TIS CONTROL LIMITED RLY-8CH-16A Tis Latching Relay Instruction Manual
- June 13, 2024
- TIS CONTROL LIMITED
Table of Contents
TIS CONTROL LIMITED RLY-8CH-16A Tis Latching Relay Instruction Manual
PRODUCT SPECIFICATION
Output Switching Voltage| Number of channels Nominal voltage Max switching
voltage| 8 0230V AC 50/60 Hz 440VAC
---|---|---
Output switching current| Nominal current per channel Maximum total channel
load Max switching current Max continuous current| 16A 128 A 50A resistive,
20A florescent 20A VAC
TIS Bus| Number of devices on 1line Bus voltage Current consumption (Normal)
Current consumption (operation) Protection| Max 64 12:32VDC
12:32VDC
15 mA/24 VDC<35 mA/24 VDCReverse polarity protection
Operation| Programming button/LED 18 buttons Mechanical Switch By TS bus
Programming| For assignment of the physical address Manual ONJOFF and
programming Relay emergency operator IS protocol messages and commands Manual
& via software
Functions| Lighting control ONJOFF Curtain control Scenes Sequences| 8
separately controllable channels Can set 4 group of curtains open/close 8
different scenarios 8 different sequences
Dimensions| Width x Length x Height| 76mm x 144mm x 90mm
Housing| Materials Casing color Button color 1P rating| Fireproof ABS Black
Silver P20
| |
Read Instructions
We recommend that you read this Instruction Manual before installation.
Safety instructions
Electrical equipment should only be installed and fitted by electrically
skilled persons. Failure to observe the instructions may cause damage to the
device and other hazards. These instructions are an integral part of the
product and must remain with the end customer
Programming
This device can be tested and programmed manually. Advanced programming
requires TIS Device Search software. Advanced software programming knowledge
should be obtained in the advanced training courses.
Simple Installation
DIN Rail mount facilitates installation Fixing points are provided for
installation without the use of DIN rail
Mounting Location
Install in a dry, well-ventilated location Controllers may emit some
mechanical noise. Take this into account when deciding on a mounting location
Data Cable
Use screened stranded RS485 data cable with four twisted pairs. Configure
devices in a “Daisy Chain,” Do not cut or terminate live data cables
Electrical Wires
The installer should adequately consider the total current consumption when
selecting the wires. Recommended wire size for load light channels) and input
wires is 2.5-4 mm
Warranty
We provide a warranty as required by law. A hologram warranty seal and product
serial number are provided on each device. Please send the description of the
defect with Product SIN to our dealer network
INSTALLATION STEPS
-
Turn off the main electrical source before installation.
WARNING! HIGH VOLTAGE -
Mount the device on a DIN Rail inside an approved enclosure. The device can also be installed without the use of DIN Rail by two mounting screw holes.
-
Connect RS485 data cable to the TISBUS port as per the connection diagram. No need to loop the TIS-bus cable if 2 DIN Rail modules are connected together\ from the side bus train terminal.
-
Complete the load connection, light, floor heating, and shutter as per the following steps:
LIGHTS / APPLIANCES / FLOOR-HEATING CONNECTION
Connect the load electrical wires to outputs 1-8. Each channel can control a maximum of 16A loads. The installer should make sure not to overload the channels.
Load neutral wire should be linked to the neutral connection in DB enclosure.
SHUTTER / CURTAIN CONNECTION
Once you combine any 2 channels as shutter/curtain, then connect the shutteropen wire to the first channel and the shutter-close wire to the second channel. The shutter neutral wire should be linked to the neutral connection in DB enclosure.
WARNING: Do not connect curtain motor wires before combining (interlocking) 2 relay channels together as curtain mode to avoid causing damage to motors. Please read about how to manually program shutter/curtain pairing in this manual -
Connect the live (supply) wire to inputs. All inputs must have an appropriate voltage source and an MCB to protect that load circuit.
-
Turn on the power source, and then test the loads by short pressing on the device’s local override buttons 1-8.
MECHANICAL EMERGENCY SWITCH
This Relay contain 8 mechanical switches to be used during power supplier
failure.Simply use any screw driver to put the mechanical switch of each
channel to up (N position for ON, and to down position for OFF.
WARNING! Do not turn mechanical switch ON/OFF if it connects to curtain to avoid causing damage to motors.
PAIRING (MANUAL PROGRAMMING)
LIGHTS / APPLIANCES PROGRAMMING
All channels by default are used for lights/appliances control. You can pair
device light channels to any wall panels by doing the following:
-
Long press on any buttons 1-8 for 6 1» seconds. The LED indicator for the PR R pressed button will start blinking.
-
Short press on any wall lights buttons on the Luna, Mars, Terre or others panels.
-
Test the button on the panel by short\ pressing it for ON/OFF.
FLOOR HEATING PROGRAMMING
-
Long press on any buttons 1-8 for 6 1» seconds. The LED indicator for the P R pressed button will start blinking.
-
Go to floor heater page on any wall panel with the floor heating function, and press ON button to turn on the floor heating.
-
Test the floor heating by changing the temperature and turning it OFF/ON.
SHUTTER COMBINATION PROGRAMMING
You can change any 2 channels in sequence like CH1 & CH2, Ch3 & CH4, … CH7
& CH8 to be combined (interlocked) together to work as shutter/curtain
control. To combine these 2 channels, complete the following steps manually:
-
Press the PRG button for 3 seconds until the LED starts blinking rapidly.
-
Short press on the first button and then the second button that you want to combine as curtain control; for example, CH3 and CH4.
-
Wait for few seconds until the PRG LED stops blinking.
-
Test by turning the first button ON and then the second button. Both buttons should not turn ON together. If you see that the first button is turning the other button off, that means that your buttons are successfully combined as shutter/ curtain mode.
-
To program the curtain to any wall panel, press and hold the CH (shutter-Open) button for 6 seconds. The LED indicator of the pressed button will start blinking,
-
Short press on any button on the Luna, Mars, Terre or others wall panels.
-
Test the button on the panel by short pressing for open/stop. Do the same to program the Close channel with another button.
-
To cancel the curtain interlock and return to lighting mode, repeat steps 1-3 above.
TROUBLESHOOTING
PRG Button Blinks Red Color
Rapidly
Reason: The Module address conflicts with other device in TIS network, you
need to press and hold the PRG button for 6 seconds so the module can get new
address
Device PRG LED is not Blinking;
Device not Powered
Reason: Device is not powered on; no TIS-BUS 24V supply connected to the
device.
Device Button LED ON but lights
not ON
Reason 1: Lights’ neutral wire not connected
Reason 2: Channel protection delay time is enabled in software.
Wall Panels can’t Pair with the
Device
Reason 1: TIS-BUS connection has a problem; check the wires and make sure
there’s not a short in the connection.
Reason 2: Manual programming function disabled in the device (default is
enabled).
Wall Panels can’t Control the
Device Channels
Reason 1: TIS-BUS connection has a problem; check the wires and make sure
there’s not a short in the connection.
Reason 2 : Programming address is wrong.
Channel is turning off by itself
after few seconds
Reason: It is programmed as shutter / curtain combination, and running time
is enabled in the software.
Copyright © 2022 TIS, All Rights Reserved