IFM SM4x20 Magnetic Inductive Flow Meter Instruction Manual
- June 16, 2024
- ifm
Table of Contents
IFM SM4x20 Magnetic Inductive Flow Meter
Product Information
Specifications
- Model Numbers: SM4x20 UK, SM6x20, SM7x20, SM8x20, SM8x30, SM6x21, SM7x21, SM8x21, SM8x31
- Manufacturer: Unknown
- Date: 02/09/2020
Functions and Features
The Magnetic-inductive flow meter is designed to monitor liquid media. It can detect flow velocity, volume flow (volumetric flow quantity/time), consumed quantity, and medium temperature.
Safety Instructions
- The manufacturer is responsible for the safety of the system.
- The system manufacturer must perform a risk assessment and provide documentation with all necessary information and safety instructions for the operator, user, and service personnel authorized by the manufacturer.
- Failure to comply with safety instructions may result in malfunction or interference.
Getting Started
When the unit is used with the factory setting, it monitors volumetric flow by providing a switching signal and an analogue signal. The display shows process values for volumetric flow, temperature, meter readings (current and saved values), and error messages. All process values and messages are available via the IO-Link interface regardless of the output configuration. A simulation model is available for simplified sensor setup.
Installation
Recommended installation position: The manual does not provide specific recommendations for installation position.
Non-recommended installation position: The manual does not provide specific recommendations for non-recommended installation positions.
Ground: The manual does not provide specific instructions for grounding.
Installation in pipes: The manual does not provide specific instructions for installation in pipes.
Electrical Connection
The manual does not provide specific instructions for the electrical connection.
Operating and Display Elements
The manual does not provide specific information about operating and display elements.
Menu
- Process value display (RUN): The manual does not provide specific instructions for the process value display.
- Main menu: The manual does not provide specific instructions for the main menu.
- Extended functions (EF): The manual does not provide specific instructions for the extended functions.
- Submenu OUT1 and OUT2: The manual does not provide specific instructions for the OUT1 and OUT2 submenus.
- Submenu CFG and TOTL: The manual does not provide specific instructions for the CFG and TOTL submenus.
- Submenu MEM and DIS: The manual does not provide specific instructions for the MEM and DIS submenus.
- Submenu COLR and SIM: The manual does not provide specific instructions for the COLR and SIM submenus.
Set-up
The manual does not provide specific instructions for the set-up process.
Operation
The manual does not provide specific instructions for operating the product.
Troubleshooting
The manual does not provide specific troubleshooting information.
Maintenance, Repair, and Disposal
The manual does not provide specific instructions for maintenance, repair, and disposal.
Factory Setting
The manual does not provide specific information about the factory setting.
Preliminary Note
For detailed instructions, technical data, approvals, and further information, please use the QR code on the unit/packaging or visit www.ifm.com.
Symbols Used
- Instruction: Indicates an instruction.
- Reaction, result: Indicates the expected reaction or result.
- […]: Designation of keys, buttons, or indications.
- Cross-reference: Refers to related information.
- Important note: Indicates important information that must be followed to avoid malfunction or interference.
- Information: Provides additional information.
- Supplementary note: Provides supplementary information.
- UK: Indicates specific instructions for UK users.
Warnings Used
CAUTION: Warning of personal injury. Slight reversible injuries may result.
Frequently Asked Questions
- Q: What are the model numbers of the Magnetic-inductive flow meter?
- A: The model numbers are SM4x20 UK, SM6x20, SM7x20, SM8x20, SM8x30, SM6x21, SM7x21, SM8x21, SM8x31.
- Q: Does the unit comply with the Pressure Equipment Directive (PED)?
- A: Yes, the unit complies with the Pressure Equipment Directive and is designed and manufactured for group 2 fluids.
- Q: Can the unit be used with group 1 fluids?
- A: Group 1 fluids can be used upon request.
- Q: Does the product cause radio interference?
- A: Yes, this product may cause radio interference in domestic areas. It is recommended to take appropriate EMC screening measures if required.
Operating instructions Magnetic-inductive flow meter
SM4x20 UK SM6x20 SM7x20 SM8x20 SM8x30 SM6x21 SM7x21 SM8x21 SM8x31
80280073 / 02 09 / 2020
Contents
1 Preliminary note4 11 Symbols used 5 12 Warnings used5
2 Safety instructions 5
3 Getting started 6 31 Device functions with factory setting 6 32 Setting
options7
4 Functions and features 7 41 Pressure Equipment Directive (PED) 7 42
Applications 7
5 Function8 51 Process measured signals 8 52 Volumetric flow direction9 521
Determining the volumetric flow direction [Fdir]9 522 Detection of the
volumetric flow direction [dirF] 9 53 Consumed quantity monitoring10 531
Metering method of the quantity meters 11 532 Meter reset 13 533 Consumed
quantity monitoring via pulse signals 13 534 Consumed quantity monitoring via
switching signal (preset counter)14 54 Frequency output15 55 Analogue output17
56 Switching output 19 57 Measured value damping 20 58 Low flow cut-off 20 59
Start-up delay 20 510 Simulation23 511 Colour of the characters in the
display24 512 IO-Link 25 5121 Additional functions via IO-Link 25
6 Installation26 61 Recommended installation position27 62 Non-recommended
installation position 27
2
63 Ground28 64 Installation in pipes 29
7 Electrical connection30
8 Operating and display elements 32
9 Menu33 91 Process value display (RUN)33 92 Main menu 34 93 Extended functions EF 35 94 Submenu OUT1 and OUT2 36 UK 95 Submenu CFG and TOTL39 96 Submenu MEM and DIS 41 97 Submenu COLR and SIM 43
10 Set-up 45
11 Parameter setting45 111 Parameter setting in general46 1111 Select submenu 46 1112 Change to the process value display (RUN mode)46 1113 Locking / unlocking 46 1114 Timeout 47 112 Settings for volumetric flow monitoring 47 1121 Limit monitoring OUT1 or OUT2 / hysteresis function 47 1122 Limit monitoring OUT1 or OUT2 / window function 47 1123 Switching signal volumetric flow direction OUT1 or OUT2 47 1124 Frequency signal volumetric flow OUT1 48 1125 Analogue signal volumetric flow OUT2 48 113 Settings for consumed quantity monitoring48 1131 Metering method of the totalisers 48 1132 Quantity monitoring via pulse output OUT148 1133 Quantity monitoring via the preset counter OUT1 49 1134 Manual meter reset 49 1135 Time-controlled meter reset 49 1136 Deactivate meter reset49 1137 Meter reset via external signal49 1138 Read consumption values 50 114 Settings for temperature monitoring50
3
1141 Limit monitoring OUT1 or OUT2 / hysteresis function 50 1142 Limit
monitoring OUT1 or OUT2 / window function 50 1143 Frequency signal temperature
OUT1 50 1144 Analogue signal temperature OUT2 51 115 User settings
(optional)51 1151 Menu language 51 1152 Standard display 51 1153 Standard unit
of measurement for volumetric flow 52 1154 Standard unit of measurement for
temperature52 1155 Measured value damping 52 1156 Start-up delay 52 1157
Output logic52 1158 Low flow cut-off52 1159 Volumetric flow direction 52 11510
Colour of the characters in the display 53 11511 Error behaviour of the
outputs54 11512 Restore factory setting54 116 Diagnostic functions55 1161 Read
min/max values 55 1162 Simulation 55
12 Operation55
13 Troubleshooting 56
14 Maintenance, repair and disposal58
15 Factory setting 59
1
Preliminary note
You will find detailed instructions, technical data, approvals and further information using the QR code on the unit / packaging or at wwwifmcom
4
1.1 Symbols used
Instruction
Reaction, result
[…] Designation of keys, buttons or indications
Cross-reference
Important note Non-compliance may result in malfunction or interference
Information
Supplementary note
UK
1.2 Warnings used
CAUTION
Warning of personal injury Slight reversible injuries may result
2
Safety instructions
· The device described is a subcomponent for integration into a system
– The manufacturer is responsible for the safety of the system
– The system manufacturer undertakes to perform a risk assessment and to
create a documentation in accordance with legal and normative requirements to
be provided to the operator and user of the system This documentation must
contain all necessary information and safety instructions for the operator,
the user and, if applicable, for any service personnel authorised by the
manufacturer of the system
· Read this document before setting up the product and keep it during the
entire service life
· The product must be suitable for the corresponding applications and
environmental conditions without any restrictions
· Only use the product for its intended purpose ( Functions and features). ·
Only use the product for permissible media ( Technical data). · If the
operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur
5
· The manufacturer assumes no liability or warranty for any consequences
caused by tampering with the product or incorrect use by the operator
· Installation, electrical connection, set-up, operation and maintenance of
the product must be carried out by qualified personnel authorised by the
machine operator
· Protect units and cables against damage
3
Getting started
When the unit is used with factory setting the volumetric flow is monitored by
providing a switching signal and an analogue signal The process values for
volumetric flow and temperature and the meter readings (current and saved
values) as well as error messages can be read from the display All process
values and messages are available via the IO-Link interface irrespective of
the output configuration A simulation model allows simplified set-up of the
sensor
3.1 Device functions with factory setting Output OUT1: · Switching signal for
volumetric flow (hysteresis function normally open, PnP,
SP1 and rP1 15) · Measured value damping 06 seconds, no start-up delay and
minimal low flow
cut-off · In case of a fault the output switches OFF Output OUT2: · Analogue
signal for volumetric flow (measuring range unscaled) · In case of a fault the
analogue signal goes to 35 mA Display: · Text in English, colour of the
characters black/white · Simultaneous display of current process values for
volumetric flow and
temperature and quantity meter · Low refresh rate, 75 % display brightness
6
3.2 Setting options · Output functions of OUT1 and OUT2 (temperature or
volumetric flow;
switching, pulse, frequency, analogue signal, totaliser function) · Reversal
of the volumetric flow direction, monitoring of the volumetric flow · Response
times for volumetric flow measurement (measured value damping,
start-up delay, low flow cut-off) · Error behaviour of the outputs · Standard
views of the display (unit of measurement, process values, quantity
meter, refresh rate, rotation, brightness, process value-dependent change of
UK the colour of the characters)
4
Functions and features
The unit monitors liquid media It detects flow velocity, volume flow
(volumetric flow quantity/time), consumed quantity and medium temperature
4.1 Pressure Equipment Directive (PED) The units comply with the Pressure
Equipment Directive and are designed and manufactured for group 2 fluids
according to the sound engineering practice Use of group 1 fluids on request
4.2 Applications Conductive liquids with the following properties: ·
Conductivity: 20 µS/cm · Viscosity: < 70 mm2/s at 40 °C; < 70 cSt at 104 °F
This is a class A product This product may cause radio interference in
domestic areas If required, take appropriate EMC screening measures
7
Function
· The unit detects the volumetric flow on the magnetic-inductive volumetric
flow measuring principle
· As additional process value the unit detects the medium temperature with
volumetric flow
· The unit has an IO-Link interface · The unit displays the current process
values · The unit has many self-diagnostic options · A simulation mode allows
simplified set-up of the sensor
5.1 Process measured signals The unit generates 2 output signals according to
the parameter setting: OUT1: 9 selection options
– Switching signal for volumetric flow – Switching signal for temperature –
Switching signal for volumetric flow direction – Switching signal for preset
counter – Pulse signal for quantity meter – Frequency signal for volumetric
flow – Frequency signal for temperature – IO-Link – OFF (output switched to
high impedance) OUT2: 7 selection options – Switching signal for volumetric
flow – Switching signal for temperature – Switching signal for volumetric flow
direction – Analogue signal for volumetric flow – Analogue signal for
temperature – Input for external meter reset signal (InD) – OFF (output
switched to high impedance)
8
5.2 Volumetric flow direction
In addition to the flow velocity and the volumetric flow, the unit also
detects the volumetric flow direction
5.2.1 Determining the volumetric flow direction [Fdir]
An arrow with the text “flow direction” on the unit indicates the positive flow direction The volumetric flow direction can be reversed ( 11.5.9)
Use the supplied label to mark the changed volumetric flow direction
(new positive flow direction)
Volumetric flow…
UK Process value display
corresponds to the marked volumetric flow direction + (positive)
against the marked volumetric flow direction
– (negative)
5.2.2 Detection of the volumetric flow direction [dir.F] When [dirF] is
activated ( 11.2.5), the volumetric flow direction is indicated by a switching
signal
The output is switched on until the volumetric flow falls below the set
minimum volumetric flow quantity in negative flow direction (- LFC)(1) Then
the following applies:
– The output switches ON when volumetric flow is above + LFC (2)
– The output switches OFF when volumetric flow is below – LFC (3)
+ Q
1
2
3
+ LFC
– LFC
– Q 1 0
Fig 1: Monitoring of the volumetric flow direction by switching signals + Q :
Volumetric flow in positive flow direction
9
– Q : Volumetric flow in negative flow direction + LFC: Minimum volumetric
flow (low flow cut-off) in positive flow direction – LFC : Minimum volumetric
flow (low flow cut-off) in negative flow direction
LFC 5.8 Low flow cut-off
Positive volumetric flow direction = marked flow direction, with factory
setting marked by the arrow on the unit or after change via [Fdir] marked by
the supplied label ( 5.2.1)
5.3 Consumed quantity monitoring
The unit has three internal quantity meters (= totalisers) The totalisers
continuously sum up the consumed quantity and provide three process values via
the parameters [Vol1], [Vol2] and [VolL]:
Totaliser Vol1 Vol2 VolL
Process value totaliser 1 totaliser 2 lifetime totalisator (= meter reading over the whole lifetime)
Read access via IO-Link cyclical acyclical acyclical
The totalisers only sum up volumetric flow quantities above the LFC value 5.8
Low flow cut-off
The metering method of the totalisers Vol1 and Vol2 can be set so that
volumetric flow values are either ignored, subtracted or totalled in negative
volumetric flow direction ( 5.3.1) The metering method of VolL cannot be set
It totals all volumetric flow quantities irrespective of the volumetric flow
direction
The process values of the quantity meter (totaliser) can be displayed (
11.3.8) or read via the IO-Link interface
Pulse signals (pulse output) or a switching signal (preset counter) can be
used to monitor the consumed quantity 5.3.3 Consumed quantity monitoring via
pulse signals 5.3.4 Consumed quantity monitoring via switching signal (preset
counter)
10
5.3.1 Metering method of the quantity meters
The quantity meters take account of the volumetric flow direction when
totalling the consumed quantity ( Fig. 2). The following metering methods can
be defined via the parameters [FPro1] and [FPro2]:
[FPro1] Metering method [FPro2]*
0+
Negative volumetric flow quantity values (against the marked flow direction)
are not taken into account for totalling
+
Negative volumetric flow quantity values are subtracted from the consumed UK
quantity
++
All volumetric flow quantity values are totalled irrespective of the volumetric
flow direction
- [FPro1] = metering method for totaliser Vol1 [FPro2] = metering method for totaliser Vol2
11
+ Q FPro1 / FPro2 = 0 + 0
Q
+ Q FPro1 / FPro2 = + 0
Q
+ Q FPro1 / FPro2 = + + 0
Q
1
2
V Q
t
V Q
t
V Q
t
Fig 2: Taking account of the volumetric flow direction when totalling the
consumed quantity
+ Q = volumetric flow quantity in positive direction – Q = volumetric flow
quantity in negative direction
V = volumetric flow quantity absolute (= sum of negative and positive
volumetric flow) 1 Volumetric flow changes to negative direction 2 Volumetric
flow changes to positive direction
When the volumetric flow direction is changed a minimum volumetric flow
quantity is taken into account: – LFC in negative direction; + LFC in positive
direction ( 522)
12
5.3.2 Meter reset There are different ways to reset the quantity meters 11.3.4
Manual meter reset 11.3.5 Time-controlled meter reset 11.3.7 Meter reset via
external signal Meter reset via the IO-Link interface If the quantity meter is
not reset by applying one of the above-mentioned methods, an automatic reset
is made when the maximum volumetric flow quantity that can be displayed is
exceeded (overflow)
UK
The total meter reading [VolL] cannot be reset
The meter saves the totalled volumetric flow quantity every 10 seconds After a
power failure this value is available as the current meter reading If a time-
controlled reset is set, the elapsed time of the set reset interval is also
