SENVA WD-1 Water Detector Installation Guide

June 14, 2024
SENVA

SENVA WD-1 Water Detector

SENVA-WD-1-Water-Detector-PRODUCT - Copy

Specifications

  • Power Supply Output: 12-24VDC/24VAC +/- 15%, 5W Max. Isolated N.C. (Form B) Solid State Relay, Isolated Output
    Rating: 30VAC/DC, 0.1A (100mA) Max.

  • Sensing: Gold-plated electrodes

  • Operating Environment: -20 to 70°C / 0-95% RH non-condensing

  • (1) Isolated Power supply from earth ground required.

Product Installation Instructions

  1. Install a sensor in the area to be monitored such that probe pins will contact collected water.
  2. Fasten the sensor with screws provided, or other means.
  3. Wire sensor as follows:
    • RED = Power Supply 9-30VAC/DC
    • BLACK = Ground/Common
    • WHITE = N.C. (Form B) Switch
    • GREEN = N.C. (Form B) Switch

Operation
Switch output opens when sensing probe pins are bridged by water, or power is removed. The device is also equipped with a status LED:

  • Green : Normal operation, no water detected
  • Red: Alarm Status, water detected

The water supply must be less than 1,000k (1M) ohms. Nearly all water supplies contain sufficient dissolved minerals to trigger the sensor including Filtered, Tap, Rain, Condensate, Melted Ice, Detergent, and Salt. Not suitable for detecting distilled water.

Dimensions
Sensing probes utilize alternating current sensing (even when powered by DC) to prevent electrolysis and oxidation of the sensing probes.

IMPORTANT WARNINGS

  • Only qualified trade installers should install this product
  • This product is not intended for life-safety applications
  • Do not install in hazardous or classified locations
  • The installer is responsible for all applicable codes
  • De-energize power supply before installation or service

PRODUCT APPLICATION LIMITATION
Senva products are not designed for life or safety applications. Senva products are not intended for use in critical applications such as nuclear facilities, human implantable device or life support. Senva is not liable, in whole or in part, for any claims or damages arising from such uses.

DIMENSIONS

SENVA-WD-1-Water-Detector-FIG-1

INSTALLATION

  1. Install sensor in the area to be monitored such that probe pins will contact collected water.
  2. Fasten the sensor with screws provided, or other means.
  3. Wire sensor as follows:
    • RED = Power Supply 9-30VAC/DC
    • BLACK = Ground/Common
    • WHITE = N.C. (Form B) Switch
    • GREEN = N.C. (Form B) Switch

OPERATION

Switch output opens when sensing probe pins are bridged by water, or power is removed.

The device is also equipped with a status LED;

  • Green – Normal operation, no water needed
  • Red – Alarm Status, water detected

The water supply must be less than 1,000k (1M) ohms. Nearly all water supplies contain sufficient dissolved minerals to trigger the sensor including Filtered, Tap, Rain, Condensate, Melted Ice, Detergent, and Salt.
Not suitable for detecting distilled water.
Sensing probes utilize alternating current sensing (even when powered by DC) to prevent electrolysis and oxidation of the sensing probes.

SPECIFICATIONS

  • Power Supply 12-24VDC/24VAC +/- 15%, 5W Max. Isolated1
  • Output N.C. (Form B) Solid State Relay, Isolated
  • Output Rating 30VAC/DC, 0.1A (100mA) Max.
  • Sensing Gold plated electrodes
  • Operating Environment -20 to 70oC / 0-95% RH non-condensing

(1)Isolated Power supply from earth groud required.

senvainc.com 1-866-660-8864 1825 NW 167th Place Beaverton Oregon 97006

FAQ

  • Q: Is the product suitable for critical applications?
    • A: No, the product is not intended for critical applications such as nuclear facilities or life support systems.
  • Q: What type of water supplies can trigger the sensor?
    • A: Filtered, Tap, Rain, Condensate, Melted Ice, Detergent, and Salt are some examples of water supplies that can trigger the sensor.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

SENVA User Manuals

Related Manuals