OPTONICA 7324 Microwave Sensor Remote Highbay Sensor User Manual

June 17, 2024
OPTONICA

OPTONICA 7324 Microwave Sensor Remote Highbay Sensor

USER MANUAL

Microwave Sensor Remote+Highbay Sensor

Sensor intelligent technology

Welcome to use Microwave Sensor!
The product is a new saving-energy switch; it adopts microwave sensor with high- frequency electro-magnetic wave (5.8GHz), integrated circuit. It gathers automatism, convenience, safety, saving-energy and practicality functions. It works by receiving human motion. When one enters the detection field, it can start the load at once and identify automatically day and night. Its installation is very convenient and its using is very wide. Detection is possible through doors, panes of glass or thin walls.

Specification

  • Power Sourcing: 120-277V/AC
  • HF System: 5.8GHz CW radar, ISM band
  • Ambient Light: 5,10,20,30,50,100,200 LUX,24H
  • Time-Delay: min.: 10,30sec,1,5,8,10,20,30min
  • DetectionDistance:25%,50%,75%,100%
  • Operating Temperature:-20°C +40°C
  • Power Frequency: 50/60Hz
  • Detection Range: 360°
  • Installing Height: 4~15m.Max
  • Transmission Power: <10mW
  • Rated Load: 2000W (lamp); 1000W (LED lamp)

Function

  • Can identify day and night: The consumer can adjust work ambient light. It can work in the daytime and at night when it is Press on the “sun.24H” position (max).
    It can work in the night when it is Press the “5LUX,10,20,30,50,100,200” position.
    As for the adjustment pattern, please refer to the testing pattern.

  • Time-Delay is added continually: When it receives the second induction signals after the first induction, it will compute time once more on the basic of the first time-delay rest.

  •  Time–Delay is adjustable. It can be set according to the consumer’s desire.
    The minimum time is 10sec. The maximum is 30min

Note

The high-frequency output of this sensor is <10mW- that is just one 100th of the transmission power of a mobile phone or the output of a microwave oven.

Installation

– Switch off the power.
– Take off the front cover, fixed the bottom on the selected position with two screws.
– Connect the power and the load into the connection-wire column of the sensor according to connection-wire diagram.
– Put the front cover on the product.

Connection-Wier sketch diagram

Connection-Wier sketch diagram

Test

– Press the AUTO Option, sensor will be work in 24H,in the delay time 10 sec, 100% distance.
– Switch on the power, the controlled load and indication lamp both are not working. Preheat 30 sec later, the load and indication lamp should be turned on synchronization. In the absence of no inductor signals, the load should be stopped working within 5-30sec, the indicator lamp is turned off.

– After the first sense is finished and it will sense again after 5-10s. The load should work. When there is no inductor signals in the indicator lamp, the load should be stopped working within 5-15sec.

– Press the button to 5lux on the minimum (MOON position). If it is adjusted in the less than 5LUX, the inductor load should not work after load stop working. If you cover the detection window with the opaque objects (towel etc), the load work .under no induction signal condition, the load should stop working within 5-15sec.

Note
Press every button, there will be a “red” led light flash in the sensor lens, which means the fuction has been change.

Note

– The unrest objects can’t be regarded as the installation basis-face.
– In front of the detection window there shouldn’t be hinder or unrest objects affecting detection.
– Avoid installing it near air temperature alteration zones for example: air condition, central heating, etc.
– In order to avoid the unexpected damage of product, please add a safe device of 6A when installing microwave sensor, for example, fuse, safe tube etc.

Some problem and solved way

– The load don’t work:
a. Check the power and the load.
b. Whether the indicator light is turned on after sensing? If yes, please check load.
c. If the indicator light is not turn on after sensing, please check if the working light corresponds to the ambient light.
d. Please check if the working voltage corresponds to the power source.

– The sensitivity is poor:

a. Please check the ambient temperature.

b. Please check the signal source is the detection fields.
c. Please check the installation height.

– The sensor can’t shut automatically the load:

a. If there are continual signal in the detection fields.
b. If the time delay is set to the longest.
c. If the power corresponds to the instruction.
d. If the air temperature changes near the sensor, air condition or central heating etc.

FAQs:

Q: How do I reset the sensor to its default settings?

A: To reset the sensor, locate the reset button on the device and press it for 10 seconds until the LED indicators flash.

Q: Can the sensor be used outdoors?

A: It is recommended to use the sensor indoors or in covered outdoor areas to protect it from harsh weather conditions.

IMPORTER:

Prima Group 2004 LTD,

Bulgaria, 1784 Soa, Mladost 1, bl. 144,

Ground Floor;

Phone: +359 2 988 45 72;

Documents / Resources

| OPTONICA 7324 Microwave Sensor Remote Highbay Sensor [pdf] User Manual
7324 Microwave Sensor Remote Highbay Sensor, 7324, Microwave Sensor Remote Highbay Sensor, Sensor Remote Highbay Sensor, Remote Highbay Sensor, Highbay Sensor, Sensor
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals