The signal from one pressure transmitter can be shared by up to 10 controllers. More details in the User Guide of the AK-CC55:
AKS 32R info
The signal from one pressure transmitter can be received by up to 10
controllers.
There must not be a significant pressure drop from the pressure transmitter’s
position in the suction line to the individual evaporators.
One AK-CC 750A and AK-CC55
(Possible, but not recommended)
The signal from one pressure transmitter can be received from up to 5
controllers.
For example : 1x AK-CC 750A and 4x AK-CC55.
Limitation : Electrically it´s possible to share the pressure
transmitter, and the signal is displayed correctly, but this is not
recommended by Danfoss. In case an AK-CC750A unit is disconnected or loses
supply voltage, this unit will affect the pressure signal.
The signal from the pressure sensor may change only slightly, so the system
still sees the signal as valid.
AK2 platform controllers with AK-XM extension modules
(Possible, but not recommended)
If all controllers have separated power supply, it is possible to connect more than one controller to one pressure transmitter.
Limitation : Electrically it´s possible to share the pressure
transmitter, and the signal is displayed correctly. Up to 10 AK2 units can
share the signal from a pressure transmitter, but this is not recommended by
Danfoss. In case an AK2 unit is disconnected or loses supply voltage, this
unit will affect the pressure signal.
The signal from the pressure sensor may change only slightly, so the system
still sees the signal as valid.
If third party controllers are involved, then Danfoss is not responsible for
the installation of the pressure transmitters sharing.
MCX controllers (Not recommended)
No, MCX controllers are not designed to share sensors with a physical
connection.
The recommendation is to use the CANBus to share the sensor data reading with
other controllers.
AK2 platform controllers with different platforms (AK2 x MCX or AK2
x Alsmart or Alsmart x MCX) (Not recommended)
No, AK2 platform controllers are not designed to share sensors with
physical connection with devices based on other platforms.
Appendix
For more informations on pressure transmitters sharing, check other
documents:
Title: Transmitter fault detection for AK-XM 101A, AK-XM 205A, AK-XM 205B
Document ID: RI8HZ552
Title: Transmitter fault detection for AK…, ECL…, ECA…
Document ID: RI8HZ452
Danfoss A/S
Climate Solutions
danfoss.com
+45 7488 2222
Danfoss reserves the right to alter its products without notice. This also
applies to products ordered but not delivered provided that such alterations
can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All
rights reserved.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>