Danfoss 28 MST VMTD Termix Compact Station Installation Guide

June 17, 2024
Danfoss

ENGINEERING
TOMORROW
Operating Guide
Termix Compact 28 MST VMTD

Danfoss 28 MST VMTD Termix Compact Station -

Functional description

District heating substation for direct heating and instantaneous domestic hot water.
Space heating and domestic hot water (DHW)
The Termix Compact 28 MST VMTD is a complete unit for space heating and domestic hot water for direct district heating in large buildings such as sports centres, schools, blocks of flats etc.
Efficient heat exchanger
The substation is fitted with an efficient plate heat exchanger, which ensures the most favourable heat extraction and achieves optimum comfort and operating economy.
Electronic regulation
The Termix Compact 28 MST VMTD is built with a plate heat exchanger for domestic hot water and direct system regulation for space heating. The electronic control is pre-set from the factory.
Electrical components are connected, and the unit is equipped with a plug for 230 V a.c. As standard, each circuit is also supplied with its own flow controller.
This allows the greatest degree of individual control, thus preventing oscillation at different loads.
It is recommended that dynamic balancing valves be installed in the building’s risers in the heat supply and on the heating system’s return line immediately before the unit.
Easy installation
The unit consists of two modules, one for space heating and one for domestic hot water production, which is easily assembled into one single module. This modular design makes work during installation significantly easier, as the weight is split between two modules during handling.
Flexible solution
Pipe connection can be made from either the top or bottom, which makes this solution highly flexible. At the same time, both space and time are saved when installing.
Minimal heat loss
Complete insulation of the unit ensures minimal heat loss.
Reliable and easy to install
Termix Compact 28 MST VMTD is a operationally reliable. A quality product manufactured in Denmark, which is easy to install and quickly commissioned.

Safety notes

3.1 Safety Notes – general
The following instructions refer to the standard design of substation. Special versions of substations are available on request.

This operating manual should be read carefully before installation and start- up of the substation. The manufacturer accepts no liability for damage or faults that result from non-compliance with the operating manual. Please read and follow all the instructions carefully to prevent accidents, injury and damage to property.
Assembly, start-up and maintenance work must be performed by qualified and authorized personnel only.
Please comply with the instructions issued by the system manufacturer or system operator.

Corrosion protection
All pipes and components are made of stainless steel and brass.
The maximum chloride compounds of the flow medium should not be higher than 150 mg/l.
The risk of equipment corrosion increases considerably if the recommended level of permissible chloride compounds is exceeded.
Energy source
The substation is designed for district heating as the primary source of energy. However, also other energy sources can be used where the operating conditions allow it and always are comparable to district heating.
Application
The substation is designed to be connected to the house installation in a frost-free room, where the temperature does not exceed 50 °C and the humidity does not exceed 60%. Do not cover or wall up the substation or in any other way block the entrance to the station.
Choice of material
Choice of materials always in compliance with local legislation.
Safety valve(s)
We recommend mounting of safety valve(s), however, always in compliance with local regulations.
Connection
The substation must be equipped with features that ensure that the substation can be separated from all energy sources (also power supply).
Emergency
In case of danger or accidents – fire, leaks or other dangerous circumstances – interrupt all energy sources to the station if possible, and seek expert help.
In case of discoloured or bad-smelling domestic hot water, close all shut-off valves on the substation, inform the operating personnel and call for expert help immediately.
REACH
All Danfoss A/S products fulfill the requirements in REACH. One of the obligations in REACH is to inform customers about presence of Candidate list substances if any, we hereby inform you about one substance on the candidate list: The product contains brass parts which contains lead (CAS no: 7439-92-1) in a concentration above 0.1% w/w.
Storage
Any storage of the substation which may be necessary prior to installation should be in conditions which are dry and heated.
Authorized personnel only
Assembly, start-up and maintenance work must be performed by qualified and authorized personnel only.
Please observe instructions carefully
To avoid injury to persons and damage to the device, it is absolutely necessary to read and observe these instructions carefully.

Warning of high pressure and temperature
Be aware of the installation’s permissible system pressure and temperature.
The maximum temperature of the flow medium in the substation is 110 °C.
The maximum operating pressure of the substation is 16 bar.
The risk of persons being injured and equipment damaged increases considerably if the recommended permissible operating parameters are exceeded.
The substation installation must be equipped with safety valves, however, always in accordance with local regulations.
Warning of hot surface
The substation has got hot surfaces, which can cause skin burns.
Please be extremely cautious in close proximity to the substation.
Power failure can result in the motor valves being stuck in open position. The surfaces of the substation can get hot, which can cause skin burns. The ball valves on district heating supply and return should be closed.
Warning of transport damage
Before substation installation, please make sure that the substation has not been damaged during transport.
IMPORTANT – Tightening of connections
Due to vibrations during transport all flange connections, screw joints and electrical clamp and screw connections must be checked and tightened before water is added to the system. After water has been added to the system and the system has been put into operation, re-tighten ALL connections.

Mounting

4.1 Mounting the Compactstation

Installation must be in compliance with local standards and regulations.
District heating (DH) – In the following sections, DH refers to the heat source which supplies the substations. A variety of energy sources, such as oil, gas or solar power, could be used as the primary supply to Danfoss substations. For the sake of simplicity, DH can be taken to mean the primary supply.

Connections:

  1. District heating (DH) supply
  2. District heating (DH) return
  3.  Heating (HE) supply
  4. . Heating (HE) return
  5.  Domestic hot water (DHW)
  6. Domestic cold water (DCW)

Connection sizes:

DH + HE : G 1” (int. thread)
HWC+ DHW + DCW: G ¾” (int. thread)

Dimensions (mm):

With insulation: H 848 x W 905 x D 400

Weight (approx.): 42kg

Authorized personnel only
Assembly, start-up and maintenance work must be performed by qualified and authorized personnel only.

Danfoss 28 MST VMTD Termix Compact Station - pipe
placement

The pipe placement can deviate from the shown drawing. Please note the markings on the station.

Remove the front.

Remove other blocks.

Danfoss 28 MST VMTD Termix Compact Station - Remove other
blocks

Attach the mounting rail to the wall.

Danfoss 28 MST VMTD Termix Compact Station - wall

Lift the station.

Mount the station on the mounting rail.

Danfoss 28 MST VMTD Termix Compact Station - rail

Attach the station to the wall in the holes on the mounting plate.

Danfoss 28 MST VMTD Termix Compact Station - plate

Install the isolation valves.

Mount block A on the left-hand side of the pump. Attach block E to block A, and attach it to the pipe above the pump by clicking it in place.

Danfoss 28 MST VMTD Termix Compact Station - pump

Mount block B on the right-hand side of the pump.

Danfoss 28 MST VMTD Termix Compact Station - Mount block
B

Mount block F. The block is hinged and can be drawn around the valve. Attach the block to block B and E.

Danfoss 28 MST VMTD Termix Compact Station - block to block B and
E

Mount block J and H around the valve for the tank control.

Danfoss 28 MST VMTD Termix Compact Station - tank
control

Mount the front cover.

4.1.1 Installing the Compactstation
Mounting:
Adequate space
Please allow adequate space around the substation for mounting and maintenance purposes.
Orientation
The station must be mounted so that components, keyholes and labels are placed correctly. If you wish to mount the station differently please contact your supplier.
Drillings
Where substations are to be wall-mounted, drillings are provided in the back mounting plate. Floor mounted units have support.
Labelling
Each connection on the substation is labelled.
Before installation:
Clean and rinse
Prior to installation, all substation pipes and connections should be cleaned and rinsed.
Tightening
Due to vibration during transport, all substation connections must be checked and tightened before installation.
Unused connections
Unused connections and shut-off valves must be sealed with a plug. Should the plugs require removal, this must only be done by an authorized service technician.

Installation:
Strainer
If a strainer is supplied with the station it must be fitted according to schematic diagram. Please note that the strainer may be supplied loose.
Connections
Internal installation and district heating pipes connections must be made using threaded, flanged or welded connections.

Keyhole for mounting.

4.2 Start-up
Start-up, Direct heating

The shut-off valves should be opened and the unit observed as it enters service. Visual checking should confirm temperatures, pressures, acceptable thermal expansion and absence of leakage. If the heat exchanger operates in accordance with design, it can be
put to regular use.
After water has been added to the system and the system has been put into operation, re-tighten ALL connections.
Summer operation:
Switch off pump
In summer the circulation pump must be switched off and the shut-off valve to HE supply closed.
Running pump bi-weekly
It is recommended to start up the circulation pump (for 2 minutes) once a month during summer; the shut-off valve of the HE supply must be shut.
Electronic controller
Most electronic controllers will start up the pump automatically (please note manufacturer´s instructions).
Re-thighten connections
After water has been added to the system and the system has been put into operation, re-tighten ALL connections.
4.3 Electrical connections
Before making electrical connections, please note the following:

Safety notes
Please read the relevant parts of the safety notes.
230 V
The substation must be connected to 230 V AC and earth.
Potential bonding
Potential bonding should be carried out according to 60364-4-41:2007 and IEC 60364-5-54:2011. Bonding point on the mounting plate below right corner marked with earth symbol.
Disconnection
The substation must be electrically connected so that it can be disconnected for repairs.
Outdoor temperature sensor
Outdoor sensors should be mounted so as to avoid exposure to direct sunlight. They should not be placed close to doors, windows or ventilation outlets.
The outdoor sensor must be connected to the station on the terminal block under the electronic control.
Authorized electrician
Electrical connections must be made by an authorized electrician only.
Local standards
Electrical connections must be made in accordance with current regulations and local standards.

Design

5.1 Design

Danfoss 28 MST VMTD Termix Compact Station - Design

Your substation might look different than the substation shown.

Design description

B Heat exchanger DHW
F Electronic controller
1 Isolation valve
9 Strainer| 10 Circulator pump
19 Surface sensor
27 Actuator
29 2–way motorized valve| 31 Differential pressure controller
48 Air vent, manual
74 IHPT
---|---|---

5.2 Schematic diagram
5.2.1 Schematic diagram Termix Compact 28 MS VMTD

Danfoss 28 MST VMTD Termix Compact Station - Schematic
diagram

Your substation might look different than the schematic diagram shown.
Schematic description

B Heat exchanger DHW
F Electronic controller
1 Isolation valve
2 Singlecheck valve
9 Strainer
10 Circulator pump| 16 Outdoor sensor
19 Surface sensor
23 Ball valve
24 Delivered loose with unit
27 Actuator
29 2–way motorized valve| 31 Differential pressure controller
39 Connection closed
48 Air vent, manual
63 Sieve
74 IHPT
---|---|---
DH Supply:| District Heating Supply
---|---
DH Return:| District Heating Return
HE Supply:| Heating Supply
HE Return:| Heating Return
DHW:| Domestic hot water
DCW:| Domestic cold water

5.2.2 Technical parameters

Nominal pressure: PN 16
Max. DH supply temperature: 110 °C
Brazing material (HEX): Copper
Heat exchangers test pressure: 30 bar
Sound level: ≤ 55 dB

Controls

6.1 Heating circuit
6.1.1 Differential pressure controller

The differential pressure controller smooths out the fluctuations in pressure arriving from the district heating network. The operating pressure in the substation is thus held steady.

6.1.2 Electric 2–way motorized valve
Actuators with or without safety function are available for 3-point controls. Spring-return actuators can be used to provide safety shut-off in the event of power failure.

6.1.3 Electronic control
Substations with electronic control must be set in accordance with manufacturer´s instructions.
Where the room temperature is controlled by radiator thermostats, it is recommended that thermostats be set for minimum temperature in each room.

6.1.4 Outside temperature sensor
Outdoor sensors should be mounted so as to avoid exposure to direct sunlight. They should not be placed close to doors, windows or ventilation outlets.

6.1.5 Circulator pump UPML
UPML Pumps can be controlled in constant pressure or proportional pressure mode defined by the means of a smart user interface.
The variable speed modulating modes allow the pump to match its performance to the system requirements, helping to reduce noise when thermostatic valves are closing down.
Energy labelling class A

Danfoss 28 MST VMTD Termix Compact Station - Circulator pump
UPML

6.1.6 Grundfos UPML / UPMXL instructions

Danfoss 28 MST VMTD Termix Compact Station - UPMXL
instructions

PP = Proportional pressure (fast flash)
CP = Constant pressure (slow flash)

6.2 Other
6.2.1 Safety valve

The purpose of the safety valve is to protect the substation from excessive pressure.
The blow-off pipe from the safety valve must not be closed. The blow-off pipe outlet should be placed so that it discharges freely and it is possible to observe any dripping from the safety valve. It is recommended to check the operation of safety valves at intervals of 6 months. This is done by turning the valve head in direction indicated.

6.2.2 Strainer
Strainers should be cleaned regularly by authorized personnel. The frequency of cleaning would depend on operating conditions and the manufacturer’s instructions.

6.2.3 IHPT 180 controller (45–65 °)
IHPT is a self-acting flow-compensated temperature controller with integrated differential pressure controller.
The IHPT operates at its best at DH supply temperatures of up to 100 °C.
By turning the handle for temperature setting in (+) direction the setting is increased, by turning it in (-) direction the setting is decreased.

Danfoss 28 MST VMTD Termix Compact Station -
controller

Turns* Scale DHW Temperature Setting [°C]
0 7 64
1 6 61
2 5 58
3 4 55
4 3 52
5 2 48
6 1 44
7 0 43

*Start position: Handle turned fully in (+) direction.
The values are intended as a guide.

6.3 Maintenance
The substation requires little monitoring, apart from routine checks. It is recommended to read the energy meter at regular intervals, and to write down the meter readings.
Regular inspections of the substation according to this Instruction are recommended, which should include:

Strainers
Cleaning of strainers.
Meters
Checking of all operating parameters such as meter readings.
Temperatures
Checking of all temperatures, such as DH supply temperature and DHW temperature.
Connections
Checking all connections for leakages.
Safety valves
The operation of the safety valves should be checked by turning the valve head in the indicated direction.
Venting
Checking that the system is thoroughly vented.
Inspections should be carried out minimum every two years.
Spare parts can be ordered from Danfoss. Please ensure that any enquiry includes the substation serial number.
Authorized personnel only
Assembly, start-up and maintenance work must be performed by qualified and authorized personnel only.

Troubleshooting

7.1 Troubleshooting in general

In the event of operating disturbances, the following basic features should be checked before carrying out actual troubleshooting:

  • the substation is connected to electricity,
  • the strainer on the DH supply pipe is clean,
  • the supply temperature of the DH is at the normal level (summer, at least 60 °C – winter, at least 70 °C),
  • the differential pressure is equal to or higher than the normal (local) differential pressure in the DH network – if in doubt, ask the DH plant supervisor,
  • pressure on the system – check the HE pressure gauge.

Authorized personnel only
Assembly, start-up and maintenance work must be performed by qualified and authorized personnel only.

7.2 Troubleshooting DHW

Problem Possible cause Solution
Too little or no DHW. Strainer in supply or return line clogged. Clean

strainer(s).
DHW circulation pump out of order or with too low setting.| Check circulation pump.
Defective or clogged non-return valve.| Replace – clean.
No electricity.| Check.
Wrong setting of automatic controls, if any.| To adjust an electronic controller for DHW, pls. note enclosed instructions for electronic controller.
Scaling of the plate heat exchanger.| Replace – rinse out.
Defective motorized valve.| Check (use manual function) – replace.
Defective temperature sensors.| Check – replace.
Defective controller.| Check – replace.
Hot water in some taps but not in all.| DCW is being mixed with the DHW, e.g. in a defective thermostatic mixing valve.| Check – replace.
Defective or clogged non-return valve on circulation valve.| Replace – clean.
Tap temperature too high; DHW tap load too high.| Thermostatic valve adjusted to a too high level.| Check – set
Temperature drop during tapping.| Scaling of the plate heat exchanger.| Replace – rinse out.
Larger DHW flow than the substation has been designed for.| Reduce DHW flow.
Thermostatic control valve does not close| Temperature difference between DH supply and DHW set point too low.| Lower the set point temperature or increase the DH supply temperature.

7.3 Troubleshooting HE

Problem Possible cause Solution
Too little or no heat. Strainer clogged in DH or HE circuit (radiator
circuit). Clean gate/strainer(s).
The filter in the energy meter on DH circuit clogged. Clean the filter (after

consulting the DH plant operator).
Defective or wrongly adjusted differential pressure controller.| Check the operation of the differential pressure controller – clean the valve seat if required.
Sensor defective – or possibly dirt in the valve housing.| Check the operation of the thermostat – clean the valve seat if required.
Automatic controls, if any, wrongly set or defective – possibly power failure.| Check if the setting of the controller is correct – see separate instructions.

Check the power supply. Temporary setting of motor to “manual” control – see instructions on automatic controls.

Pump out of operation.| Check if the pump is receiving power and that it turns. Check if there is air trapped in the pump housing – see pump manual.
The pump is set at too low speed of rotation.| Set the pump at higher speed of rotation.
Pressure drop – the pressure drop on the radiator circuit shows lower than recommended operating pressure.| Fill water on the system and check the functioning of the pressure expansion vessel if required.
Air pockets in the system.| Vent the installation thoroughly.
Limiting of the return temperature adjusted too low.| Adjust according to instructions.
Defective radiator valves.| Check – replace.
Uneven heat distribution in building because of incorrectly set balancing valves, or because there are no balancing valves.| Adjust/install balancing valves.
Diameter of pipe to substation too small or branch pipe too long.| Check pipe dimensions.
Uneven heat distribution.| Air pockets in the system.| Vent the installation thoroughly.
DH supply temperature too high.| Wrong setting of thermostat or of automatic controls, if any.| Adjust automatic controls, – see instructions for automatic controls.
Defective controller. The controller does not react as it should according to the instructions.| Call automatic controls manufacturer or replace the regulator.
Defective sensor on self-acting thermostat.| Replace thermostat – or sensor only.
DH supply temperature too low.| Wrong setting of automatic controls, if any.| Adjust automatic controls – see instructions for automatic controls.
Defective controller. The controller does not react as it should according to the instructions.| Call in automatic controls manufacturer or replace controller.
Defective sensor on self-acting thermostat.| Replace thermostat – or sensor only.
Wrong placement/fitting of outdoor temperature sensor.| Adjust location of outdoor temperature sensor.
Strainer clogged.| Clean gate/strainer.
Too high DH return temperature.| Too small heating surface/too small radiators compared to the total heating requirement of the building.| Increase total heating surface.
---|---|---
Poor utilization of existing heating surface. Defective sensor on self-acting thermostat.| Make sure the heat is distributed evenly across the full heating surface – open all radiators and keep the radiators in the system from heating up at the bottom. It is extremely important to keep the supply temperature to the radiators as low as possible, while maintaining a reasonable level of comfort.
The system is single pipe loop.| The system should feature electronic controls as well as return sensors.
Pump pressure too high.| Adjust pump to a lower level.
Air in system.| Vent the system.
Defective or incorrectly set radiator valve(s). Single pipe loop systems require special one-pipe radiator valves.| Check – set/replace.
Dirt in the motorized valve or in the differential pressure controller.| Check – clean out.
Defective motorized valve, sensor or automatic controller.| Check – replace.
Electronic controller not adjusted correctly.| Adjust according to instructions.
Noise in system.| Pump pressure too high.| Adjust pump to a lower level.
Heat load too high.| Defective motorized valve, sensor or electronic controller.| Check – replace.

7.4 Disposal

| Disposal note
This symbol on the product indicates that it may not be disposed of as household waste..
It must be handed over to the applicable take-back scheme for the recycling of electrical and electronic equipment.
• Dispose of the product through channels provided for this purpose.
• Comply with all local and currently applicable laws and regulations.
---|---

Declaration

8.1 Declaration of conformity

ENGINEERING
TOMORROW
Danfoss A/S
6430 Nordborg
Denmark
CVR nr. 20 16 57 15
Telephone: +45 7488 2222
Fax: +45 7449 0949
EU DECLARATION OF CONFORMITY
Danfoss A/S
Danfoss District Energy Division

Declares under our sole responsibility that the:
Product category: Small substations
Type designations:

Ø18: HD BTD VMTD mini mix KST-I One Solar A+/B+
BVX VMTD mix KST-M One Solar Mixing loop
BV VMTD F mix KST-L FLS Measuring Unit
VX VVX BL
C28: CS 28 HD CS 28 BV CS 28 VMTD CS 28 VX CS 28 VVX
C32: CS 32 HD CS 32 BV CS 32 VMTD CS 32 VX CS 32 VVX
C40: CS 40 HD CS 40 BY CS 40 VMTD CS 40 VX CS 40 VVX

Covered by this declaration is in conformity with the following directives, standards or other normative documents, provided that the product is used in accordance with our instructions.
Machinery Directive 2006/42 /EC
EN 1SO 12100:2011
Safety of machinery – General principles for design – Risk assessment and risk reduction
EN 60204-1:2018
Safety of machinery – Electrical equipment of machines —
Part 1: General requirements
RoHS Directive 2011/65/EU
Including amendment 2015/863
EN IEC 63000:2018
Technical documentation for the assessment of electrical and electronic products with respect to the restriction of hazardous substances.
EMC Directive – 2014/30/EU
EN 61000-6-1:2007
Electromagnetic compatibility (EMC) – Part 6-1:
Generic standards – Immunity residential, commercial and light-industrial environments
EN 61000-6-2:2005
Electromagnetic compatibility (EMC) – Part 6-2:
Generic standards – Immunity for industrial environments
EN 61000-6-3:2007 + A1:2011
Electromagnetic compatibility (EMC) ~ Part 6-3:
Generic standards – Emission standard for residential, commercial and light- industrial environments

Danfoss 28 MST VMTD Termix Compact Station - signature

Danfoss only vouches for the correctness of the English version of this declaration. In the event of the deciaration being translated into any other language, the translator concerned shall be tiabie for the correctness of the translation
ID No : LUK30002
This doc. is managed by 500B05//
Revision No: 01

Gemina Termix A/S – Member of the Danfoss Group
danfoss.com . +45 9714 1444 – mail@termix.dk
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.