CyberPower OL1000RTXL2U Smart App UPS Systems User Manual

June 17, 2024
CyberPower

CyberPower-logo

CyberPower OL1000RTXL2U Smart App UPS Systems

CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-product-
image

Product Information

Specifications:

  • Models: OL1000RTXL2U, OL1500RTXL2U, OL2200RTXL2U, OL3000RTXL2U
  • Manufacturer: CyberPower Systems (USA), Inc.
  • Address: 4241 12th Avenue East Suite 400 Shakopee, MN 55379
  • Phone: 877-297-6937
  • Fax: 952-403-0009
  • Website: www.CPSww.com

Important Safety Instructions:

  • This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate the UPS.
  • CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an outlet that is not grounded. If you need to power-drain this equipment, turn off and unplug the unit.
  • CAUTION! The battery can power hazardous components inside the unit, even when the AC input power is disconnected.
  • CAUTION! The UPS should be placed near the connected equipment and easily accessible.
  • CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of conductive contaminants. (Please see specifications for acceptable temperature and humidity range).
  • CAUTION! (No User Serviceable Parts): Risk of electric shock, do not remove cover. No user serviceable parts inside. Refer servicing to qualified service personnel.
  • CAUTION! (Non-Isolated Battery Supply): Risk of electric shock, battery circuit is not isolated from AC power source; hazardous voltage may exist between battery terminals and ground. Test before touching.
  • CAUTION! To reduce the risk of fire, connect the UPS to a branch circuit with 12 amperes (OL1000) / 15 amperes (OL1500) / 20 amperes (OL2200) / 30 amperes (OL3000) maximum over-current protection in accordance with the National Electric Code, ANSI/NFPA 70.
  • CAUTION! The AC outlet where the UPS is connected should be close to the unit and easily accessible.
  • CAUTION! Please use only UL-marked mains cable, (e.g. the mains cable of your equipment), to connect the UPS to the AC outlet.
  • CAUTION! Please use only UL-marked power cables to connect any equipment to the UPS.
  • CAUTION! When installing the equipment, ensure that the sum of the leakage current of the UPS and the connected equipment does not exceed 3.5mA.
  • CAUTION! The OL1000 / OL1500 / OL2200 / OL3000 models may only be installed by qualified maintenance personnel.
  • CAUTION! Do not unplug the unit from AC Power during operation, as this will invalidate the protective ground insulation.
  • CAUTION! To avoid electric shock, turn off and unplug the unit before installing the input/output power cord with a ground wire. Connect the ground wire prior to connecting the line wires!
  • CAUTION! Do not use an improper size power cord as it may cause damage to your equipment and cause fire hazards.
  • CAUTION! Wiring must be done by qualified personnel.
  • CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Under no circumstances should this unit be used for medical applications involving life support equipment and/or patient care.
  • CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation from the aquarium can come in contact with metal electrical contacts and cause the machine to short out.

Product Usage Instructions

Installation:

  1. Ensure the UPS is placed in a temperature and humidity controlled indoor area, free of conductive contaminants.
  2. Connect the UPS to a grounded AC power outlet with fuse or circuit breaker protection.
  3. Use only UL-marked mains cable to connect the UPS to the AC outlet.
  4. Connect the equipment you want to protect to the UPS using UL-marked power cables.
  5. Ensure that the sum of the leakage current of the UPS and the connected equipment does not exceed 3.5mA.

Operation:

  1. Make sure the UPS is plugged into a functioning AC power outlet.
  2. Turn on the UPS using the power switch.
  3. The UPS is now ready to provide backup power to the connected equipment during power outages.

Maintenance:
Refer to the user manual for maintenance instructions and contact qualified service personnel for any servicing needs.

FAQ:

  • Q: Can I use the UPS for medical equipment?
    A: No, the UPS should not be used for medical applications involving life support equipment and/or patient care.

  • Q: Can I use the UPS near aquariums?
    A: No, using the UPS near aquariums can increase the risk of fire due to condensation coming in contact with metal electrical contacts.

CyberPower Systems (USA), Inc.

IMPORTANT SAFETY INSTRUCTIONS

This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate the UPS.

  • CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an outlet that is not grounded. If you need to power-drain this equipment, turn off and unplug the unit.
  • CAUTION! The battery can power hazardous components inside the unit, even when the AC input power is disconnected.
  • CAUTION! The UPS should be placed near the connected equipment and easily accessible.
  • CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of conductive contaminants. (Please see specifications for  acceptable temperature and humidity range).
  • CAUTION! (No User Serviceable Parts): Risk of electric shock, do not remove cover. No user serviceable parts inside. Refer servicing to qualified service personnel.
  • CAUTION! (Non-Isolated Battery Supply): Risk of electric shock, battery circuit is not isolated from AC power source; hazardous voltage may exist between battery terminals and ground. Test before touching.
  • CAUTION! To reduce the risk of fire, connect the UPS to a branch circuit with 12 amperes (OL1000) / 15 amperes (OL1500) / 20 amperes (OL2200) / 30 amperes (OL3000) maximum over-current protection in accordance with the National Electric Code, ANSI/NFPA 70.
  • CAUTION! The AC outlet where the UPS is connected should be close to the unit and easily accessible.
  • CAUTION! Please use only UL-marked mains cable, (e.g. the mains cable of your equipment), to connect the UPS to the AC outlet.
  • CAUTION! Please use only UL-marked power cables to connect any equipment to the UPS.
  • CAUTION! When installing the equipment, ensure that the sum of the leakage current of the UPS and the connected equipment does not exceed 3.5mA.
  • CAUTION! The OL1000 / OL1500 / OL2200 / OL3000 models may only be installed by qualified maintenance personnel..
  • CAUTION! Do not unplug the unit from AC Power during operation, as this will invalidate the protective ground insulation.
  • CAUTION! To avoid electric shock, turn off and unplug the unit before installing the input/output power cord with a ground wire. Connect the ground wire prior to connecting the line wires!
  • CAUTION! Do not use an improper size power cord as it may cause damage to your equipment and cause fire hazards.
  • CAUTION! Wiring must be done by qualified personnel.
  • CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Under no circumstances this unit should be used for medical applications involving life support equipment and/or patient care.
  • CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation from the aquarium can come in contact with metal electrical contacts and cause the machine to short out.
  • CAUTION! Do not dispose of batteries in fire as the battery may explode.
  • CAUTION! Do not open or mutilate the battery, released electrolyte is harmful to the skin and eyes.
  • CAUTION! A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed when working on batteries
    • Remove watches, rings or other metal objects.
    • Use tools with insulated handles.
  • CAUTION! The unit has a dangerous amount of voltage. When the UPS indicators is on, the units may continue to supply power thus the unit’s outlets may have a dangerous amount of voltage even when it’s not plugged in to the wall outlet.
  • CAUTION! Make sure everything is turned off and disconnected completely before conducting any maintenance, repairs or shipment.
  • CAUTION! Connect the Protection Earth (PE) safety conductor before any other cables are connected.
  • WARNING! (Fuses): To reduce the risk of fire, replace only with the same type and rating of fuse.

DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE!

  • DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE HOUSING!
  • DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO UPS OUTPUT SOCKETS!
  • SERVICING OF BATTERIES SHOULD BE PERFORMED OR SUPERVISED BY PERSONNEL KNOWLEDGE OF BATTERIES AND THE REQUIRED PRECAUTIONS. KEEP UNAUTHORIZED PERSONNEL AWAY FROM BATTERIES!

UNPACKING

CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01 \(1\) CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01
\(2\)

HARDWARE INSTALLATION

HARDWARE INSTALLATION
These versatile UPS systems can be mounted in a rackmount or vertical tower orientation. This versatility is especially important to growing organizations with changing needs that value having the option to position a UPS on a floor or in a rackmount system. Please follow the instructions below for the respective mounting methods.

SAFETY PRECAUTIONS
CAUTION! To prevent the risk of fire or electric shock, only use the supplied hardware to attach the mounting brackets.

RACKMOUNT INSTALLATION

  1. Step 1: Rackmount ears installation
    Attach the two rackmount ears to the UPS using the provided screws M5X8L*8pcs. CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01 \(1\)

  2. Step 2: Rackmount rail Installation
    The rails adjust to mount in 48-cm (19-inch) panel racks from 52 to 91.5cm (20.5 to 36 inches) deep. Select the proper holes in the rack for positioning the UPS in the rack. The UPS takes up position 1 through position 6.

  3. Step 3: Adjust rackmount rails to fit your rack

  4. Attach the rackmount rail to your rack with two M5X12L screws and two plastic washers at the front of the rack. (Located in position 1 & position 6) Do not tighten the screws.

  5. Adjust the rail size on the rail assembly of your rack. Secure the rail to the rear of the rack with two M5X12L screws and two plastic washers. Tighten all screws at the front and rear of the rail. Once completed, perform the same steps for assembling the other rackmount rail. CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01 \(3\)

  6. Place the UPS on a flat stable surface with the front of the unit facing toward you. Secure the UPS to your rack with four M5X12L screws at the front of the rack. (Located in position 2 & position 5)

VERTICAL/TOWER INSTALLATION

  1. Step 1: Adhere the rubber feet on the bottom side of base stands
    Adhere the protective rubber feet on the bottom side of base stands (rackmount ears) and UPS. CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01
\(3\)

  2. Step 2: Attach the base stands and attach the dust covers
    Tighten the screws (M5X12*4pcs) of the base stands (rackmount ears) onto the bottom of the UPS. Insert dust covers into the screw holes that are not being used.

  3. Step 3: Rotate the Multifunction LCD Module
    Unscrew the upper panel of the UPS. Separate the upper panel from the UPS. Gently lift the LCD module out. Rotate it to the tower orientation. Reinstall it for a tower configuration.
    CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01 \(4\)

ELECTRICAL INSTALLATION
After completing the hardware installation of the UPS, you are now ready to plug in the UPS and connect your equipment.

SAFETY PRECAUTIONS

  • CAUTION! Installation environment should be in a temperature and humidity controlled indoor area free of conductive contaminants. Do not install this UPS where excessive moisture or heat is present (Please see specifications for acceptable temperature and humidity range).
  • CAUTION! Never install a UPS, or associated wiring or equipment, during a lightning storm.
  • CAUTION! Do not work alone under hazardous conditions.
  • CAUTION! In case of the risk of electric shock, do not remove the top cover.
  • CAUTION! The battery can energize hazardous live parts inside even when the AC input power is disconnected.

INSTALLING YOUR UPS SYSTEM

SYSTEM BLOCK DIAGRAM
CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01 \(5\)

HARDWARE INSTALLATION GUIDE

  1. Battery charge loss may occur during shipping and storage. Before using the UPS, it’s strongly recommended to charge batteries for four hours to ensure the batteries’ maximum charge capacity. To recharge the batteries, simply plug the UPS into an AC outlet.

  2. When using the included software, connect either the serial or the USB cable between the computer and the corresponding port on the UPS. Note: If the USB port is used, the serial port will be disabled. They cannot be used simultaneously. After connecting to either the USB port or the Serial port on the UPS, a computer with the PowerPanel® Business Edition Agent software installed can control the operating schedule, battery test, outlets, as well as obtain UPS status information. However, other computers with PowerPanel® Business Edition Client software can only obtain UPS status information via LAN connection.

  3. Connect your computer, monitor, and any externally-powered data storage device (Hard drive, Tape drive, etc.) into the outlets only when the UPS is off and unplugged. DO NOT plug a laser printer, copier, space heater, vacuum, paper shredder or other large electrical device into the UPS. The power demands of these devices will overload and possibly damage the unit.

  4. To protect a fax machine, telephone, modem line or network cable, connect the telephone or network cable from the wall jack outlet to the jack marked “IN” on the UPS and connect a telephone cable or network cable from the jack marked “OUT” on the UPS to the modem, computer, telephone, fax machine, or network device.

  5. Press the ON/OFF switch to turn the UPS on. The Power-On indicator light will display when activated. If an overload is detected, an audible alarm will sound and the UPS will continuously emit two beeps per second. For resetting the unit, unplug some equipment from the outlets. Make sure your equipment carries a load current within the unit’s safe range, (refer to the technical specifications).

  6. This UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will automatically charge, even when the unit is switched off.

  7. To maintain an optimal battery charge, leave the UPS plugged into an AC outlet at all times.

  8. Before storing the UPS for an extended period of time, turn the unit OFF. Then cover it and store it with the batteries fully charged. Recharge the batteries every three months to ensure good battery capacity and long battery life. Maintaining a good battery charge will help prevent possible damage to the unit from battery leakage.

  9. The UPS has one USB port (default) and one Serial port that allows connection and communication between the UPS and any attached computer running the PowerPanel® Business Edition Agent software. The UPS can control the computer’s shutdown during a power outage through the connection while the computer can monitor the UPS and alter various programmable parameters. Note: Only one communication port can be used at a time. The port not in use will automatically become disabled or the serial port will be disabled if both ports are attached.

  10. EPO (Emergency Power Off) Port:
    EPO ports allow administrators the capability to connect the UPS unit to customer-supplied EPO switches. These installations give operators a single access point to immediately power-off all equipment connected to the UPS during an emergency.

  11. To avoid electric shock, turn the unit OFF and disconnect the unit from utility power before hardwiring the UPS (in/out power cord). The in/out power cord MUST be grounded.

  12. Please note the internal UPS temperature will increase when fans are not in operation or ventilation is obstructed. When the high temperature sensor activates protection, the UPS generates an alarm and shuts down to avoid unexpected equipment damage. When the over temperature occurs, please check the Trouble Shooting section on page 15. If the condition persists, please contact CyberPower for technical support.

BASIC OPERATION

POWER MODULE FRONT/REAR PANEL DESCRIPTION

  1. Power Button / Power on Indicator
    Master ON/OFF for the UPS. Indicates that the UPS is on and supplying power.

  2. UPS Status / Fault / Replace Battery LED Indicator
    Indicates the status of the UPS, displaying whether it is operating in Line, Battery or Bypass Mode, if it has an internal fault or if the battery needs to be replaced.

  3. Multifunction LCD Readout
    Shows UPS status, information, settings and events.

  4. Function Buttons
    Scroll up, scroll down, select and cancel LCD menu.

  5. Input Circuit Breaker
    Provides input overload and fault protection.

  6. Battery Backup & Surge Protected Outlets
    Provides battery backup and surge protection. They ensure power is provided to connected equipment over a period of time during a power failure.

  7. Critical / Noncritical Load
    Allows the creation of load priorities to ensure that battery power reserves are transferred to specified outlets during a power outage. The unit can be programmed to provide additional runtime for equipment connected to the “CRITICAL” outlets, while stopping the power supply to equipment connected to “NONCRITICAL” outlets after a designated period of time.

  8. Serial Port
    Serial port provides communication between the UPS and the computer. The UPS can control the computer’s shutdown during a power outage through the connection while the computer can monitor the UPS and alter its various programmable parameters.

  9. USB port
    This is a connectivity port which allows communication and control between the UPS and the connected computer. It is recommended to install the PowerPanel® Business Edition Agent software on the PC/Server connected with the USB cord.

  10. Surge Protected Communication Ports
    RJ-45/RJ-11 These ports are used to protect standard RJ-45/RJ-11 based products (ADSL, LAN, Phone/ Modem-Lines) and cabling systems from surges.

  11. Relay Output Connector
    Convert UPS signals into real potential-free Dry Contacts for industrial control.

  12. SNMP/HTTP Network slot
    Slot to install the optional SNMP card for remote network control and monitoring.

  13. Extended Runtime Battery Module Connector
    Connection for additional CyberPower XL Battery modules.

  14. EPO (Emergency Power Off) Connector
    Enables an emergency UPS Power-Off from a remote location.

  15. AC Input Inlet
    Connect the AC Power cord to a properly wired and grounded outlet.

CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01 \(6\) OL1000RTXL2U / OL1500RTXL2U / OL2200RTXL2U / OL3000RTXL2U CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01
\(7\)

OL1000RTXL2U / OL1500RTXL2UCyberPower-OL1000RTXL2U-Smart-App-UPS-
Systems-01 \(8\)

OL2200RTXL2U CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01
\(9\)

OL3000RTXL2U

OPERATION INSTRUCTIONS FOR LCD MODULE

CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01
\(10\)

LED INDICATORS – UPS STATUS

LED Indicators Color UPS Status Description
ON/OFF White UPS power is on.
ON- LINE Green UPS is operating in Line Mode.
BATTERY ON Yellow UPS is operating in Battery Mode.
BYPASS Yellow UPS is operating in Bypass Mode, Manual Bypass or ECO

(Economy) Mode.
FAULT| Red| UPS has an internal fault. See “Trouble Shooting” for additional information.
REPLACE BATTERY| Red| Battery will soon need to be replaced due to insufficient runtime.

LCD SCREEN – UPS STATUS

LCD Screen UPS Status Description
Line Mode UPS is operating in Line Mode.
Battery Mode UPS is operating in Battery Mode.
Bypass Mode UPS is operating in Bypass Mode.
Manual Bypass UPS is operating in Manual Bypass.
ECO Mode UPS is operating in ECO (Economy) Mode.

BUTTON OPERATION

Button Operation Description
ON/OFF Press this button to turn on or turn off UPS.
Press this button to scroll up in the LCD menu.
Press this button to scroll down in the LCD menu.
ENTER Press this button to select an option.
ESC Press this button to cancel or return to previous LCD menu.

LCD SETUP FUNCTIONS

MULTI-FUNCTION LCD MAIN MENU
Press “Enter” button to activate “MAIN MENU”.

MAIN MENU submenu Function Description
Information Displays the UPS information.
Configure Displays the UPS settings that can be configured by the user.
Event Log Displays  the  5  most recent  events, by  event count, time

(day/hour/minute), and event description.

LCD INFORMATION READOUT
There are 19 types of UPS information available for display.

  1. Press the “ENTER” button to activate the “MAIN MENU”.
  2. Press the “▲” and “▼” buttons to scroll to the “Information” option.
  3. Press the “ENTER” button to select the “Information” submenu.
  4. Press the “▲” and “▼” buttons to scroll through the “Information” submenu in the following table.
  5. Press the “ESC” button to return to UPS Status.
Information Submenu Description
O/P Volt     = XXX.XV Displays the Output Voltage
O/P Freq    = XX.XHz Displays the Output Frequency
I/P Volt      = XXX.XV Displays the Input Voltage
I/P Freq     = XX.XHz Displays the Input Frequency
O/P Load =  XXX% Displays the Output Load as a Percentage of Maximum

load
O/P Amp    =     X.XA| Displays the Output Current
O/P Watt    =XXXXXW| Displays the Output Wattage
O/P VA      =XXXXXVA| Displays the Output VA
BAT Volt = XXX.XV| Displays the Battery Voltage
BAT Cap =  XXX%| Displays the Estimated Percentage of Battery Capacity
BAT Runtime=XXXM| Displays the Estimated Battery Runtime in Minutes
EBM Number=      X| Displays the External Battery Module Number
TEMP =XX°C / XXX°F| Displays the Approximate inside Temperature in both ℃(Celsius) and ℉ (Fahrenheit) for the UPS
SBM = XXXXX XH(M)| Displays the stage of Smart Battery Management with Operation Time
Rating = XXK VA| Displays the UPS Rating
MCU Ver =     XXXX| Displays the MCU Firmware Version
Model Name| Displays the UPS Model Name
Date & Time **– – – – / – – / – –    – -:- –| Displays the present Date & Time
Next BAT Change XXX / XXXX**| Displays the next Battery Change Date & Time

LCD EVENT LOG
5 Event Logs of UPS can be recorded.

  1. Press the “ENTER” button to activate the “MAIN MENU”.
  2. Press the “▲” and “▼” buttons to scroll to the “Event Log” option.
  3. Press the “ENTER” button to select the “Event Log” submenu.
  4. Press the “▲” and “▼” buttons to scroll through the “Event Log” submenu in the following table.
  5. Press the “ESC” button to return to UPS Status.
Event Log Submenu Description
(X) XXDXXHXXM (without PowerPanel® Business or RMCARD) – – /————– (with

PowerPanel® Business or RMCARD)
| Event Content

MULTI-LANGUAGE INTERFACE
Users can configure 1 of the 4 available languages for display.
([English], [Español-Spanish], [Français-French], [Deutsch-German])

  1. Press the “ENTER” button to activate the “MAIN MENU”.

  2. Press the “▲” and “▼” buttons to scroll to the “Configure” option.

  3. Press the “ENTER” button to select the “Configure” submenu.

  4. Press the “▲” and “▼” buttons to scroll through the “Language” options.

  5. Press the “ENTER” button to select the “Language” submenu.

  6. Press the “▲” and “▼” buttons to scroll to the language that you want to select.
    You may be prompted to save the selection, if so press the “ENTER” button to save the setting.

  7. Press the “ESC” button to cancel or return to previous LCD menu.

LCD SETTINGS CONFIGURATION
There are 22 UPS settings that can be configured by the user.

  1. Press the “ENTER” button to activate the “MAIN MENU”.

  2. Press the “▲” and “▼” buttons to scroll to the “Configure” option.

  3. Press the “ENTER” button to select the “Configure” submenu.

  4. Press the “▲” and “▼” buttons to scroll to the “Configure” submenu in the following table.

  5. Press the “ENTER” button to select the setting you want to configure.
    The first configuration parameter will be displayed on the second column of LCD screen.

