Kessil TOX End Feed Wiring O Type Track User Guide
- June 17, 2024
- Kessil
Table of Contents
TOX End Feed Wiring Guide
STEP-BY-STEP INSTRUCTIONS
Please refer to the Video Links for detailed, step-by-step instructions for wiring the end feed. Contact Kessil Customer Support (Kessil@Kessil.com) for any questions
https://www.youtube.com/watch?v=QWoxzFN4ZkY
READ AND SAVE ALL INSTRUCTIONS
- Disconnect electrical power before adding to or changing the configuration of the track.
- Do not install this track in damp or wet locations (IP20 , 45°C max).
- Do not install any part of a track system less than 5 ft. above the floor.
- Do not install track on any vertical surface.
- Check with a qualified electrician prior to any installation.
- Do not attempt to energize anything other than the Fiilex track lighting fixtures on the track.
- In order to reduce the risk of fire and electrical shock, do not attempt to connect power tools, extension cords, appliances and the like to the track.
- Do not slide light fixtures along track when relocating. Always remove fixtures and adapters from the track first.
- Before reinstalling in new location, make sure to properly secure the fixtures and adapters to the track.
Wire Power to End Feed
Each End Feed component has two (2) sets of 20A-max conductors for two (2) individual power circuits.
In order to correctly wire the system, the End
Feed has a mechanical key / groove (A) that ensures the correct insertion into
the track. When installing, ensure that the mechanical key is oriented
properly.
For the end feed, use either 5x AWG12 or 7x AWG12 wire. Unscrew and remove the
end-feed so that contacts are visible. Knock out either B or C to create a
hole, and then pass the wire through it. When passing the wire through hole C,
the screw cord grip must be used. When using hole B, we recommend a plastic
cord grip (not provided). Remove 3-3.5″ of protective covering from the wires,
then strip approximately 1/2″ off the wire.
End feed Component with pin-outs
Wire DMX to End Feed
DMX signal requires 2 signal carriers and the polarity of the DMX conductors are labelled on the next to corresponding screws.
Standard DMX Cabling and Polarity
Connector| | |
---|---|---|---
Description| DMX lighting standard| Architectural, corporate,
and fixed installations| Fiilex RPU, P3 / Q3 / G3.
Connector Pin-out| | |
Signal| Ground| 1| 7, 8| Tip
Data –| 2| 2| Ring1 (closest to tip)
Data +| 3| 1| Sleeve