saved So the possible data loss is maximum 10 seconds
5.3.3 Consumed quantity monitoring via pulse signals Every time the volumetric
flow quantity (pulse value) set under [ImPS] has been reached, the output
provides a pulse signal The pulse signal consists of a short switching on and
off of the output The switching status LEDs on the unit do not display the
switching operation
Pulse signals are not available via the IO-Link interface
13
5.3.4 Consumed quantity monitoring via switching signal (preset counter)
When the volumetric flow quantity set under [ImPS] has been reached, the
output provides a switching signal The output remains switched until the meter
reset After a totaliser reset metering starts again
The accuracy of the consumed quantity measurement depends on the accuracy of the volumetric flow measurement
By setting [rTo1] it is set when the output switches and when the totaliser Vol1 is reset:
[rTo1] Output
Meter reset
OFF
· The output switches when the · The preset counter is reset
volumetric flow quantity set
– when a manual reset is made (
under [ImPS] is reached
- or
· The output remains switched until the meter reset
– when the maximum display range is exceeded (overflow)
1, 2, h 1, 2, d 1, 2, w
· The output switches only when the volumetric flow quantity set under [ImPS]
is reached within the set time
· The output remains switched until the meter reset
· If the output is not switched the preset counter is reset when the set time
is exceeded
· If the output is switched, the preset counter is only reset – when a manual
reset is made ( 1134) or – when the maximum display range is exceeded
(overflow)
By setting [rTo2] it is set when the totaliser Vol 2 is reset The setting of [rTo2] has no effect on the output:
[rTo2] OFF
Output No effect on the output
Meter reset
· The preset counter is reset – when a manual reset is made ( 1134) or – when
the maximum display range is exceeded (overflow)
14
[rTo2] [rTo2] = 1, 2, h 1, 2, d 1, 2, w
Output No effect on the output
Meter reset
· The preset counter is reset – when a manual reset is made ( 1134) or – when
the maximum display range is exceeded (overflow) or – when the set time is
exceeded
5.4 Frequency output The unit provides a frequency signal that is proportional
to the volumetric flow UK (velocity or volume flow) or to the medium
temperature
Within the measuring range the frequency signal is between 0 and 10 kHz
The frequency signal is scalable:
· [FrP1] defines the frequency signal in Hz that is provided when the upper
measured value (MEW or FEP1) is reached
The measuring range is scalable:
· [FSP1] defines the lower measured value from which a frequency signal is
provided Note: [FSP1] cannot be set for volumetric flow measurement
· [FEP1] defines the upper measured value at which the frequency signal FrP1
is provided Minimum difference between [FSP1] and [FEP1] = 20 % of the final
value of the measuring range
If the measured value is outside the measuring range or in the event of an
internal error, the frequency signals indicated in figure 3 are provided
For measured values outside the display range or in case of an error, messages
are displayed (OL, crOL, Err; ) The frequency signal in case of an error is
adjustable ( 11.5.11): · [FOU] = On defines that the frequency signal goes to
the upper final value
(130 % FrP1) in case of an error
· [FOU] = OFF defines that the frequency signal is 0 Hz in case of an error
· [FOU] = OU defines that in case of an error the frequency signal reacts as
defined by the current parameters
15
Frequency signals are not available via the IO-Link interface
Volumetric flow measurement
1
FOU=On 130 %
120 %
3
4
FrP
=100 %
5
Temperature monitoring
1
FOU=On 130 %
120 %
3
4
FrP
5
=100 %
FOU=OFF
0 %
MAW
2
FEP MEW OL cr.OL
FOU=OFF 0 %
MAW FSP
2
FEP MEW OL Err
100 % 120 % 130 % 100 % 120 % 130 %
Fig 3: Output characteristics frequency output
1 Frequency signal in kHz 2 Measured value (volumetric flow or temperature) 3
Display range 4 Measuring range 5 Scaled measuring range
MAW: Initial value of the measuring range with non-scaled measuring range
(with setting of low flow cut-off for Q: signal output starting at MAW + LFC
5.8)
MEW: Final value of the measuring range with non-scaled measuring range FSP:
Frequency start point with scaled measuring range (only temperature) FEP:
Frequency end point with scaled measuring range FrP: Frequency signal for
upper measured value OL: Above the display range crOL: Above the detection
zone (error) Err: The unit is in the error state
16
5.5 Analogue output The unit provides an analogue signal that is proportional to the volumetric flow (velocity or volume flow) or to the medium temperature Within the measuring range the analogue signal is between 4 and 20 mA The measuring range is scalable: · [ASP2] defines at which measured value the output signal is 4 mA · [AEP2] defines at which measured value the output signal is 20 mA
Minimum difference between [ASP2] and [AEP2] = 20 % of the final value of the measuring range
UK
If the measured value is outside the measuring range or in the event of an
internal error, the current signal indicated in figure 4 is provided
For measured values outside the display range or in case of an error, messages
are displayed (crUL, UL, OL, crOL, Err; ) The analogue signal in case of an
error is adjustable ( 11.5.11): · [FOU] = On defines that the analogue signal
goes to the upper final value
(215 mA) in case of an error
· [FOU] = OFF defines that the analogue signal goes to the lower final value
(35 mA) in case of an error
· [FOU] = OU defines that in case of an error the analogue signal reacts as
defined by the current parameters
17
1 [mA] FOU=On 21,5 20,5
20
4
3,8
FOU=OFF 3,5 3
4
5
6
cr.UL UL
MAW ASP
2
AEP MEW OL cr.OL
Q
-130 -120 0
100 120 130 [% MEW]
T
-50 -40 -20
-58 -40 -4
90 110 110 [°C] 194 212 230 [°F]
Fig 4: Characteristics of the analogue output according to the standard IEC 60947-5-7
1 Analogue signal 2 Measured value (volumetric flow or temperature) 3 Detection zone 4 Display range 5 Measuring range 6 Scaled measuring range
Q: Volumetric flow (negative volumetric flow quantity value = volumetric flow
against the marked flow direction)
T: Temperature MAW: Initial value of the measuring range with non-scaled
measuring range (With setting
of low flow cut-off for Q: signal output starting at MAW + LFC 5.8) MEW: Final
value of the measuring range with non-scaled measuring range ASP: Analogue
start point with scaled measuring range AEP Analogue end point with scaled
measuring range UL: Below the display range OL: Above the display range crUL:
Below the detection zone (error) crOL: Above the detection zone (error)
18
5.6 Switching output
OUTx changes its switching status if it is above or below the set switching
limits (flow velocity or volume flow or temperature) Hysteresis or window
function can be selected Example of volumetric flow monitoring:
SP
FH
rP
FL
UK
Fig 5: hysteresis function
SP = set point rP = reset point HY = hysteresis Hno / Fno = NO (normally open)
Fig 6: window function
FH = upper limit FL = lower limit FE = window Hnc / Fnc = NC (normally closed)
When the hysteresis function is set, the set point (SP) is defined first and then the reset point (rP) which must have a lower value If only the set point is changed, the reset point is changed automatically; the difference remains constant
When the window function is set, the upper limit (FH) and the lower limit (FL) have a fixed hysteresis of 025 % of the final value of the measuring range This keeps the switching status of the output stable if the volumetric flow varies slightly
19
5.7 Measured value damping The damping time [dAP] enables setting after how
many seconds the output signal has reached 63 % of the final value if the
volumetric flow value changes suddenly The set damping time stabilises the
switching outputs, the analogue outputs, the display and the process value
transmission via the IO-Link interface The damping time is added to the
response time of the sensor ( Technical data) The signals UL, crUL, OL and
crOL ( ) are determined by taking the damping time into account
The damping time only has an effect on the volumetric flow measurement
5.8 Low flow cut-off With the function low flow cut-off [LFC] it is possible
to suppress low volumetric flow values Volumetric flow below the LFC value is
evaluated by the sensor as standstill (Q = 0)
5.9 Start-up delay
The start-up delay [dSt] influences the switching outputs of the volumetric
flow monitoring
If the start-up delay is active ([dSt] > 0), the following applies: As soon as
the volumetric flow quantity exceeds the LFC value ( 5.8), the following
processes are carried out: > The start-up delay is activated > The outputs
switch as programmed: ON for NO function, OFF for NC function After activation
of the start-up delay there are 3 options: 1 The volumetric flow increases
quickly and reaches the set point / good range
within [dSt] > Outputs remain active 2 The volumetric flow increases slowly
and does not reach the set point / good
range within [dSt] > Outputs are reset
20
3 Volumetric flow falls below [LFC] within [dSt] > Outputs are reset at once; [dSt] is stopped
UK
Fig 7: dSt for hysteresis function (Example)
Condition
Reaction
1 Volumetric flow quantity Q reaches LFC dSt starts, output becomes active
2 dSt elapsed, Q reached SP
Output remains active
3 Q below SP but above rP
Output remains active
4 Q below rP
Output is reset
5 Q reaches again LFC
dSt starts, output becomes active
6 dSt elapsed, Q has not reached SP Output is reset
7 Q reaches SP
Output becomes active
21
Fig 8: dSt for window function (Example)
Condition 1 Volumetric flow quantity Q reaches LFC 2 dSt elapsed, Q reached
good range 3 Q above FH (leaves good range) 4 Q again below FH 5 Q below FL
(leaves good range) 6 Q reaches again LFC 7 dSt elapsed, Q has not reached
good
range 8 Q reaches good range
Reaction dSt starts, output becomes active Output remains active Output is
reset Output becomes active again Output is reset again dSt starts, output
becomes active Output is reset
Output becomes active
22
5.10 Simulation
With this function, the process values volumetric flow, temperature and meter reading of the totaliser are simulated and their signal chain is checked
When the parameters crUL, UL, OL und crOL are set, process values that lead to an error message or warning can be simulated ( )
When the simulation is started, the values of the totalisers 1-3 are frozen and the
simulated totaliser is set to 0 The simulated volumetric flow value then has an
effect on the simulated totaliser When the simulation is ended, the initial totaliser
values are restored
UK
The simulation has no effect on the current process values The outputs
operate as previously set
During the simulation the original totaliser value remains saved without any changes even if there is a real volumetric flow
During the simulation no error message of the current application is available They are suppressed by the simulation
23
5.11 Colour of the characters in the display Via the parameters [coLF], [coLT]
and [coLV] the colour of the characters in the display can be set: · Permanent
definition of the display colour:
– bk/wh (black/white) – yellow – green – red · Colour change from red to green
or vice versa (Fig 9): – r-cF (red display colour between the limits cFLcFH) –
G-cF (green display colour between the limits cFLcFH)
cFL.T cFL.F MAW
cFH.T MEW cFH.F
Fig 9: Colour setting window function
cFLT = lower limit for temperature cFLF = lower limit for volumetric flow cFHT
= upper limit for temperature cFHF = upper limit for volumetric flow
MAW = initial value of the measuring range MEW = final value of the measuring
range
The limits can be freely selected within the measuring range and are independent of the output function set for OUT1 and OUT2
24
5.12 IO-Link
This unit has an IO-Link communication interface which enables direct access
to process and diagnostic data In addition it is possible to set the
parameters of the unit while it is in operation Operation of the unit via the
IO-Link interface requires an IO-Link master
With a PC, suitable IO-Link software and an IO-Link adapter cable
communication is possible while the system is not in operation
The IODDs necessary for the configuration of the unit, detailed information
about process data structure, diagnostic information, parameter addresses and
the UK necessary information about the required IO-Link hardware and software
can be found at wwwifmcom
The IO-Link interface provides the following additional functions using
suitable hardware and software:
– Remote parameter setting of the unit
– Noise-immune signal transmission without measured value losses
– Transmission of the parameter settings to a replaced unit or to other units
of the same type
– Simultaneous reading of all process values (volumetric flow, temperature,
totaliser), the binary switching signals and the device status
– Comprehensive display of error and event messages (events)
– Paperless logging of parameter sets, process values and diagnostic
information
5.12.1 Additional functions via IO-Link
The following functions are only available via the IO-Link interface:
Function
Flash ON / Flash OFF
Explanation Standard command for localising the sensor in the system When activated: > Switching status LEDs flashing > Display: “IO-Link” (green, flashing)
25
Function Explanation
Flow Override When activated: simulation volumetric flow standstill (Q = 0)
All outputs behave as with volumetric flow standstill
During the simulation the original totaliser value remains saved without any changes even if there is a real volumetric flow
Lock via system
When activated: setting buttons locked via parameter setting software, parameter change rejected
6
Installation
CAUTION! If the medium temperature is above 50 °C (122 °F) parts of the
housing can increase in temperature to over 65 °C (149 °F) > Risk of burns
Protect the housing against contact with flammable substances
and unintentional contact Apply the supplied warning label to the sensor cable
Ensure that the system is free of pressure during installation Ensure that no
media can leak at the mounting location during
installation
The unit can be installed independently of the orientation if the following is
ensured:
– No air bubbles can form in the pipe system – The pipes are always completely
filled
Calming sections on the sensor’s inlet or outlet side are not necessary
26
F F
6.1 Recommended installation position Install the unit so that the measuring
pipe is always completely filled Install in front of or in a rising pipe
UK
F
6.2 Non-recommended installation position
F
Directly in front of a falling pipe
In a falling pipe 27
F F
Directly in front of the spout of a pipe
On the suction side of a pump
F
At the highest point of the pipe system F = volumetric flow direction
6.3 Ground If installed in an ungrounded pipe system (eg plastic pipes), the
unit must be grounded (functional earth)
Ground brackets for the M12 connector are available as accessories
www.ifm.com.
28
6.4 Installation in pipes The units with a G thread can be installed in the pipes using adapters Information about the available mounting accessories at wwwifmcom A correct fit of the unit and ingress resistance of the connection are only ensured using ifm adapters
A
B CD
DCB
A
UK
1 Grease the threads of the process connection, adapter and sensor Use a
lubricating paste which is suitable and approved for the application
2 Screw the adapter (B) into the pipe (A) 3 Place the seals (C) and install
the unit according to the marked flow direction 4 Screw the adapter (B) with
the process connections (D) until it is hand-tight 5 Tighten the two adapters
in opposite direction:
– tightening torque DN15DN25: 30 Nm – tightening torque DN6: 15 Nm
After installation air bubbles in the system can affect the measurement
Corrective measure: Rinse the system after installation for ventilation
29
7 Electrical connection
The unit must be connected by a qualified electrician Voltage supply according
to EN 50178, SELV, PELV
Disconnect power Connect the unit as follows:
1 BN 2 WH 4 BK 3 BU
Colours to DIN EN 60947-5-2 BK: black; BN: brown; BU: blue; WH: white
L+ OUT2 OUT1 L
Pin 4 (OUT1)
2 (OUT2/InD)
Connection
· switching signal for volumetric flow · switching signal for temperature ·
switching signal for volumetric flow direction · switching signal for preset
counter · pulse signal for quantity meter · frequency signal for volumetric
flow · frequency signal for temperature · IO-Link · OFF
· switching signal for volumetric flow · switching signal for temperature ·
switching signal for volumetric flow direction · analogue signal for
volumetric flow · analogue signal for temperature · input for external meter
reset signal (InD) · OFF
30
Circuit examples: 1 2 x PnP
1 BN
L+
2 WH
4 BK
3 BU
L
3 1 x PnP / 1 x analogue
1 BN
L+
2 WH
4 BK
3 BU
L
2 2 x nPn
1 BN
L+
2 WH
4 BK
3 BU
L
4 1 x nPn / 1 x analogue
UK
1 BN
L+
4 BK
2 WH
3 BU
L
31
8 Operating and display elements
1
2
3
5 4
1 and 2: Switching status LEDs · LED 1 = switching status OUT1 (on if output 1
is switched) · LED 2 = switching status OUT2 (on if output 2 is switched) 3:
TFT display · Display of the current process values (volumetric flow,
temperature, totaliser) · Display of the parameters and parameter values 4:
Buttons [] and [] · Select parameter · Change parameter value (hold button
pressed) · Change of the process value display in the normal operating mode
(RUN mode) · Locking / unlocking (buttons pressed simultaneously > 10 seconds)
5: Button [] = Enter · Change from the RUN mode to the main menu · Change to
the setting mode · Apply the set parameter value
Display illumination: · Device temperature > 70 °C: brightness automatically
reduced · Device temperature 100 °C: display automatically switched off.