  6. Press the “▲” and “▼” buttons to scroll through the different parameters.

  7. Press the “ENTER” button to select the parameter you want to change.
    You may be prompted to save the selection, if so press the “ENTER” button to save the setting. Some options are saved and started automatically. (See the following table for additional details.)

  8. Press the “ESC” button to cancel or return to the previous LCD menu.

LCD SETUP FUNCTIONS

Configure Submenu Available Settings Default Setting
**Output Voltage*** = [100V] [110V] [115V] [120V] [125V] 120V
Sync Freq Window Range= [+/- 1%] [+/- 2%] [+/- 3%] [+/- 4%] [+/- 5%]
[+/- 6%] [+/- 7%] [+/- 8%] [+/- 9%] [+/-10%] +/- 5%
Bypass V Window Range= [+10%/-10%] [+10%/-15%] [+10%/-20%] [+15%/-10%]
[+15%/-15%] [+15%/-20%] +10%/-15%
Bypass Condition [Check Freq/Volt] [Check Volt Only] [No Bypass] Check

Freq/Volt
| [Disable] [Enable]| Disable
ECO Mode**|
| [V Range= +/-15%] [V Range= +/-10%]  (for [Enable])| V Range= +/-10%
Manual Bypass| [Disable] [Enable]| Disable
Battery Test| [Activate?]| None
Audible Alarms| [Disable] [Enable]| Enable
EBM Number| = [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]| 0
Wiring Fault| [Disable] [Enable]| Disable
NCL Control| [Outlet On] [Outlet Off]| Outlet On
Language| [English] [Español-Spanish] [Français-French] [Deutsch- German]| English
**Generator Mode***| [Disable] [Enable]| Disable
Communication| [Disable] [Enable]| Enable
Dry Relay Set| [I/P Power Fail] [Battery Low] [Summary Alarm] [UPS On Bypass] [UPS Fail]| I/P Power Fail
Converter Mode**| [Converter Off] [O/P Freq = 50Hz] [O/P Freq = 60Hz]| Converter OFF
Screen Saver| [Disable] [1 Minutes] [5 Minutes]| 5 minutes
Clear Event Log| [Activate?]| None
Button OFF LOCK| [Disable] [Enable]| Disable
Charger Function| [SBM] [Constant]| SBM
Signal Inputs| [Disable] [EPO] [ROO]| Disable
Charger Check| [Disable] [Enable]| Disable

  • *) 100V are derated by 20%, 110 V are derated by 10%
  • Output voltage default setting depends on different nation or order requested.
  • **) This function can’t be set when Manual Bypass, Generator Mode or Converter Mode is enabled.
  • ***) UPS has no bypass when Generator Mode is enabled.
  • ****) UPS has no bypass when Converter Mode is enabled. This function can only be set before the UPS is on.

LCD SETUP FUNCTIONS

SILENCING AUDIBLE ALARMS

  1. Press any of four function buttons on the LCD module; Note: the alarm can not be turned off for a “Battery Low” condition. This condition will still result in an audible alarm.
  2. Change the ‘Audible Alarms’ option to ‘Disable’ in the LCD screen and it will no long give an audible alarm for any malfunction.

MANUAL BATTERY TEST
Select ‘Active’ in the ‘Battery Test’ portion of the LCD screen and the unit will perform a manual battery test.

GRAPHICAL LOAD/BATTERY CAPACITY DISPLAY

  1. Press the “ESC” button to return to UPS Status.
  2. Press the “▲” and “▼” buttons to scroll to the “LOAD“ and “BAT“ Capacity.
  3. Press the “▲” and “▼” buttons to scroll to the “Charging” or “Discharging” Capacity.CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01 \(6\)

LCD MODULE REMOTE CONTROL and WALL-MOUNTING INSTRUCTIONS

REMOTE CONTROL

  1. Step 1: Remove the Multifunction LCD Module
    Unscrew the right panel of the UPS. Separate the right panel from the UPS. Gently lift the LCD module out. Reinstall the right panel.

  2. Step 2: Connect the DB26 Cable
    Connect the DB26 cable from LCD module to the “Remote Control Port” on the front panel as shown in the following figure. CyberPower-OL1000RTXL2U-Smart-
App-UPS-Systems-01 \(7\)

WALL-MOUNTING INSTRUCTIONS

  1. Step 1: Remove the Multifunction LCD Module
    Unscrew the right panel of the UPS. Separate the right panel from the UPS. Gently lift the LCD module out. Reinstall the right panel.

  2. Step 2: Rotate the DB26 Connector of LCD Module

  3. Step 3: Connect the DB26 Cable
    Connect the DB26 cable from LCD module to the “Remote Control Port” on the front panel as shown in the following figure.

  4. Step 4: Mount LCD Module on the Wall CyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01 \(11\)

SAFETY PRECAUTIONS

  • CAUTION! It must be done by qualified personnel.
  • CAUTION! To avoid electric shock, turn off and unplug the unit before installing REMOTE CONTROL or WALL-MOUNTING INSTRUCTIONS.

MAINTENANCE

  • Storage
    To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to ensure battery life.

  • Battery Replacement
    Please read and follow the Safety Instructions before servicing the battery. Battery replacement should be performed by trained personnel who are familiar with the procedures and safety precautions. Make a note of the replacement Battery tray number.

  • Safety Precautions

    • CAUTION! Only use replacement batteries which are certified by CyberPower Systems. Use of incorrect battery type is an electrical hazard that could lead to explosion, fire, electric shock, or short circuit.
    • CAUTION! Batteries contain an electrical charge that can cause severe burns. Before servicing batteries, please remove any conductive materials such as jewelry, chains, wrist watches, and rings.
    • CAUTION! Do not open or mutilate the batteries. Electrolyte fluid is harmful to the skin/eyes and may be toxic.
    • CAUTION! To avoid electric shock, turn off and unplug the UPS from the wall receptacle before servicing the battery.
    • CAUTION! Only use tools with insulated handles. Do not lay tools or metal parts on top of the UPS or battery terminals.
  • Replacement Batteries
    Please refer to the front side of the UPS for the model number of the correct replacement batteries. For battery procurement, log onto www.CPSww.com , or contact your local dealer.

  • Battery Disposal

    • Batteries are considered hazardous waste and must be disposed of properly. Contact your local government for more information about proper disposal and recycling of batteries. Do not dispose of batteries in fire.
    • CyberPower Systems encourages environmentally sound methods for disposal and recycling of its UPS products. Please dispose and/or recycle your UPS and batteries in accordance to the local regulations of your state.

Battery Installation

  1. Step 1: Remove the front panels
  2. Step 2: Remove the retaining screws from the cable protection cover and then remove the cover itselfCyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01 \(9\)
  3. Step 3: Pull the battery tray out slowly and then put the new battery tray back into the compartment
  4. Step 4: Fasten back the connectors on the battery retaining cover. Then insert the battery connectors and tighten the screws of battery retaining cover
  5. Step 5: Install the front panelsCyberPower-OL1000RTXL2U-Smart-App-UPS-Systems-01 \(10\)

TECHNICAL SPECIFICATIONS

Model| OL1000RTXL2U| OL1500RTXL2U| OL2200RTXL2U| OL3000RTXL2U
---|---|---|---|---
Configuration
| Capacity (VA)| 1000VA| 1500VA| 2200VA| 3000VA
| Capacity (Watts)| 900W| 1350W| 1800W| 2700W
| Form Factor| Rackmount / Tower
| Energy-saving Technology| Yes, ECO Mode Efficiency > 93%
Input
| Input Voltage Range| 100~125Vac
| Input Frequency Range| 50 / 60Hz
| Input Power Factor| 0.99
| Cold Start| Yes
Output
| Output Waveform| Sine wave
| Output Voltage1| 100, 110, 115, 120, 125Vac (Configurable) ±2%
| Output Frequency| 50 / 60Hz (Auto-Sensing or Configurable) ±0.25Hz
| Transfer Time (Typically)| 0ms
| Rated Power Factor| 0.9| 0.82| 0.9
| Harmonic Distortion| THD < 3% at Linear Load, < 5% at Non-linear Load
| Crest Factor| 3 : 1
| ECO Mode Voltage Regulation| ±10%, ±15% (Configurable)
| UPS Outlets| (8) NEMA 5-15R| (6) NEMA 5-20R, (1) L5-20R| (6) NEMA 5-20R, (1) L5-30R
Protection
| Surge Protection| IEC 61000-4-5 Level 3
| Phone / Network Protection| RJ11/RJ45 (One In/One Out)
| Overload Protection| Line Mode:   105~125% Load for 1 min,      126~150% Load for 10 sec Battery Mode: 105~130% Load for 10 sec,    131~150% Load for 2 sec
| Short Circuit Protection| UPS Output Cut off Immediately or Input Fuse / Circuit Breaker Protection
Battery
| Specifications| (3) 12V/9AH| (6) 12V/9AH
| Recharge Time (Typically)| 4 hours (0-90%)
| Sealed, Maintenance Free| Yes
| Hot-Swappable| Yes
Status Indicators
| LCD Screen| Multi-Function LCD Readout that Supports: Multi-Language Interface,              (19) Types of Read Out, (22) Types of Function Setting,     (3) Event Logs
| LED Indicators| Power On (White),           Line Mode (Green), Battery Mode (Yellow), Bypass Mode (Yellow), Fault (Red), Replace Battery (Red)
| Audible Alarms| Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery
Environment
| Operating Temperature| 32℉ to 104℉ ( 0℃ to 40℃)
| Operating Relative Humidity| 0 to 90% Non-Condensing
Management
| On-Device Features| Self Test, Auto-Charge, Auto-Restart, Auto-Overload Recovery
| Connectivity Ports| (1) Serial Port (RS232), (1) USB Port, (1) Relay Out
| SNMP/HTTP Capable| (1) Expansion Port (With optional SNMP card)
Software
| Power Management Software| PowerPanel® Business Edition
Physical
| ****

Dimensions

| L x W x H = 16.9 x 17 x 3.5in.

(43 x 43.3 x 8.8cm)

| L x W x H = 23.6 x 17 x 3.5in. (60 x 43.3 x 8.8cm)
| Net Weight| 39.6lbs(18Kg)| 68.2lbs(31Kg)
Safety
| Conformance Approvals| CE, UL

100V are derated by 20%, 110V and 115V are derated by 10%

TROUBLE SHOOTING

Problem Possible Cause Solution

Warning
O/P Overload| Your equipment requires more power than the UPS can provide. If the UPS is in Line Mode then it will transfer to Bypass Mode; if the UPS is in Battery Mode it will shutdown.| Shut off non-essential equipment. If this solves the overload problem, the UPS will transfer to normal operation.
Load Over XXX%| Your equipment requires more power than the setting in the Power Management Software (PowerPanel® Business) will allow.| Shut off the non-essential equipment or increase the level in the Power Management Software.
Battery Mode| UPS is operating on battery power.| Save your data and perform a controlled- shutdown.
Battery Low| UPS is operating on battery power and will be shutting down soon due to extremely low battery voltage.| UPS will restart automatically when acceptable utility power returns.
BAT Disconnected| Missing battery power.| Check battery connector and battery breaker.
Battery Failure| UPS has failed a Battery Test.|

  1. Check battery connector and battery breaker.
  2. Contact technical support to replace the battery.

Replace Battery| Battery will soon need to be replaced due to insufficient runtime.| Contact technical support to replace the battery.
EPO OFF| Missing the EPO connection.| Check the EPO connection.
Wiring Fault| Line and neutral wires are reversed.| Exchange line and neutral wires.
Missing ground wire.| Connect ground wire.
No ground wire.| Disable Wiring Fault alarm on LCD panel.
Line Abnormal| Wrong utility power backed up during UPS auto- restart.| Check whether voltage or frequency of utility power is out of range.
Output Short| Output short circuit.| Your attached equipment may have problems, please remove them and check again.
Over Temperature| High temperature sensor activates protection.| Check the fan for operation and if ventilation is obstructed.
Coldstart Lock| UPS is locked to prevent consuming battery power during shipping.| Plug into utility power for first-time operation.
Autorestart Lock| “Automatic Restore” is disabled in Power Management Software (PowerPanel® Business)| Press “ON/OFF“ button to turn on UPS
Fault
Over Charge| Battery is overcharged.|

  1. Remove battery connector and check charger voltage.
  2. Contact CyberPower for repair.

Charger Failure| Charger has failed.
High O/P V| Output voltage is too high.|

  1. Shut down UPS and turn off input breaker.
  2. Contact CyberPower for repair.

Low O/P V| Output voltage is too low.
Bus Fault| Internal DC bus voltage is too high or too low.
Fan Error| Internal Fan has failed.

CyberPower Systems Inc.

  • www.cpsww.com
  • Entire contents copyright© 2012 CyberPower Systems Inc., All rights reserved. Reproduction in whole or in part without permission is prohibited. PowerPanel® Business Edition and PowerPanel® Personal Edition are trademarks of CyberPower Systems Inc.

PRODUCT REGISTRATION
CyberPower requests that you complete and return the Warranty Registration Card enclosed with the Product or register the Product at its website ( www.cpsww.com ) to establish that you are the Initial Customer of the Product, and therefore entitled coverage under the Limited Warranty and the Connected Equipment Guarantee. (Registration is not required for coverage, but note: if you do not register your purchase, you will be required to provide proof of purchase.)

LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARNTEE

Read the following terms and conditions carefully before using the CyberPower OL1000RTXL2U / OL1500RTXL2U / OL2200RTXL2U / OL3000RTXL2U. By using the Product you consent to be bound by and become a party to the terms and conditions of this Limited Warranty and Connected Equipment Guarantee (together referred to as this “Warranty”). If you do not agree to the terms and conditions of this Warranty, you should return the Product for a full refund prior to using it.

  • Who is Providing this Warranty?
    CyberPower Systems (USA), Inc. (“CyberPower”) provides this Limited Warranty.

  • What Does This Warranty Cover?
    This warranty covers defects in materials and workmanship in the Product under normal use and conditions. It also covers equipment that was connected to the Product and damaged because of the failure of the Product.

  • What is the Period of Coverage?
    This warranty covers the Product for three years and connected equipment for as long as you own the Product.

  • Who Is Covered?
    This warranty only covers the original purchaser. Coverage ends if you sell or otherwise transfer the Product.

  • How Do You Get Warranty Service?

    • Before contacting CyberPower, identify Your Product model number, the Purchase Date, and each item of Connected Equipment.
    • Email us at tech@cpsww.com or Call us at 877-297-6937.
    • If your product requires warranty service you must provide a copy of your dated purchase receipt or invoice.
  • How Do You Open A Connected Equipment Claim?

    • Call us at 877-297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave. E., STE 400, Shakopee, MN 55379, or send us an e-mail message at claims@cpsww.com for instructions, within 10 days of the occurrence.
    • When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment. Have information on all applicable insurance or other resources of recovery/payment that are available to the Initial Customer and Request a Claim Number.
    • You must provide a dated purchase receipt (or other proof of the original purchase) and provide a description of the damage to your connected equipment.
    • Pack and ship the product to CyberPower and, if requested, the item(s) of Connected Equipment, a repair cost estimate for the damage to the Connected Equipment, and all claim forms that CyberPower provides to you. Show the Claim Number on the shipping label or include it with the product. You must prepay all shipping costs, you are responsible for packaging and shipment, and you must pay the cost of the repair estimate.
  • How Long Do I Have To Make A Claim?
    All claims must be made within ten days of the occurrence.

  • What Will We Do To Correct Problems?

    • CyberPower will inspect and examine the Product.
    • If the Product is defective in material or workmanship, CyberPower will repair or replace it at CyberPower’s expense, or, if CyberPower is unable to or decides not to repair or replace the Product (if defective) within a reasonable time, CyberPower will refund to you the full purchase price you paid for the Product (purchase receipt showing price paid is required).
    • If it appears that our Product failed to protect any equipment plugged into it, we will also send you forms for making your claim for the connected equipment. We will repair or replace the equipment that was damaged because of the failure of our Product or pay you the fair market value (NOT REPLACEMENT COST) of the equipment at of the time of the damage. We will use Orion Blue Book, or another a third-party valuation guide, or eBay, craigslist, or other source to establish that amount. Our maximum liability is limited to $400,000 for OL1000RTXL2U / OL1500RTXL2U / OL2200RTXL2U / OL3000RTXL2U.
  • Who Pays For Shipping?
    We pay when we send items to you; you pay when you send items to us.

  • What Are Some Examples Of What This Warranty Does Not Cover?

    • This Warranty does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any data that is lost as a result of the failure or the restoration of data or records, or the reinstallation of software.
    • This Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the Product or the equipment connected to it, nor for damage while in transit or in storage, nor if there has been improper operation or maintenance, or use with items not designed or intended for use with the Product, such as laser printers, appliances, aquariums, medical or life support devices, etc.
  • What Other Limitations Apply?
    The sole and exclusive remedies of the Initial Customer are those provided by this Warranty.

    • This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired and grounded outlets (including compliance with electrical and safety codes of the most current electrical code), without the use of any adapters or other connectors.
    • The Product must have been plugged directly into the power source and the equipment connected to the Product must be directly connected to the Product and not “daisy-chained” together in serial fashion with any extension cords, another Product or device similar to the Product, surge suppressor, or power tap. Any such installation voids the Limited Warranty.
    • The Product and equipment connected to it must have been used properly in a suitable and proper environment and in conformance with any license, instruction manual, or warnings provided with the Product and the equipment connected to it.
    • The Product must have been used at all times within the limitations on the Product’s VA capacity.

The Product was designed to eliminate disrupting and damaging effects of momentary (less than 1ms) voltage spikes or impulses from lightning or other power transients. If it can be shown that a voltage spike lasting longer than 1ms has occurred, the occurrence will be deemed outside the rated capabilities of the Product and the Limited Warranty is void.

CyberPower Does Not Cover or Undertake Any Liability in Any Event for Any of the Following:

  1. Loss of or damage to data, records, or software or the restoration of data or records, or the reinstallation of software.
  2. Damage from causes other than AC Power Line Transients, spikes, or surges on properly installed, grounded and code-compliant 120 volt power lines in the United States and Canada; transients, surges or spikes on standard telephone land lines, PBX telephone equipment lines or Base 10T Ethernet lines, when properly installed and connected. (This exclusion applies, for example, to fluctuations in data transmission or reception, by CATV or RF transmission or fluctuations, or by transients in such transmission.)
  3. Damage from any circumstance described as excluded above with respect to the Product.
  4. Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse, misuse or alteration of either the product or the Connected Equipment.
  5. CyberPower excludes any liability for personal injury under the Limited Warranty and Connected Equipment Guarantee. CyberPower excludes any liability for direct, indirect, special, incidental or consequential damages, whether for damage to or loss of property [EXCEPT FOR (AND ONLY FOR) the specific limited agreement of CyberPower to provide certain warranty benefits regarding “Connected Equipment” under this Warranty], loss of profits, business interruption, or loss of information or data. NOTE: Some States or Provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation may not apply to you.
  6. The Product is not for use in high-risk activities or with aquariums. The Product is not designed or intended for use in hazardous environments requiring fail-safe performance, or for use in any circumstance in which the failure of the Product could lead directly to death, personal injury, or severe physical or property damage, or that would affect operation or safety of any medical or life support device (collectively, “High Risk Activities”). CyberPower expressly disclaims any express or implied warranty of fitness for High Risk Activities or with aquariums. CyberPower does not authorize use of any Product in any High Risk Activities or with Aquariums. ANY SUCH USE IS IMPROPER AND IS A MISUSE OF THE PRODUCT.

Where Can I Get More Information?

  • The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded.
  • CyberPower is the warrantor under this Limited Warranty.
  • For further information please feel free to contact CyberPower at CyberPower Systems (USA), Inc. 4241 12th Ave E., STE 400, Shakopee, MN 55379; call us at 877-297-6937; or send us an e-mail message at claims@cyberpowersystems.com .

CONFORMANCE APPROVALS

FCC Notice
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. This device must accept any interference that may cause undesired operation.

WARNING!!

  • This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Shielded signal cables must be used with this product to ensure compliance with the Class A FCC limits.
  • The Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulation.

This document is believed to be accurate, but CyberPower reserves the right to change or correct the contents and does not assume any responsibility for omissions or errors.

Need Additional Help?

  • Feel free to contact our Tech Support department with installation, troubleshooting, or general product questions.
  • CyberPower Technical Support
  • Hours of Operation:
    • Monday – Friday, 7:00am – 6:00pm (CST)
    • Entire contents copyright © 2012 CyberPower Systems, Inc.
  • All rights reserved. Reproduction in whole or in part without permission is prohibited.

Copyright © 2016 CyberPower Systems, Inc.

Documents / Resources

| CyberPower OL1000RTXL2U Smart App UPS Systems [pdf] User Manual
OL1000RTXL2U Smart App UPS Systems, OL1000RTXL2U, Smart App UPS Systems, App UPS Systems, UPS Systems, Systems
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals