signify TM05-06 TruGroove Suspended Micro Instruction Manual

June 17, 2024
signify

signify TM05-06 TruGroove Suspended Micro

Product Information

Specifications

Product Name: TruGroove Suspended Micro

Model Number: IS-TM05/06

System Type: Suspended Direct/Indirect

Module Lengths:

Length Feet Inches mm
2ft 2.0 24.0 610
2.5ft 2.5 30.0 762
3ft 3.0 36.0 914
3.5ft 3.5 42.0 1067
4ft 4.0 48.0 1219
5ft 5.0 60.0 1524
6ft 6.0 72.0 1829
8ft 8.0 96.0 2438

System Overview

The TruGroove Suspended Micro fixtures are designed for architectural linear lighting applications. They feature MesoOptics AccuRender technology for precise light distribution. The fixtures can be installed as standalone units or joined together to create continuous runs and patterns.

Tools Required

The following tools are required for installation:

  • Installation instruction manual
  • Mounting components
  • Vertical aircraft cables

Product Usage Instructions

Installation Notes

  1. Arrange the boxed fixtures on the floor according to the supplied layout drawings.
  2. Remove the fixtures from their boxes.
  3. Install all ceiling mounting components and vertical aircraft cables following the separate installation instructions for Aircraft Cable Mounting (supplied).

Mounting & Power Location

Fixture Length: The variable aircraft cable mounting point must be located within 12″ of the fixture end to ensure a safe installation.

Power Feed Location:

  • 2ft, 2.5ft, 3ft, and 3.5ft symmetric fixtures have only one power feed location.
  • 4ft, 5ft, 6ft, and 8ft fixtures have two power feed locations, one at each end.

For mounting flexibility on-site, each fixture housing can accommodate up to 1″ of variability from each end.

Warning!

Shock Hazard!

Before attempting any installation, service, or maintenance:

  • Disconnect or turn off power.
  • Connect the fixture to the building ground via the provided ground wire before re-connecting to the main power supply.

Power Label Location

For D/I symmetric and asymmetric fixtures, power labels can be found on light engine pans or under end louver modules. For Direct and Surface symmetric and asymmetric fixtures, power labels can be found on the upper pan.

Important Safety Information

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

FAQ

1. Can the TruGroove Suspended Micro fixtures be joined together to create longer runs?

Yes, the fixtures can be joined together to create continuous runs and patterns.

What tools are required for installation?

The tools required for installation include the installation instruction manual, mounting components, and vertical aircraft cables.

How should the fixtures be mounted and powered?

The variable aircraft cable mounting point must be located within 12″ of the fixture end. The fixtures have designated power feed locations based on their length.

How should I handle the fixtures to ensure safety?

Before attempting any installation, service, or maintenance, make sure to disconnect or turn off the power. The fixture must be connected to the building ground via the provided ground wire before re-connecting to the main power supply.

System Overview

These instructions review how to install TruGroove suspended micro fixtures. Modules can be installed as individual 2ft, 2.5ft, 3ft, 3.5ft, 4ft, 5ft, 6ft, or 8ft standalone units, or they can be joined together to create continuous runs and patterns. The diagram below shows the components required to install a typical run of TruGroove suspended micro fixtures.

IMPORTANT: Read all instructions including fixture/sensor wiring AND mechanical details before beginning installation.

Module Lengths

TruGroove suspended micro fixtures come in the module lengths shown below. Add 0.25” for each endcap for accurate run length.

__

Length without endcaps

| feet| 2.0| 2.5| 3.0| 3.5| 4.0| 5.0| 6.0| 8.0
---|---|---|---|---|---|---|---|---|---
Inches| 24.0| 30.0| 36.0| 42.0| 48.0| 60.0| 72.0| 96.0
mm| 610| 762| 914| 1067| 1219| 1524| 1829| 2438

Mount Spacing

Fixture modules are designed for exact on-grid mounting. For non-accessible ceilings or in tile installations, mounts are adjustable within 1” of each module end.

TOOLS REQUIRED:

  • 2 Phillips screwdriver

  • 3/8” nut driver
  • Medium flat or #2 robertson screwdriver
  • Heyco PN0019(R12) crimping tool
  • Small ratchet and 1/4” socket

ATTENTION: Install in accordance with local and national building and electric codes.

Direct/Indirect Installation Instructions

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interreference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Lens Removal

  1. Lens Removal: To remove snap-in lens for maintenance purposes, insert a flat, smooth edged object between lens and housing (avoid screwdrivers). Twist to release pressure and remove lens.

  2. Remove lens from fixture and set aside until fixture installation is complete. Use cotton gloves to handle lenses and keep in a clean environment.
    Note: Optional Drop Lens is shipped separately.

  3. Remove lens and set aside until fixture installation is complete. Use cotton gloves to handle lenses and keep in a clean environment.
    Remove the 2 screws securing the lower light engine and temporarily support light engine in position below fixture.
    DO NOT ALLOW LIGHT ENGINE TO HANG FROM ELECTRICAL WIRES.
    Save screws for re-installation later.

Installation Preparation

  1. Remove one louver from end of fixture by pulling gently and temporarily suspend from available holes.

    • Remaining louvers can be pushed to center for better access.
    • DO NOT ALLOW LOUVER TO HANG FROM ELECTRICAL WIRES.
    • For louver-lens combinations, remove both louver and lens. Use cotton gloves to handle lenses and keep in a clean environment.
    • If installing a fixture with one power feed location, ensure electrical knockout orientation matches required power feed location.
  2. With module 1 on the ground, slide sling cable assembly into top fixture screw chase on both ends of the fixture.

  3. Attach two push pins to screw chases to secure sling cable assembly inside fixture during installation process. Gently tap each push pin into the housing leaving a 1/16” gap for easier removal later.

  4. Raise fixture to installed level and insert suspension cable inside sling cable assembly. Ensure end of aircraft cable exits from side of sling cable assembly as shown.

Important: Modules must be level relative to each other when joining of sections is required

IMPORTANT: LEVELING INSTRUCTIONS
For side to side leveling, loosen adjustment screw at bottom of cable gripper and slide slowly until level. When complete, re-tighten levelling screw by hand.
For vertical leveling, support bottom of fixture, press plunger on top of cable gripper and slowly lift/lower fixture to desired position. Release plunger when complete. Ensure fixture is secure before removing support.

  1. Ensure module 1 is installed level. Do not install at an angle.

  2. Determine power feed location and break ½” electrical knockout at required end. Install ½” bushing from below fixture as shown. Feed power cord from above into fixture wiring cavity.

  3. Determine power feed location and break ½” electrical knockout at required end. Install ½” bushing from inside fixture as shown. Feed power cord from above into fixture wiring cavity.

    1. Install and crimp provided cable metal strain relief bushing to secure power cord below fixture bracket. Use a Heyco PN0019(R12) crimping tool to ensure proper installation. If installing a standalone fixture, skip to step 13.
  4. With module 2 on the ground, tap joiner aligners inside top and bottom screw chases as shown.
    IMPORTANT: To allow for proper joining, ensure each center aligner tab is fully inserted inside module 2 housing, about ¼” past the middle point.

  5. Raise module 2 to installed module 1 position. Install and secure sling cable assembly of module 2 and at opposite. Remove push pins from module 1. IMPORTANT: WIRING INSTRUCTIONS Quick wire connectors (supplied) are used for through wiring connections between fixtures. Wire nuts (by others) are used for connection of power drops wiring to fixture wiring.

  6. Bring modules close together, support module 2, complete wiring connections and tuck wires inside fixture wiring cavity. Engage joiner aligners from module 2 inside module 1.

  7. Ensure all connections are secure and all wires are fully tucked inside fixture wiring cavity. Slide fixture modules together gently. Level fixtures.

  8. Secure fixture modules together using the two #10-32 machine screws and the two Self-locking #10-32 nuts supplied. Tighten until joint seam is tight.
    IMPORTANT: Do not overtighten.

  9. Before installing the endcap, slide the sensor towards the center of the fixture to gain access. Proceed with endcap installation for drop lens, step 13c.

  10. Place drop lens endcap as shown over the emboss of endcap and proceed with endcap Installation of endcap, step 13c.

  11. Slide endcap onto end of fixture module and secure from below using two #8-32 X 3/8″ screws. Ensure excess aircraft cable does not interfere with endcap attachment. Use ratchet or angle driver to tighten screws until endcap seam is tight.
    IMPORTANT: Do not overtighten.

  12. If a corner is required, it is recommended the corner module be installed first. All corners come with a factory installed cable sling assembly in the middle.

  13. If installing a square or rectangular closed pattern, it is recommended to install opposite U-shaped fixture/corner patterns first and complete the installation by bringing U-shaped sections together as shown.

  14. Reinstall the lower led pans with the screws provided. Ensure direction of light is as shown on layout drawings.

  15. Installation Tip: For easier installation, start on one end of the louver pressing gently on side tabs. IMPORTANT: For asymmetric louver fixtures, orient the arrows on the louver pan to point at the label on the outside of the housing.

  16. Install lenses removed in step 1. Installation Tip: For easier installation, start at a housing end or a joint by placing lens at an angle and squeezing in slightly from the other side to guide inside housing.

  17. Once lens is positioned inside housing, starting on one end or joint, push upwards gently and work outward to complete the run.
    Note: Flush lens and drop lens are installed the same way. Flush lens is shown for reference.

  18. Installation Tip: For easier installation of corner lenses, start at the corner and work outward to complete the run. Follow steps 18 and 19.

  19. Installation filler plate before installing louvers. Tin: For easier installation. start ov louvers. Tip: For easier installation, start by squeezing filler plate in slightly from both sides and guiding inside housing.

  20. Installation Tip: For easier installation, star on one end of the louver pressing gently o side tabs.

  21. Finishing

    • Ensure all fixtures and corners are level and in line with each other.
    • Trim excess vertical aircraft cable installed in step 4.
    • If horizontal leveling is required, loosen adjustment screw shown in step 4, level fixture and re-tighten screw.
    • Check that all joint or endcap screws are installed, and all seams are tight.
    • Use spare 1/2″ plug(s) provided to close any open 1/2″ electrical knockout location(s) in top reflector.

PRF/PRA Interact Pro Foundation/Advance Install & Setup

*not for Enterprise or Signify Commissioned projects

To configure a lighting system with Interact sensors or RF nodes;

  • Ensure the luminaires are installed and powered on.

  • Download the Interact Pro app from either Apple’s App Store (for iOS) or Google’s Play Store.

  • Register by tapping Request access on the login screen in the app.

  • Click or scan the QR codes below to view instructions for setup.

Sensors in Rows

Single Sensor Controlling Whole Row

  1. Purple & brown (or purple & grey/pink) control wires MUST be connected between fixtures.
    Note:
    A maximum of 8 drivers can be wired to one sensor; confirm fixture driver count with factory.

Multiple Sensors Controlling Separate Zones in a Row

  1. Purple & brown (or purple & grey/pink) control wires MUST NOT be connected between zones.
    Notes:
    A maximum of 8 drivers can be wired to one sensor; confirm fixture driver count with factory.
    Only one sensor is allowed on a wired zone. (Sensors can be paired together wirelessly via a mobile app).

Sensor Spacing

  • For correct operation, sensors should be placed a minimum distance of 8ft apart.
  • Wireless sensors should be placed no further than 40ft apart for good wireless signal connection.

Important Consideration When Using Sensors in a Row

  • For fixtures with wireless sensors (CS. SB or RA options):
    DO NOT connect fixture purple & brown (or purple & grey/pink) control wires to an external dimming switch. Fixture mains wiring should not be connected to a circuit with an external on/off switch.

  • For best aesthetic condition, place sensors at ends of row only so as not to break the continuous lens.

  • For better occupancy coverage in longer rows, sensors may be placed mid run, but keep in mind this will break the continuous lens into discrete sections. Alternatively, remote sensor may be used, note the same wiring rules will apply.

Occupancy Sensor Coverage:
Note: Longer dimension of detection area (Y1, Y2) is parallel to longer dimension of the luminaire.

Daylight sensor
The light sensor measures the total amount of light in a circular field of approximately 80% of the PIR detection area. The following aspects should be observed during installation:

  • Minimum distance from the window ≥2ft (0.6m).
  • Prevent light reflections from outside entering the sensor (for example sunlight reflection on a car hood) as this will lead to incorrect light regulation.
    As a guideline the formula 0.72 x H can be used to calculate the minimum distance between the window and sensor whereby His the height from the bottom of the window to the sensor.

Photosensor spatial response

© 2021 Signify Holding. All rights reserved. The information provided herein is subject to change, without notice. Signify does not give any representation or warranty as to the accuracy or completeness of the information included herein and shall not be liable for any action in reliance thereon. The information presented in this document is not intended as any commercial offer and does not form part of any quotation or contract, unless otherwise agreed by Signify.

Signify North America Corporation
400 Crossing Bivd, Suite 600
Bridgewater, NJ 08807
Telephone: 855-486-2216

Signify Canada Ltd.
281 Hillmount Road,
Markham, ON, Canada L6C 2S3
Telephone: 800-668-9008

All trademarks are owned by Signify Holding or their respective owners.

www.signify.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals