GROWATT 600TL-X Photovoltaic Approval VDE Wi-fi Inverter Instruction Manual

June 16, 2024
Growatt

GROWATT 600TL-X Photovoltaic Approval VDE Wi-fi Inverter

Installation & Operation Manual

Download Manual
Growatt New Energy
Shenzhen Growatt New Energy Co., Ltd
4-13/F,Building A,Sino-German(Europe) Industrial Park,
Hangcheng Ave,Bao’an District, Shenzhen, China
+86 0755 2747 1942
www.ginverter.com
service@ginverter.com
GR-UM-196-A-03

1. Notes on this manual

1.1 Validity
This manual describes the assembly, installation, commissioning and maintenance of the following Growatt Inverter model:
MIC 600TL-X
MIC 750TL-X
MIC 1000TL-X
MIC 1500TL-X
MIC 2000TL-X
MIC 2500TL-X
MIC 3000TL-X
MIC 3300TL-X

This manual does not cover any details concerning equipment connected to the MIC TL-X (e.g. PV modules). Information concerning the connected equipment is available from the manufacturer of the equipment.

1.2 Target Group
This manual is for qualified personnel. Qualified personnel have received training and have demonstrated skills and knowledge in the construction and operation of this device. Qualified Personnel are trained to deal with the dangers and hazards involved in installing electric devices.

1.3 Additional information
Find further information on special topics in the download area at www.ginverter.com The manual and other documents must be stored in a convenient place and be available at all times. We assume no liability for any damage caused by failure to observe these instructions. For possible changes in this manual, GROWATT NEW ENERGY CO.,LTD accepts no responsibilities to inform the users.

1.4 Symbols in this document
1.4.1 Warnings in this document
A warning describes a hazard to equipment or personnel. It calls attention to a procedure or practice, which, if not correctly performed or adhered to, could result in damage to or destruction of part or all of the Growatt equipment and/or other equipment connected to the Growatt equipment or personal injury.

Symbol Description
DANGER result in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided,could result

in death or serious injury.
| CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
| NOTICE is used to address practices not related to personal injury.
| Information that you must read and know to ensure optimal operation of the system.

1.4.2 Markings on this product

Symbol Explanation
Electrical voltage!
Risk of fire or explosion!
Risk of burns
Operation after 5 minutes
Point of connection for grounding protection
Direct Current (DC)
Alternating Current (AC)
Read the manual
--- ---
CE mark.

The inverter complies with the requirements of the applicable CE guidelines.
---|---
| The inverter must not be disposed of with the household waste.
---|---

1.5 Glossary

AC
Abbreviation for “Alternating Current”

DC
Abbreviation for “Direct Current”

Energy
Energy is measured in Wh (watt hours), kWh (kilowatt hours) or MWh (megawatt hours). The energy is the power calculated over time. For example, your inverter operates at a constant power of 4600 W for half an hour and then at a constant power of 2300 W for another half an hour, it has fed 3450Wh of energy into the power distribution grid within that hour.

Power
Power is measured in W (watts), kW (kilowatts) or MW (megawatts). Power is an instantaneous value. It displays the power your inverter is currently feeding into the power distribution grid.

Power rate
Power rate is the radio of current power feeding into the power distribution grid and the maximum power of the inverter that can feed into the power distribution grid.

Power factor
Power factor is the ratio of true power or watts to apparent power or volt amps. They are identical only when current and voltage are in phase than the power factor is 1.0. The power in an ac circuit is very seldom equal to the direct product of the volts and amperes. In order to find the power of a single phase ac circuit the product of volts and amperes must be multiplied by the power factor.

PV
Abbreviation for photovoltaic.

Wireless communication
The external wireless communication technology is a radio technology that allows the inverter and other communication products to communicate with each other. The external wireless communication does not require line of sight between the devices and it is selective purchasing.

2. Safety

2.1 Intended Use
The unit converts the DC current generated by the photovoltaic (PV) modules to gridcompliant alternating current and performs single-phase feed-in into the electricity grid. MIC 750TL-X,MIC 1000TL-X,MIC 1500TL-X,MIC 2000TL-X,MIC 2500TL-X,MIC 3000TL-X, MIC 3300TL-X inverters are built according to all required safety rules. Nevertheless, improper use may cause lethal hazards for the operator or third parties, or may result indamage to the units and other property.

Principle of a PV plant with this MIC TL-X single-phase inverter

Principle of a PV

Position Description
A PV modules
B DC load circuit breaker
C Inverter
D AC load circuit breaker
E Energy meter
F Utility grid

The inverter may only be operated with a permanent connection to the public power grid. The inverter is not intended for mobile use. Any other or additional use is not considered the intended use. The manufacturer/supplier is not liable for damage caused by such unintended use. Damage caused by such unintended use is at the sole risk of the operator.

PV modules Capacitive Discharge Currents
PV modules with large capacities relative to earth, such as thin-film PV modules with cells on a metallic substrate, may only be used if their coupling capacity does not exceed 1uF. During feed-in operation, a leakage current flows from the cells to earth, the size of which depends on the manner in which the PV modules are installed (e.g. foil on metal roof) and on the weather (rain, snow). This “normal” leakage current may not exceed50mA due to the fact that the inverter would otherwise automatically disconnect from the electricity grid as a protective measure.

2.2 Qualification of skilled person
This grid-tied inverter system operates only when properly connected to the AC distribution network. Before connecting the MIC TL-X to the power distribution grid, contact the local power distribution grid company. This connection must be made only by qualified technical personnel to connect, and only after receiving appropriate approvals, as required by the local authority having jurisdiction.

2.3 Safety instruction
The MIC TL-X Inverters is designed and tested according to international safety requirements (IEC62109-1,CE,VDE0126-1-1, AS4777,etc); however, certain safety precautions must be observed when installing and operating this inverter. Read and follow all instructions, cautions and warnings in this installation manual. If questions arise, please contact Growatt’s technical services at +86 (0)755 2747 1942.

2.4 Assembly Warnings

| ►Prior to installation, inspect the unit to ensure absence of any transport or handling damage, which could affect insulation integrity or safety clearances; failure to do so could result in safety hazards.
►Assemble the inverter per the instructions in this manual. Use care when choosing installation location and adhere to specified cooling requirements.
►Unauthorized removal of necessary protections, improper use, incorrect installation and operation may lead to serious safety and shock hazards and/or equipment damage.
►In order to minimize the potential of a shock hazard due to hazardous voltages, cover the entire solar array with dark material prior to connecting the array to any equipment.
---|---
| ►Grounding  the  PV  modules: The  MIC  TL-X  is  a  transformerless inverter. That is why it has no galvanic separation. Do not ground the  DC circuits  of  the  PV  modules  connected  to  the  MIC  TL-X. Only   ground the   mounting   frame   of   the   PV   modules.If   you
connect   grounded   PV   modules   to   the   MIC   TL-X,   the   error message “PV ISO Low”.
►Comply    with    the    local    requirements    for    grounding    the PV
modules    and    the    PV    generator.    GROWATT    recommends connecting the generator frame and other electrically conductive surfaces  in  a  manner which  ensures  continuous  conduction  with ground  in  order  to  have optimal  protection  of  the  system  and personnel.
---|---

2.5 Electrical Connection Warnings

| ►The components in the inverter are live. Touching live components can result in serious injury or death.
•Do not open the inverter except the wire box by qualified persons.
•Electrical installation, repairs and conversions may only be carried out by electrically qualified persons.
•Do not touch damaged inverters.
►Danger to life due to high voltages in the inverter
•There is residual voltage in the inverter. The inverter takes 20 minutes discharge.
►Persons with limited physical or mental abilities may only work with the Growatt inverter following proper instruction and under constant supervision. Children are forbidden to play with the Growatt inverter. Must keep the Growatt inverter away from children.
---|---
| ►Make all electrical connections (e.g. conductor termination, fuses, PE connection, etc.) in accordance with prevailing regulations. When working with the inverter powered on, adhere to all prevailing safety regulations to minimize risk of accidents.
►Systems  with  inverters  typically  require  additional  control  (e.g.,
switches,  disconnects)  or  protective  devices  (e.g.,  fusing  circuit breakers) depending upon the prevailing safety rules.
---|---

2.6 Operation Warnings

| ►Ensure all connectors are sealed and secure during operation.
►Although  designed  to  meet  all  safety  requirements,  some  parts and surfaces  of  Inverter  are  still  hot  during  operation.  To  reduce the risk of injury, do not touch the heat sink at the back of the PV- Inverter or nearby surfaces while Inverter is operating.
►Incorrect  sizing  of  the  PV  plant  may  result  in  voltages  being present which could destroy the inverter. The inverter display will read the error message “PV voltage High!”
►Turn  the  rotary  switch  of  the  DC  Disconnect  to  the  Off  position immediately.
►Contact installer.
•Turn  the  rotary  switch  of  the  DC  Disconnect  to  the  Off  position immediately.
•Contact installer.
---|---
| ►All operations regarding transport, installation and start-up, including maintenance must be operated by qualified, trained personnel and in compliance with all prevailing codes and regulations.
►Anytime the inverter has been disconnected from the power network, use extreme caution as some components can retain charge sufficient to create a shock hazard; to minimize occurrence of such conditions, comply with all corresponding safety symbols and markings present on the unit and in this manual.
►In special cases, there may still be interference for the specified application area despite maintaining standardized emission limit values (e.g. when sensitive equipment is located at the setup location or when the setup location is near radio or television receivers).In this case, the operator is obliged to take proper action to rectify the situation.
►Do  not  stay  closer  than  20  cm  to  the  inverter  for  any  length  of time.
---|---

3. Product description

3.1 MIC TL-X Overview

MIC TL-X Overview

Position Description
A COVER
B DC SWITCH
C LED
D OLED
E TOUCH BUTTON
F PV INPUT +
G PV INPUT –
H DRM PORT
I AC OUTPUT
J VENTILATION VALVE
K COM PORT
L USB PORT

Symbol on the inverter

Symbol Description Explanation
Touch symbol Touch button.We can switch the OLED display and set parameter

by touching.
| Inverter status symbol| Indicates inverter operation status: Red:Fault.
Green:Nomal.
Red leaf flash:Warning or DSP Programming. Green leaf flash:M3 Programming.

3.2 Type label

The type labels provide a unique identification of the inverter (The type of product, Device-specific characteristics, Certificates and approvals). The type labels are on the left-hand side of the enclosure.

Type label

More detail about the type label as the chart below:

Model Name MIC 600 TL-X MIC 750 TL-X MIC 1000 TL-X MIC1500 TL-X
Max. input voltage 500V
Max. input current 13A
Start voltage 50V
MPP voltage range 50V~500V
AC nominal voltage 230V
AC grid frequency 50/60 Hz
Max. apparent power 600VA 750VA 1000VA 1500VA
Max. output current 2.9A 3.6A 4.8A 7.1A
--- --- --- --- ---
Power factor 0.8leading…0.8lagging
--- ---
Environmental Protection Rating IP 65
--- ---
Operation Ambient temperature -25…+60℃  (-13…+ 140°F)

with derating above  45°C( 113°F)
---|---
Model Name| MIC 2000
TL-X| MIC 2500
TL-X| MIC 3000
TL-X| MIC3300
TL-X
---|---|---|---|---
Max. input voltage| 550V
Max. input current| 13A
Start voltage| 80V
MPP voltage range| 65V~550V
AC nominal voltage| 230V
AC grid frequency| 50/60 Hz
---|---
Max. apparent power| 2000VA| 2500VA| 3000VA| 3300VA
---|---|---|---|---
Max. output current| 9.5A| 11.9A| 14.3A| 14.3A
Power factor| 0.8leading…0.8lagging
---|---
Environmental Protection Rating| IP 65
Operation Ambient temperature| -25…+60℃  (-13…+ 140°F)
with derating above  45°C( 113°F)

3.3 Size and weight

Size and weight

Model Height (H) Width (W) Depth (D) Weight
MIC 600-2000 TL-X 282mm 11.1inch 274mm 10.78inch 138mm 5.4inch 6.0kg
MIC 2500-3300 TL-X 282mm 11.1inch 274mm 10.78inch 138mm 5.4inch 6.2kg

3.4 Storage of Inverter

If you want to storage the inverter in your warehouse, you should choose an appropriate location to store the inverter.

►The unit must be stored in original package and desiccant must be left in the package.
►The storage temperature should be always between -25℃and +60℃. And the storage relative humidity can achieve to 100%.
►If there are a batch of inverters need to be stored, the maximum layers for original carton is ten.
►After long term storage, local installer or service department of GROWATT should perform a comprehensive test before installation.

3.5 The advantage of the unit

►Maximum efficiency of 97.6%
►Wide input voltage range from 65–550Vdc
►Reactive power regulate
►Integrated DC switch
►DSP controller
►Touch control
►Multi active power control mode
►Easy installation

4. Unpacking and inspection

The inverter is thoroughly tested and inspected strictly before delivery. Our inverters leave our factory in proper electrical and mechanical condition. Special packaging ensures safe and careful transportation. However, transport damage may still occur. The shipping company is responsible in such cases. Thoroughly inspect the inverter upon delivery. Immediately notify the responsible shipping company if you discover any damage to the packaging which indicates that the inverter may have been damaged or if you discover any visible damage to the inverter. We will be glad to assist you, if required. When transporting the inverter, the original or equivalent packaging should be used, and the maximum layers for original carton is four, as this ensures safe transport.

After opening the package, please check the contents of the box. It should contain the following, Please check all of the accessories carefully in the carton. If anything missing, contact your dealer at once.

Unpacking

Object Description Quantity
A Inverter 1
B Mounting bracket 1
C Quick Guide 1
D Monitor(Optional) 1
E Signal connector 1
F DRM PORT(Australia or EU) 1
G Self-tapping screws 3
H Safety-lock screws 2
I Plastic expansion pipe 3
J PV+/PV- terminal 1/1
K PV+/PV- metal terminal 1/1
L AC connector 1
M Uninstall signal and AC connector tool 1
N Uninstall PV tool(except Australia) 1

5. Installation

5.1 Safety instructions

| Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
Do  not  install  the  inverter  on  easily  flammable  materials  and  where flammable materials are stored.
---|---
| Risk of burns due to hot enclosure parts Mount   the   inverter   in   such a   way   that   it   cannot   be   touched inadvertently.
| Possible damage to health as a result of the effects of radiation!
►In special cases, there may still be interference for the specified application area despite maintaining standardized emission limit values (e.g. when sensitive equipment is located at the setup location or when the setup location is near radio or television receivers).In this case, the operator is obliged to take proper action to rectify the situation.
►Never install the inverter near the sensitive equipment( e.g. Radios, telephone, television, etc)
►Do not stay closer than 20 cm to the inverter for any length of time unless it is absolutely necessary.
►Growatt assumes no responsibility for compliance to EMC regulations for the complete system

►All electrical installations shall be done in accordance with the local and national electrical codes. Do not remove the casing. Inverter contains no user serviceable parts. Refer servicing to qualified service personnel. all wiring and electrical installation should be conducted by a qualified service personnel .
►Carefully remove the unit from its packaging and inspect for external damage. If you find any imperfections, please contact your local dealer.
►Be sure that the inverters connect to the ground in order to protect property and personal safety.
►The inverter must only be operated with PV generator. Do not connect any other source of energy to it.
►Both AC and DC voltage sources are terminated inside the PV Inverter. Please disconnect these circuits before servicing.
►This unit is designed to feed power to the public power grid (utility) only. Do not connect this unit to an AC source or generator. Connecting Inverter to external devices could result in serious damage to your equipment.

►When a photovoltaic panel is exposed to light, it generates a DC voltage. When connected to this equipment, a photovoltaic panel will charge the DC link capacitors.
►Energy stored in this equipment’s DC link capacitors presents a risk of electric shock.
Even after the unit is disconnected from the grid and photovoltaic panels, high voltages may still exist inside the PV-Inverter. Do not remove the casing until at least 5 minutes after disconnecting all power sources.
►Although designed to meet all safety requirements, some parts and surfaces of Inverter are still hot during operation. To reduce the risk of injury, do not touch the heat sink at the back of the PV-Inverter or nearby surfaces while Inverter is operating.

5.2 Selecting the installation location

►This is guidance for installer to choose a suitable installation location, to avoid potential damages to device and operators.
►The installation location must be suitable for the inverter’s weight and dimensions for a long period time.
►Select the installation location so that the status display can be easily viewed.
►Do not install the inverter on structures constructed of inflammable or thermolabile materials.
►Never install the inverter in environment of little or no air flow, nor dust environment. That may derate the efficiency of the cooling fan of the inverter.
►The Ingress Protection rate is IP65 which means the inverter can be installed outdoors and indoors.
►The humidity of the installation location should be 0~100% without condensation.
►The installation location must be freely and safely to get at all times.
►Vertically installation and make sure the connection of inverter must be downwards. Never install horizontal and avoids forward and sideways tilt.

location

►Be sure that the inverter is out of the children’s reach.
►Don’t put any things on the inverter. Do not cover the inverter.
►Do not install the inverter near television antenna or any other antennas and antenna cables.
►Inverter requires adequate cooling space. Providing better ventilation for the inverter to ensure the heat escape adequately. The ambient temperature should be below 40°C to ensure optimum operation.
►Do not expose the inverter to direct sunlight, as this can cause excessive heating and thus power reduction.
►Observe the Min. clearances to walls, other inverters, or objects as shown below:

Dimensions

►There must be sufficient clearance between the individual inverters to ensure that the cooling air of the adjacent inverter is not taken in.
►If necessary, increase the clearance spaces and make sure there is enough fresh air supply to ensure sufficient cooling of the inverters.

The inverter can’t install to solarization,drench,firn location. We suggest that the inverters should be installed at the location with some cover or protection.

Solarization

►Please make sure the inverter is installed at the right place.The inverter can’t install close to trunk.

5.3 Mounting the Inverter

5.3.1 Mounting the Inverter with bracket

In order to avoid electrical shock or other injury, inspect existing electronic or plumbing installations before drilling holes.

185

Fix the mounting bracket as the figure shows. Do not make the screws to be flush to the wall. Instead, leave 2 to 4mm exposed.

5.3.2 Fixed the inverter on the wall

Falling equipment can cause serious or even fatal injury, never mount the inverter on the bracket unless you are sure that the mounting frame is really firmly mounted on the wall after carefully checking.

►Rise up the inverter a little higher than the bracket. Considered the weight of them.During the process please maintain the balance of the inverter.
Hang the inverter on the bracket through the match hooks on bracket.

►After confirming the inverter is fixed reliably, fasten one M4 safety-lock screws on the right or left side firmly to prevent the inverter from being lifted off the bracket.

bracket

6. Electrical connection

Decisive Voltage Class (DVC) indicated for ports

Port Name Class
AC C
DC C
DRM A
RS485&USB A

6.1 Safety

Danger to life due to lethal voltages!
High voltages which may cause electric shocks are present in the conductive parts of the inverter. Prior to performing any work on the inverter, disconnect the inverter on the AC and DC sides

Danger of damage to electronic components due to electrostatic discharge.
Take appropriate ESD precautions when replacing and installing the inverter.

6.2 Wiring AC Output

You must install a separate single-phase circuit-breaker or other load disconnection unit for each inverter in order to ensure that the inverter can be safely disconnected under load.

NOTE :
The inverter has the function of detecting residual current and protecting the inverter against residual current. If your inverter has to equip a AC breaker which has the function of detecting residual current ,you must choose a AC breaker with the rating residual current more than 300mA.

You must install a separate single-phase circuit-breaker or other load disconnection unit for each inverter in order to ensure that the inverter can be safely disconnected under load.
We suggest you choice the AC breaker rating current in this table:

MIC 600TL-X 5A/230V
MIC 750TL-X 5A/230V
MIC 1000TL-X 10A/230V
MIC 1500TL-X 10A/230V
MIC 2000TL-X 16A/230V
MIC 2500TL-X 16A/230V
MIC 3000TL-X 16A/230V
MIC 3300TL-X 16A/230V

The AC wiring step:
1. Uninstall the parts of the AC connection plug from the accessory bag.

2.Insert the stripped and bared cable through pressure screw, seal ring, threaded sleeve in sequence, insert cables into connection terminal according to polarities indicates on it and tighten the screws firmly. Please try to pull out the wire to make sure the it’s well connected.

Insert the strippe

3. Push the threaded sleeve into the socket, Tighten up the cap on the terminal.

4.Finally, Push or screw the threaded sleeve to connection terminal until both are locked tightly on the inverter.

5. To remove the AC connector, press the bayonet out of the slot with a small screwdriver and pull it out,or unscrew the threaded sleeve,then pull it out.

Wire suggestion length

Conductor cross section Max. cable length
MIC 600TL-X MIC 750TL-X
2 mm²  14AWG 92m
3.3 mm²  12AWG 150m
Conductor cross section Max. cable length
MIC 2000TL-X MIC 2500TL-X
3.3 mm²  12AWG 45m
5.2 mm²  10AWG 73m

6.3 Connecting the second protective conductor
In some installation countries, a second protective conductor is required to prevent a touch current in the event of a malfunction in the original protective conductor.For installation countries falling within the scope of validity of the IEC standard 62109, you must install the protective conductor on the AC terminal with a conductor cross-section of at least 10 mm²Cu.Or Install a second protective conductor on the earth terminal with the same cross-section as the original protective conductor on the AC terminal. This prevents touch current if the original protective conductor fails.

6.4 Connecting the PV Array (DC input)
6.4.1 Conditions for DC Connection

The solar modules connected to the inverter must conform to the Class A requirements of the IEC 61730 standard.
Please use the same brand male and female PV connectors.

The MIC TL-X single-phase inverter has only one independent PV input : Notice that the connectors are in paired (male and female connectors). The connectors for PV arrays and inverters are VP-D4 connectors;

If the inverter is not equipped with a DC switch but this is mandatory in the country of installation, install an external DC switch.
The following limit values at the DC input of the inverter must not be exceeded:

Types PV max current Max voltage
MIC 600-2000TL-X 13A 500V
MIC 2500-3300TL-X 13A 550V

6.4.2 Connecting the PV Array (DC input)

| Danger to life due to lethal voltages!
PV  array  supplies  d.c  voltage  to  inverter  when  exposed  to light,before connecting    the    PV    array,    conver    some    light screens    above    PV arrays,ensure  that  the  DC  switch  and  AC  breaker are  disconnect  from the  inverter.  NEVER  connect  or  disconnect  the  DC connectors  under load.
Make sure the maximum open circuit voltage(Voc) of  each  PV  string is  less than the maximum  input  voltage of  the  inverter.
Check the design of the PV plant. The Max. open circuit voltage, which can occur  at  solar  panels  temperature  of  -10℃ ,  must  not  exceed  the Max. input voltage of the inverter.
---|---
| Improper operation during the wiring process can cause fatal injury to operator   or   unrecoverable   damage   to   the   inverter.   Only qualified personnel can perform the wiring work.
Please don’t connect PV array positive or negative pole to the ground, it could cause serious damages to the inverter.
Check the connection cables of the PV modules for correct polarity and make sure   that   the   maximum   input   voltage   of   the   inverter   is   not exceeded.
---|---

Connection of PV terminal

Connection of PV terminal

6.5 Connecting signal cable

This series inverter has one 8 Pin signal connector. Signal Cable Ports:

Connecting signal cable

Procedure

Step 1: Insert the stripped and bared cable through pressure screw, seal ring, threaded sleeve in sequence, insert cables into connection terminal according to number indicates on it and tighten the screws firmly. Please try to pull out the wire to make sure the it’s well connected.

Step 2: Push the threaded sleeve into the socket, Tighten up the cap on the terminal.

Step 3: Push the threaded sleeve to connection terminal until both are locked tightly on the inverter.

Step 3

Uninstall signal connector

Step 1: Press the fasteners and pull it out from the inverter.

Step 1

Step 2: Insert the H type tool and pull it out from the socket.

6.6 Grounding the inverter
The inverter must be connected to the AC grounding conductor of the power distribution grid via the ground terminal (PE) .

Because of the transformerless design, the DC positive pole and DC negative pole of PV arrays are not permitted to be grounded.

6.7 Active power control with smart meter , CT (Optional)or ripple control signal receiver

The position of export limitation CT or Meter must between the Inverter & Load and gird.

This series inverter has integrated export limitation functionality. To use this function, you can connect smart meter or CT, but CT is optional. The smart meter model is Eastron SDM230-Modbus. The CT Model is TOP 90-S10/SP4 (LEM).The primary aperture is 10mm,output cable length is 5m . The arrow on the CT must pointing towards the inverter.

This series inverter

Active power control with a Radio Ripple Control Receiver(RRCR).

Active power

6.8 Inverter demand response modes (DRMS)
This series inverter has the function of demand response modes, We use RJ45 terminal as inverter DRED connection.

| DRMS application description
AØpplicable to AS/NZS4777.2:2015 or Commission Regulation (EU) 2016/631.
DØRM0, DRM5, DRM6, DRM7, DRM8 are available.
---|---
| Damage to the inverter due to moisture and dust penetration MØake sure the cable gland has been tightened firmly.

If the cable gland are not mounted properly, the inverter can be destroyed due to moisture and dust penetration. All the warranty claim will be invalid.

| Excessive voltage can damage the inverter!External voltage of DRM PORT don’t over +5V.

6.8.1 RJ45 terminal pin assignment

RJ45

6.8.2 Method of asserting demand response modes

Mode Socket    Asserted by shorting pins Function
DRM 0 5 6
DRM 5 1 5
DRM 6 2 5
DRM 7 3 5

power if capabie
DRM 8| 4| 5| Increase power generation (subject to constraints from other active DRMs)

6.8.3 Using the Power Control Interface for EU

6.8.3.1 The following table describes the connector pin assignment and function:

DRM Socket Pin NO. Description Connect to RRCR
1 Relay contact 1 input K1 – Relay 1 output
2 Relay contact 2 input K2 – Relay 2 output
3 Relay contact 3 input K3 – Relay 3 output
4 Relay contact 4 input K4 – Relay 4 output
5 GND Relays common node
6 Not connected Not connected
7 Not connected Not connected
8 Not connected Not connected

6.8.3.2The inverter is preconfigured to the following RRCR power levels:

DRMs
Connector Pin1| DRMs
Connector Pin2| DRMs
Connector Pin3| DRMs
Connector Pin4| Active power| Cos(φ)
---|---|---|---|---|---
Short circuit with Pin5| | | | 0%| 1
| Short circuit with Pin5| | | 30%| 1
| | Short circuit with Pin5| | 60%| 1
| | | Short circuit with Pin5| 100%| 1

Active power control and reactive power control are enabled separately.

6.9 AFCI(Optional)

6.9.1 Arc-Fault Circuit Interrupter (AFCI)
In accordance with the National Electrical Code R, Article 690.11, the inverter has a system for the recognition of electric arc detection and interruption. An electric arc with a power of 300 W or greater must be interrupted by the AFCI within the time specified by UL 1699B. A tripped AFCI can only be reset manually. You can deactivate the automatic arc fault detection and interruption (AFCI) via a communication product in “Installer” mode if you do not require the function. The 2011 edition of the National Electrical Code R, Section 690.11 stipulates that newly installed PV systems attached to a building must be fitted with a means of detecting and disconnecting serial electric arcs (AFCI) on the PV side.

6.9.2 Danger information

Danger of fire from electric arc
Only test the AFCI for false tripping in the order described below. Do not deactivate the AFCI permanently.

If an “Error 200” message is displayed, the buzzer alarms, an electric arc occurred in the PV system. The AFCI has tripped and the inverter is in permanent shutdown.

The inverter has large electrical potential differences between its conductors. Arc flashes can occur through air when high-voltage current flows. Do not work on the product during operation.
When the inverter error 200, please follow the steps:

6.9.3 Operation step

6.9.3.1 Turn the DC & AC Disconnect to position “oFF”.

Operation step

Wait for the display to go out.

6.9.3.2 Perform troubleshooting on the PV system:

Check all PV strings for the correct open-circuit voltage.

6.9.3.3 After the fault is rectified, restart the inverter:

Turn the DC & AC Disconnect to position “ON”.

Turn the DC & AC

7. Commissioning

Do not disconnect the DC connectors under load.

Improper operation during the wiring process can cause fatal injury to operator or unrecoverable damage to the inverter. Only qualified personnel can perform the wiring work.

Damage to the inverter due to moisture and dust penetration

Make sure the cable gland has been tightened firmly.

If the cable gland are not mounted properly, the inverter can be destroyed due to moisture and dust penetration. All the warranty claim will be invalid.

Requirements:

  • The AC cable is correctly connected.
  • The DC cable is correctly connected.
  • The country is set correctly.

7.1 Start the inverter

7.1.1 Touch control

Touch Description
Single touch Switch display or Number +1
Double touch Enter or confinmation
Three touch Previous menu
Hold 5s C o n f i r m c o u n t r y s e t t i n g o r Number recover default

value

7.1.2 Country setting

Country setting
When the inverter start up,we need to select the right country,if we don’t select any country, the inverter will run under AS/NZS4777.2 as default for Australia,or run under VDE0126-1-1 for other region after 30s.

When inverter powered on, OLED will light automatically. Once the PV power is sufficient, OLED displays the following:

If we touch the touch button to scroll through the different countries the screen will constantly change.For example,if you want to choose Newzealand,touch the touch button until the OLED panel shows “Newzealand” as below:

Press the touch button for 5s the OLED shows the country , setting is completed.

