Honeywell WRA-xC-I05 Sounder Strobe Isolation Red Flash Instruction Manual
- June 12, 2024
- Honeywell
Table of Contents
INSTALLATION INSTRUCTIONS FOR EN54-23 W CLASS WALL MOUNTED LOOP POWERED
ADDRESSABLE SOUNDER STROBES.
MODELS
WRA-xC-I05 = Sounder Strobe Isolation Red Flash
WWA-xC-I05 = Sounder Strobe Isolation White Flash
Adjustable performance
Wall Mounted Sounder Strobe
x = Denotes body colour (P – Pure White, R – Red)
GENERAL
The range is used in analogue addressable fire alarm systems.
These devices must only be connected to control panels that use a compatible
proprietary analogue addressable communication protocol.
These devices receive their power from the loop, and can be controlled via the
communication protocol(s).
Note: if the control equipment is not capable of taking over 99 module
addresses, a fault condition will be generated for every address over 99.
For isolator specification refer to document S00-7400 available on request.
V (isolation)| 15 to 29VDC
(24VDC typical)
---|---
I (max) @24V)| High Output
Standard Output
Legacy Output| 25.2mA
21.2mA
16.2mA
P (max)| High Output
Standard Output
Legacy Output| 605mW
509mW
389mW
EN54-3 (sound output)
(High Volume Tone 8 @24V)|
96dB(A) ± 3dB
(terminal size)| 2.5mm²
maximum
(flash rate)|
0.5 &1Hz
(standby mode)|
130uA
°C (operating temperature)|
-10°C to +55°C
% (humidity)|
up to 96% (± 3%) non condensing
IP rating|
IP 21C
This symbol on our product shows a crossed-out “wheelie-bin” as required by
law regarding the Waste of Electrical and Electronic Equipment (WEEE)
disposal. This indicates your responsibility to contribute in saving the
environment by proper disposal of this Waste i.e. Do not dispose of this
product with your other wastes.
To know the right disposal mechanism please check the applicable law.
KAC ALARM COMPANY LIMITED, Honeywell House, Skimped Hill Lane, Bracknell, Berks, RG12 1EB. T. 02034091779 E. technical@kac.co.uk W. www.kac.co.uk
INSTALLATION / PRODUCT ORIENTATION
Affix B501AP to a suitably flat wall. Terminate the cable to the appropriate terminals. For surface mount wiring the cable can enter the B501AP via the break outs provided. Select the appropriate Light Coverage, Tone and Volume settings via the DIP switch.
Make sure the product is fitted in the correct orientation!
Scan the barcode below to see the correct fitting to the wall:
CONTINUITY SPRING
The B501AP incorporates a continuity spring between terminals 2 and 4. This
allows the continuity of the field wiring to be checked without the need for
the device to be present. Inserting the device will disengage the spring.
Removing the device will close the loop.
TERMINAL CONNECTIONS
ANTI TAMPER RELEASE
IMPORTANT: Follow the instruction strictly:
- Insert a flat screwdriver
- Lever the screwdriver down and twist the device anticlockwise.
- Remove the screwdriver to unlock the device.
For a full video on how to release the anti-tamper feature please scan the QR code:
Table 1 (Tone selection)
Address settings
S1 S2
Address 108 = 10 8
- Switch 1
- Switch 2
To set one of the 159 available addresses for the device use the two rotary switches located either side of the dip switch unit. The ‘tens’ digits goes from 0 to 15 and the ‘units’ from 0 to 9. *100 – 159 Only available with advanced protocol.
Dimensions
Volume, coverage and frequency settings
- (Refer to table 1 )
- (Refer to table 2 )
DIP setting 0=Off/1=On.
Table 2
| | ON| OFF
---|---|---|---
SW6
| | LOW VOLUME| HIGH VOLUME
SW7
| | 0.5Hz
Red
(W-2.4-10.5/W-3.6-10.5)
White
(W-2.4-9/W-3.8-9)| 0.5Hz
Red
(W-2.4-11.5/W-4.2-11.5)
White
(W-2.4-11.5/W-4-11.5)
SW8
|
f
| 1Hz (O-2.4-3)| 0.5Hz (EN54-23 W Class)
Coverage data
EN 54-23
| Led| V| X (Max)| Y (Max)| V (m ³)
---|---|---|---|---|---
W-4.2-11.5
W-2.4-11.5| RED| 15-29V| 4.2m
2.4m| 11.5m
11.5m| 555
317
W-3.6-10.5
W-2.4-10.5| RED| 15-29V| 3.6m
2.4m| 10.5m
10.5m| 397
265
O – 2.4 – 3| RED| 15-29V| 2.4| 3m| 21.6
W- 4 -11.5
W- 2.4-11.5| WHITE| 15-29V| 4m
2.4m| 11.5m
11.5m| 529
317
W-3.8-9
W-2.4-9| WHITE| 15-29V| 3.8m
2.4m| 9m
9m| 308
194
O – 2.4 – 3| WHITE| 15-29V| 2.4| 3m| 21.6
For the ‘O’ class detailed coverage data, in accordance with EN54-23, please request the following doc.: S00- 7006
2831 23 0832 23
Morley IAS by Honeywell,
Pittway Tecnologica Srl, Via Caboto 19/3, 34147
Trieste, ItalyDOP050
EN 54-3:2001 +A1: 2002 + A2:2006
Fire detection and fire alarm systems – SoundersEN54-23:2010
Fire detection and fire alarm systems – Visual Alarm DevicesEN 54-17:2005
Fire detection and fire alarm systems – Short-circuit isolators.WA-C-I05
For LPCB: approved to EN 54-3: 2014 + A1: 2019.
Sounder Output data, in accordance with EN54-3, is available on Document Ref:
S00-7005
I56-5003-000
Documents / Resources
|
Honeywell WRA-xC-I05 Sounder Strobe Isolation Red
Flash
[pdf] Instruction Manual
WRA-xC-I05, WWA-xC-I05, Sounder Strobe Isolation Red Flash, WRA-xC-I05 Sounder
Strobe Isolation Red Flash, Strobe Isolation Red Flash, Isolation Red Flash,
Red Flash, Flash
---|---