PRODUCT INFORMATION
This product is a programming and communication gateway ideal for integration of third-party devices with TIS network. Additionally, it can be used as a modbus RTU master or slave converter.
PRODUCT SPECIFICATIONS
| Ports| RS232RS485RJ45| RS232 ASCII / HEX 2-way connection Modbus, RS485
ASCII / HEX 2-way connection Ethernet UDP – TCP/IP connection
---|---|---|---
| TIS Bus| Number of devices on 1 lienitis Bus Bus voltage Current consumption
Protection| Max. 6412-32 V DC<30 mA / 24 V DC Reverse polarity protection
| Function programmable options| PRG button| IP address 192.168.1.100
(default)
| Dimensions| Width x length x height| 90mm x 73mm x 76mm
| Housing| Materials Casing Colori rating| Fireproof ABS Black IP 20
Read Instructions
We recommend that you read this Instruction Manual before installation.
Safety instructions
Electrical equipment should only be installed and fitted by electrically
skilled persons. Failure to observe the instructions may cause damage to the
device and other hazards. These instructions are an integral part of the
product and must remain with the end customer
Programming
Advanced programming requires TIS Device Search software. Advanced software
programming knowledge should be obtained in the advanced training courses.
Simple Installation
DIN Rail mount facilitates installation. Fixing points are provided for
installation without the use of DIN rail.
Mounting Location
Install in a dry, well-ventilated location. Controllers may emit some
mechanical noise. Take this into account when deciding on a mounting location.
Data Cable
Use screened stranded RS485 data cable with four twisted pairs. Configure
devices in a “Daisy Chain.” Do not cut or terminate live data cables.
Warranty
We provide a warranty as required by law. A hologram warranty seal and product
serial number are provided on each device. Please send the description of the
defect with Product S/N to our dealer network.
INSTALLATION STEPS
-
Turn Off TIS Power supply
-
Mount the device on a DIN rail inside an approved enclosure. The device can also be installed without the use of DIN rail by two mounting screw holes.
-
Connect a Cat5e TIS network data cable to the TIS-BUS port as per the connection diagram. No need to loop the TIS-bus cable if 2 DIN rail modules are connected together from the side bus train terminal
WARNING! HIGH VOLTAGE
Complete the connection, as per the following steps:
CONNECTING TO ETHERNET
Connect the IP ethernet cable to the module’s RG45 ethernet port.
PARTY rd3 232RS TO CONNECTING
Connect as follows:
- 3rd-party device RS232 TX pin to TIS RS232 RX terminal.
- 3rd-party device RS232 RX pin to TIS RS232 TX terminal.
- 3rd-party device GND pin to TIS GND terminal.
- If required to use RS232 DTR pin in some 3rd-party devices, then connect it to TIS RS232 DTR terminal.
INSTALLATION STEPS
CONNECTING TO MODBUS RTU OR RS485 3rd PARTY
Connect as follows: Modbus RTU or 3-party device RS485 A pin to TIS RS485
D+ terminal. Modbus RTU or 3″-party device RS485 B pin to TIS RS485
D-terminal.
Turn on TIS power supply. The module’s PRG LED should start blinking
(PROGRAMMING MANUAL (PAIRING
TO PAIR THE MODULE TO APPLICATION AS A SERVER GATEWAY:
Press the PRG button for 6 seconds until the green LED turns on and produces a
steady light.
Go to the application’s Air configuration setting and follow the steps on the
app.
TO RESET THE IP ADDRESS SETTING TO THE DEFAULT ADDRESS (192.168.1.100):
Press the PRG button for 15 seconds until the red LED turns on and produces a
steady light.
TO DISABLE THE ADVANCED SECURITY LOCK SETTING IF ENABLED BY SOFTWARE:
Press the PRG button for 6 seconds until the green LED turns on and produces a
steady light.
PRG Button Blinks Red Color Rapidly
Reason: The module’s address conflicts with another device in the TIS
network. You need to press and hold the PRG button for 6 seconds so that the
module can get a new address.
Device PRG LED is not Blinking Device not Powered
Reason: Device is not powered on; no TIS-BUS 24V supply connected to the
device.
Device Ethernet LED is not blinking
Reason 1 : The ethernet cable is not plugged in to the module port
firmly
Reason 1: PC IP address is not in the same range as the IP Module
(192.168.1.xxxx).
Device Search software can not communicate with the module
Reason 2: Device search software was opened before setting the PC IP
address; you need to restart your software. Reason 3: Il linked by
ethernet cable, check the connectivity, disable the WiFi on your laptop/PC,
and restart the software.
Reason 4: TIS software is opened in the same PC. Close all TIS software
and open just one
Device Search software can only search the IP module but no other TIS
devices.
Reason: Could be a short in connection between devices in TIS bus network.
New IP address in the software could not be changed.
Reason: The module is protected. You need to press the PRG button for 6
seconds to open the protection for 2 minutes so that you can give the module a
new address
TIS app is not able to communicate with TIS devices in your local area network.
Reason 2: In app network settings, you should add the Subnet ID, Device
ID, and MAC Address of the IP-COM-PORT.
Reason 3: Some setting or address is wrong in the app.