terneo Beert Smart Control of Heating Instruction Manual

May 15, 2024
terneo

terneo Beert Smart Control of Heating Instruction

Specifications

  • Temperature hysteresis: 2 – 3 °C
  • Pump overrun time: 3 minutes
  • Maximum load current (for category AC-1): 50A
  • Rated load capacity (for category AC-1): 440V~
  • Input voltage: 230V~ 50 Hz
  • Weight in the complete set: Not specified
  • Temperature sensor: R10 in heat shrink, 4m cable length
  • Degree of protection: IP20

Product Information

The Terneo BeeRT thermostat is designed to control electric heating systems based on electrode or heating element boilers. It can manage the operation of the pump, monitor its serviceability, and connect to an external programmer for maximum comfort and energy savings. The non-volatile storage ensures all settings are saved in the event of a power outage.

Installation Instructions
The thermostat should be mounted in a special cabinet with a standard 35 mm DIN rail for accessible installation and operation. Ensure the cabinet is equipped with the necessary components as specified in the manual.

Wiring Instructions
The thermostat supports two types of sensors: analog sensor (R10) or digital sensor (D18). Follow the wiring connections for controlling the pump, boiler heater, and temperature programmer as indicated in the manual.

Load Checking and Safety Measures
Before installation, check the load requirements and ensure the power of automatics, power relay, and magnetic starter are chosen based on the maximum power of the boiler. Install an automatic circuit breaker (CB) to protect against short circuits and excess power events.

FAQ

  • Q: What should I do if the thermostat settings are lost after a power outage?
    A: The non-volatile storage feature of the thermostat ensures that all settings are saved during a power outage. Simply power on the device to restore the settings.

  • Q: Can I use both analog and digital sensors with the thermostat simultaneously?
    A: No, the thermostat supports either an analog sensor (R10) or a digital sensor (D18) at a time. Ensure to use only one type of sensor as per your installation requirements.

Technical data sheet and installation and operation manual

  • Terneo BeeRT thermostat is designed to control electric heating systems based on electrode or heating element boilers with the ability to control the operation of the pump and monitor its serviceability. Ateneo BeeRT also allows you to connect an external programmer for maximum comfort and energy savings.
  • The thermostat ensures the comfortable and safe operation of the boiler due to the regulation of «feed» and «return» temperatures. The heating starts when the «return» temperature drops to the hysteresis value and is turned off when the «feed» or «return» temperature reaches the set value. Non-volatile thermostat storage saves all settings in the event of a power outage.

IMPORTANT. Before the installation and operation of the device, please read by the end of this document. This will help to avoid possible danger, mistakes and misunderstandings.

TECHNICAL DATA

IN THE BOX

  • Thermostat 1 piece
  • Temperature sensor with connecting wire 2 piece
  • Technical data sheet and installation and operation manual and warranty card 1 piece
  • The packing box 1 piece

WIRING

  • The thermostat supports two types of sensors: analog sensor (R10) or digital sensor (D18).
  • Connect the analog red feed temperature sensor to terminals 1 and 2. « » red (or yellow) white digital sensor is connected to terminal 1 using wire and to terminal 2 using wire.
  • Connect the analog blue «return» temperature sensor to terminals 5 and 6. The digital sensor is connected to terminal 5 using red (or yellow) wire and to terminal 6 using white wlre.
  • Be sure to select the type of sensor in the functional menu of the thermostat when using a digital sensor (see Table 1, menu item «Selecting the type of sensor»). If sensors are connected incorrectly or one of them fails, when the thermostat is turned on, eights are displayed on the screen for 5 seconds, and then «OC» or «SC» (see page 7).
  • The supply voltage (230 V %, 50 Hz) is supplied to terminals 9 (phase, L) and 10 (zero, N).
  • Terminals 7 and 8 (voltage-free relay contacts) are used to control the pump.
  • Terminals 11 and 12 (voltage-free relay contacts) are used to control the boiler heater.
  • The contact group of the temperature programmer is connected to terminals 3 and 4.

INSTALL AND CHECK THE LOAD before installing and connecting the thermostat. POWER OF AUTOMATICS, POWER RELAY, magnetic starter should be chosen based on maximum power of the boiler. FOR THE OPERATION OF THE PUMP AND THE BOILER, CONNECT APPROPRIATE PHASES TO THE CONTROL RELAYS of BeeRT for switching, since the relay contacts do not have a galvanic connection with the power supply circuits, that is, the relays used in the thermostat have a «dry normally open contact» (see Wirings 1 , 2).

Wiring 1 . Connecting a single-phase boiler using a power relay

Wiring 2. Connecting the automation of a 3-phase boiler

INSTALLATION

  • The thermostat is designed for indoor installation. The ingress risk of moisture or liquid into the place of installation must be minimized. The ambient temperature during installation must be between —5 + 45 0 C. The installation height of the thermostat should be in the range m above the floor level.
  • The thermostat should be mounted in a special cabinet, which allows accessible installation and operation. The cabinet must be equipped with a standard 35 mm mounting rail (DIN-rail). The temperature controller has a width of three standard 18 mm modules.
  • The temperature controller must switch the current to no more than 213 of the maximum current specified in the specification. If the current exceeds this value, the load must be connected through a contactor (magnetic actuator, power relay), which is optimized for this current (Wiring 1).
  • To protect from short circuits and excess power events appearing in the load circuit, it is necessary to install an automatic circuit breaker (CB), which should be installed in the live wire break, as shown on Wiring 1.
  • The thermostat terminals are designed for a wire with a section not more than 2,5 mm2. To reduce the mechanical loads on the terminals it is desirable to use a soft wire. The wires are tightened in the terminals using a screwdriver with a blade width of no more than 3 mm. The terminals should be tightened with torque (),5 N•m. The use of aluminum is not desirable. A screwdriver with a blade width of more than 3 mm can cause mechanical damage to the terminals. This may result in the loss of the right to warranty.
  • If necessary, it is allowed to shorten and expand sensor connecting wires (separate cable not more than 40 m). Power wires should not be placed near the connection wire of the sensor otherwise they may cause interference.

WARRANTY TERMS

  • The warranty for stereo devices is valid for 36 months from the date of sale, provided that the instructions are followed. The warranty period for products without a warranty certificate is counted from the date of production.
  • If your device is not working properly, we recommend that you first read the section «Possible problems».
  • If you cannot find an answer, contact the Service Center. In most cases, these actions resolve all issues. If you continue to have issues with the device, please send it to a Service Center or to the store where you purchased the device. If your device is defective due to our fault, we will repair or replace it under warranty within 14 business days.
  • Please see the full text of the warranty and the data you need to send to your Service Center on the website https://www.ds-electronics.com.ua/en/. If you have a warranty case, please, contact the General distributor In your area.

SERVICE CENTER CONTACT +38 (091) 481-91-81 Viber WhatsApp Telegram support@dse.com.ua

WARRANTY CARDterneo-Beert-Smart-Control-of-Heating-Instruction-
fig-4

EXPLOITATION

  • Use the « » button to select the desired menu item. Use «+» or «—» to change the parameters. The temperature display returns after 5 sec after the last pressing the buttons.
  • For the operation of the boiler, set the main parameters: the temperature and hysteresis of «return» and «feed», as well as the run-out time of the pump. To prevent incorrect settings when BeeRT cannot turn on the heating, the lower value of the «feed» temperature in the thermostat is limited by the «return» temperature.

Set «return» temperature (factory setting 50 0 C)

  • The «return» temperature is the temperature of the coolant at the inlet to the boiler. The air temperature in the room is selected according
  • It is displayed on the bottom screen of the thermostat. To view and change, press the «—» button. Next press «+» or «—» to change the temperature value.

Set feed temperature « » (factory setting 70 °С)

  • The feed temperature is the temperature of the coolant at the outlet of the boiler. The value of this temperature determines the heating rate of the room and the temperature of the radiators. Once the temperature is reached, the top screen will flash.
  • To view and change, press the «+» button. Next press «+» or «—» to change the temperature value.

Reset to the factory settings

  • To reset the factory settings, hold the three buttons at the same time for more than 12 sec until the «dEF» message appears on the screen. After release, it will reset to the factory settings and reboot.

View firmware version

  • Hold down the button for 6 seconds. The manufacturer reserves the right to modify the firmware to enhance the device’s technical characteristics.

Button blocking (child and public protection)

  • To enable (disable) button blocking press the «+» and «—» buttons at the same time for 6 seconds till the «Loc» («unlock») sign appears on the screen.

Table 1. FUNCTION MENUterneo-Beert-Smart-Control-of-Heating-Instruction-
fig-10

Operation principle of stereo BeeRT thermostat with an external programmer
The programmer controls the heating system based on set schedule. To achieve savings, for example, on weekdays, when everyone is at work, the programmer turns off the boiler by blocking the operation of terneo BeeRT.

  • When the Terneo BeeRT thermostat is blocked by the programmer, and feed temperature will flash alternately on the upper screen.

POSSIBLE PROBLEMS, CAUSES, AND WAYS TO OVERCOME THEM
The load is off, screen and indicator are off

  • Possible cause: No power supply.
  • It is necessary: to make sure that the supply voltage at terminals 9 and 10 is available. If a power supply is available, contact the Service Center.

On the thermostat screen «OC» or «SC»

  • The upper screen displays the failures of the «feed» sensor, the lower one displays the failure of the «return» sensor. The inscription «OS» means a sensor failure while «SC»

  • Possible cause: damage to the sensor and its circuit, incorrectly selected sensor type in the thermostat settings.

  • It is necessary: to check the integrity of the sensor and the absence of mechanical damage to its circuit, the absence of power wires that are laid close. Make sure that the appropriate type is selected in the sensor settings (see Table 1).

On the screen of the thermostat, the temperature froze at the level of 98 … 105 oc, the measured temperature does not correspond to the actual one

  • Possible cause: in the settings, the type of sensor RIO is selected instead of which the digital sensor D18 is connected and its connection does not meet the requirements (see page 2).
  • It is necessary: to check the correct connection of the digital sensor and its compliance with the type in the thermostat settings.

ADDITIONAL INFORMATION

  • Do not fire and do not throw away the device with the household waste.
  • After the end of its service life, the product must be disposed of under applicable law.
  • Transportation of goods carried in the package, ensuring the safety of the product.
  • The device is transported by any kind of transport (rail, sea, motor, air transportation).
  • The date of manufacture is on the back side of the device. Application time is unlimited.
  • The device does not contain harmful substances.
  • If you have any questions or you something will not clear, call the Service Center at the telephone number listed below.

SAFETY INSTRUCTIONS

  • Carefully read and become aware of these instructions.
  • Connection of the device must be done by a qualified electrician.
  • Do not connect 230 V mains voltage instead of the sensor (it leads to the failure of the thermostat).
  • Before the installation (dismantling) and connection (disconnection) of the device, turn off the voltage supply and also act according to the «Rules of an arrangement of electric installations».
  • Do not immerse the sensor with a connecting wire in the liquid medium.
  • Do not switch the non-assembled device to the network.
  • Turning on and off or and configuring the device should be with dry hands.
  • Do not connect the device to the network disassembled. Avoid hitting of water or moisture to the device.
  • Do not expose the device to extreme temperatures (higher than 40 oc or below —5 oc) and high humidity.
  • Never clean the device with the use of chemicals such as benzene, or solvents.
  • Do not store the device and do not use it in areas with dust.
  • Do not attempt to disassemble and repair the device. Do not exceed the landmarks value adaptor and power.
  • To protect against overvoltage caused by lightning discharges, use a lightning protector. Protect the children from games with the working device, it is dangerous.

Low Voltage Directive 2014/35/EU EMC Directive 2014/30/EU
Manufacturer and vendor: DS ELECTRONICS, LTD 04136, Ukraine, Kyiv region, Kyiv, 1—3 Pivnichno-Syretska str. . +38 (091) 481-91-81, Service Center: +38 (091) 481-91-81
support@dse.com.ua www.ds- electronics.com.ua/en/

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals