TIS 350 AC DC Earth Leakage Clamp Meter Instruction Manual
- June 17, 2024
- TIS
Table of Contents
Instruction Manual
AC / DC Earth Leakage
Clamp Meter to 0.001A
SAFETY INFORMATION
Do not operate the tester if the body of meter or the test lead appear
damaged.
Check the main function dial and make sure it is at the correct position
before each measurement.
Do not perform resistance and continuity test on a live power system.
Do not apply voltage between the test terminals and test terminal to ground
that exceed the maximum limit indicated in this manual.
Ensure your hand and fingers are kept below the Safety Protection Ring (see
4-2 item 2).
Replace the battery when the symbol appears to avoid incorrect readings.
Environmental Conditions
Operation Temperature: 0°C to 40°C(32°F to 104°F); < 80 % RH
Storage Temperature: -10°C to 60°C(14°F to 140°F); < 80 % RH
Explanation Symbols
Attention refer to operation Instructions.
Dangerous voltage may be present at terminals.
This instrument has double insulation.
Approvals: EN61010 300V CAT IV
GENERAL SPECIFICATION
Digital Display:
4 digital liquid crystal (LCD), Maximum reading 5000 count.
Polarity:
When a negative signal is applied, the signal appears.
Low Battery Indication:
When the battery is below the correct operation range, will appear on the LCD
display.
Sample Rate:
2 times/sec for digital data.
Power Source:
1.5V size AAA battery X 2
Typical battery Life: (without buzzer, backlight)
Type: 15 hours at DCA function; 60 hours at ACA and ACV function; 100 hours at
DCV and Ohm function.
Auto Power Off:
If there is no key or dial operation for 30 minutes, the meter will power
itself off to save battery consumption. This function can be disabled by
pressing and holding the “ HOLD ” button then power the unit on
Over Load:
If the reading is greater than the maximum, the display indicates .
Maximum jaw opening:
∅ 23 mm
Dimensions:
206 x 76 x 33.5 mm
Weight:
262g (with batteries)
Accessories:
Carrying case, Batteries, Test Lead & Instruction Manual.
ELECTRICAL SPECIFICATION
The accuracy specification is defined as ± ( percent of reading + digit ) At 23±5°C, ≦80 %RH.
3-1 Direct Voltage
Range | Resolution | Accuracy |
---|---|---|
50V / 300V | 0.01V / 0.1V | 1.0% + 2dgts |
Input impedance: 1 MΩ
3-2 Alternating Voltage (True RMS)
Range | Resolution | Accuracy(40~1KHz) |
---|---|---|
50V / 300V | 0.01V / 0.1V | 1.2% ± 5dgts |
Input impedance: 1 MΩ
3-3 Direct Current
Range | Resolution | Accuracy |
---|---|---|
300.0mA | 0.1mA | 1.0% + 10dgts |
3.000A | 0.001A | |
10.00A | 0.01A | 3.0% + 10dgts |
Influence of terrestrial magnetism: Less than ±1.0mA
Influence of CT opening and closing: Less than ±1.0mA
3-4 Alternating Current (True RMS)
Range | Resolution | Accuracy(50~60Hz) |
---|---|---|
300.0mA | 0.1mA | 1.0% + 5dgts |
3.000A | 0.001A | |
20.00A | 0.01A |
3-5 Resistance (Ω)
Range | Resolution | Accuracy |
---|---|---|
500 Ω | 0.1Ω | 1.0% + 2dgts |
5KΩ | 1Ω | |
50KΩ | 10Ω | |
500KΩ | 100Ω |
3-6 Continuity
Range | Buzzer Function |
---|---|
Ohm < 100Ω |
DESCRIPTION OF THE INSTRUMENT
4-1 Description Of The Display
| Auto power off indication
---|---
| Polarity indication
| Low battery indication
| Alternative source indication
| Direct source indication
| Current measurement indication
| Voltage measurement indication
| ZERO indication
| Data hold indication
| Maximum indication
| Minimum indication
| Continuity test indication
| Measurement unit
| Resistance measurement indication
| Measurement unit
TEST INSTRUMENT SOLUTIONS
Unit 12/14, Luddite Way Business Par, Rawfolds Way
Rawfolds, Cleckheaton, BD19 5DQ
Telephone: 01274 752 407 Fax: 01274 870 175
Email: sales@tis-tic.co.uk
Web:
www.testinstrumentsolutions.co.uk
GCA000262-12000
4-2 Description Of Front And Rear
1 Current Sensing Clamp
2 Safety protection ring
3 Backlight button
4 Clamp opening handle
5 Function select dial
6 ZERO button| 7 Max/Min button
8 Data hold button
9 LCD display
10 COM input terminal
11 Positive input terminal
12 Battery compartment
---|---
BUTTON INSTRUCTION
5-1 HOLD Function
It is possible to freeze the value displayed by pressing the “HOLD” button.
Press the “HOLD” button again to exit the Hold mode.
5-2 MAX/MIN Function
When the “MAX/MIN” button is pressed, the meter enter MAX/MIN mode.
Press the button, to read MAX, MIN sequence. Press the button for 1 sec. or
more to exit the MAX/MIN mode.
When you turn the rotary switch on the Continuity Test.
Press the “MAX/MIN” button to select Resistance measurement, press the
“MAX/MIN” button again to select continuity test with buzzer.
5-3 ZERO Function
Press “ZERO” button to enter the Zero mode, ZERO Annunciate will appear and
Zero the display. The reading is stored as reference value for subsequent
measurement.
Press the ” ZERO ” button again, to exit the zero mode.
5-4 BACKLIGHT Function
When the ” ” button is pressed, the backlight will be turned on.
To disable the function, the button is pressed again. The backlight will be
automatically turned off after 30 seconds.
MEASURING INSTRUCTION
6-1 ACA Measurement:
With the clamp disconnected from any conductor, switch the function selector
to range.
Open the clamp by pressing the jaw-opening handle and insert the Cable to be
measured into the jaw.
Close the clamp and get the reading from the LCD panel.
Note: Before this measurement, disconnect any test lead with the meter
for safety.
In some cases where reading is difficult, press the HOLD button and read the
result later.
CORRECT
INCORRECT
The above diagrams are appropriate for standard current measurements.
However for leakage measurement the most accurate measurement is to clamp
around the live and neutral conductors simultaneously.
6.2 DCA measurement:
With the clamp disconnected from any conductor, switch the function selector
to range.
Press “ZERO” button to enter the zero reading.
Open the clamp by pressing the jaw-opening handle and insert the cable to be
measured into the jaw. Close the clamp and get the reading from the LCD panel.
Note: Before these measurements, disconnect any test lead from the meter
for safety.
In some cases where reading is difficult, press the “HOLD” button and read the
result later.
6-3 ACV Measurement:
WARNING!
Maximum Input Voltage is 300V AC/DC. Do not attempt to Take any voltage
measurement that may exceed this maximum to avoid Electrical shock hazard
and/or damage to this instrument.
Switch the main function selector to range.
Connect red test lead to “ + ” terminal and black one to the “COM”terminal.
Measure the voltage by touching the test lead tips to the circuit where the
voltage is expected.
Read the result from the LCD panel.
6-4 DCV Measurement:
Switch the main function selector to range.
Connect red test lead to “+”terminal and black one to the “COM” terminal.
Measure the voltage by touching the test lead tips to the circuit where the
voltage is expected.
Read the result from the LCD panel.
6-5 Continuity Test With Buzzer:
Switch the main function to range. Press the “MAX/MIN” to change from KΩ to
range.
Connect red test lead to “ + ” terminal and black one to the “COM” terminal.
Connect tip of the test leads to the points where the conduction condition
expected.
If the resistance is under 100Ω, the beeper will sound continuously.
6-6 Resistance Measurement
Switch the main function to range.
Connect red test lead to “ + ” terminal and black one to the “COM” terminal.
Connect tip of the test leads to the points where the value of the resistance
is expected.
Read the result from the LCD panel.
Note: When taking a value from a circuit system, make sure the power is
cut off and all capacitors have been discharged.
BATTERY CHANGING
When the battery voltage indicator appears on the LCD Display the battery
needs to be changed.
Before changing the battery, switch the main dial to “OFF ”and disconnect the
test leads.
Open the back cover by removing the screw.
Replace the old batteries with two new 1.5V(AAA Size) batteries, take care
with the correct polarity. Close the back cover and fasten the screw, taking
care not to over tighten.
MAINTENANCE
WARNING! Before opening the meter, disconnect both test lead and never
use the meter before the battery cover is closed.
CAUTION! To avoid contamination or static damage, do not touch the
circuit board without proper static protection.
8-1 MAINTENANCE / WARRANTY:
- If the meter is not going to be used for a long time, take out the batteries and do not store the meter in high temperature or high humidity environment.
- When taking current measurement, keep the cable at the center of the clamp which will produce more accurate test results.
- Repairs or servicing not covered in this manual must be performed by returning your instrument to T.I.S. for an under warranty repair (with proof of purchase) or outside of warranty for a quotation to repair.
8-2 CLEANING:
Periodically wipe the case with a dry cloth. Do not use abrasives or solvents
on these instruments.
References