POTTER PFC-6000 Series Fire Alarm Control Panels User Manual
- June 9, 2024
- POTTER
Table of Contents
PFC-6000 Series
Reporting Code Summary
(Panel Version 3.0)
Report by Point
The following table identifies the reporting codes generated for specific panel events when reporting by point.
Report By Point | SIA Format | Contact ID Format |
---|---|---|
Description | Event Code | Parameter |
System Power Up | RR | |
AC Power Trouble | AT | 10+id |
AC Power Trouble Restore | AR | 10+id |
Earth Trouble | YP | 10 00 |
Earth Trouble Restore | YQ | 10 00 |
Battery Trouble | YT | 10+id |
Battery Trouble Restore | YR | 10+id |
Battery Charger Trouble | IA | 10+id |
Battery Charger Trouble Restore | IR | 10+id |
RA-6075 Trouble | ET | 03+id |
RA-6075 Trouble Restore | ER | 03+id |
UD-1000 Trouble | ET | 04+id |
UD-1000 Trouble Restore | ER | 04+id |
SLCE-127 Trouble | ET | 05+id |
SLCE-127 Trouble Restore | ER | 05+id |
CA-6075 Trouble | ET | 07 00 |
CA-6075 Trouble Restore | ER | 07 00 |
CA-6500 Trouble | ET | 08 00 |
CA-6500 Trouble Restore | ER | 08 00 |
RA-6500 Trouble | ET | 09+id |
RA-6500 Trouble Restore | ER | 09+id |
PSN-1000 Trouble | ET | 10+id |
PSN-1000 Trouble Restore | ER | 10+id |
DRV-50 Trouble | ET | 13+id |
DRV-50 Trouble Restore | ER | 13+id |
RLY-5 Trouble | ET | 14+id |
RLY-5 Trouble Restore | ER | 14+id |
LED-16 Trouble | ET | 15+id |
LED-16 Trouble Restore | ER | 15+id |
FCB-1000 Trouble | ET | 16+id |
FCB-1000 Trouble Restore | ER | 16+id |
SPG-1000 Trouble | ET | 17+id |
SPG-1000 Trouble Restore | ER | 17+id |
FIB-1000 Trouble | ET | 18+id |
FIB-1000 Trouble Restore | ER | 18+id |
IP Reporting Ethernet Trouble | LT | 0 |
IP Reporting Ethernet Restore | LR | 0 |
DACT Line 1 Trouble | LT | 1 |
DACT Line 1 Restore | LR | 1 |
DACT Line 2 Trouble | LT | 2 |
DACT Line 2 Restore | LR | 2 |
DACT Communication Fail | YC | 0 |
DACT Communication Restore | YK | 0 |
Report By Point | SIA Format | Contact ID Format |
--- | --- | --- |
Description | Event Code | Parameter |
DACT Com 1 Trouble | YS | 100 |
DACT Com 1 Restore | YK | 100 |
DACT Com 2 Trouble | YS | 200 |
DACT Com 2 Restore | YK | 200 |
DACT Primary Target Trouble | YS | id (1-20) |
DACT Primary Target Restore | YK | id (1-20) |
Date Changed | JD | |
Time Changed | JT | |
Local Program Successful | LS | |
Remote Program Successful | RS | |
Remote Program Failed | RU | |
System Reset | OR | |
System Manual Test | RX | |
Periodic Test – Normal | RP | |
Periodic Test – Off Normal | RY | |
Fire Drill Begin | FI | |
Fire Drill End | FK | |
Printer Off-Line Trouble | VZ | 17+id |
Printer Off-Line Trouble Restore | VY | 17+id |
Printer Out of Paper Trouble | VO | 17+id |
Printer Out of Paper Restore | VI | 17+id |
PC Connect Supervision Trouble | NC | User |
PC Connect Supervision Restore | NC | User |
Disable Events | ||
Waterflow Disable | SB | id + Address* |
Aux Input Disable | UB | id + Address* |
Supervisory Disable | SB | id + Address* |
CO Disable | GB | Id + Address* |
All Other Disables | FB | id + Address* |
Enable Events | ||
Waterflow Enable | SU | id + Address* |
Aux Input Enable | UU | id + Address* |
Supervisory Enable | SU | id + Address* |
CO Enable | GU | id + Address* |
All Other Enables | FU | id + Address* |
Alarm Events | ||
Manual Pull Station | FA | id + Address* |
Water Flow | SA | id + Address* |
Aux Contact Input | UA | id + Address* |
CO Alarm | GA | id + Address* |
All Other Alarms | FA | id + Address* |
Alarm Restore Events | ||
Manual Pull | FH | id + Address* |
Water Flow | SH | id + Address* |
Aux Contact Input | UH | id + Address* |
CO Alarm | GH | id + Address* |
All Other Alarms | FH | id + Address* |
Supervisory Events | ||
Supervisory | SS | id + Address* |
Tamper | SS | id + Address* |
Report By Point | SIA Format | Contact ID Format |
--- | --- | --- |
Description | Event Code | Parameter |
CO Supervisory | GS | id + Address* |
Supervisory Restore | SR | id + Address* |
Tamper Restore | SR | id + Address* |
CO Supervisory Restore | GR | id + Address* |
Trouble Events | ||
Manual Pull Trouble | FT | id + Address* |
Waterflow Trouble | ST | id + Address* |
Aux Trouble | UT | id + Address* |
Supervisory Trouble | ST | id + Address* |
CO Trouble | GT | id + Address* |
All Other Troubles | FT | id + Address* |
Trouble Restore Events | ||
Manual Pull Trouble Restore | FJ | id + Address* |
Waterflow Trouble Restore | SJ | id + Address* |
Aux Trouble Restore | UJ | id + Address* |
Supervisory Trouble Restore | SJ | id + Address* |
CO Trouble Restore | GJ | id + Address* |
All Other Trouble Restore | FJ | id + Address* |
- see Identifying Points for address details
Report by Zone
The following table identifies the reporting codes generated for specific panel events when reporting by zone.
Report By Zone | SIA Format | Contact ID Format |
---|---|---|
Description | Event Code | Parameter |
System Power Up | RR | |
AC Power Trouble | AT | 10+id |
AC Power Trouble Restore | AR | 10+id |
Earth Trouble | YP | 10 00 |
Earth Trouble Restore | YQ | 10 00 |
Battery Trouble | YT | 10+id |
Battery Trouble Restore | YR | 10+id |
Battery Charger Trouble | IA | 10+id |
Battery Charger Trouble Restore | IR | 10+id |
RA-6075 Trouble | ET | 03+id |
RA-6075 Trouble Restore | ER | 03+id |
UD-1000 Trouble | ET | 04+id |
UD-1000 Trouble Restore | ER | 04+id |
SLCE-127 Trouble | ET | 05+id |
SLCE-127 Trouble Restore | ER | 05+id |
CA-6075 Trouble | ET | 07 00 |
CA-6075 Trouble Restore | ER | 07 00 |
CA-6500 Trouble | ET | 08 00 |
CA-6500 Trouble Restore | ER | 08 00 |
RA-6500 Trouble | ET | 09+id |
RA-6500 Trouble Restore | ER | 09+id |
PSN-1000 Trouble | ET | 10+id |
PSN-1000 Trouble Restore | ER | 10+id |
DRV-50 Trouble | ET | 13+id |
DRV-50 Trouble Restore | ER | 13+id |
RLY-5 Trouble | ET | 14+id |
RLY-5 Trouble Restore | ER | 14+id |
LED-16 Trouble | ET | 15+id |
LED-16 Trouble Restore | ER | 15+id |
FCB-1000 Trouble | ET | 16+id |
FCB-1000 Trouble Restore | ER | 16+id |
SPG-1000 Trouble | ET | 17+id |
SPG-1000 Trouble Restore | ER | 17+id |
FIB-1000 Trouble | ET | 18+id |
FIB-1000 Trouble Restore | ER | 18+id |
DACT Line 1 Trouble | LT | 1 |
DACT Line 1 Restore | LR | 1 |
DACT Line 2 Trouble | LT | 2 |
DACT Line 2 Restore | LR | 2 |
DACT Communication Fail | YC | 0 |
DACT Communication Restore | YK | 0 |
DACT Com 1 Trouble | YS | 100 |
DACT Com 1 Restore | YK | 100 |
DACT Com 2 Trouble | YS | 200 |
Report By Zone | SIA Format | Contact ID Format |
--- | --- | --- |
Description | Event |
Code
| Parameter| Qualifier| Event| Group| Zone
DACT Com 2 Restore| YK| 200| 3| 354| 00| 200
DACT Primary Target Trouble| YS| id (1-20)| 1| 354| 00| id
DACT Primary Target Restore| YK| id (1-20)| 3| 354| 00| id
DACT Secondary Target Trouble| YS| id (21-40)| 1| 354| 00| id
DACT Secondary Target Restore| YK| id (21-40)| 3| 354| 00| id
Date Changed| JD| | 1| 625| 00| 000
Time Changed| JT| | 1| 625| 00| 000
Local Program Successful| LS| | 1| 628| 00| 000
Remote Program Successful| RS| | 1| 412| 00| 000
Remote Program Failed| RU| | 1| 413| 00| 000
System Reset| OR| | 1| 305| 00| 000
System Manual Test| RX| | 1| 601| 00| 000
Periodic Test – Normal| RP| | 1| 602| 00| 000
Periodic Test – Off Normal| RY| | 1| 608| 00| 000
Fire Drill Begin| FI| | 1| 604| 00| 000
Fire Drill End| FK| | 3| 604| 00| 000
Printer Off-Line Trouble| VZ| 17+id| 1| 336| 17| id
Printer Off-Line Trouble Restore| VY| 17+id| 3| 336| 17| id
Printer Out of Paper Trouble| VO| 17+id| 1| 335| 17| id
Printer Out of Paper Restore| VI| 17+id| 3| 335| 17| id
PC Connect Supervision Trouble| NC| User| 1| 330| User| 00
PC Connect Supervision Restore| NC| User| 3| 330| User| 00
Disable Events| | | | | |
Waterflow Disable| SB| id + Address| 1| 571| id| Address
Aux Input Disable| UB| id + Address| 1| 571| id| Address
Supervisory Disable| SB| id + Address| 1| 571| id| Address
CO Disable| GB| id + Address| 1| 571| id| Address
All Other Disables| FB| id + Address| 1| 571| id| Address
Enable Events| | | | | |
Waterflow Enable| SU| id + Address| 3| 571| id| Address
Aux Input Enable| UU| id + Address| 3| 571| id| Address
Supervisory Enable| SU| id + Address| 3| 571| id| Address
CO Enable| GU| id + Address| 3| 571| id| Address
All Other Enables| FU| id + Address| 3| 571| id| Address
Zone Events| | | | | |
Fire Alarm| FA| zone| 1| 110| 00| zone
Fire Alarm Restore| FH| zone| 3| 110| 00| zone
Supervisory| SS| zone| 1| 203| 00| zone
Supervisory Restore| SR| zone| 3| 203| 00| zone
Aux Alarm| UA| zone| 1| 140| 00| zone
Aux Alarm Restore| UH| zone| 3| 140| 00| zone
Fire Zone – Trouble| FT| zone| 1| 373| 00| zone
Fire Zone – Trouble Restore| FJ| zone| 3| 373| 00| zone
Supervisory Zone – Trouble| ST| zone| 1| 373| 00| zone
Supervisory Zone – Restore| SJ| zone| 3| 373| 00| zone
Aux Zone – Trouble| UT| zone| 1| 373| 00| zone
Aux Zone – Trouble Restore| UJ| zone| 3| 373| 00| zone
Report by System
The following table identifies the reporting codes generated for specific panel events when reporting by system.
Report By System | SIA Format | Contact ID Format |
---|---|---|
Description | Event Code | Parameter |
System Power Up | RR | |
Date Changed | JD | |
Time Changed | JT | |
System Reset | OR | |
System Manual Test | RX | |
Periodic Test – Normal | RP | |
Periodic Test – Off Normal | RY | |
Remote Program Success | RS | |
Local Program Success | LS | |
Remote Program Fail | RU | |
Fire Drill Begin | FI | |
Fire Drill End | FK | |
System Alarm | FA | |
System Alarm Restore | FH | |
System Supervisory | SS | |
System Supervisory Restore | SR | |
System Trouble | FT | |
System Trouble Restore | FJ |
Identifying Points
In order to uniquely identify points in all situations, points on specific PLink devices are assigned a distinct address reporting range as shown in the table below:
Plink Device | Reported Address | Notes: |
---|---|---|
Built-in SLC and SLCE-127 | 1-127 | |
Built-in Power Supplies and PSN-1000/E | 301-310 | NAC1-6 reported as 301-306 |
I/O 1-4 reported as 307-310
DRV-50| 401-454| LED 1-50 reported as 401-450
Inputs 1-4 reported as 451-454
LED-16| 501-548| LED 1-48 reported as 501-548
RLY-5| 601-605| Relay 1-5 reported as 601-605
Example: A trouble associated with address 1 on a SLCE-127 #2.
Format:
SIA:
Contact ID| As shown in Table
FT id+Address
373 id+Address| Actual Reported Data
FT 02 001
373 02 001
---|---|---
Example: A trouble associated with NAC 1 on PSN-1000 #2
Format:
SIA:
Contact ID| As shown in Table
FT id+Address
373 id+Address| Actual Reported Data
FT 02 301
373 02 301
---|---|---
Example: A trouble associated with LED 1 on DRV-50 #2
Format:
SIA:
Contact ID| As shown in Table
FT id+Address
373 id+Address| Actual Reported Data
FT 02 401
373 02 401
---|---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>