Danfoss RT 9E Automatic Thermostat Installation Guide
- June 17, 2024
- Danfoss
Table of Contents
Installation guide
Thermostat
RT 9E, RT 14E, RT 101E, RT 107E, RT 123E
RT 9E Automatic Thermostat
Approvals and standards:
ATEX: EN 60079-0:2018; EN 60079-11:2012; IECEx: IEC 60079-0:2017; IEC 6 0 079
-11:2011
UK-type Examination Certicate: BS EN IEC 60079-0:2018, BS EN IEC 60079-11:2018
Specific conditions of use:
The enclosure fascia has been coated with a layer of stainless steel to
prevent the accumulation of electrostatic charge. In order to ensure that
there is no accumulation of electrostatic charge on the enclosure, the end
user shall ensure that the external metal work of the enclosure is locally
bonded to earth. Information on the durability of the coating with regards to
use of the equipment is contained within the instruction manual.
Product marking
Temperature class | Process temperature limit [°C] |
---|
T1
T2
T3
T4
T5
T6| 300
289
194
129
94
79
Technical data
Type | Range [°C] | Max. permissible bulb temperature [°C] |
---|---|---|
RT 9E | -45 – -15 | 150 |
RT 14E | -5 – 30 | 150 |
RT 101E | 25 – 90 | 300 |
RT 107E | 70 – 150 | 215 |
RT 123E | 150 – 250 | 300 |
Permissible ambient temperature | -20 – 65 °C | |
--- | --- | |
Intrinsically safe specification | Ui = 29 V |
li = 0.5 A
Pi = 1 W
Ci = 0.5 nF
L = 0.2 µH
Contact load| max. 100 mA, 30 V AC / DC
min. 1 mA, 5 V AC / DC
Must be used with a certified Ex ia barrier satisfying the input parameters.
Installation
Aset of Pg13.5 cable gland is attached to the RT in a separate bag. To ensure IP66 (units with automatic reset) or IP54 (units with external reset) grade of RT enclosure it is necessary to assemble this gland as shown in the fig. 2. If this gland is not used with a cable, a metal blinding should be also assembled.
RT units can be fitted in any position. Use the mounting holes (25). With
outdoor installation, the unit should be protected against rainfall. The bulb
should be fixed to the wall by means of a bulb holding bracket (26). If it is
desired to install the bulb in a water or brine tank, this can be done by
using either a capillary stuffing box (31) or a bulb pocket (30).
If bulb pocket is to be used, for correct bulb fitting see fig. 4.
Electrical connection
See fig. 5.
START = make. STOP = break. DIFF. = differential.
Cable diameter: 6 – 14mm.
The earth terminal (38) should be connected to earth.
Wire dimension: min. 0,75mm2
Adjustment
Set the thermostat for minimum actuating temperature (range setting).
Setting is done by rotating the knob (5), at the same time reading the main
scale (9).
The differential is set by rotating the differential adjusting nut (19)
according to the nomogram concerned (fig. 3).
Maximum actuating temperature is the sum of the temperature setting and the
differential.
Example:
An RT 123 is required to regulate the temperature in a drying oven.
Max. temperature 188 °C, min. temperature 180 °C, differential 188 °C – 180°C
=8°C.
- Set the thermostat on 180 °C with the knob (5).
- Set the differential adjusting nut (19) on number 3 which can be found by reading off the nomogram for the RT 123 in fig. 3.
In general, turning the knob automatically moves both the maximum and minimum actuating temperatures (break and make) up or down because of the fixed differential. On the other hand, turning the differential adjusting nut only, alters the maximum actuating temperature.
**** Safety requirements
-
The refrigeration system must always comply with European Ex installation standard, EN 60079-14, any local directive and legislation as well as any other regulation applying in the area of installation.
-
RT-E temperature control must be used only with reliable means of limiting the voltage and current to prevent sparks between the contact surfaces. The equipment to be used for electrical load limiting must be certified for gas group IIC. Also RT-E thermostat must be installed as a part of IIC electrical installation.
-
Cable and cable entries approved for the application must be used.
Cables must not be in contact with sharp edges. The cable must be connected with adequate stress relief in order to prevent that pulling forces can be carried through the cable to the terminal. -
The cycle frequency of the RT-E switch must be kept as low as possible to prevent fatique failure on the bellows. The vibration level must be kept as low as possible.
-
It is recommended to regularly check the function of the RT-E switch.
-
Only apparatus designed, constructed and released by Danfoss must be used for application concerned. Danfoss can accept no responsibility in case of alterations made on the thermostats or the use of them against the instructions of Danfoss.
-
Any overload of the RT switch must be prevented. Overloaded or damaged apparatus must be exchanged.
