ABB Magne 3 Electromagnetic Process Lock Instruction Manual
- June 17, 2024
- ABB
Table of Contents
Excerpts from Original instructions
Magne 3 and 4 Electromagnetic process lock
Complete Product Manual found at:
abb.com/lowvoltage
Product description
Magne is an electromagnetic process lock that locks a door or a hatch and is
intended for applications that are sensitive to unintentional or unnecessary
interruptions.
Magne has a holding force of up to 1500 N.
Magne can be installed on a door, preferably using an ABB mounting kit,
available for sliding doors or hinged (conventional) doors.
Magne 3 keeps a door locked. If used in safety applications, Magne 3 needs to
be complemented with an external interlocking device.
Magne 4 has an integrated Adam sensor which provides an interlocking function
together with an Eva actuator. The Eva actuator is ordered and installed
separately.
Magne 4 is available with integrated Adam DYN (DYNlink signal) or Adam OSSD
(OSSD signal) using M12 5-pole or M12 8-pole connector.
Anchor plates are delivered with a cellular rubber. Anchor plate 32E has an
integrated permanent magnet. Anchor plate 32D is without a magnet.
Y-connectors and other accessories are available to facilitate connection in
series.
Connections
M12 5-pole connector
- Brown: Locking signal +24 VDC
- White: Not used
- Blue: 0 V
- Black: Not used
- Grey: Info output, locked
M12 5-pole connector
- Brown: +24 VDC
- White: DYNlink signal in
- Blue: 0 V
- Black: DYNlink signal out
- Grey: Locking signal +24 VDC
M12 8-pole connector
- White: DYNlink signal in
- Brown: +24 VDC
- Green: Locking signal +24 VDC
- Yellow: 0 V
- Grey: Info output (Adam and Eva closed & Magne locked)
- Pink: DYNlink signal out
- Blue: 0 V
- Red: Not used
M12 8-pole connector
- White: DYNlink signal in
- Brown: +24 VDC
- Green: Locking signal +24 VDC
- Yellow: 0 V
- Grey: Info output (Adam and Eva closed)
- Pink: DYNlink signal out
- Blue: 0V
- Red: Info output (Locked)
M12 8-pole connector
- White: OSSD1 out
- Brown: +24 VDC
- Green: OSSD1 in
- Yellow: OSSD2 in
- Grey: Info output (Adam and Eva closed & Magne locked)
- Pink: OSSD2 out
- Blue: 0 V
- Red: Locking signal +24 VDC
Warning! Always use shielded cables to connect the unit to the rest of the
safety circuit.
Warning! The info output is non-failsafe and shall never be used to
control a safety application.
Warning! The DYNlink signal or OSSD signals are used to control the
safety application.
Note! Several Magne 3X units can be connected using a M12-3A Y-connector
or several Magne 4 OSSD-Info using a M12-3G Y- connector, but the info-signal
will not be available. Several Magne 4X DYN units can be connected using a
M12-3S Y-conector.
Safety precautions
Warning! Carefully read through the entire product manual before using
the device.
Warning! The devices shall be installed by authorized personnel following
the
Safety regulations, standards and the Machinery directive.
Warning! Failure to comply with instructions, operation that is not in
accordancewith the use prescribed in the instructions, improper installation
or handling of the device can affect the safety of people and the plant.
Installation
Installation shall be done in accordance with a risk assessment for the
individual application.
Warning! All safety functions shall be tested before starting up the
system.
Warning! Do not defeat, tamper or bypass the safety function. Failure can
result in death or serious injury.
Warning! The M12 connector shall be connected after Magne has been
installed on the intended surface.
Caution! Magne shall be installed as close to the door handle as
possible. The distance between the lock and the handle creates a lever effect,
reducing the holding force.
-
Install Magne and accessories as close to the door handle as possible. Use relevant mounting kit and follow the installation guide included in the kit. Installation tolerances for Magne 3 and JSM D23C on a sliding door:A. Magne
B. Anchor plate
C. Cellular rubber
D. Sliding door
E. Fence
X. 60 mm
Y. 69 mm ±5
Z. 18 mm ±5 -
Anchor plate (B) is installed with cellular rubber (C) between the anchor plate and the bracket (G) mounted on the door. The cellular rubber is attached to the anchor plate with adhesive tape and enables the anchor plate to adjust to Magne. Use suitable M8 screw (F). Recommended tightening torque is 7 Nm ±2.
Note! Do not compress the cellular rubber to a thickness less than 8 mm. Do not overtighten the screw. This can deform the anchor plate, causing reduced or no holding force. Make sure the surfaces of the electromagnet (A) and the anchor plate (B) are completely parallel, i.e. that full contact is obtained when the door is closed.
Installation tolerances:
X. ±3 mm sideways
Y. ±5 mm lengthways -
The safety functionality of Magne 4 is based on the integrated Adam sensor and the Eva actuator. Eva unit (A) must be correctly positioned above the yellow cover on Magne/Adam (B) when the door is closed.
Positioning tolerances:
X. ±5 mm sideways
Y. ±5 mm lengthways
Z. 2-7 mm Note! For the sensor to work as intended it is very important that the units are correctly positioned and that the safety functions are tested. -
Connect the pin out according to chapter ‘Connections’.
-
Connect the M12 connector to Magne.
Note! Make sure no power supply is connected when cable is fitted to the Magne M12 pin out. -
Close the door to put Eva within sensing distance of Adam.
-
Connect Magne to the power supply and turn power on.
Note! Only connect Magne to power supply when Eva is within sensing distance. The integrated Adam sensor in Magne 4 needs to learn the Eva code.
For Magne 3 the blue LED will illuminate with a solid light when connected.
For Magne 4 the green LED will illuminate with a solid light. The blue LED will illuminate with a solid light when the locking signal is activated. -
After installation, check the locking function.
Caution! After installation, check the locking function and that the surfaces of the magnet and the anchor plate are parallel, i.e. that full contact is obtained when the door is closed. If the anchor plate tilts, the holding force of the lock can be significantly reduced or eliminated.
Maintenance
Warning! The safety functions and the mechanics shall be tested
regularly. Check correct operation of all circuits and the locking function at
least once a year.
Warning! A defective unit shall be replaced with a new unit. Never bypass
the safety circuit.
Warning! In case of breakdown or damage to the product, contact nearest
ABB Electrification Sweden service office or reseller. Do not try to repair
the product yoursel f.
Warning! ABB will not accept responsibility for failure of the switch
functions if the installation and maintenance requirements shown in this
document are not implemented.
Caution! The electromagnet shall be regularly cleaned to maintain its
full holding force. Dirt or dust on the anchor plate or Magne can cause low or
no holding force.
Instructions regarding ‘Testing safety function’ and ‘Replacing Eva unit’ can
be found in the complete ‘Magne 3 and 4 Product Manual’ available on web.
LED indications
Model | LED Indication | Description | Safety circuit |
---|---|---|---|
Magne 3 + Magne 4 | Blue | Magne is locked | N/A |
Magne 3 + Magne 4 | Blue flashing | Lock signal, but Magne is not detecting the | |
anchor plate | N/A | ||
Magne 4 | Green | Eva within sensing distance of Adam (door closed) | Closed |
Magne 4 | Green flashing | Eva within 2 mm from maximum sensing distance (door | |
closed) | Open | ||
Magne 4 | Green-Red flashing | Eva within sensing distance, safety circuit | |
before this unit broken (door closed) | Open | ||
Magne 4 | Red | Eva out of sensing distance (door open) | Open |
Magne 4 | Red flashing | Eva code not stored in Adam | Open |
Magne 4 | Red fast flashing | Fail safe mode | Closed |
Magne 4 (OSSD) | Red-Red-Green fast flashing | Invalid input signal | Open |
Troubleshooting
LED Indication | Probable cause | Action |
---|---|---|
No LED light | No voltage | Check +24 VDC power supply. |
Blue flashing | Anchor plate is missing or notcentered | Check anchor plate |
position.
Magne 4:
Green flashing| Eva within 2 mm from maximum sensing distance| Adjust Eva
position.
Red solid light| Eva out of sensing distance, safety circuit broken (door
open)| Move Eva within sensing distance of Adam (close door).
Metal between Adam and Eva| Remove metal.
Green and Red at the same time| Unit is defective| Replace the unit.
Green-Red fast flashing| Valid Eva code missing| Perform procedure to replace
Eva. If fault indication remains, the unit is defective and must be replaced.
Red fast flashing| Fail safe mode| Power cycle (i.e.turn off power, wait for
one minute and turn it on again).
Green-Red flashing| Input signal is missing| 1. Check output signal from the
previous unit in the signal chain.
2. Turn off power supply.
3. Move Eva within sensing distance of Adam.
4. Power supply.
Red-Red-Greenfast flashing (OSSD only)| Invalid input signal| Power cycle
(i.e. turn off the power, wait for one minute and turn it on again). If
fault indication remains, check incoming signals.
Technical data
Manufacturer
Address| ABB Electrification Sweden AB SE-721 61 Västerås Sweden
Mechanical data
Anchor plate material| Iron with nickel coating
Electromagnet material| Iron with zink coating
Housing material| Anodized aluminum and polycarbonate
Potting material| PUR, epoxy
PCB coating material| SEPUR 540RT
Enclosure protection| IP67
Ambient temperature| Operating temperature: -20 °C to +50 °C
Storage temperature: -20 °C to +70 °C
Holding force| Up to 1500 N (on correct installation)
Anchor plate permanent magnet 32E holding force: 30 N
Humidity| 35-85 % (without ice formation or condensation)
Weight| Magne 3, Magne 4: 700 g
Anchor plate 32D/32E: 290 g
Electrical data
Operating voltage| Electromagnet +24 VDC ±15 %
Current consumption| +24 VDC:
Magne 3: 10 mA, Magne 4: 50 mA
Note! Any current drawn on outputs (e.g. the information output) will be an
additional input current on +24 VDC.
Locking signal:
Nominal: 250 mA at 24 VDC, max. 350 mA at 27.6 VDC
---|---
Information output| Max. 20 mA
Cable dimension| Cable dimensioning should be checked when connecting several
units in series. Standard cables from ABB have a cross sectional area of 0.34
mm2. Magne does not cause any power surge when locking is activated.
Connector| M12 5-pole male connector (Magne 3X, Magne 4X DYN)
M12 8-pole male connector (Magne 4 DYN-Info, Magne 4 DYN-2Info and Magne 4
OSSD-Info)
Safety / Harmonized standards
Conformity| European Machinery Directive 2006/42/EC
EMC directive 2014/30/EU
RoHS directive 2011/65/EU
RoHS3 directive 2015/863
Application standard compliance| EN ISO 14119:2013
Functional safety standard compliance| EN ISO 12100:2010
EN ISO 13849-1:2015, PL e/Category 4, PFHD = 4.50·10-9
EN ISO 13849-2:2012
EN 62061:2005+A1:2012+A2:2015, SIL3, PFHD = 4.50·10-9
EN 61508:2010, SIL3, PFHD = 4.50·10-9
Warning!| The safety related values are based on interlocking device
Eden and are not valid for the locking function.
Electrical safety standard compliance| EN 60204-1:2006 + A1:2009
EN 60664-1:2007
Electromagnetic compatibility standard compliance| EN 60947-5-2:2007+A1:2012
EN 60947-5-3:2013
Certifications| cULus, TÜV Süd
Information for use in USA/Canada (UL)
Enclosure| Type 1
Intended usage| Applications according to NFPA 79
Connecting cables| Cables to comply with CYJV/7, with a conductor area of min.
0.2 mm2.
Power source| The Limited Voltage / Current source must comply with one of the
following:
A) An isolating device such that the maximum open circuit voltage potential
available to the circuit is not more than 30 VDC and the current is limited to
a value not exceeding 8 amperes measured after one minute of operation.
B) A suitable isolating source in conjunction with a fuse in accordance with
UL248. The fuse shall be rated max. 3 A and be installed in the 30 VDC power
supply to the device in order to limit the available current.
Conductor area| Max. current limit for overload protection:
AWG (mm2) Amps
24 (0,20)2
22 (0,32)3
20 (0,52)5
18 (0,82)7
Further information regarding the interlock switch can be found in ‘Eden
Product Manual’ available on web.
Descriptions and examples show how the product works and can be used. It does
not mean that it fulfills the requirements for all types of machines and
processes. The buyer/user is responsible for installing and using the product
according to applicable standards and regulations. We reserve the right to
make changes to the product and the documentation without prior notice.