Honeywell RedLINK Wireless Accessories Outdoor Air Sensor Installation Guide

June 17, 2024
Honeywell

Honeywell RedLINK Wireless Accessories Outdoor Air Sensor

Product Information

Specifications:

  • Product: RedLINKTM Wireless Accessories
  • Included Components: Thermostat, Outdoor air sensor, Remote control, HVAC equipment, Equipment interface module (or TrueZONETM panel with wireless adapter)

Product Usage Instructions

Installation Procedure:

  1. Install batteries in wireless devices (Page 2)
  2. Link devices to wireless network (Pages 2-3)
  3. Mount outdoor sensor (Page 4)

Install batteries in wireless devices:

Make sure batteries are inserted properly (see polarity marks on illustrations below).

Remote control: Install 3 fresh AA batteries

Outdoor air sensor: Install 2 fresh AA lithium batteries

Link devices to wireless network:

  • Press CONNECT button at the Equipment Interface Module (EIM) or wireless adapter and wait for the green flashing light to begin linking devices to the wireless network (see page 3).
  • If the light stops flashing before you have linked all devices, press CONNECT again.
  • If the light does not flash, another EIM/wireless adapter may be in wireless setup mode. Exit wireless setup at the other EIM/wireless adapter.

Link remote control to wireless network:

  1. Make sure the Connected light on the EIM or wireless adapter is flashing (see page 2).
  2. Press CONNECT at the remote. There will be a short delay as the remote seeks a signal from the wireless network.
  3. When the screen displays “Connected,” press DONE.
  4. Press NO at the next screen to save and exit. (Or press YES and repeat steps 1-4 to link another EIM/zone panel.)

Link outdoor sensor to wireless network:

  1. Make sure the Connected light on the EIM or wireless adapter is flashing (see page 2).

  2. Press the CONNECT button on the back of the sensor.

  3. Check thermostat to verify that the outdoor sensor is working.
    After about 15 seconds, the thermostat should display outdoor temperature and humidity.

  4. If there is more than one EIM/zone panel, repeat steps 1-3 for each.

Mount outdoor sensor:

  • Mount the sensor on a vertical exterior wall, at least 6 inches below any overhang. Choose a location protected from directsunlight.
  • Place the sensor securely in the bracket, facing away from the wall.
  • To check the location before mounting: Restore thermostat Home screen, then hold the sensor where you intend to install it and press the CONNECT button. If the sensor is working properly, the thermostat will switch to display outdoor temperature and humidity.

Frequently Asked Questions

Q: What should I do if E1 appears during the linking procedure?

A: Please refer to the error codes on page 5 of the manual for troubleshooting steps.

Q: What should I do if the linking procedure times out?

A: To begin again, press and hold the blank space (or arrow if present) in the lower right corner of the screen until the display changes (about 3 seconds).

RedLINK™ Wireless Accessories

Remote control  Outdoor air sensor

Honeywell-RedLINK-Wireless-Accessories-Outdoor-Air-Sensor-
FIG-1

If there is more than one Equipment Interface Module (EIM) or zone panel: Wireless devices must be linked separately to each EIM or zone panel.

® U.S. Registered Trademark.
Copyright © 2008 Honeywell International Inc. All rights reserved.

Install batteries in wireless devices

Make sure batteries are inserted properly (see polarity marks on illustrations below).

V

Link devices to wireless network

Press the CONNECT button at the EIM or wireless adapter and wait for green flashing light to begin linking devices to the wireless network (see page 3).
If the light stops flashing before you have linked all devices, press CONNECT again.

If light does not flash, another EIM/wireless adapter may be in wireless setup mode. Exit wireless setup at the other EIM/wireless adapter.

Link remote control to wireless network

  1. Make sure the Connected light on the EIM or wireless adapter is flashing (see page 2).
  2. Press CONNECT at the remote. There will be a short delay as the remote seeks a signal from the wireless network.
  3. When the screen displays “Connected,” press DONE.
  4. Press NO at the next screen to save and exit. (Or press YES and repeat steps 1-4 to link another EIM/zone panel.)

If E1 appears, see error codes on page 5.
The linking procedure may time out if there is no keypress within 30 minutes. To begin again, press and hold the blank space (or arrow if present) in the lower right corner of the screen until the display changes (about 3 seconds)

Link outdoor sensor to wireless network

  1. Make sure the Connected light on the EIM or wireless adapter is flashing (see page 2).
  2. Press the CONNECT button on the back of the sensor.
  3. Check thermostat to verify that the outdoor sensor is working. After about 15 seconds, the thermostat should display outdoor temperature and humidity.
    (If there is more than one EIM/zone panel, repeat steps 1-3 for each.)

Mount outdoor sensor

Mount the sensor on a vertical exterior wall, at least 6 inches below any overhang. Choose a location protected from direct sunlight.

Place sensor securely in bracket, facing away from wall

To check location before mounting: Restore thermostat Home screen, then hold the sensor where you intend to install it and press the CONNECT button. If sensor is working properly, thermostat will switch to display outdoor temperature and humidity.

Honeywell-RedLINK-Wireless-Accessories-Outdoor-Air-Sensor-
FIG-9

Error codes (remote control)

If E1 appears during setup, check error code number:

  • 29 You are attempting to connect a remote control to an incompatible device.
  • 34 Low signal strength. Move remote control to a different location and try again.
  • 38 Make sure Connected light is flashing and you are 2+ feet away from EIM or wireless adapter.

Replacing system components

Remote control or outdoor sensor
To replace a remote control or outdoor air sensor, install batteries in the new component and follow the procedure on pages 2-3 to link it to the wireless network.

EIM or zone panel
After installing a new EIM or zone panel, you must re-set the remote control to communicate with the new equipment, as described below.

At the remote control:

  1. Press and hold the blank space (or arrow if present) in the lower right corner of the screen until the display changes (about 3 seconds).
  2. Press REMOVE , then YES to disconnect from old equipment.
  3. Follow the procedure on pages 2-3 to link to new equipment.

Honeywell-RedLINK-Wireless-Accessories-Outdoor-Air-Sensor-
FIG-9

Regulatory information

FCC Compliance Statement (Part 15.19) (USA only)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. This device must accept any interference received, including interference that may cause undesired operation.

FCC Warning (Part 15.21) (USA only)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

FCC Interference Statement (Part 15.105 (b)) (USA only)
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

Outdoor sensor
To comply with FCC and Industry Canada RF exposure limits for general population/ uncon-trolled exposure, the antenna(s) used for these transmitters must be installed to provide a separation distance of at least 20 cm from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter.

Remote control
This portable transmitter with its antenna complies with FCC and Industry Canada RF exposure limits for general population/uncontrolled exposure.

Section 7.1.5 of RSS-GEN
Operation is subject to the following two conditions:

  1. this device may not cause interference, and
  2. this device must accept any interference, including interference that may cause undesired operation of the device.

Need Help?
For assistance with this product please visit http://customer.honeywell.com or call Honeywell Customer Care toll-free at 1-800-468-1502

Automation and Control Solutions

Honeywell International Inc.
1985 Douglas Drive North Golden Valley, MN 55422
http://yourhome.honeywell.com

Honeywell Limited-Honeywell Limitée 35 Dynamic Drive
Scarborough, Ontario M1V 4Z9

Printed in U.S.A. on recycled paper containing at least 10%post-consumer paper fibers.

69-2055EFS-03
07-2008
© 2008 Honeywell International Inc. ® U.S. Registered Trademark.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals