Article | Commercial Refrigeration
FAQ – Your guide to choosing
low-GWP refrigerants
Low GWP Refrigerants
Commercial refrigeration engineers, OEMs and cold room owners are faced with
dificult decisions as they move to lower-GWP refrigerants. We can help you
make the move with confidence by answering your most urgent refrigerant
questions.
By Jorg Saar, Global Application Manager, Danfoss Cooling
Refrigeration engineers, installers, OEMs, and cold room owners must make the
move to low-GWP refrigerants to comply with F-Gas regulations and other
refrigerant regulations.
However, uncertainty over refrigerant selection and future supply, as well as
misunderstandings about component suitability, could be preventing some
designers, engineers and installers from making refrigerant decisions with
confidence.
To help you select and install both new and retrofitted refrigerants, we’ve
answered some of the most common low-GWP refrigerant questions.
- Is there a simple way to select the right refrigerant?
- What refrigerants should I consider, and why?
- Will a new refrigerant force me to use new components?
- Where can I learn more?
Is there a simple way to select the right refrigerant?
There is no one-size-fits-all solution available, as no single refrigerant can
operate efficiently across all temperature ranges, applications and operating
conditions.
To select the right refrigerants for your applications, you’ll need to
consider the properties of each – and how they match up to your environments
and equipment.
For new systems, the process is relatively straightforward; retrofitting is
potentially a little more complex.
Things to consider:
New systems | Retrofit |
---|
• Long and short-term refrigerant availability
• Component availability
• Cost
• Flammability
• Charge limitations and safety requirements
• Specific capacity
• Pipe sizing
• Overall system GWP (TEWI)
• How different components impact energy efficiency| • Long and short-term
refrigerant availability
• Capacity deviation to current refrigerant in typical temperature range
• Compressor, oil and component compatibility with alternative refrigerants
• Flammability (A2L class or higher)
• Discharge temperature
• Glide
• Superheat setting
• Safety device settings
• Pipe sizing
Which refrigerants should I consider, and why?
Based on regulations and system needs, lower GWP refrigerant alternatives are
available.
R404A/R507 alternatives: R448A, R449A, R407H, R452A (A1, non-flammable),
R454A, R454C, R455A (A2L, mildly flammable, GWP < 150), 290 propane, R600a
isobutane (A3, highly flammable).
R134a alternatives: R513A, R450A, R513B (A1, non-flammable), R516A, R445A
(A2L, mildly flammable, GWP < 150), R290 propane, R600a isobutane (A3, highly
flammable).
Additionally, R744 (CO2) is an alternative for R404A/R507 and R134a, but it
operates at considerably higher pressure, requiring a different system design.
Retrofit existing R404A /R507 systems with A1 refrigerants only; A2L and A3
are for new installations.
When retrofitting old systems, there are some key things to consider when
choosing a lower-GWP refrigerant:
- How close is the new refrigerant to your current refrigerant’s pressure and capacity?
- Using new lower GWP A1 refrigerants to retrofit R404A, R507, and R134a systems avoids the need to check for flammable refrigerant requirements.
- In case the new refrigerant has a higher flammability class, check charge limits and safety requirements in standards and regulations.
- Refrigerant charge limits are defined in EN 378-1:2016 table C2 and in Application Specific standards IEC 60335-2-xx series.
- Be aware that auxiliary electrical equipment could become an ignition source when using a flammable refrigerant in a new system; for more information, refer to the Asercom guide about safety standards and components for flammable refrigerants
- If you’re considering a new refrigerant with high glide, please read our technical paper on Retrofit and high glide refrigerants
- Recover the old refrigerant in the system, and don’t mix it with other refrigerants.
Main refrigerants at Play
A complex picture in continuous evolution
Will a new refrigerant force me to use new components?
In some cases, you can continue to use the same compressors, heat exchangers,
valves and controls you used before. It is always necessary to check if
components may need to be modified before they are ready for a new
refrigerant.
Check points may include:
- Oil and compressor approval for the new refrigerant. If not replace with a compatible compressor,
- Components with gaskets must be compatible with the new refrigerant and oils,
- Thermostatic expansion valves likely need to be adjusted or even become replaced with a new version as it might need a bulb charge that’s compatible with the new refrigerant to allow good superheat control,
- Electronic expansion valve controllers may need new refrigerant specific parameters. Set the new refrigerant in the superheat controller for the electric expansion valve. If the refrigerant is not in the list, use user-defined and input parameters. Please note that Danfoss controllers already include many of the lower-GWP refrigerants,
- Control devices like pressure switches might need to be adjusted to the new refrigerant pressures.
Where can I learn more?
That said, if you have specific needs and requirements from your refrigerant,
you may need to investigate other flammable refrigerant options.
Danfoss offers a range of content to help cold room operators, installers and
OEMs select the right lowGWP refrigerant for their needs. Our engineers are
committed to low-GWP refrigerants and solutions, and can help you keep up to
date with the latest solutions and developments.
For more information, view our full low-GWP resources library at
refrigerants.danfoss.com.
For the selection of components, turn to coolselector.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues,
brochures and other printed material. Danfoss reserves the right to alter its
products without notice. This also applies to products already on order
provided that such alterations can be made without subsequential changes
being necessary eady agreed.
All trademarks in this material are property of the respective companies.
Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights
reserved.
AC294357164964en-000201
© Danfoss | 2024.02
References
- Guides - ASERCOM
- Refrigerants and energy efficiency | Sustainable refrigeration | Danfoss
- Coolselector®2 free cooling calculation software | Danfoss
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>