32
9 Menu
9.1 Process value display (RUN) It is possible to select three process value
indications during operation: Press button [ ] or []. > The display changes
between the standard indication and two other views > After 30 s, the device
returns to the standard display
1
Running
2000
L/min
2
Running
20.00 L/min
30.0 °C
1000.0
Totaliser 1
l
3
UK
Running
1000.0
Totaliser 1
l
0.000
Last Totaliser 1 l
–Time since reset
1: Standard display as set under [diSL] ( 11.5.2) 2: Overview of all process
values
3: Overview totaliser values
33
9.2 Main menu
Process value display (RUN)
FSP1
SP1
FH1
ImPS
FEP1
rP1
FL1
ImPR
FrP1
ASP2
SP2
AEP2
rP2
EF
FH2
DIn2
FL2
EF rES, Info, OUT1, OUT2, CFG, TOTL, MEM, DIS, COLR, SIM
Explanation of the parameters 9.4 Submenu OUT1 and OUT2
34
9.3 Extended functions EF
Main menu
rES Info OUT1 OUT2 CFG TOTL MEM DIS COLR SIM
– – – – – – –
EF
Parameter rES
Explanation and setting options
Restore factory setting
Info OUT1
Display device information
UK Configuration output 1
OUT2
Configuration output 2
CGF
Configuration basic settings
TOTL
Display totaliser values
MEM
Display min/max process
values
DIS
Configuration display view
COLR
Configuration display colour
SIM
Configuration simulation mode
35
9.4 Submenu OUT1 and OUT2
Main menu
rES Info OUT1 OUT2 CFG TOTL MEM DIS COLR SIM
SEL1 ou1
FLOW TEMP Hno Hnc Fno Fnc ImP OFF FRQ dirF
FSP1
SP1
FH1 ImPS FEP1
rP1
FL1 ImPR FrP1
FOU1
OU On OFF
OUT1
SEL2
FLOW TEMP
ou2
EF
Hno Hnc Fno Fnc In.D OFF dirF I
ASP2 SP2 AEP2 rP2
FH2 DIn2 FL2
+EDG -EDG HIGH LOW
FOU2
OU On OFF
OUT2
36
Explanation submenu OUT1
Parameter Explanation and setting options
SEL1
Standard measured variable for evaluation by OUT1: FLOW (volumetric flow) or TEMP (temperature)
ou1
Output function for OUT1:
· Volumetric flow: Hno, Hnc, Fno, Fnc, ImP, OFF, FRQ, dirF
· Temperature: Hno, Hnc, Fno, Fnc, OFF, FRQ
Hno = switching signal with hysteresis function normally open
Hnc = switching signal with hysteresis function normally closed
Fno = switching signal with window function normally open
UK
Fnc = switching signal with window function normally closed
ImP = consumed quantity monitoring (totaliser function)
OFF = output OFF (of high impedance)
FRQ = frequency signal
dirF = detection of the volumetric flow direction
SP1
Set point for OUT1
rP1
Reset point for OUT1
FH1
Upper limit for OUT1
FL1 ImPS ImPR
FSP1 FEP1
Lower limit for OUT1 Pulse value = volumetric flow quantity at which 1 pulse is delivered Configuration of the output for consumed quantity monitoring: YES (pulse signal), no (switching signal) Start point for OUT1, only for SEL1 = TEMP (temperature) End point for OUT1
FrP1
Frequency for end point FEP1 at OUT1
FOU1
Status of OUT 1 in case of an internal fault: OU = output 1 switches
irrespective of the fault as defined with the
parameters On = output switches ON / frequency signal goes to the upper final
value OFF = output switches OFF / frequency signal goes to 0
FOU1 is not available if ou1 = ImP
37
Explanation submenu OUT2
Parameter SEL2 ou2
SP2 rP2 FH2 FL2 ASP2 AEP2 DIn2 FOU2
Explanation and setting options
Standard measured variable for evaluation by OUT2: FLOW (volumetric flow) or
TEMP (temperature)
Output function for OUT2: · Volumetric flow: Hno, Hnc, Fno, Fnc, In.D, OFF,
dir.F, I · Temperature: Hno, Hnc, Fno, Fnc, OFF, I
Hno = switching signal with hysteresis function normally open Hnc = switching
signal with hysteresis function normally closed Fno = switching signal with
window function normally open Fnc = switching signal with window function
normally closed In.D = input for external meter reset signal OFF = output OFF
(of high impedance) dirF = detection of the volumetric flow direction I =
analogue signal 420 mA
Set point for OUT2
Reset point for OUT2
Upper limit for OUT2
Lower limit for OUT2
Analogue start point for OUT2
Analogue end point for OUT2
Reset of totaliser Vol1 via external signal: +EDG, -EDG, HIGH, LOW
Status of OUT 2 in case of an internal fault: OU = output switches
irrespective of the fault as defined with the
parameters On = output switches ON / analogue signal goes to 215 mA OFF =
output switches OFF / analogue signal goes to 35 mA
38
9.5 Submenu CFG and TOTL
Main menu uni.F
rES Info OUT1 OUT2 CFG TOTL MEM DIS COLR SIM
uni.T dAP dSt P-n LFC Fdir
rTo1
rTo2
EF
FPro1
FPro2
Vol.1
Vol.2
Vol.L
L/min m3/h m/s gal/min gal/h floz/min ft/s
°C °F
– – –
UK
– – –
PnP nPn
– – –
+-
CFG
rES.T OFF 1 h 2 h 3 h 4 h 5 h …
rES.T OFF 1 h 2 h 3 h 4 h 5 h …
-+ 0+ ++
-+ 0+ ++
…
…
…
TOTL
39
Explanation submenu CFG
Parameter uniF
uniT dAP
dSt P-n LFC Fdir
Explanation and setting options
Standard unit of measurement for volumetric flow: m/s, l/min, m3/h, gal/min,
gal/h, fl oz/min, ft/s (SM4: ml/min) Standard unit of measurement for
temperature: °C or °F Measured value damping for switching output in seconds
(only volumetric flow) Start-up delay in seconds (only volumetric flow) Output
logic: PnP or nPn Low flow cut-off Volumetric flow direction: + or
Explanation submenu TOTL
Parameter rTo1 rTo2 FPro1 FPro2 Vol1 Vol2 VolL
Explanation and setting options Reset of totaliser Vol1: OFF, resT or time Reset of totaliser Vol2: OFF, resT or time Metering method of totaliser Vol1: 0+ or + or ++ Metering method of totaliser Vol2: 0+ or + or ++ Display of current meter reading totaliser 1 Display of current meter reading totaliser 2 Display of current meter reading over the whole lifetime
40
9.6 Submenu MEM and DIS
Main menu
rES Info OUT1 OUT2 CFG TOTL MEM DIS
COLR EF
SIM
Lo.F
…
UK
Hi.F
…
Lo.T
…
Hi.T
…
MEM
LanG diS.L diS.U diS.R diS.B
DE EN FR L1 L2.Temp L2.Totl L3 d1 d2 d3 0 90 180 270
25 50 75 100 OFF DIS
41
Explanation submenu MEM
Parameter LoF HiF LoT HiT
Explanation and setting options Min value of the volumetric flow quantity measured in the process Max value of the volumetric flow quantity measured in the process Min value of the temperature measured in the process Max value of the temperature measured in the process
Explanation submenu DIS
Parameter LanG diSL
diSU
diSR diSB
Explanation and setting options
Menu language: DE or EN or FR
Standard process value display (in selected standard unit of measure-
ment)
L1
= current process value for volumetric flow
L2Temp = current process value for volumetric flow and temperature
L2Totl = current process value for volumetric flow and totaliser Vol1
L3
= current process value for volumetric flow and temperature and
totaliser Vol1
Display refresh rate:
d1 = high d2 = medium d3 = low
Display rotation: 0°, 90°, 180°, 270°
Display brightness: 25 %, 50 %, 75 %, 100 %, OFF (measured value display in the RUN mode switched off)
42
9.7 Submenu COLR and SIM
Main menu
rES Info OUT1 OUT2 CFG TOTL MEM DIS COLR SIM
EF
coL.F
bk/wh red green yellow r-cF G-cF
cFHF
– – –
UK
cFLF
– – –
coL.T
bk/wh red green yellow r-cF G-cF
cFHT
– – –
cFLT
– – –
coL.V
bk/wh red green yellow
COLR
SFLW STMP STim S.On
– – –
OL crOL crUL UL
– – –
OL crOL crUL UL
1 2 3 4 5 10
OFF On SIM
43
Explanation submenu COLR
Parameter Explanation and setting options
coLF
Colour of the characters in the display for the volumetric flow value
cFHF
Upper limit of the colour change for volumetric flow measurement
cFLF
Lower limit of the colour change for volumetric flow measurement
coLT
Colour of the characters in the display for the temperature value
cFHT
Upper limit of the colour change for temperature measurement
cFLT
Lower limit of the colour change for temperature measurement
coLV
Colour of the characters in the display for totaliser value Vol1
bk/wh Permanently black/white
yellow Permanently yellow
green Permanently green
red Permanently red
r-cF Display colour red between the limits cFLcFH, outside colour change to green
G-cF Display colour green between the limits cFLcFH, outside colour change to red
Explanation submenu SIM
Parameter Explanation and setting options
SFLW
Simulated volumetric flow value
STMP
Simulated temperature value
crUL Measured value below the detection zone error message
UL Measured value below the display range warning
OL Measured value above the display range warning
crOL Measured value above the detection zone error message
STim
Simulation time in minutes
SOn
Simulation status: OFF, On
44
10
Set-up
After power on and expiry of the power-on delay time of approx 5 s the unit is in the Run mode (= normal operating mode) It carries out its measurement and evaluation functions and generates output signals according to the set parameters
· During the power-on delay time the outputs are switched as programmed:
– ON with normally open function (Hno / Fno)
– OFF with normally closed function (Hnc / Fnc)
– ON for detection of flow direction (dirF)
UK
– OFF for frequency output (FRQ)
– OFF for consumed quantity monitoring (ImP)
· If output 2 is configured as analogue output, the output signal is at 20 mA during the power-on delay time
11
Parameter setting
CAUTION
If the medium temperature is above 50 °C (122 °F) parts of the housing can
increase in temperature to over 65 °C (149 °F)
Risk of burns Do not touch the device with your hands Use another object (eg a ballpoint pen) to carry out settings
on the unit
Parameters can be set before installation or during operation
If you change parameters during operation, this will influence the function of
the plant
Ensure that there will be no malfunctions in your plant During parameter
setting the unit remains in the operating mode It continues to monitor with
the existing parameter until the parameter setting has been completed
The parameters can also be set via the IO-Link interface
45
11.1 Parameter setting in general
1 Change from the RUN mode to the main menu 2 Select the requested parameter 3 Change to the setting mode 4 Modification of the parameter value 5 Apply the set parameter value 6 Return to the RUN mode
[] [] or [] [] [] or [] > 1 s [] > 30 seconds (timeout)
If [ Locked via Communication] is displayed when you try to change a parameter
value, an IO-Link communication is active (temporary locking) If [ Locked via
system] is displayed, the sensor is permanently locked via software This
locking can only be removed with a parameter setting software
11.1.1 Select submenu 1 Press [] to change from the process value display to
the main menu 2 Press [] to select the menu EF and press [] 3 Press [] to
select the submenu and press [] 11.1.2 Change to the process value display
(RUN mode) There are 2 possibilities: 1 Wait for 30 seconds ( 11.1.4 Timeout)
2 Press [] or [] to go to the end of the menu and change to the next higher
menu
11.1.3 Locking / unlocking The unit can be locked electronically to prevent
unintentional settings On delivery: not locked Locking: Make sure that the
unit is in the normal operating mode Press [] and [] simultaneously for 10 s
until [ Set menu lock] is displayed
During operation: [ ] is displayed if you try to change parameter values
46
Unlocking: Make sure that the unit is in the normal operating mode Press [] and [] simultaneously for 10 s until [Reset menu lock] is displayed.
Via the IO-Link interface the setting buttons can be locked with [Lock via system] so that you can no longer set parameters on the unit
11.1.4 Timeout
If no button is pressed for 30 s during parameter setting, the unit returns to the
operating mode with unchanged values
UK
11.2 Settings for volumetric flow monitoring
11.2.1 Limit monitoring OUT1 or OUT2 / hysteresis function
Select [uniF] and set the unit of measurement Select [SELx] and set FLOW
Select [oux] and set the switching signal:
– Hno = hysteresis function / normally open – Hnc = hysteresis function /
normally closed Select [SPx] and set the value at which the output switches
Select [rPx] and set the value at which the output switches off
Menu OUTx: [SELx] [oux] [SPx] [rPx]
11.2.2 Limit monitoring OUT1 or OUT2 / window function
Select [uniF] and set the unit of measurement Select [SELx] and set FLOW
Select [oux] and set the switching signal:
– Fno = window function / normally open – Fnc = window function / normally
closed
Select [FHx] and set the upper limit of the window section Select [FLx] and
set the lower limit of the window section
Menu OUTx: [SELx] [oux] [FHx] [FLx]
11.2.3 Switching signal volumetric flow direction OUT1 or OUT2
Select [SELx] and set FLOW Select [oux] and select detection of flow direction
dirF > Output switches when the volumetric flow direction is reversed (
522)
Menu OUTx: [SELx] [oux]47
11.2.4 Frequency signal volumetric flow OUT1
Select [uniF] and set the unit of measurement Select [SEL1] and set FLOW
Select [ou1] and select frequency signal: FRQ Select [FEP1] and set the upper
volumetric flow value at which the
frequency set in FrP1 is provided Select [FrP1] and set the frequency
11.2.5 Analogue signal volumetric flow OUT2
Select [uniF] and set the unit of measurement Select [SEL2] and set FLOW
Select [ou2] and select analogue signal: I (4…20 mA) Select [ASP] and set the
value at which 4 mA is provided Select [AEP] and set the value at which 20 mA
is provided
Menu OUT1: [SEL1] [ou1] [FEP1] [FrP1] Menu OUT2: [SEL2] [ou2] [ASP2] [AEP2]
11.3 Settings for consumed quantity monitoring
11.3.1 Metering method of the totalisers
Select [FPro1] and set the metering method for totaliser Vol1 Select [FPro2]
and set the metering method for totaliser Vol2
0+ = totalling only positive volumetric flow values -+ = totalling the
volumetric flow quantity values with the correct sign ++ = all volumetric flow
quantities are totalled irrespective of the volu-
metric flow direction
Menu TOTL: [FPro1] [FPro2]
11.3.2 Quantity monitoring via pulse output OUT1
Select [uniF] and set the unit of measurement
Menu OUT1:
Select [SEL1] and set FLOW
[SEL1]
Select [ou1] and set pulse output: ImP
[ou1]
Select [ImPS] and set pulse value (= volumetric flow quantity at which a [ImPS]
pulse is provided):
[ImPR]
1 Press [] or [] to select the setting range.
2 Briefly press [] to confirm the setting range
3 Press [] or [] to set the requested numeric value.
4 Briefly press [] to apply the value
Select [ImPR] and set YES
48
11.3.3 Quantity monitoring via the preset counter OUT1
Select [uniF] and set the unit of measurement Select [SEL1] and set FLOW
Select [ou1] and set pulse output: ImP Select [ImPS] and set the volumetric
flow quantity at which output 1
switches Select [ImPR] and set no
Menu OUT1: [SEL1] [ou1] [ImPS] [ImPR]
11.3.4 Manual meter reset
Select [rTo1] for totaliser Vol1 or [rTo2] for totaliser Vol2 and set rEST Menu TOTL: UK
The respective totaliser is reset to zero
[rTo1] [rTo2]
11.3.5 Time-controlled meter reset
Select [rTo1] for totaliser Vol1 or [rTo2] for totaliser Vol2 and set the
requested value (intervals of hours, days or weeks)
The respective totaliser is reset automatically with the value set
Menu TOTL: [rTo1] [rTo2]
11.3.6 Deactivate meter reset
Select [rTo1] for totaliser Vol1 or [rTo2] for totaliser Vol2 and set OFF >
The respective totaliser is only reset after overflow
Menu TOTL: [rTo1] [rTo2]
11.3.7 Meter reset via external signal
Select [ou2] and set In.D. Select [DIn2] and set the meter reset signal:
– HIGH = reset for high signal – LOW = reset for low signal – +EDG = reset for
rising edge – EDG = reset for falling edge > Totaliser Vol1 is reset to zero
An external meter reset is only possible for totaliser Vol1
Menu OUT2: [ou2] [DIn2]
49
11.3.8 Read consumption values
Select [Vol1], [Vol2] or [VolL] to display the respective meter reading: – [Vol1] = current meter reading totaliser 1 – [Vol2] = current meter reading totaliser 2 – [VolL] = current meter reading lifetime totaliser
Menu TOTL: [Vol1] [Vol2] [VolL]
11.4 Settings for temperature monitoring
11.4.1 Limit monitoring OUT1 or OUT2 / hysteresis function
Select [uniT] and set the unit of measurement Select [SELx] and set TEMP
Select [oux] and set the switching signal:
– Hno = hysteresis function / normally open – Hnc = hysteresis function /
normally closed Select [SPx] and set the value at which the output switches
Select [rPx] and set the value at which the output switches off
11.4.2 Limit monitoring OUT1 or OUT2 / window function
Select [uniT] and set the unit of measurement Select [SELx] and set TEMP
Select [oux] and set the switching signal:
– Fno = window function / normally open – Fnc = window function / normally
closed Select [FHx] and set the upper limit of the window section Select [FLx]
and set the lower limit of the window section
11.4.3 Frequency signal temperature OUT1
Select [uniT] and set the unit of measurement Select [SEL1] and set TEMP
Select [ou1] and select frequency function: FRQ Select [FSP1] and set the
lower temperature value from which a
frequency signal is provided Select [FEP1] and set the upper temperature value
at which the
frequency set in FrP1 is provided Select [FrP1] and set the frequency
Menu OUTx: [SELx] [oux] [SPx] [rPx] Menu OUTx: [SELx] [oux] [FHx] [FLx] Menu OUT1: [SEL1] [ou1] [FSP1] [FEP1] [FrP1]
50
11.4.4 Analogue signal temperature OUT2
Select [uniT] and set the unit of measurement Select [SEL2] and set TEMP
Select [ou2] and select analogue signal: I (4…20 mA) Select [ASP] and set the
value at which 4 mA is provided Select [AEP] and set the value at which 20 mA
is provided
Menu OUT2: [SEL2] [ou2] [ASP2] [AEP2]
11.5 User settings (optional)
11.5.1 Menu language
Select [LanG] and set menu language: – DE = German – EN = English – FR =
French
UK Menu DIS:
[LanG]
11.5.2 Standard display
Select [diSL] and set process value display:
Menu DIS:
– L1 = current process value for volumetric flow
[diSL]
– L2Temp = current process value for volumetric flow and temperature [diSU]
– L2Totl = current process value for volumetric flow and totaliser Vol1 [diSR]
– L3 = current process value for volumetric flow and temperature [diSB]
and totaliser Vol1
Select [diSU] and set the refresh rate of the display:
– d1 = high
– d2 = medium – d3 = low
Select [diSR] and set the orientation of the display: 0°, 90°, 180°, 270°
Select [diSB] and set the brightness of the display: 25 %, 50 %, 75 %, 100 %
or OFF (= energy-saving mode The display is switched off in the
operating mode Error messages are displayed even if the display is
deactivated Display activation by pressing any button)
51
11.5.3 Standard unit of measurement for volumetric flow
Select [uniF] and set the unit of measurement for standard display ( 1152)
m/s ml/min l/min m3/h gal/min gal/h floz/min ft/s
SM4x
xx
xxx xx
SM6/SM7/SM8 x
xx x x x x
Menu CFG: [uniF]
Set [uniF] prior to configurating the outputs
The consumed quantity (meter reading) is automatically displayed in the unit of measurement providing the highest accuracy
11.5.4 Standard unit of measurement for temperature
Select [uniT] and set the unit of measurement for standard display ( Menu CFG:
1152): °C or °F
[uniT]
Set [uniT] prior to configurating the outputs
11.5.5 Measured value damping
Select [dAP] and set the damping constant in seconds ( value 63 %).
Menu CFG: [dAP]
11.5.6 Start-up delay
Select [dSt] and set the switching delay in seconds
Menu CFG: [dSt]
11.5.7 Output logic
Select [P-n] and set PnP or nPn
Menu CFG: [P-n]
11.5.8 Low flow cut-off
Select [LFC] and set the limit below which a volumetric flow is evaluated as
standstill
Menu CFG: [LFC]
52
11.5.9 Volumetric flow direction
Select [Fdir] and set the volumetric flow direction: + = volumetric flow in
direction of the arrow (= factory setting) = volumetric flow against the
direction of the arrow Apply enclosed label over the arrow ( 5.2.1)
Menu CFG: [Fdir]
11.5.10 Colour of the characters in the display
Select [coLF] for volumetric flow or [coLT] for temperature and set the colour
of the characters for the process value in the standard display:
– bk/wh = permanently black/white – yellow = permanently yellow – green =
permanently green – red = permanently red – r-cF = display colour red between
the limits cFLcFH, outside
colour change to green – G-cF = display colour green between the limits
cFLcFH, outside
colour change to red
Select [cFHx] and [cFLx] and set the limits for the colour window: – cFHF =
upper limit for volumetric flow – cFLF = lower limit for volumetric flow –
cFHT = upper limit for temperature – cFLT = lower limit for temperature
Select [coLV] and set the colour of the characters for totaliser Vol1: – bk/wh
= permanently black/white – yellow = permanently yellow – green = permanently
green – red = permanently red
Menu COLR:
[coLF] [coLT]
UK
[cFHF] [cFLF] [cFHT] [cFLT] [coLV]
53
11.5.11 Error behaviour of the outputs
Select [FOU1] and set the error behaviour for output 1: Switching output – On
= Output 1 switches ON in case of an error – OFF = Output 1 switches OFF in
case of an error – OU = Output 1 switches irrespective of the error as defined
with the parameters
Frequency output – On = The frequency signal goes to the upper error value (
5.4) – OFF = The frequency signal goes to the lower error value ( 5.4) – OU =
The frequency signal corresponds to the measured value
Select [FOU2] and set the error behaviour for output 2: Switching output – On
= Output 2 switches ON in case of an error – OFF = Output 2 switches OFF in
case of an error – OU = Output 2 switches irrespective of the error as defined
with the parameters
Analogue output – On = The analogue signal goes to the upper error value (
5.5) – OFF = The analogue signal goes to the lower error value ( 5.5) – OU =
The analogue signal corresponds to the measured value
The parameter [FOUx] is not available if [ou1] = ImP (consumed quantity
monitoring) is selected Pulses or switching signals are provided irrespective
of the error
Menu OUT1: [FOU1] Menu OUT2: [FOU2]
11.5.12 Restore factory setting
Select [rES] Briefly press [] Keep [] or [] pressed. > [—-] is displayed
Briefly press [] > The device carries out a reboot
15 Factory setting We recommend taking down your own settings in that table
before carrying out a reset
Menu EF: [rES]
54
11.6 Diagnostic functions 11.6.1 Read min/max values
Select [Lox] or [Hix] to display the highest or lowest process value measured:
– [LoF] = min value of the volume flow measured in the process – [HiF] = max
value of the volume flow measured in the process – [LoT] = min value of the
temperature measured in the process – [HiT] = max value of the temperature
measured in the process
Menu MEM: [LoF] [HiF] [LoT] [HiT]
Delete memory:
Select [Lox] or [Hix]
UK
Keep [] and [] pressed.
[—-] is displayed
Briefly press []
It makes sense to delete the memories as soon as the unit operates under normal operating conditions for the first time
11.6.2 Simulation
Select [SFLW] and set the volume flow value to be simulated Select [STMP] and
set the temperature value to be simulated Select [STim] and set the time of
the simulation in minutes Select [SOn] and set the function:
– On = The simulation starts The values are simulated for the time set under
[STim] Abort by pressing any button
– OFF = The simulation is not active
Menu SIM: [SFLW] [STMP] [STim] [SOn]
12 Operation
The process values to be displayed permanently can be preset ( 11.5.2 Standard
display) A standard unit of measurement can be defined for the volumetric flow
measurement and temperature measurement ( 11.5.3 and 1154)
As an option for the preset standard display, the display can be changed by
pressing the button [] or [] 9.1 Process value display (RUN)
55
13 Troubleshooting
The unit has many self-diagnostic options It monitors itself automatically
during operation Warnings and error states are displayed even if the display
is switched off Error indications are also available via IO-Link The status
signals are classified according to NAMUR recommendation NE107 If several
diagnostic events occur simultaneously, only the diagnostic message of the
event with the highest priority is displayed
If a process value fails, the other process values are still available
Additional diagnostic functions are available via IO-Link IODD interface
description at wwwifmcom
Process value line Title line
Status LED Type Description Output behaviour Troubleshooting
ERROR ERROR —
Off
Off
—
—
—
—
—
—
—
PARA Param- –eter Error
ERROR Flow
—
Error
ERROR Temp
—
Error
56
Unit faulty / malfunction Supply voltage too low
Device temperature too high, display off Device temperature too high, display
brightness reduced Parameter setting outside the valid range Error volumetric
flow measurement
Error in temperature measurement
FOU Replace device
off Check supply voltage Change setting [diSB] ( 11.5.2)
OU Check device temperature
OU Check device temperature
FOU Repeat parameter setting
FOU Check volumetric flow measurement Replace device
FOU Check temperature measurement Replace device
Process value line Title line
Status LED Type Description Output behaviour Troubleshooting
crOL Critical –over limit
crUL Critical –under limit
— Short OUT1 circuit OUT2 OUT1/ OUT2
— Short OUT1 circuit OUT1
— Short OUT2 circuit OUT2
OL Over
—
limit
UL Under
—
limit
Lock via —
—
key
Lock via —
—
commu-
nication
Detection zone exceeded
Detection zone not reached
Short circuit OUT1 and OUT2
Short circuit OUT1
Short circuit OUT2
Measuring range exceeded
Measuring range not reached
Setting buttons on the unit locked, parameter change rejected Parameter
setting locked via pushbuttons, parameter setting is active via IO-Link
communication
FOU Check volumetric flow range / temperature range
FOU Check volumetric
flow range / tempera-
ture range
UK
— Check switching
outputs OUT1 and
OUT2 for short circuit
or excessive current
— Check switching output OUT1 for short circuit or excessive current
— Check switching output OUT2 for short circuit or excessive current
OU Check volumetric flow range / temperature range
OU Check volumetric flow range / temperature range
OU Unlock unit ( 11.1.3)
OU Finish parameter setting via IO-Link communication
57
Process value line Title line
Status LED Type Description Output behaviour Troubleshooting
Lock via —
—
system
Setting buttons locked via parameter setting software, parameter change rejected
OU Unlock the unit via IO-Link interface using the parameter setting software
IO-Link IO-Link OUT1 flash OUT2
IO-Link function for optical identification of the unit active
OU Deactivate IO-Link function
Display range / detection zone 5.5, figure 1
Error In the event of an error, the outputs react according to the setting
under [FOU1] and [FOU2] ( 11.5.11)
Warning
LED flashes
LED flashes quickly
14 Maintenance, repair and disposal
As a rule, no measures for maintenance are necessary
Define regular calibration intervals according to the process requirements
Recommendation: every 12 months
If media with a tendency to build-up are used:
Check measuring pipe at regular intervals and clean it, if necessary Only the
manufacturer is allowed to repair the unit
After use dispose of the unit in an environmentally friendly way in accordance
with the applicable national regulations
58
15 Factory setting
Parameter SM4020 SM6020 SM6621 SM7020 SM7621 SM8020 SM8621 SM8030
SM4120 SM6120
SM7120
SM8120
SM8130
SM6420
SM7420
SM8420
SEL1 FLOW FLOW FLOW FLOW FLOW FLOW FLOW FLOW
ou1
Hno Hno Hno Hno Hno Hno Hno Hno
SP1 / FH1
600 ml/min
500 l/min
132 gal/min
100 l/min
264 gal/min
20 l/min
528 gal/min
333 l/min
rP1 / FL1
548 ml/min
464 l/min
122 gal/min
92 l/min
244 gal/min
184 l/min
487 gal/min
307 l/min
UK
FSP1 -20°C -20°C -4 °F -20°C -4 °F -20°C -4 °F -20°C
FEP1
3000 25 66 50 1321 100 2642 1667 ml/min l/min gal/min l/min gal/min l/min gal/min l/min 80°C 80°C 176°F 80°C 176°F 80°C 176°F 80°C
FrP1 1000 Hz 1000 Hz 1000 Hz 1000 Hz 1000 Hz 1000 Hz 1000 Hz 1000 Hz
ImPS 0001 0001 00002 001 0002 001 0002 001
ImPR
Yes Yes Yes Yes Yes Yes Yes Yes
FOU1 OFF OFF OFF OFF OFF OFF OFF OFF
SEL2 FLOW FLOW FLOW FLOW FLOW FLOW FLOW FLOW
ou2
I
I
I
I
I
I
I
I
ASP2
0
0
0
0
0
0
0
0
AEP2
3000 25 66 50 1321 100 2642 250 ml/min l/min gal/min l/min gal/min l/min gal/min l/min
SP2 / FH2
1200 ml/min
10 l/min
264 gal/min
20 l/min
528 gal/min
40 l/min
1057 gal/min
667 l/min
rP2 / FL2
1148 ml/min
963 l/min
254 gal/min
192 l/min
507 gal/min
384 l/min
1015 gal/min
64 l/min
DIn2 +EDG +EDG +EDG +EDG +EDG +EDG +EDG +EDG
FOU2 OFF OFF OFF OFF OFF OFF OFF OFF
uni.F ml/min l/min gal/min l/min gal/min l/min gal/min l/min
uni.T
°C
°C
°F
°C
°F
°C
°C
°C
dAP
06 06 06 06 06 06 06 06
dST
00 00 00 00 00 00 00 00
P-n
PnP PnP PnP PnP PnP PnP PnP PnP
59
Parameter SM4020 SM6020 SM6621 SM7020 SM7621 SM8020 SM8621 SM8030
SM4120 SM6120
SM7120
SM8120
SM8130
SM6420
SM7420
SM8420
LFC
5 005 001 001 003 02 005 02 ml l/min gal/min l/min gal/min l/min gal/min l/min
Fdir
rTo1
OFF OFF OFF OFF OFF OFF OFF OFF
rTo2
OFF OFF OFF OFF OFF OFF OFF OFF
FPro1
0+
0+
0+
0+
0+
0+
0+
0+
FPro2
0+
0+
0+
0+
0+
0+
0+
0+
LanG
EN EN EN EN EN EN EN EN
diS.L
L3
L3
L3
L3
L3
L3
L3
L3
diS.U
d3
d3
d3
d3
d3
d3
d3
d3
diS.B 75% 75% 75% 75% 75% 75% 75% 75%
col.F bk/wh bk/wh bk/wh bk/wh bk/wh bk/wh bk/wh bk/wh
col.T bk/wh bk/wh bk/wh bk/wh bk/wh bk/wh bk/wh bk/wh
col.V bk/wh bk/wh bk/wh bk/wh bk/wh bk/wh bk/wh bk/wh
60
References
- Manual-Hub.com - Free PDF manuals!
- ifm - automation made in Germany
- Manual-Hub.com – Free PDF manuals!
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>