TIS HVAC6-3A-T HVAC Controller System Ventilation and Heating Smart Instructions
- June 15, 2024
- TIS
Table of Contents
TIS HVAC6-3A-T HVAC Controller System Ventilation and Heating Smart
INFORMATION PRODUCT
Ventilation ,Heating smart a provides device This maintain help best to system Conditioning Air and ventilation adequate through quality air indoor good .comfort thermal and filtration with
SPECIFICATIONS PRODUCT
switching Output| Number of channels Nominal voltage VAV outputs| 6
0 – 230 V AC 50/60 Hz
0-10V / 50mA
---|---|---
Output switching current| Nominal current per channel Low current
Air condition controllers
Max switching current
Max Continues current| 3 A / VDC
2 A / VAC
3A / VDC
2A / VAC
Input| Temperature| Resistive temperature sensor
TIS Bus| Number of devices on 1 line
Bus voltage
Current consumption (Normal)
Current consumption (Peak)
Protection| Max. 64
12-32 V DC
<20 mA / 24 V DC
<100 mA / 24 V DC
Reverse polarity protection
Operation & programmable options| Cool, Heat, Aux
Fan speed control
VAV 0-10V
Look the buttons
Programming| Cool, Heat, Aux programmable outputs
Low, Medium, High linked outputs
Can set any voltage for Low, Med & High
Can look the Module buttons or unlock it.
Manual & via software
Dimensions| Width × Length × Height| 90mm × 73mm × 76mm
Housing| Materials
Casing color
IP rating| Fireproof ABS
Black
IP 20
Read Instructions
We recommend that you read this Instruction Manual before installation.
Safety instructions
Electrical equipment should only be installed and fitted by electrically
skilled persons.
Failure to observe the instructions may cause damage to the device and other
hazards.
These instructions are an integral part of the product and must remain with
the end customer.
Programming
This device can be tested and programmed manually. Advanced programming requires TIS Device Search software. Advanced software programming knowledge should be obtained in the advanced training courses.
Simple Installation
DIN Rail mount facilitates installation. Fixing points are provided for installation without the use of DIN rail.
Mounting Location
Install in a dry, well-ventilated location.
Controllers may emit some mechanical noises. Consider this when deciding on a
mounting location.
Data Cable
Use screened stranded RS485 data cable with four twisted pairs. Configure
devices in a “Daisy Chain.”
Do not cut or terminate live data cables.
Electrical Wires
The installer should adequately consider the total current consumption when selecting the wires.
Warranty
We provide a warranty as required by law.
A hologram warranty seal and product serial number are provided on each
device. Please send the description of the defect with Product S/N to our
dealer network.
INSTALLATION STEPS
-
Turn off the main electrical source before installation.
WARNING! HIGH VOLTAGE -
Mount the device on a DIN Rail inside an approved enclosure. The device can also be installed without the use of DIN Rail by two mounting screw holes.
-
Connect RS485 data cable to the TISBUS port as per the connection diagram. No need to loop the TIS-bus cable if 2 DIN Rail modules are connected together from the side bus train terminal.
-
Complete the connection, as per the following steps:
CONNECTING TO FCU/HVAC UNIT
Connect the cool (Y), heat (W), and fan speed wires (Low, Med, Heat) to their respective terminals on the module.
WARNING: For Aux connection you should configure the aux output (Y2, W2, O/B, humidifier or dehumidifier) in software before connecting it to the unit terminal. Each channel can control a maximum of 5A loads. The installer should make sure not to overload the channels.
Connect the supply wire (24V,110V, or 220V) to module COM connection. All inputs must have an appropriate voltage source and an MCB to protect that load circuit.
CONNECTING TO VAV UNIT
Connect the 0-10v wires of the unit to the module 0-10V connection.
TEMPERATURE SENSOR
If you want to use the HVAC as standalone device without the wall panel (thermostat).
Then connect TIS temperature sensor 2 wires to Temperature sensor terminal in the module.
-
Turn on the power source, and then test the loads by short pressing on the device’s local override buttons Cool, Heat, Aux, Low, Med, High.
PAIRING (MANUAL PROGRAMMING)
To pair the module to wall panel (thermostat) complete the following steps manually:
-
Press the PRG button for 6 seconds until the green LED steady turns on.
-
Go to the Air Conditioning page in your Luna TFT, Mars AC, Terre AC, or other thermostat panel, and turn the AC ON.
-
Test your air conditioning by changing the fan speed from low to medium to high. HVAC module should respond accordingly.
DISABLING/ ENABLING LOCAL OVERRIDE BUTTONS
-
To disable device’s local override buttons, press on the PRG button for 12 seconds until the LED starts blinking rapidly.
-
To enable device’s local override buttons if it was disabled, press on the PRG button for 12 seconds until the LED starts blinking rapidly.
TROUBLESHOOTING
PRG Button Blinks Red Color Rapidly| Reason: The Module address
conflicts with other device in TIS network, you need to press and hold the PRG
button for 6 seconds so the module can get new address
---|---
Device PRG LED is not Blinking; Device not Powered| Reason: Device is
not powered on; no TIS-BUS 24V supply connected to the device.
Device Button LED is ON but unit is not responding| Reason 1: Compressor
/ heat protection time enabled
Reason 2: Unit main supply is off.
Wall Panels can’t Pair with the Device| Reason 1: TIS-BUS connection has
a problem; check the wires and make sure there’s not a short in the
connection.
Reason 2: Manual programming function disabled in the device (default is
enabled).
Wall Panels can’t Control the Device Channels| Reason 1 : TIS-BUS
connection has a problem; check the wires and make sure there’s not a short in
the connection.
Reason 2 : Programming address is wrong.
HVAC Turned ON even when the Wall Thermostat is Off.| Reason 1: HVAC
stand-alone Logic enabled in software.
Reason 2 : another wall panel thermostat programmed to the same HVAC
module address.
Customer Support
Copyright © 2022 TIS, All Rights Reserved
TIS Logo is registered trademark of TIS CONTROL.
All of the specification are subject to change without notice.
TIS CONTROL PTY LIMITED
SA , AUSTRALIA
TIS CONTROL LIMITED
Wanchai, Hong Kong
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>