-
Only authorised persons, who are certified in installing and maintaining refrigration system may do the installation, maintenance and exchange of the switch. Use only appropriate tools.
-
Dispose of the switch in an environmentally-friendly way.
-
RTE switches must be installed in area where is low risk of mechanical damage.
-
Components within the equipment can exceed the enclosure tem- perature by 1K (1 °C). When the media temperature exceeds 80 °C, it is the responsibility of the user to ensure that the media temperature does not cause a thermal ignition risk on parts between the media and the switch enclosure. Maximum media temperature on temperature switch with 2m or longer capillary tube is 300 °C.
-
Isolation of the intrinsically safe circuit to ground and to the contact mounting screw has been verified through 500 VACrms dielectric strength testing, carried out in accordance with IEC 60079-11:2011 section 10.3.
-
Surface of the front cover is sputtered with stainless steel – avoid abrasion.
-
Power must be switched off before maintenance and opening the RT-E.
Danfoss A/S
6430 Nordborg
Denmark
CYR nr.: 20 16 $7 15
Telephone: +45 7488 2222
Fax: +45 7449 0949
UK DECLARATION OF CONFORMITY
Danfoss A/S
Refrigeration & Air Conditioning Controls
declares under our sole responsibility that the
Product category: Pressure and temperature switches
Type designation(s): RT112E, RTI13E, RTIAE, RTLIGE, RTSE, RT9E, RT117E,
RT260AE, RT262AE, RTI4E, RTIOLE, RTI07E, RT121E, RTI23E
Covered by this declaration is in conformity with the following directive(s),
regulation(s), standard(s) or other normative document(s), provided that the
product is used in accordance with our instructions.
Equipment and Protective Systems Intended for use in Potentially Explosive
Atmospheres Regulations 2016, UKSI 2016 No. 1107
Marking:
**** 0843 II 2G
Ex ia WC T6…T1 Gb
Tamb. -20C to +65C
UK-Type Examination Certificate: UL21 UKEX2021X
Approved Body: UL International (UK) Ltd, No. 0843
Test basis:
BS EN IEC 60079-0:2018 Explosive atmospheres, Part 0, Equipment-General
requirements
BS EN IEC 60079-11:2012 Explosive atmospheres, Part 11, Equipment Protection
by Intrinsic safety “i”.
The Restriction of the Use of Certain Hazardous Substances in Electrical and
Electronic Equipment Regulations 2012 (as amended)
BS EN 63000:2018 Technical documentation for the assessment of electrical and
electronics products with respect to the restriction of hazardous substances
Danfoss only vouches for the correctness of the English version of this declaration. In the event of the declarstionMeing translated into any other language, the translator concerned shall be liable for the correctness of the translation
ID. No : 060-9684 Revision No: AA
This doc. is managed by 500B0577
Classified as Business
Danfoss A/S
6430 Nordborg
Denmark
CVR ne. 20 16 57 15
Telephone: +45 7488 2222
Fax: +45 7449 0949
EU DECLARATION OF CONFORMITY
Danfoss A/S
Refrigeration & Air Conditioning Controls
declares under our sole responsibility that the
Product category: Pressure and temperature switches
Type designation(s): RT112E, RT113E, RTIAE, RT1I16E, RTSE, RT9E, RT117E,
RT260AE, RT262AE, RT14E, RTIOLE, RT107E, RT121E, RT123E
Covered by this declaration is in conformity with the following directive(s),
standard(s) or other normative document(s), provided that the product is used
in accordance with our instructions.
Explosive or Protective Systems Intended for use in Potentially Explosive
Atmospheres, Directive 2014/34/EU
Marking:
0539 II 2G
Ex ia IIC T6…T1 Gb
Tamb. -20C to +65C
EC-Type Examination Certificate: DEMKO 14 ATEX 1406X, Rev. 4
Notifying Body: UL Demko, No.: 0539
Test basis:
EN 60079-0:2018 Explosive atmospheres, Part 0, Equipment-General requirements
EN 60079-11:2012 Explosive atmospheres, Part 11, Equipment Protection by
Intrinsic safety “i”.
ROHS Directive 2011/65/EU including amendment 2015/863
EN IEC 63000:2018 Technical documentation for the assessment of electrical and
electronics products with respect to the restriction of hazardous substances
Danfoss only vouches for the correctness of the English version of this
declaration. In the event of the declaration being translated into any other
language, the translator concerned shal be liable for the correctness of the
transiation
ID No: 060-9657 Revision No: AG
This doc is managed by 500B0577
Classified as Business
© Danfoss | Climate solutions | 2024.01
3 | AN179486440929en-001201
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>