 2 ESPE), EN 61496-2 (Type 4 and Type 2 AOPD),
EN61508-1 through -4 (SIL 3 for Type 4 and SIL 1 for Type 2),
EN ISO 13849-1:2015 (PL e, Category 4 for Type 4 and PL c, Category 2 for Type
- Dispose in accordance with applicable regulations.
Safety Precautions
-
Indications and Meanings for Safe Use
The precautions listed in this document indicated by alert symbols and statements must be followed for the safe use of the F3SG-SR. Failure to follow all precautions and alerts may result in an unsafe use or operation.Thoroughly read this document before using the F3SG-SR. The following word and symbols are used in this document. -
Alert Statements
DANGER
Make sure that the machine can be controlled correctly and as intended. Also
make sure that the machine can be stopped immediately at any time of the
operation cycle without danger to machine operators when the machine behavior
does not meet safety related requirements. Otherwise, continued use of the
machine may result in serious injury or death.
Users
WARNING
The F3SG-SR must be installed, configured, and incorporated into a machine
control system by a sufficiently trained and qualified person.
An unqualified person may not be able to perform these operations properly,
which may cause a person to go undetected, resulting in serious injury.
Machines
WARNING
Do not use this sensor for machines that cannot be stopped quickly by
electrical control. For example, do not use it for a pressing machine that
uses full-rotation clutch. Otherwise, the machine may not stopbefore a person
reaches the hazardous part, resulting in serious injury.
To use the F3SG-SR in PSDI mode (initiation of cyclic operation by a presence
sensing device), you must configure an appropriate circuit between the F3SG-SR
and the machine. For details about PSDI, refer to OSHA 1910.217, IEC 61496-1,
and other relevant standards and regulations.
Installation
WARNING
Make sure Responsible Person tests the operation of the F3SG-SR and F39-SGIT-
IL3 after installation to verify that the F3SG-SR and F39-SGIT-IL3 operate as
intended.
Make sure to stop the machine until the test is complete. Unintended
installation, wiring or function settings may cause a person to go undetected,
resulting in serious injury.
Make sure to install the F3SG-SR at the safety distance from the hazardous
part of the machine. Otherwise, the machine may not stop before a person
reaches the hazardous part, resulting in serious injury.
Install a protective structure so that the hazardous part of a machine can
only be reached by passing through the sensor’s detection zone. If access to
the hazardous part by reaching over the detection zone of a vertically mounted
F3SG-SR cannot be excluded, the height of the detection zone and the safety
distance shall be determined in consideration of such a risk. Install the
sensors so that part of the person is always present in the detection zone
when working in a machine’s hazardous zones. If a person is able to step into
the hazardous zone of a machine and remain behind the F3SG-SR’s detection
zone, configure the system with Restart Interlock function. Failure to do so
may result in serious injury due to unexpected startup.
Install the reset switch in a location that provides a clear view of the
entire hazardous zone and where it cannot be activated from within the
hazardous zone.
Install the pre-reset switch always in the hazardous zone and where it cannot
be activated from outside the hazardous zone.
The F3SG-SR cannot protect a person from an object flying from the hazardous
zone. Install protective cover(s) or fence(s).
Install a protective structure to cover the whole blanked zone in order to
prevent personnel approach to hazardous part of the machine through the
blanked zone.
Detection capability gets larger when Fixed Blanking, Floating Blanking or
Reduced Resolution function is used. When these functions are used, the safety
distance calculation must be based on the increased detection capability for
these functions.
Otherwise, the machine may not stop before a person reaches to the hazardous
part, resulting in serious injury.
If detection capability may get larger and a human body may pass a detection
zone to reach a hazardous source, additional safety protection equipment must
be installed such as a safety fence.
The Muting and Override functions disable the safety functions of the device.
Especially setting the Muting Time Limit parameter to infinite may cause the
safety functions to be disabled for a long time. Install the F3SG-SR, muting
sensor and physical barrier and configure time settings for Muting and
Override so that an operator should not enter hazardous zone when the Muting
and Override are active.
Install muting sensors so that they can distinguish between the object that is
being allowed to pass through the detection zone and a person. If the Muting
function is activated by the detection of a person, the machine may not stop
operating, resulting in serious injury.
Muting lamps that indicate the state of the Muting and Override functions must
be installed where they are clearly visible to workers from all the operating
positions.
Use two independent input devices for muting inputs. Failure to do so may
cause the MUTING state due to a single muting sensor’s failure.
Install the switch to activate the Override function in a location that
provides a clear view of the entire hazardous zone and where it cannot be
activated from within the hazardous zone. Make sure that nobody is in the
hazardous zone before activating the Override function.
Make sure to connect an override cancel switch to the RESET line when using
the Override function. Otherwise, the OVERRIDE state may not be released by
the override cancel switch, resulting in serious injury.
When muting error occurs with workpiece blocking the F3SG-SR, there are two
methods to forcibly remove the workpiece.
- Manual operation (with additional safety measure); or
- Override function (Override at Normal Operation / Override upon Startup)
Only one of the methods, either 1) or 2) must be used.
If they are used at the same time, the Override may be activated at an unexpected timing
Install the F3SG-SR so that it is not affected by reflective surfaces. Failure to do so may hinder detection, resulting in serious injury.
When using more than one set of F3SG-SR’s in adjacent areas, the emitter of one F3SG-SR may interfere with the receiver of the other, causing the safety functions to stop working properly. Install, configure and maintain them so that mutual interference does not occur.
To change the response time, calculate the safety distance based on the setting. Otherwise, the machine may not stop before a person reaches the hazardous part, resulting in serious injury.
Do not use the F3SG-SR with mirrors in a retro-reflective configuration.
Doing so may hinder detection.
It is possible to use mirrors to alter the detection zone to a 90-degree angle.
Wiring
WARNING
When using the PNP output, connect the load between the output and 0 V line.
When using the NPN output, connect the load between the output and +24 VDC
line.
Connecting the load between the output and a different power supply line from
the above line will result in a dangerous condition because the operation mode
of safety outputs are reversed to “Dark-ON”.
When using the PNP output, do not ground +24 VDC line. When using the NPN
output, do not ground 0 V line. Otherwise, a ground fault may turn the safety
outputs ON, resulting in a failure of stopping the machine.
Configure the system by using the optimal number of safety outputs that
satisfy the requirements of the necessary safety category.
Do not connect each line of the F3SG-SR to a DC power supply of higher than 24
VDC+20%. Also, do not connect it to an AC power supply. Failure to do so may
result in electric shock.
Make sure to perform wiring while the power supply is OFF.
Do not use the output signal of the auxiliary output or IO-Link output for
safety applications. Failure to do so may result in serious injury when the
F3SG-SR fails.
For the F3SG-SR to comply with IEC 61496-1 and UL 508, the DC power supply unit must satisfy all of the following conditions:
- The DC power supply operates within the rated power voltage (24 VDC ± 20%).
- The DC power supply has tolerance against the total rated current of devices if it is connected to multiple devices.
- The DC power supply complies with EMC directives (industrial environment).
- Double or reinforced insulation is applied between the primary and secondary circuits.
- The DC power supply has an automatic recovery type of overcurrent protection characteristics.
- Output holding time is 20 ms or longer.
- The DC power supply satisfies output characteristic requirements for class 2 circuit or limited voltage current circuit defined by UL 508.
- The DC power supply complies with laws and regulations, regarding EMC and electrical equipment safety, of the country or region where the F3SG-SR is used. (For example, in EU, the power supply must comply with the EMC Directive and the Low Voltage Directive.)
Double or reinforced insulation from hazardous voltage must be applied to all
input and output lines. Failure to do so may result in electric shock.
Extension of the cable must be within a specified length.
If it isn’t, safety functions may not work properly, resulting in danger.
Settings
WARNING
Make sure the Responsible Person tests the operation of the F3SG-SR after
setting with the DIP Switch on the F39-SGIT-IL3, Teach-in or SD Manager 3 to
verify that the F3SG-SR operates as intended. Make sure to stop the machine
until the test is complete. Unintended settings may cause a person to go
undetected, resulting in serious injury.
Other
WARNING
Perform daily and 6-month inspections for all F3SG-SR as described in the
User’s Manual or the Quick Installation Manual. When using the F3SG-SR in
cascade connection, perform inspections for every connected F3SG-SR.
Otherwise, the system may fail to work properly, resulting in serious injury.
Do not try to disassemble, repair, or modify the product. Doing so may cause
the safety functions to stop working properly.
Do not use the product in environments where flammable or explosive gases are
present. Doing so may result in explosion.
Do not use the F3SG-SR in environments where strong electromagnetic field may
be produced. Doing so may cause the safety functions to stop working properly.
Precautions for Safe Use
Make sure to observe the following precautions that are necessary for ensuring safe use of the product.
-
Storage conditions and installation environment
• Do not install, use, or store the product in the following types of environments:
– Areas exposed to intense interference light, such as direct sunlight
– Areas with high humidity where condensation is likely to occur
– Areas where corrosive gases are present
– Areas exposed to vibration or shock levels higher than in the specification provisions
– Areas where the pollution degree is harsher than 3, such as outdoor environment
– Areas where the product may get wet with liquid that can solve adhesive
• When carrying and installing the product, make sure that two people work together according to the weight of the product so that it should not fall. Otherwise injury and/orproperty damage may occur. -
Wiring and installation
• The rated life of the LEDs used for this product is 6 years.
• Loads must satisfy both of the following conditions:
– Not short-circuited
– Not used with a current that is higher than the rating
• Make sure that the mounting brackets, fixing screws and connectors are properly secured with the torque recommended in the User’s Manual or the Quick Installation Manual.
• Bending radii of cables must be equal to or higher than specified minimum values.
• When replacing the cables with those other than the dedicated cables, use cable connectors that provide a protection grade of IP54 or higher, for the cables.
• To extend a cable length with a cable other than the dedicated cable, use a cable with the same or superior specifications.
• Be sure to route the input/output lines for the F3SG-SR separate from high- potential power lines or through an exclusive conduit.
• Make sure that foreign material such as water, oil, or dust does not enter the F39-SGIT-IL3 or the connector while the cover of the DIP Switch on the F39 -SGIT-IL3 is removed.
• The F39-SGIT-IL3 is dedicated to the F3SG-SR/PG series. Do not use it for the equipment other than F3SG-SR/PG. -
Water-proof
• Do not use the product with degraded protective structure such as swelling and crack in housing and/or sealing components. Otherwise water or other substance may enter the product, resulting in a risk of corruption or burning. -
Disposal
• Dispose of the product in accordance with the relevant rules and regulations of the country or area where the product is used.
Observe the precautions described below to prevent operation failure, malfunctions, or undesirable effects on product performance. -
Storage conditions and installation environment
• Do not install, use, or store the product in the following types of environments:
– Areas with a temperature or humidity out of the specified range
– Areas submerged in water or subject to rain water
• This is a class A product (for industrial environments). In residential areas it may cause radio interference, in which case the Responsible Person may be required to take adequatemeasures to reduce interference.
• Use the sensor after water droplets have been removed when water droplets such as condensation have adhered to the optical surface of the sensor. -
Wiring and installation
• Properly perform the wiring after confirming the signal names of all the terminals.
• Do not operate the control system until 3 s or more after turning ON the power of the F3SG-SR.
• When using a commercially available switching regulator power supply, make sure to ground the PE terminal (protective earth terminal).
• Install the emitter and receiver to the same vertical direction.
• Use brackets of specified quantities and locations according to the dimensions. If the brackets described above are not used, ratings and performance cannot be met.
• Do not install the F3SG-SR close to a device that generates high-frequency noise. Otherwise, take sufficient blocking measures.
• Sharing the power supply with other devices may cause the F3SG-SR to be affected by noise or voltage drop. It is recommended that the F3SG-SR use a power supply dedicated for safety components, not shared with other devices.
• Do not change the scan code during normal operation. The F3SG-SR transitions to lockout.
• Do not apply load to the connectors.
• The operating range of the F3SG-SR-K is about 20% lower than the normal model. -
Cleaning
• Do not use thinner, benzene, or acetone for cleaning. They affect the product’s resin parts and paint on the housing.
• Use a soft cloth which is dry or wetted with clean water for cleaning. Do not use solvents. -
Object detection
• The F3SG-SR cannot detect transparent and/or translucent objects. -
Settings
• Do not operate the DIP Switch on the F39-SGIT-IL3 during normal operation of the F3SG-SR.
Otherwise, the F3SG-SR enters the LOCKOUT state.
• Do not operate the DIP Switch and Push Switch on the F39-SGIT-IL3 with tools that may damage the product.
• Be sure that the F3SG-SR is in the SETTING state when making a change to the setting.
Reference Manuals
Document Title | Cat. No. |
---|
Safety Light Curtain F3SG-□SR□ Series Safety Multi-Light Beam F3SG-□PG□ Series
User’s Manual| Z405-E1
Safety Light Curtain F3SG-□SR□-K Series Quick Installation Manual| 2871537-9
Suitability for Use
Omron Companies shall not be responsible for conformity with any standards,
codes or regulations which apply to the combination of the Product in the
Buyer’s application or use of the Product. At Buyer’s request, Omron will
provide applicable third party certification documents identifying ratings and
limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product
in combination with the end product, machine, system, or other application or
use. Buyer shall be solely responsible for determining appropriateness of the
particular Product with respect to Buyer’s application, product or system.
Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE
HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS
PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT
OR SYSTEM.
OMRON Corporation (Manufacturer)
Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 JAPAN
Contact: www.ia.omron.com
Regional Headquarters
-
OMRON EUROPE B.V. (Importer in EU)
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388 -
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 -
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711 -
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
Apr, 2021 uF
LED Indicators
-
LED Indicators of the Emitter
-
LED Indicators of the Receiver
- The indicator of the emitter is illuminated only in the case the Wired Synchronization is enabled and is off in the case the Optical Synchronization is enabled.
- DIP switches is on the Intelligent Tap.
- Refer to the F3SG-SR User’s Manual for more information on blinking patterns.
Note: In the SETTING state to make settings with the SD Manager 3, the TEST, LONG and CODE indicators on the emitter and the CFG, PNP and CODE indicators on the receiver blink. (TEST: Yellow, LONG/CODE: Green, CFG/PNP/CODE: Green)
© OMRON Corporation 2020-2022 All Rights Reserved.