TIS MS-PIR-CM Detector Motion Mount Ceiling Instruction Manual

June 13, 2024
TIS

INSTALLATION MANUAL
TIS PIR SENOR
Ceiling-mount Motion Detector
Model: MS-PIR-CM
TIS MS-PIR-CM Detector Motion Mount Ceiling

**** PRODUCT INFORMATION

This product is a BUS-operated PIR sensor designed for automatic light adjustments in areas where motion detection is a priority.

PRODUCT SPECIFICATIONS

| PIR, Lux and Dry inputs| PIR motion sensor
Digital input. Open / Close
Length of connected wire to DI
Light intensity sensor| Dual element pyro-electric ceramic
2 Channels
< 350 meter
0 – 8000 Lux meter
---|---|---|---
| Temperature sensor| accuracy
Operating range
Respond time| +/- 0.3 C
-40°C – 85°C
5-30 Seconds
| TIS Bus| Number of devices on 1 line
Bus voltage
Current consumption| Max. 64
12-32 V DC
<15 mA / 24 V DC
| PIR Detection| PIR range
PIR detection angle| 4-6 meters (installation height 2.6 – 3 meters)
110° from the celling down
| Operation| Programming button
Indicator LED
TIS bus
Upgrading| For assignment of the physical address
Blue or red LED (optional)
TIS protocol messages and commands
1 X mini USB for upgrading
| Functions| Logic/ Timers
IR Code memory / Flags
Security function
IR receiver| 32 Timers and Logic conditions
250 IR code memory & flags
Away, Night, Day, fire alarm setting
8 buttons function
| Weight| Without packaging| 60g
| Dimensions| Width × length × height| 92mm × 92mm × 39mm
| Housing| Materials
Casing color
Base color
IR window cover
IP rating| Fireproof ABS & PC
Gray White
Black
Transparent White
IP 20
| Temperature range| Operation
Storage
Transport| -10…60°C
-20…50°C
-25…75°C
          | Air humidity| | <85% non-condensing

TIS MS-PIR-CM Detector Motion Mount Ceiling - fig

Read Instructions
We recommend that you read this Instruction Manual before installation.
Safety instructions
Electrical equipment should only be installed and fitted by electrically skilled persons.
Failure to follow the instructions may cause damage to the device and other hazards.
These instructions are an integral part of the product and must remain with the end customer.
Programming
Advanced programming requires knowledge of the TIS Device Search software and instruction in the TIS advanced training courses.
Simple Installation
You can use 2 screws to install this sensor on the celling.
Mounting Location
Install in a dry, indoor area with a suitable temperature and humidity range.
Data Cable
Use screened stranded RS485 data cable with four twisted pairs. Configure devices in a “Daisy Chain.”
Do not cut or terminate live data cables.
Warranty
There is a two-year warranty provided by law. The hologram warranty seal and product serial number are available on each device.

INSTALLATION STEPS

  1. Turn off TIS power supply.

  2. Rotate the sensor cover to open it.

  3. Remove the PCB from the holding pins.

  4. Open the wire holes, and insert the TISBUS cable in the sensor base.
    WARNING! HIGH VOLTAGETIS MS-PIR-CM Detector Motion Mount Ceiling -
VOLTAGE

  5. Mount the sensor base on the celling by 2 screws.

  6. Connect the TIS-BUS cable to the 4-pin terminal and Insert the terminal in the board. Make sure to connect the BUS cable to the green connector.

  7. Secure the board inside the sensor base using the base pins.

  8. Install the extra 3 screws (optional).

  9. Close the cover of the sensor.

  10. Turn the power supply ON. The sensor LED should turn on.

TROUBLESHOOTING

| The sensor’s LED blinks rapidly.| Reason: The sensor address conflicts with another device in the TIS network. You need to press and hold on the sensor PCB PRG button for 6 seconds so that the sensor can get a new address.
---|---|---
| The sensor’s LEDs do not turn ON, and the device is not powered.| Reason: The TIS 24V power supply is not connected to the TIS-BUS.
| The sensor fails to control the device channels.| Reason 1: The TIS-BUS connection has a problem, or the wire has a short.
Reason 2: The programming address is faulty.
| The sensor LED is always off, but it works fine.| Reason: LED is disabled in the software.
| The sensor’s sensitivity is not strong.| Reason 1: The sensitivity level is reduced in the software.
Reason 2: The ceiling where the sensor is installed is not high enough.

Copyright © 2022 TIS, All Rights Reserved
TIS Logo is registered trademark of TIS CONTROL.
All of the specification are subject to change without notice.
TIS CONTROL PTY LIMITED
SA , AUSTRALIA
TIS CONTROL LIMITED
Wanchai, Hong Kong
www.tiscontrol.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals