Falcon E3478 Dominator Plus Electric Steaming Oven Instructions
- June 16, 2024
- Falcon
Table of Contents
Falcon E3478 Dominator Plus Electric Steaming Oven Instructions
IMPORTANT
The installer must ensure that the installation of the appliance is in
conformity with these instructions and National Regulations in force at the
time of installation. Particular attention MUST be paid to:
BS7671 IEE Wiring Regulations Electricity at Work Regulations Health and
Safety at Work Act Fire Precautions Act National Water Regulations EN1717
This appliance has been UKCA/CE marked based on compliance with the relevant
Electrical and Electromagnetic Compatibility (EMC) Regulations/Directives for
the voltages stated on the data plate.
WARNING: THIS APPLIANCE MUST BE EARTHED.
On completion of the installation, these instructions should be left with the
Engineer-in-Charge for reference during servicing. Further to this, The Users
Instructions should be handed over to the User, having had a demonstration of
the operation and cleaning of the appliance.
IT IS MOST IMPORTANT THAT THESE INSTRUCTIONS BE CONSULTED BEFORE INSTALLING AND COMMISSIONING THIS APPLIANCE. FAILURE TO COMPLY WITH THE SPECIFIED PROCEDURES MAY RESULT IN DAMAGE OR THE NEED FOR A SERVICE CALL.
PREVENTATIVE MAINTENANCE CONTRACT
To obtain maximum performance from this unit regular servicing of the
appliance should be undertaken to ensure correct operation, it is functioning
as intended, and safe to use. We recommend servicing in accordance with SFG20
Maintenance Schedules and as a minimum, after 2,500 hours of use, or annually,
whichever comes first and that a maintenance contract be arranged with an
appointed service contact. Visits may then be made at agreed intervals to
carry out adjustments and repairs.
WEEE Directive Registration No. WEE/DC0059TT/PRO At end of unit life, dispose of appliance and any replacement parts in a safe manner, via a licenced waste handler. Units are designed to be dismantled easily and recycling of all material is encouraged whenever practicable.
Falcon Foodservice Equipment
Wallace View, Hillfoots Road, Stirling, FK9 5PY, Scotland Phone: 01786 455 200
IMPORTANT INFORMATION
ELECTRICAL SAFETY AND ADVICE REGARDING SUPPLEMENTARY ELECTRICAL PROTECTION
Commercial kitchens and foodservice areas are environments where electrical
appliances may be located close to liquids or operate in and around damp
conditions or where restricted movement for installation and service is
evident.
The installation and periodic inspection of the appliance should only be
undertaken by a qualified, skilled and competent electrician; and connected to
the correct power supply suitable for the load as stipulated by the appliance
data label.
The electrical installation and connections should meet the necessary
requirements to the local electrical wiring regulations and any electrical
safety guidelines.
We recommend:-
- Supplementary electrical protection with the use of a type A residual current device (RCD)
- Fixed wiring appliances incorporate a locally situated switch disconnector to connect to, which is easily accessible for switching off and safe isolation purposes. The switch disconnector must meet the specification requirements of IEC 60947.
Your attention is drawn to:BS 7671:2018Guidance Note 8 – 8.13 : Other
locations of increased risk
It is recognized that there may be locations of increased risk of electric
shock other than those specifically addressed in Part 7 of BS 7671. Examples
of such locations could include laundries where there are washing and drying
machines in close proximity and water is present, and commercial kitchens with
stainless steel units, where once again, water is present.
Where because of the perception of additional risks being likely, the
installation designer decides that an installation or location warrants
further protective measures, the options available include:
- Automatic Disconnection of Supply (ADS) by means of a residual current device having a residual operating current not exceeding 30mA;
- Supplementary protective equipotential bonding; and
- Reduction of maximum fault clearance time.
The provision of RCDs and supplementary bonding must be specified by the host organization’s appointed installation designer or electrical contractor and installed by a suitably qualified and competent electrician so as to comply with Regulations 419.2 and
SECTION 1 – INSTALLATION
⚠ UNLESS OTHERWISE STATED, PARTS WHICH HAVE BEEN PROTECTED BY THE MANUFACTURER ARE NOT TO BE ADJUSTED BY THE INSTALLER.
1.1 MODEL NUMBERS, NETT WEIGHTs and DIMENSIONS
1.2 SITING
The unit MUST be installed upon a FIRM, LEVEL floor in a well- lit position.
It requires to be secured to this surface.
The oven can be positioned to within 150mm of a combustible wall.
⚠ WARNING: ALWAYS TAKE CARE WHEN MOVING THE APPLIANCE AS IT IS HEAVY. ALWAYS
USE SAFETY GLOVES AND ENCLOSED FOOTWEAR. DO NOT PULL THE APPLIANCE BY THE
HANDLE.
1.3 ELECTRICITY SUPPLY
The unit is designed to be connected to an AC supply only, i.e., single phase
or 3 phase 4 wire. The cable entry is located at rear of appliance (25mm
conduit).
The supply must be installed using a suitable isolating switch with a minimum
contact separation of 3mm in all poles. All wiring must be executed in
accordance with regulations listed on the cover of this document.
Ensure that the mains power cable is routed free from the appliance to avoid
damage.
We recommend supplementary electrical protection with the use of a residual
current device (RCD). Periodical testing, repair and fixing wiring connection
should only be undertaken by a skilled and competent electrician.
This appliance is also provided with a terminal for connection of an external equipotential conductor. This terminal is in effective electrical contact with all fixed exposed metal parts of the appliance, and shall allow the connection of a conductor having a normal crosssectional area of up to 10mm². It is located on the rear panel and is identified by the following symbol and must only be used for bonding purposes.
1.4 ELECTRICAL RATING
The rating is as stated below.
1.5 WATER SUPPLY (IRN R001)
⚠ WARNING: THIS UNIT SHALL NOT BE USED EMPTY.
The appliance is intended for connection to a main water supply only. The unit
must be connected in accordance with R160 and that an Approved
double check
valve or some other no less effective device providing backflow prevention
protection to at least fluid category three shall be fitted at the point of
connection(s) between the water supply and the fitting or appliance. Supply
pressure must be within the range of 0.5 to 5 bar. A stop cock must be fitted
in an easily accessible position on the supply to enable shut off for cleaning
and maintenance. The front trough drain should be sited over a floor grating
where possible.
SECTION 2 ASSEMBLY and COMMISSIONING
2.1 ASSEMBLY
-
Position the unit and level by adjusting the screwed feet. Secure to the floor using the fixing points provided.
(Figure 1) 2 -
Check that all packing is removed from the oven compartment and from the water cistern area at the rear.
-
Ensure also that the steam vent is clear.
-
Check shelf runners hang properly upon brackets.
2.2 CONNECTION TO ELECTRICAL SUPPLY
Remove the control panel (2 fixings at the bottom, 1 at the top) and connect to the electricity supply. All ovens are supplied for use on either a 3-phase/4 wire supply or a single-phase supply. Terminals are arranged for direct connection to 3 phase/4 wire supplies. if a single-phase supply is to be used, it will be necessary to link terminals L1, L2, and L3 to form line terminal. Check supply voltage corresponds to the data plate details.
⚠ WARNING: THIS APPLIANCE MUST BE EARTHED USING THE TERMINAL PROVIDED.
2.3 CONNECTION TO WATER SUPPLY
- Connect water supply. The cistern ball valve has been set to achieve the correct level, but this should be checked. The level is indicated by a mark on the inner wall of t h e cistern that corresponds to a 60mm water depth in the well. An additional level mark is located on the oven chamber wall.
- Test the unit by switching to Position 3, i.e. highest setting. Steam should escape freely from the vent pipe within 15 minutes and t h e control knob can be turned down to a lower setting.
- Check door seal is in good condition. When the oven is operating on full steam, there should be no escape of steam around the door periphery. Condensed water should not drip into the trough when the door is securely closed. Adjust the seal and/or door hinges as necessary.
2.4 INSTRUCTIONS TO THE USER
Wherever possible, the user should be instructed in the general operation of the unit and made familiar with the location of isolating switch and main water cock.
SECTION 3 – MAINTENANCE
SERVICE INFORMATION
This unit carries an extensive mainland UK warranty. The warranty is in
addition to and does not change your statutory or legal rights. The warranty
policy can be found on our website which details the conditions of the
warranty and the exclusions. https://www.falconfoodservice.com/info-
centre/policy
https://www.falconfoodservice.com/info-centre/policy
Service calls to equipment under warranty will be carried out in accordance with the conditions of the sale. Warranty calls can be made between 8:30 am and 5:00 pm on weekdays only. To ensure your warranty enquiry is handled as efficiently as possible, ensure you have the following appliance information prior to calling us:
- Model number found on the data plate
- Serial number found on the data plate
- Brief description of the issue
To contact Falcon for a warranty issue dial (UK only) 01786 455 200 and select Warranty Issues from the menu.
3.1 ADJUSTING DOOR FIT
Check that the door seal is in good condition. When the oven is operating on full steam there should be no escape of steam around the door periphery. Condensed water should not drip into the trough when the door is securely closed. If the seal is damaged, remove the seal by pulling away from the door. Replace the seal by firmly pushing the new seal into the door frame until fully home. To adjust the door, catch: Undo the lock nut on the door catch Adjust the catch Tighten lock nut
3.2 ELECTRICAL MAINTENANCE
⚠ WARNING: BEFORE ATTEMPTING ANY ELECTRICAL MAINTENANCE, SWITCH OFF THE MAIN SWITCH AND TAKE STEPS TO ENSURE THAT IT IS NOT INADVERTENTLY SWITCHED ON.
MAINTENANCE CHECK
Regular servicing of the appliance should be undertaken to ensure correct
operation, it is functioning as intended, and safe to use. We recommend
servicing after 2,500 hours of use, or annually, whichever comes first. Any
maintenance schedule should be carried out in accordance with SFG20
Maintenance Schedule. Should any issues with the integrity of the components
be identified these should be replaced. If the appliance is not considered
safe the unit should be removed from service and the responsible person
advised why the unit is not safe to use and what remedial action is needed.
Contents of the maintenance schedule should be agreed with the maintenance
provider.
3.2.1 Elements – To Replace
- Turn off the mains water cock and drain the oven well.
- Remove the element cover and connections to the faulty element.
- Remove elements using a suitable spanner.
- When fitting the replacement, place the rubber washer on the inside of the well and fibre washer on the outside. Tighten the fixing nut firmly and replace the electrical connections.
- Fill the tank with water and check for leaks before replacing the cover and switching it on.
3.3 CONTROL SWITCH and NEON INDICATORS
Access to control gear components is gained upon removing the control panel. Undo fixings at top of the panel.
3.3.1 Control Switch
To remove, pull off the control knob and release the fixing nuts.
3.3.2 Neon Indicator
To remove, remove terminals and undo the nut. Replace in reverse order.
3.3.3 Ball valve
Turn off the water supply. Drain steamer at draw-off tap. Remove the lid from the cistern. Remove the split pin from the valve body. Raise the arm slightly and withdraw from the valve socket. Unscrew the cap at the valve end and pull out the valve plug. Clean all parts with a soft rag (abrasives must not be used). Replace in reverse order. Test soundness. Flush out pipes to the reservoir. Allow the reservoir to refill.
3.4 DOUBLE CHECK VALVE
This component is maintenance free.
This water supply safety feature must always be fitted to prevent backflow.
Ensure the flow direction arrow points toward the ball valve inlet.
SECTION 4 – SPARE PARTS
When ordering spares, always quote unit type and serial number. This information will be found on the data plate.
E3478 Wiring Diagram
Documents / Resources
|
Falcon E3478 Dominator Plus Electric Steaming
Oven
[pdf] Instructions
E3478 Dominator Plus Electric Steaming Oven, E3478, Dominator Plus Electric
Steaming Oven, Plus Electric Steaming Oven, Electric Steaming Oven, Steaming
Oven, Oven
---|---
|
Falcon E3478 Dominator Plus Electric Steaming
Oven
[pdf] Instructions
E3478 Dominator Plus Electric Steaming Oven, E3478, Dominator Plus Electric
Steaming Oven, Plus Electric Steaming Oven, Electric Steaming Oven, Steaming
Oven, Oven
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>