POTTER FEP Series Flush Mount Expander Plate Fire Alarm Resources Owner’s Manual

June 9, 2024
POTTER

FEP Series Flush Mount Expander Plate
Fire Alarm Resources
Owner’s Manual

Application

The Potter FEP and SEP Series is an indoor wall mount expander plate with a quality colored lens strobe to be used in conjunction with a Potter speaker or wall mount  speaker/strobe allowing the ability to mount multiple strobes on a single electrical box. Applications include emergency communication, severe weather, evacuation,  emergency response and many more.

Description

The FEP Series is to be used in flush mount applications and the SEP Series is to be used in surface mount applications. The FEP and SEP Series strobes are to be used on a  24 VDC system and are available in amber, blue, green, and red lens colors. The amber lens units are provided with a turn dial for field selectable candela options. The blue, green and red lens units are only available in 15/75 candela option. The strobes can be synchronized using the Potter AVSM, FACP’s or power supplies that provide a Gentex  Synchronization Protocol. All units feature ALERT text on the lens.
The FEP and SEP Series are constructed of high impact textured plastic. The amber lens units additionally comply with the light output dispersion requirement of ANSI/UL  1971 for wall mount applications with a measured candela rating that is equal to the candela listed on the product.

Technical Specifications

Strobe Operating Voltage 16-33VDC
Synchronization Module Potter AVSM
Operating Temperature 32°F to 120°F (0°C to 49°C)
FEP Unit Dimensions 10.8”H X 6.6”W X 2.8”D
SEP Unit Dimensions 11.5” H X 7.26” W X 5.04” D
Back Box 4” square X 2.125” deep
Shipping Weight 1.5 lbs.

Product Listings

  • ANSI/UL1638

Product Compliance

  • NFPA 72
  • IBC/IFC/IRC

FEP Series Flush Mount Expander Plate

Model Number| Stock Number| Lens Color| Nominal Voltage| Candela(s)
FEP-A| 4890180| Amber| 24 VDC| 15, 30, 60, 75, 110
FEP-B| 4890181| Blue| 24 VDC| Fixed 15/75
FEP-G| 4890182| Green| 24 VDC| Fixed 15/75
FEP-R| 4890183| Red| 24 VDC| Fixed 15/75
SEP Series Surface Mount Expander Plate

Model Number| Stock Number| Lens Color| Nominal Voltage| Candela(s)
SEP-A| 4890184| Amber| 24 VDC| 15, 30, 60, 75, 110
SEP-B| 4890185| Blue| 24 VDC| Fixed 15/75
SEP-G| 4890186| Green| 24 VDC| Fixed 15/75
SEP-R| 4890186| Red| 24 VDC| Fixed 15/75
FEP/SEP Blue, Green, and Red Lens Strobe Current Ratings

Fixed 15/75 Candela Strobe
Lens Color| Regulated 24 VDC Max.
Operating Current (mA)| Regulated 24 VFWR Max
Operating Current (mA)
Blue| 280| 274
Green| 360| 479
Red| 397| 438
FEP/SEP Amber Lens Strobe Current Ratings

Candela| Regulated 24 VDC Max.
Operating Current (mA)| Regulated 24 VFWR Max
Operating Current (mA)
15| 78| 113
30| 96| 135
60| 137| 186
75| 180| 245
I I 0| 224| 313

NOTE:

  • For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered (FWR(Full Wave Rectified)) power see installation manual.
  • Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products.
  • The FEP/SEP series is not to be used as a visual public mode alarm notification appliance.

Wiring Diagram

CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS.
BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTION.

WIRE CONDUCTIVITY

18 AWG 60
16 AWG 95
14 AWG 153
12 AWG 244

NOTE: SPEAKER OR SPEAKER/STROBE USED WITH FEP OR SEP MUST BE ORDERED SEPERATELY.

  • MAX WIRE DISTANCE – – X WIRE CONDUCTIVITY PANEL VOLTAGE – DEVICE MINIMUM VOLTAGE TOTAL CURRENT DRAW
  • CAUTION: APPLIES ONLY TO REGULATED SUPPLIES.
  • NOTICE: POWER IS SUPPLIED TO DEVICES WHEN CONTROL PANEL IS LATCHED.

NOTE: All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits.
However use of the Potter AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn.

Candela Selection: FEP and SEP Only

Additional Mounting Notes:

  • Attach speaker or speaker/strobe using the mounting ring.
  • Level line is to aid in alignment during installation.
  • Includes wire strip guide.
  • Includes four base locations for additional screw support, if needed.

Installation FEP Flush Mount Expander Plate

Installation SEP Surface Mount Expander Plate

Architect and Engineering Specifications

The expander plate shall be Potter FEP or SEP Colored Lens Expander Plate or approved equivalent and shall be listed by Underwriters Laboratories, Inc.
per ANSI/UL 1638 and the amber lens shall have compliance with the polar dispersion requirements of ANSI/UL 1971. The FEP or SEP shall comply with all local, state  and federal fire alarm code/standards. The visual signal shall have a minimum 1 Hz flash rate regardless of input voltage. The unit shall have an input range of 16-33 volts  with either direct current of full wave rectified power for 24 volt models. All field wiring connections shall be made via separate in-out terminal connections.

Potter Electric Signal Company, LLC St. Louis, MO
Tech Support:866-956-1211 / Customer Service: 866-572-3005 
www.pottersignal.com
firealarmresources.com