7.2 General setting

7.2.1 Set inverter display language

This series inverter provides multi languages.
Single touch to switch different language.
Double touch to confirm you setting.
Set the language as described below:

7.2.2 Set inverter COM address

The default COM address is 1.We can change COM address as described below:
Single touch to switch display or make the number + 1.
Hold 5s ,the COM address become 001.
Double touch to confirm you setting.

7.2.3 Set inverter date & time

Single touch make the number 1.
Double touch to confirm you setting.
Hold 5s recover defaut value.

Single touch

7.3 Advanced setting

7.3.1 Reset Country

Single touch to switch display or make the number + 1.
Double touch to confirm you setting.
The password of advanced setting is 123.

Reset Country

7.3.2 Export limitation setting

Single touch to switch display or make the number + 1.
Double touch to confirm you setting.

setting

7.3.3 Reset factory

Perform this operation with caution because all configured parameters except the current date,time, and model parameters will be restored to their factory defaults.

Single touch to switch display or make the number + 1.
Double touch to confirm you setting.

Set parameter

7.4 Communications

7.4.1 RS485

This series inverter provides two RS485 ports. You can monitor one or more inverters by
RS485.Another RS485 port is for smart meter(Export limitation functionality.).

RS485

7.4.2 USB-A

USB-A port is mainly for connecting monitor or firmware updage
Through USB connection,we can connect external optional monitor ,for example :Shine
WIFI-X,Shine 4G-X, Shine LAN-X,ect.
And also you can quickly update the software by U disk.
We can monitor as below:
Make sure the on the front side, then insert the monitor,fasten the screw.

8. Start-up and shut down the Inverter

8.1 Start-Up the inverter

1. Connect the AC breaker of the inverter.
2.Turn on the dc switch, and the inverter will start automatically when the input voltage is higher than 70 V.

8.2 Turn-off the Inverter

Do not disconnect the DC connectors under load.

Turn-off the inverter step:
1.Disconect the line circuit breaker from single-phases grid and prevent it from being reactivated.
2.Turn off the dc switch.
3.Check the inverter operating status.
4.Waiting until LED, OLED have go out, the inverter is shut down.

9. Maintenance and Cleaning

9.1 Checking Heat Dissipation
If the inverter regularly reduces its output power due to high temperature, please improve the heat dissipation condition. Maybe you need to clean the heat sink.
9.2 Cleaning the Inverter
If the inverter is dirty, turn-off the AC breaker and DC switch ,waiting the inverter shut down ,then clean the enclosure lid, the display, and the LEDs using only a wet cloth. Do not use any cleaning agents (e.g. solvents or abrasives).
9.3 Checking the DC Disconnect
Check for externally visible damage and discoloration of the DC Disconnect and the cables at regular intervals.If there is any visible damage to the DC Disconnect, or visible discoloration or damage to the cables, contact the installer.

Once a year, turn the rotary switch of the DC Disconnect from the On position to the Off position 5 times in succession. This cleans the contacts of the rotary switch and prolongs the electrical endurance of the DC Disconnect.

10. EU Declaration of Conformity

With the scope of EU directives:

• 2014/35/EU Low Voltage Directive (LVD)
• 2014/30/EU Electromagnetic Compatibility Directive (EMC)
• 2011/65/EU RoHS Directive and its amendment (EU)2015/863

Shenzhen Growatt New Energy Technology Co. Ltd confirms that the Growatt inverters and accessories described in this document are in compliance with the above mentioned EU directives. The entire EU Declaration of Conformity can be found at www.ginverter.com.

11. Trouble shooting

Our quality control program assures that every inverter is manufactured to accurate specifications and is thoroughly tested before leaving our factory. If you have difficulty in the operation of your inverter, please read through the following information to correct the problem.

11.1 Error Messages displayed on OLED
An error message will be displayed on the OLED screen when a fault occurs. The faults consist of system fault and inverter fault.
You may be advised to contact Growatt in some situation, please provide the following information.

Information concerning the inverter:

  • Serial number
  • Model number
  • Error message on OLED
  • Short description of the problem
  • Grid voltage
  • DC input voltage
  • Can you reproduce the failure? If yes, how?
  • Has this problem occurred in the past?
  • What was the ambient condition when the problem occurred?

Information concerning the PV panels:

  • Manufacturer name and model number of the PV panel
  • Output power of the panel
  • Voc of the panel
  • Vmp of the panel
  • Imp of the panel
  • Number of panels in each string
  • If it is necessary to replace the unit, please ship it in the original box.

11.2 System fault

System fault (system faults are mainly caused by system instead of inverter, please check the items as instructed below before replacing inverter).

Error message Description Suggestion
Residual I High Error: 201 Leakage current too high 1.Restart the invert.

2.  If  error  message  still  exists, contact Growatt.
---|---|---
PV Voltage High Error: 202| The    DC    input    voltage    is exceeding the    maximum tolerable value.| 1.    Disconnect    the    DC    switch immediately.
2.  Check  the  voltage  of  each  PV string with multimerter.
3.   If   the   voltage   of   PV   string   is l o w e r    t h a n    5 5 0 V,    c o n t a c t Growatt.
---|---|---
PV Isolation Low Error: 203| Insulation problem| 1.  Check  if  panel enclosure  ground properly.
2 .    Ch e c k    i f    i n v e r t e r    gro u n d properly.
3.   Check   if   the   DC   breaker   gets wet.
4. Check the impedance of PV (+) & PV   (-)   between   ground   (must   be more  than  25  KΩ  or  500  KΩ(VDE 0126)).    If    the    error    message is d i s p l a y e d    d e s p i t e    t h e    a b o v e checking passed, contact Growatt.
AC V Outrange Error: 300| Utility  grid  voltage  is  out of permissible range.| Please switch off DC switch.
Check    AC    wiring,    especially neutral and ground wire.
Check   grid   voltage   is   complied with   local   grid   standard. Restart inverter,    if    problem    still    exist, Contact Growatt.
No AC connection Error: 302| No AC connection| Check AC wiring.
Check the status of AC breaker
PE abnormal Error: 303| Voltage  of  Neutral  and  PE above 30V.| 1.Check the voltage of Neutral and PE.
2.Check AC wiring.
3.Restart inverter, if error message still exisits,contact Manufacturer
AC F Outrange Error: 304| Utility  grid  frequency  out of permissible range.| Please switch off DC switch.
Che ck    AC    wi r i ng,    e s pe c i a l l y neutral and ground wire.
Check  grid  frequency  is  complied with   local   grid   standard.   Restart inverter,    if    problem    still    exist, Contact Growatt.
Auto Test Failed Error: 407| Auto test didn’t pass.| Restart  inverter, repeat  Auto  Test, if    problem    still    exist,    contact Growatt.
---|---|---

11.3 Inverter warning

Warning code

|

Meanings

|

Suggestion

---|---|---

Warning202

|

DC SPD function abnormal

|

Warning 203

|

PV1 or PV2 Circuit short

|

Check the PV panel polarity.

Restart the inverter. If the warning still exist, please contact Growatt customer service to replace the POWER board.

Warning204

|

Dryconnect function abnormal

|

Warning 205

|

PV1 or PV2 boost broken

|

Restart the inverter. If the warning still exist, please contact Growatt customer service to replace the power board.

Warning207

|

USB over-current

|

1: Unplug the U disk or monitor.

2: Re-access U disk or monitor after shutdown.

3.If the error message still exists, contact manufacturer.

Warning 401

|

Inverter communicates with Meter abnormal

|

1: Check if the meter is on.

2: Check the inverter and the meter connection is normal .

Warning404

|

EEPROM abnormal

|

Restart the inverter. If the warning still exist, please contact Growatt customer service to replace the M3 board.

Warning405

|

Firmware version is not consistent

|

Uptate the right version firmware

11.4 Inverter fault

Error code

|

Meanings

|

Suggestion

---|---|---

Error: 200

|

AFCI fault

|

Error: 402

|

Output High DCI

|

Restart inverter, if problem still exist, Contact Growatt.

Error: 404

|

Bus sample fault

|

Restart inverter, if problem still exist, Contact Growatt.

Error: 405

|

Relay fault

|

Restart inverter, if problem still exist, Contact Growatt.

Error: 408

|

Over Temperature

|

If the ambient temperature of inverter is lower than 60°C, restart inverter, if error message still exists, contact Growatt.

Error: 409

|

Bus over voltage

|

Restart inverter, if problem still exist, Contact Growatt.

Error: 411

|

DSP communicates with M3 abnormal

|

Restart inverter, if problem still exist, contact Growatt.

Error: 414

|

EEPROM fault.

|

Restart inverter, if problem still exist, Contact Growatt.

Error: 417

|

The data sampled by the DSP and redundant M3 is not the same.

|

Restart inverter, if problem still exist, Contact Growatt.

Error: 420

|

GFCI fault.

|

Restart inverter, if problem still exist, or contact Growatt.

Error: 425

|

AFCI self-test fault

|

Restart inverter, if problem still exist, or contact Growatt.

12. Manufacturer Warranty

Please refer to the warranty card.

13 Decommissioning

13.1 Dismantling the Inverter

1. Disconnect the inverter as described in section8.
2. Remove all connection cables from the inverter.

Danger of burn injuries due to hot enclosure parts!
Wait 20 minutes before disassembling until the housing has cooled down.

3. Screw off all projecting cable glands.
4. Lift the inverter off the bracket and unscrew the bracket screws.

13.2 Packing the Inverter
If possible, always pack the inverter in its original carton and secure it with tension belts. If it is no longer available, you can also use an equivalent carton. The box must be capable of being closed completely and made to support both the weight and the size of the inverter.
13.3 Storing the Inverter
Store the inverter in a dry place where ambient temperatures are always between -25°C and +60°C.
13.4 Disposing of the Inverter

Do not dispose of faulty inverters or accessories together with household waste. Please accordance with the disposal regulations for electronic waste which apply at the installation site at that time. Ensure that the old unit and, where applicable, any accessories are disposed of in a proper manner

14. Technical Data

14.1 Specification

Model

Specifications

|

MIC 600TL-X

|

MIC 750TL-X

|

MIC 1000TL-X

|

MIC 1500TL-X

---|---|---|---|---

Input data(DC)

Max. recommended PV power(for module STC)

|

840W

|

1050W

|

1400W

|

2100W

Max. DC voltage

|

500V

Start voltage

|

50V

Nominal voltage

|

360V

MPP voltage range

|

50V-500V

MPP voltage range at Full Power

|

55V-450V

|

65V-450V

|

85V-450V

|

130V-450V

No. of MPP trackers

|

1

No. of PV strings per MPP trackers

|

1

Max. input current per MPP trackers

|

13A

Max. short-circuit current per MPP trackers

|

16A

DC overvoltage category

|

Category II

Output data(AC)

AC nominal power

|

600W

|

750W

|

1000W

|

1500W

Max. AC apparent power

|

600VA

|

750VA

|

1000VA

|

1500VA

Nominal AC voltage/range*

|

230V/180~280V

AC grid frequency/range

|

50-60Hz/44-55Hz;54-65Hz

Max. output current

|

2.9A

|

3.6A

|

4.7A

|

7.1A

Inrush current

|

<10A

Max output fault current

|

66A

Max output overload protection

|

10A

|

10A

|

10A

|

10A

Backfeed current

|

0A

P o we r fa c t o r ( @ n o m i n a l power)

|

0.99

‌Adjustable power factor

|

0.8leading… 0.8lagging

---|---

THDi

|

<3%

AC grid connection type

|

Single phase

AC overvoltage category

|

Category III

Efficiency

Max. efficiency

|

96.5%

|

97.4%

|

97.4%

|

97.4%

Euro-eta

|

96.0%

|

96.5%

|

96.5%

|

97.0%

Protection devices

DC reverse-polarity protection

|

Integrated

DC switch

|

Integrated

DC Surge protection

|

Type III

Insulation resistance monitoring

|

Integrated

AC surge protection

|

Type III

AC short-circuit protection Integrated

Ground fault monitoring

|

Integrated

Grid monitoring

|

Integrated

Anti-islanding protection

|

Integrated

Residual-current monitoring

unit

|

Integrated

General data

Dimensions (W / H / D) in mm

|

274254138

Weight

|

6.0 kg

Operating temperature range

|

–25 °C … +60 °C

Noise emission (typical)

|

≤ 25 dB(A)

Altitude

|

4000m

Internal consumption at night

|

<0.5W

Topology

|

transformerless

Cooling

|

Natural convection

Protection degree

|

IP65

Relative humidity

|

0~100%

DC connection

|

VP-D4/MC4(Optional)

AC connection

|

AC connector

Interfaces

Display

|

OLED+LED

---|---

RS485/USB

|

Integrated

WIFI/GPRS/4G/LAN/ RF

|

Optional

Warranty:5/10 years

|

Yes/ Optional

Model

Specifications

|

MIC 2000TL-X

|

MIC 2500TL-X

|

MIC 3000TL-X

|

MIC 3300TL-X

---|---|---|---|---

Input data(DC)

Max. recommended PV power(for module STC)

|

2800W

|

3500W

|

4200W

|

4290W

Max. DC voltage

|

550V

Start voltage

|

80V

Nominal voltage

|

360V

MPP voltage range

|

65V-550V

MPP voltage range at Full Power

|

170V-450V

|

200V-500V

|

250V-500V

|

270V-500V

No. of MPP trackers

|

1

No. of PV strings per MPP trackers

|

1

Max. input current per MPP trackers

|

13A

Max. short-circuit current per MPP trackers

|

16A

DC overvoltage category

|

Category II

Output data(AC)

AC nominal power

|

2000W

|

2500W

|

3000W

|

3300W

Max. AC apparent power

|

2000VA

|

2500VA

|

3000VA

|

3300VA

Nominal AC voltage/range*

|

230V/180~280V

AC grid frequency/range

|

50-60Hz/44-55Hz;54-65Hz

Max. output current

|

9.5A

|

11.9A

|

14.3A

|

14.3A

Inrush current

|

<10A

‌Noise emission (typical)

|

≤ 25 dB(A)

---|---

Altitude

|

4000m

Internal consumption at night

|

<0.5W

Topology

|

transformerless

Cooling

|

Natural convection

Protection degree

|

IP65

Relative humidity

|

0~100%

DC connection

|

VP-D4/MC4(Optional)

AC connection

|

AC connector

Interfaces

Display

|

OLED+LED

RS485/USB

|

Integrated

WIFI/GPRS/4G/LAN/ RF

|

Optional

Warranty:5/10 years

|

Yes/ Optional

  • The AC Voltage Range may vary depending on specific country grid standard. All specifications are subject to change without notice.

MIC 600TL-X is only available in Germany.

14.2 DC &AC connector info

DC connector

|

VP-D4/ MC4(opt)

---|---

AC connector

|

EN030-2028-1001 VPAC06EP-3S(SC) VPAC06EW-3P(SC4)

14.3 Torque

Enclosure lid screws

|

12kgf.cm

---|---

AC terminal

|

6kgf.cm

Signal terminal

|

4kgf.cm

Safety screw

|

12kgf.cm

Additional ground screws

|

12kgf.cm

Max output fault current

|

66A

---|---

Max output overload protection

|

16A

Backfeed current

|

0A

P o we r fa c t o r ( @ n o m i n a l power)

|

0.99

Adjustable power factor

|

0.8leading… 0.8lagging

THDi

|

<3%

AC grid connection type

|

Single phase

AC overvoltage category

|

Category III

Efficiency

Max. efficiency

|

97.4%

|

97.6%

|

97.6%

|

97.6%

Euro-eta

|

97.0%

|

97.0%

|

97.1%

|

97.1%

Protection devices

DC reverse-polarity protection

|

Integrated

DC switch

|

Integrated

DC Surge protection

|

Type III

Insulation resistance monitoring

|

Integrated

AC surge protection

|

Type III

AC short-circuit protection

|

Integrated

Ground fault monitoring

|

Integrated

Grid monitoring

|

Integrated

Anti-islanding protection

|

Integrated

Residual-current monitoring unit

|

Integrated

General data

Dimensions (W / H / D) in mm

|

274254138

Weight

|

6.0kg

|

6.2kg

Operating temperature range

|

–25 °C … +60 °C

14.4 Accessories

In the following table you will find the optional accessories for your product. If required, you can order these from GROWATT NEW ENERGY TECHNOLOGY CO.,LTD or your dealer.

Name

|

Brief description

---|---

Shine WIFI-X

|

WIFI monitor with USB interface

Shine 4G-X

|

4G monitor with USB interface

Shine Link-X

|

RF monitor with USB interface

Shine LAN-X

|

LAN monitor with USB interface

Shipped to a Growatt service centre for repair, or repaired on-site, or exchanged for a replacement device of equivalent value according to model and age.

The warranty shall not cover transportation costs in connection with the return of defective modules . The cost of the installation or reinstallation of the modules shall also be expressly exclude as are all other related logistical and process costs incurred by all parties in relation to this warranty claim.

Contact 16

If you have technical problems about our products, contact the GROWATT Serviceline. We need the following information in order to provide you with the necessary assistance:

►Inverter type

►Serial number of the inverter

►Event number or display message of the inverter

►Type and number of PV modules connected

►Optional equipment

Shenzhen Growatt New Energy Co., Ltd

4-13/F,Building A,Sino-German(Europe) Industrial Park, Hangcheng Ave,Bao’an District, Shenzhen, China

15. Compliance Certificates

Certificates
With the appropriate settings, the unit will comply with the requirements specified in the following standards and directives (dated: April/2020):

Model

|

Certificates

---|---

MIC 600-3300TL-X

|

CE , IEC 62109,IEC62116/61727,IEC60068/61683, VDE0126-1-1,EN 50549,C10/11,Inmetro

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals