GROWATT 600TL-X Photovoltaic Approval VDE Wi-fi Inverter Instruction Manual
- June 16, 2024
- Growatt
Table of Contents
- GROWATT 600TL-X Photovoltaic Approval VDE Wi-fi Inverter
- 1. Notes on this manual
- 2. Safety
- 3. Product description
- 4. Unpacking and inspection
- 5. Installation
- 6. Electrical connection
- 7. Commissioning
- 8. Start-up and shut down the Inverter
- 9. Maintenance and Cleaning
- 10. EU Declaration of Conformity
- 11. Trouble shooting
- 12. Manufacturer Warranty
- 13 Decommissioning
- 14. Technical Data
- 15. Compliance Certificates
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
GROWATT 600TL-X Photovoltaic Approval VDE Wi-fi Inverter
Installation & Operation Manual
Download Manual
Growatt New Energy
Shenzhen Growatt New Energy Co., Ltd
4-13/F,Building A,Sino-German(Europe) Industrial Park,
Hangcheng Ave,Bao’an District, Shenzhen, China
+86 0755 2747 1942
www.ginverter.com
service@ginverter.com
GR-UM-196-A-03
1. Notes on this manual
1.1 Validity
This manual describes the assembly, installation, commissioning and
maintenance of the following Growatt Inverter model:
MIC 600TL-X
MIC 750TL-X
MIC 1000TL-X
MIC 1500TL-X
MIC 2000TL-X
MIC 2500TL-X
MIC 3000TL-X
MIC 3300TL-X
This manual does not cover any details concerning equipment connected to the MIC TL-X (e.g. PV modules). Information concerning the connected equipment is available from the manufacturer of the equipment.
1.2 Target Group
This manual is for qualified personnel. Qualified personnel have received
training and have demonstrated skills and knowledge in the construction and
operation of this device. Qualified Personnel are trained to deal with the
dangers and hazards involved in installing electric devices.
1.3 Additional information
Find further information on special topics in the download area at
www.ginverter.com The manual and other documents must be stored in a
convenient place and be available at all times. We assume no liability for any
damage caused by failure to observe these instructions. For possible changes
in this manual, GROWATT NEW ENERGY CO.,LTD accepts no responsibilities to
inform the users.
1.4 Symbols in this document
1.4.1 Warnings in this document
A warning describes a hazard to equipment or personnel. It calls attention to
a procedure or practice, which, if not correctly performed or adhered to,
could result in damage to or destruction of part or all of the Growatt
equipment and/or other equipment connected to the Growatt equipment or
personal injury.
Symbol | Description |
---|---|
DANGER result in death or serious injury. | |
WARNING indicates a hazardous situation which, if not avoided,could result |
in death or serious injury.
| CAUTION indicates a hazardous situation which, if not avoided, could result
in minor or moderate injury.
| NOTICE is used to address practices not related to personal injury.
| Information that you must read and know to ensure optimal operation of the
system.
1.4.2 Markings on this product
Symbol | Explanation |
---|---|
Electrical voltage! | |
Risk of fire or explosion! | |
Risk of burns | |
Operation after 5 minutes | |
Point of connection for grounding protection | |
Direct Current (DC) | |
Alternating Current (AC) | |
Read the manual | |
--- | --- |
CE mark. |
The inverter complies with the requirements of the applicable CE guidelines.
---|---
| The inverter must not be disposed of with the household waste.
---|---
1.5 Glossary
AC
Abbreviation for “Alternating Current”
DC
Abbreviation for “Direct Current”
Energy
Energy is measured in Wh (watt hours), kWh (kilowatt hours) or MWh (megawatt
hours). The energy is the power calculated over time. For example, your
inverter operates at a constant power of 4600 W for half an hour and then at a
constant power of 2300 W for another half an hour, it has fed 3450Wh of energy
into the power distribution grid within that hour.
Power
Power is measured in W (watts), kW (kilowatts) or MW (megawatts). Power is an
instantaneous value. It displays the power your inverter is currently feeding
into the power distribution grid.
Power rate
Power rate is the radio of current power feeding into the power distribution
grid and the maximum power of the inverter that can feed into the power
distribution grid.
Power factor
Power factor is the ratio of true power or watts to apparent power or volt
amps. They are identical only when current and voltage are in phase than the
power factor is 1.0. The power in an ac circuit is very seldom equal to the
direct product of the volts and amperes. In order to find the power of a
single phase ac circuit the product of volts and amperes must be multiplied by
the power factor.
PV
Abbreviation for photovoltaic.
Wireless communication
The external wireless communication technology is a radio technology that
allows the inverter and other communication products to communicate with each
other. The external wireless communication does not require line of sight
between the devices and it is selective purchasing.
2. Safety
2.1 Intended Use
The unit converts the DC current generated by the photovoltaic (PV) modules to
gridcompliant alternating current and performs single-phase feed-in into the
electricity grid. MIC 750TL-X,MIC 1000TL-X,MIC 1500TL-X,MIC 2000TL-X,MIC
2500TL-X,MIC 3000TL-X, MIC 3300TL-X inverters are built according to all
required safety rules. Nevertheless, improper use may cause lethal hazards for
the operator or third parties, or may result indamage to the units and other
property.
Principle of a PV plant with this MIC TL-X single-phase inverter
Position | Description |
---|---|
A | PV modules |
B | DC load circuit breaker |
C | Inverter |
D | AC load circuit breaker |
E | Energy meter |
F | Utility grid |
The inverter may only be operated with a permanent connection to the public power grid. The inverter is not intended for mobile use. Any other or additional use is not considered the intended use. The manufacturer/supplier is not liable for damage caused by such unintended use. Damage caused by such unintended use is at the sole risk of the operator.
PV modules Capacitive Discharge Currents
PV modules with large capacities relative to earth, such as thin-film PV
modules with cells on a metallic substrate, may only be used if their coupling
capacity does not exceed 1uF. During feed-in operation, a leakage current
flows from the cells to earth, the size of which depends on the manner in
which the PV modules are installed (e.g. foil on metal roof) and on the
weather (rain, snow). This “normal” leakage current may not exceed50mA due to
the fact that the inverter would otherwise automatically disconnect from the
electricity grid as a protective measure.
2.2 Qualification of skilled person
This grid-tied inverter system operates only when properly connected to the AC
distribution network. Before connecting the MIC TL-X to the power distribution
grid, contact the local power distribution grid company. This connection must
be made only by qualified technical personnel to connect, and only after
receiving appropriate approvals, as required by the local authority having
jurisdiction.
2.3 Safety instruction
The MIC TL-X Inverters is designed and tested according to international
safety requirements (IEC62109-1,CE,VDE0126-1-1, AS4777,etc); however, certain
safety precautions must be observed when installing and operating this
inverter. Read and follow all instructions, cautions and warnings in this
installation manual. If questions arise, please contact Growatt’s technical
services at +86 (0)755 2747 1942.
2.4 Assembly Warnings
| ►Prior to installation, inspect the unit to ensure absence of any transport
or handling damage, which could affect insulation integrity or safety
clearances; failure to do so could result in safety hazards.
►Assemble the inverter per the instructions in this manual. Use care when
choosing installation location and adhere to specified cooling requirements.
►Unauthorized removal of necessary protections, improper use, incorrect
installation and operation may lead to serious safety and shock hazards and/or
equipment damage.
►In order to minimize the potential of a shock hazard due to hazardous
voltages, cover the entire solar array with dark material prior to connecting
the array to any equipment.
---|---
| ►Grounding the PV modules: The MIC TL-X is a transformerless
inverter. That is why it has no galvanic separation. Do not ground the DC
circuits of the PV modules connected to the MIC TL-X. Only ground
the mounting frame of the PV modules.If you
connect grounded PV modules to the MIC TL-X, the error
message “PV ISO Low”.
►Comply with the local requirements for grounding the
PV
modules and the PV generator. GROWATT recommends connecting
the generator frame and other electrically conductive surfaces in a manner
which ensures continuous conduction with ground in order to have
optimal protection of the system and personnel.
---|---
2.5 Electrical Connection Warnings
| ►The components in the inverter are live. Touching live components can
result in serious injury or death.
•Do not open the inverter except the wire box by qualified persons.
•Electrical installation, repairs and conversions may only be carried out by
electrically qualified persons.
•Do not touch damaged inverters.
►Danger to life due to high voltages in the inverter
•There is residual voltage in the inverter. The inverter takes 20 minutes
discharge.
►Persons with limited physical or mental abilities may only work with the
Growatt inverter following proper instruction and under constant supervision.
Children are forbidden to play with the Growatt inverter. Must keep the
Growatt inverter away from children.
---|---
| ►Make all electrical connections (e.g. conductor termination, fuses, PE
connection, etc.) in accordance with prevailing regulations. When working with
the inverter powered on, adhere to all prevailing safety regulations to
minimize risk of accidents.
►Systems with inverters typically require additional control (e.g.,
switches, disconnects) or protective devices (e.g., fusing circuit
breakers) depending upon the prevailing safety rules.
---|---
2.6 Operation Warnings
| ►Ensure all connectors are sealed and secure during operation.
►Although designed to meet all safety requirements, some parts and
surfaces of Inverter are still hot during operation. To reduce the
risk of injury, do not touch the heat sink at the back of the PV- Inverter or
nearby surfaces while Inverter is operating.
►Incorrect sizing of the PV plant may result in voltages being
present which could destroy the inverter. The inverter display will read the
error message “PV voltage High!”
►Turn the rotary switch of the DC Disconnect to the Off position
immediately.
►Contact installer.
•Turn the rotary switch of the DC Disconnect to the Off position
immediately.
•Contact installer.
---|---
| ►All operations regarding transport, installation and start-up, including
maintenance must be operated by qualified, trained personnel and in compliance
with all prevailing codes and regulations.
►Anytime the inverter has been disconnected from the power network, use
extreme caution as some components can retain charge sufficient to create a
shock hazard; to minimize occurrence of such conditions, comply with all
corresponding safety symbols and markings present on the unit and in this
manual.
►In special cases, there may still be interference for the specified
application area despite maintaining standardized emission limit values (e.g.
when sensitive equipment is located at the setup location or when the setup
location is near radio or television receivers).In this case, the operator is
obliged to take proper action to rectify the situation.
►Do not stay closer than 20 cm to the inverter for any length of
time.
---|---
3. Product description
3.1 MIC TL-X Overview
Position | Description |
---|---|
A | COVER |
B | DC SWITCH |
C | LED |
D | OLED |
E | TOUCH BUTTON |
F | PV INPUT + |
G | PV INPUT – |
H | DRM PORT |
I | AC OUTPUT |
J | VENTILATION VALVE |
K | COM PORT |
L | USB PORT |
Symbol on the inverter
Symbol | Description | Explanation |
---|---|---|
Touch symbol | Touch button.We can switch the OLED display and set parameter |
by touching.
| Inverter status symbol| Indicates inverter operation status: Red:Fault.
Green:Nomal.
Red leaf flash:Warning or DSP Programming. Green leaf flash:M3 Programming.
3.2 Type label
The type labels provide a unique identification of the inverter (The type of product, Device-specific characteristics, Certificates and approvals). The type labels are on the left-hand side of the enclosure.
More detail about the type label as the chart below:
Model Name | MIC 600 TL-X | MIC 750 TL-X | MIC 1000 TL-X | MIC1500 TL-X |
---|---|---|---|---|
Max. input voltage | 500V | |||
Max. input current | 13A | |||
Start voltage | 50V | |||
MPP voltage range | 50V~500V | |||
AC nominal voltage | 230V | |||
AC grid frequency | 50/60 Hz | |||
Max. apparent power | 600VA | 750VA | 1000VA | 1500VA |
Max. output current | 2.9A | 3.6A | 4.8A | 7.1A |
--- | --- | --- | --- | --- |
Power factor | 0.8leading…0.8lagging | |||
--- | --- | |||
Environmental Protection Rating | IP 65 | |||
--- | --- | |||
Operation Ambient temperature | -25…+60℃ (-13…+ 140°F) |
with derating above 45°C( 113°F)
---|---
Model Name| MIC 2000
TL-X| MIC 2500
TL-X| MIC 3000
TL-X| MIC3300
TL-X
---|---|---|---|---
Max. input voltage| 550V
Max. input current| 13A
Start voltage| 80V
MPP voltage range| 65V~550V
AC nominal voltage| 230V
AC grid frequency| 50/60 Hz
---|---
Max. apparent power| 2000VA| 2500VA| 3000VA| 3300VA
---|---|---|---|---
Max. output current| 9.5A| 11.9A| 14.3A| 14.3A
Power factor| 0.8leading…0.8lagging
---|---
Environmental Protection Rating| IP 65
Operation Ambient temperature| -25…+60℃ (-13…+ 140°F)
with derating above 45°C( 113°F)
3.3 Size and weight
Model | Height (H) | Width (W) | Depth (D) | Weight |
---|---|---|---|---|
MIC 600-2000 TL-X | 282mm 11.1inch | 274mm 10.78inch | 138mm 5.4inch | 6.0kg |
MIC 2500-3300 TL-X | 282mm 11.1inch | 274mm 10.78inch | 138mm 5.4inch | 6.2kg |
3.4 Storage of Inverter
If you want to storage the inverter in your warehouse, you should choose an appropriate location to store the inverter.
►The unit must be stored in original package and desiccant must be left in the
package.
►The storage temperature should be always between -25℃and +60℃. And the
storage relative humidity can achieve to 100%.
►If there are a batch of inverters need to be stored, the maximum layers for
original carton is ten.
►After long term storage, local installer or service department of GROWATT
should perform a comprehensive test before installation.
3.5 The advantage of the unit
►Maximum efficiency of 97.6%
►Wide input voltage range from 65–550Vdc
►Reactive power regulate
►Integrated DC switch
►DSP controller
►Touch control
►Multi active power control mode
►Easy installation
4. Unpacking and inspection
The inverter is thoroughly tested and inspected strictly before delivery. Our inverters leave our factory in proper electrical and mechanical condition. Special packaging ensures safe and careful transportation. However, transport damage may still occur. The shipping company is responsible in such cases. Thoroughly inspect the inverter upon delivery. Immediately notify the responsible shipping company if you discover any damage to the packaging which indicates that the inverter may have been damaged or if you discover any visible damage to the inverter. We will be glad to assist you, if required. When transporting the inverter, the original or equivalent packaging should be used, and the maximum layers for original carton is four, as this ensures safe transport.
After opening the package, please check the contents of the box. It should contain the following, Please check all of the accessories carefully in the carton. If anything missing, contact your dealer at once.
Object | Description | Quantity |
---|---|---|
A | Inverter | 1 |
B | Mounting bracket | 1 |
C | Quick Guide | 1 |
D | Monitor(Optional) | 1 |
E | Signal connector | 1 |
F | DRM PORT(Australia or EU) | 1 |
G | Self-tapping screws | 3 |
H | Safety-lock screws | 2 |
I | Plastic expansion pipe | 3 |
J | PV+/PV- terminal | 1/1 |
K | PV+/PV- metal terminal | 1/1 |
L | AC connector | 1 |
M | Uninstall signal and AC connector tool | 1 |
N | Uninstall PV tool(except Australia) | 1 |
5. Installation
5.1 Safety instructions
| Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
Do not install the inverter on easily flammable materials and where
flammable materials are stored.
---|---
| Risk of burns due to hot enclosure parts Mount the inverter in such
a way that it cannot be touched inadvertently.
| Possible damage to health as a result of the effects of radiation!
►In special cases, there may still be interference for the specified
application area despite maintaining standardized emission limit values (e.g.
when sensitive equipment is located at the setup location or when the setup
location is near radio or television receivers).In this case, the operator is
obliged to take proper action to rectify the situation.
►Never install the inverter near the sensitive equipment( e.g. Radios,
telephone, television, etc)
►Do not stay closer than 20 cm to the inverter for any length of time unless
it is absolutely necessary.
►Growatt assumes no responsibility for compliance to EMC regulations for the
complete system
►All electrical installations shall be done in accordance with the local and
national electrical codes. Do not remove the casing. Inverter contains no user
serviceable parts. Refer servicing to qualified service personnel. all wiring
and electrical installation should be conducted by a qualified service
personnel .
►Carefully remove the unit from its packaging and inspect for external damage.
If you find any imperfections, please contact your local dealer.
►Be sure that the inverters connect to the ground in order to protect property
and personal safety.
►The inverter must only be operated with PV generator. Do not connect any
other source of energy to it.
►Both AC and DC voltage sources are terminated inside the PV Inverter. Please
disconnect these circuits before servicing.
►This unit is designed to feed power to the public power grid (utility) only.
Do not connect this unit to an AC source or generator. Connecting Inverter to
external devices could result in serious damage to your equipment.
►When a photovoltaic panel is exposed to light, it generates a DC voltage.
When connected to this equipment, a photovoltaic panel will charge the DC link
capacitors.
►Energy stored in this equipment’s DC link capacitors presents a risk of
electric shock.
Even after the unit is disconnected from the grid and photovoltaic panels,
high voltages may still exist inside the PV-Inverter. Do not remove the casing
until at least 5 minutes after disconnecting all power sources.
►Although designed to meet all safety requirements, some parts and surfaces of
Inverter are still hot during operation. To reduce the risk of injury, do not
touch the heat sink at the back of the PV-Inverter or nearby surfaces while
Inverter is operating.
5.2 Selecting the installation location
►This is guidance for installer to choose a suitable installation location, to
avoid potential damages to device and operators.
►The installation location must be suitable for the inverter’s weight and
dimensions for a long period time.
►Select the installation location so that the status display can be easily
viewed.
►Do not install the inverter on structures constructed of inflammable or
thermolabile materials.
►Never install the inverter in environment of little or no air flow, nor dust
environment. That may derate the efficiency of the cooling fan of the
inverter.
►The Ingress Protection rate is IP65 which means the inverter can be installed
outdoors and indoors.
►The humidity of the installation location should be 0~100% without
condensation.
►The installation location must be freely and safely to get at all times.
►Vertically installation and make sure the connection of inverter must be
downwards. Never install horizontal and avoids forward and sideways tilt.
►Be sure that the inverter is out of the children’s reach.
►Don’t put any things on the inverter. Do not cover the inverter.
►Do not install the inverter near television antenna or any other antennas and
antenna cables.
►Inverter requires adequate cooling space. Providing better ventilation for
the inverter to ensure the heat escape adequately. The ambient temperature
should be below 40°C to ensure optimum operation.
►Do not expose the inverter to direct sunlight, as this can cause excessive
heating and thus power reduction.
►Observe the Min. clearances to walls, other inverters, or objects as shown
below:
►There must be sufficient clearance between the individual inverters to ensure
that the cooling air of the adjacent inverter is not taken in.
►If necessary, increase the clearance spaces and make sure there is enough
fresh air supply to ensure sufficient cooling of the inverters.
The inverter can’t install to solarization,drench,firn location. We suggest that the inverters should be installed at the location with some cover or protection.
►Please make sure the inverter is installed at the right place.The inverter can’t install close to trunk.
5.3 Mounting the Inverter
5.3.1 Mounting the Inverter with bracket
In order to avoid electrical shock or other injury, inspect existing electronic or plumbing installations before drilling holes.
Fix the mounting bracket as the figure shows. Do not make the screws to be flush to the wall. Instead, leave 2 to 4mm exposed.
5.3.2 Fixed the inverter on the wall
Falling equipment can cause serious or even fatal injury, never mount the inverter on the bracket unless you are sure that the mounting frame is really firmly mounted on the wall after carefully checking.
►Rise up the inverter a little higher than the bracket. Considered the weight
of them.During the process please maintain the balance of the inverter.
Hang the inverter on the bracket through the match hooks on bracket.
►After confirming the inverter is fixed reliably, fasten one M4 safety-lock screws on the right or left side firmly to prevent the inverter from being lifted off the bracket.
6. Electrical connection
Decisive Voltage Class (DVC) indicated for ports
Port Name | Class |
---|---|
AC | C |
DC | C |
DRM | A |
RS485&USB | A |
6.1 Safety
Danger to life due to lethal voltages!
High voltages which may cause electric shocks are present in the conductive
parts of the inverter. Prior to performing any work on the inverter,
disconnect the inverter on the AC and DC sides
Danger of damage to electronic components due to electrostatic discharge.
Take appropriate ESD precautions when replacing and installing the inverter.
6.2 Wiring AC Output
You must install a separate single-phase circuit-breaker or other load disconnection unit for each inverter in order to ensure that the inverter can be safely disconnected under load.
NOTE :
The inverter has the function of detecting residual current and protecting the
inverter against residual current. If your inverter has to equip a AC breaker
which has the function of detecting residual current ,you must choose a AC
breaker with the rating residual current more than 300mA.
You must install a separate single-phase circuit-breaker or other load
disconnection unit for each inverter in order to ensure that the inverter can
be safely disconnected under load.
We suggest you choice the AC breaker rating current in this table:
MIC 600TL-X | 5A/230V |
---|---|
MIC 750TL-X | 5A/230V |
MIC 1000TL-X | 10A/230V |
MIC 1500TL-X | 10A/230V |
MIC 2000TL-X | 16A/230V |
MIC 2500TL-X | 16A/230V |
MIC 3000TL-X | 16A/230V |
MIC 3300TL-X | 16A/230V |
The AC wiring step:
1. Uninstall the parts of the AC connection plug from the accessory bag.
2.Insert the stripped and bared cable through pressure screw, seal ring, threaded sleeve in sequence, insert cables into connection terminal according to polarities indicates on it and tighten the screws firmly. Please try to pull out the wire to make sure the it’s well connected.
3. Push the threaded sleeve into the socket, Tighten up the cap on the terminal.
4.Finally, Push or screw the threaded sleeve to connection terminal until both are locked tightly on the inverter.
5. To remove the AC connector, press the bayonet out of the slot with a small screwdriver and pull it out,or unscrew the threaded sleeve,then pull it out.
Wire suggestion length
Conductor cross section | Max. cable length |
---|---|
MIC 600TL-X | MIC 750TL-X |
2 mm² 14AWG | 92m |
3.3 mm² 12AWG | 150m |
Conductor cross section | Max. cable length |
MIC 2000TL-X | MIC 2500TL-X |
3.3 mm² 12AWG | 45m |
5.2 mm² 10AWG | 73m |
6.3 Connecting the second protective conductor
In some installation countries, a second protective conductor is required to
prevent a touch current in the event of a malfunction in the original
protective conductor.For installation countries falling within the scope of
validity of the IEC standard 62109, you must install the protective conductor
on the AC terminal with a conductor cross-section of at least 10 mm²Cu.Or
Install a second protective conductor on the earth terminal with the same
cross-section as the original protective conductor on the AC terminal. This
prevents touch current if the original protective conductor fails.
6.4 Connecting the PV Array (DC input)
6.4.1 Conditions for DC Connection
The solar modules connected to the inverter must conform to the Class A
requirements of the IEC 61730 standard.
Please use the same brand male and female PV connectors.
The MIC TL-X single-phase inverter has only one independent PV input : Notice that the connectors are in paired (male and female connectors). The connectors for PV arrays and inverters are VP-D4 connectors;
If the inverter is not equipped with a DC switch but this is mandatory in the
country of installation, install an external DC switch.
The following limit values at the DC input of the inverter must not be
exceeded:
Types | PV max current | Max voltage |
---|---|---|
MIC 600-2000TL-X | 13A | 500V |
MIC 2500-3300TL-X | 13A | 550V |
6.4.2 Connecting the PV Array (DC input)
| Danger to life due to lethal voltages!
PV array supplies d.c voltage to inverter when exposed to
light,before connecting the PV array, conver some light
screens above PV arrays,ensure that the DC switch and AC breaker
are disconnect from the inverter. NEVER connect or disconnect the DC
connectors under load.
Make sure the maximum open circuit voltage(Voc) of each PV string is less
than the maximum input voltage of the inverter.
Check the design of the PV plant. The Max. open circuit voltage, which can
occur at solar panels temperature of -10℃ , must not exceed the Max.
input voltage of the inverter.
---|---
| Improper operation during the wiring process can cause fatal injury to
operator or unrecoverable damage to the inverter. Only
qualified personnel can perform the wiring work.
Please don’t connect PV array positive or negative pole to the ground, it
could cause serious damages to the inverter.
Check the connection cables of the PV modules for correct polarity and make
sure that the maximum input voltage of the inverter is not
exceeded.
---|---
Connection of PV terminal
6.5 Connecting signal cable
This series inverter has one 8 Pin signal connector. Signal Cable Ports:
Procedure
Step 1: Insert the stripped and bared cable through pressure screw, seal ring, threaded sleeve in sequence, insert cables into connection terminal according to number indicates on it and tighten the screws firmly. Please try to pull out the wire to make sure the it’s well connected.
Step 2: Push the threaded sleeve into the socket, Tighten up the cap on the terminal.
Step 3: Push the threaded sleeve to connection terminal until both are locked tightly on the inverter.
Uninstall signal connector
Step 1: Press the fasteners and pull it out from the inverter.
Step 2: Insert the H type tool and pull it out from the socket.
6.6 Grounding the inverter
The inverter must be connected to the AC grounding conductor of the power
distribution grid via the ground terminal (PE) .
Because of the transformerless design, the DC positive pole and DC negative pole of PV arrays are not permitted to be grounded.
6.7 Active power control with smart meter , CT (Optional)or ripple control signal receiver
The position of export limitation CT or Meter must between the Inverter & Load and gird.
This series inverter has integrated export limitation functionality. To use this function, you can connect smart meter or CT, but CT is optional. The smart meter model is Eastron SDM230-Modbus. The CT Model is TOP 90-S10/SP4 (LEM).The primary aperture is 10mm,output cable length is 5m . The arrow on the CT must pointing towards the inverter.
Active power control with a Radio Ripple Control Receiver(RRCR).
6.8 Inverter demand response modes (DRMS)
This series inverter has the function of demand response modes, We use RJ45
terminal as inverter DRED connection.
| DRMS application description
AØpplicable to AS/NZS4777.2:2015 or Commission Regulation (EU) 2016/631.
DØRM0, DRM5, DRM6, DRM7, DRM8 are available.
---|---
| Damage to the inverter due to moisture and dust penetration MØake sure the
cable gland has been tightened firmly.
If the cable gland are not mounted properly, the inverter can be destroyed due to moisture and dust penetration. All the warranty claim will be invalid.
| Excessive voltage can damage the inverter!External voltage of DRM PORT don’t over +5V.
6.8.1 RJ45 terminal pin assignment
6.8.2 Method of asserting demand response modes
Mode | Socket Asserted by shorting pins | Function |
---|---|---|
DRM 0 | 5 | 6 |
DRM 5 | 1 | 5 |
DRM 6 | 2 | 5 |
DRM 7 | 3 | 5 |
power if capabie
DRM 8| 4| 5| Increase power generation (subject to constraints from other
active DRMs)
6.8.3 Using the Power Control Interface for EU
6.8.3.1 The following table describes the connector pin assignment and function:
DRM Socket Pin NO. | Description | Connect to RRCR |
---|---|---|
1 | Relay contact 1 input | K1 – Relay 1 output |
2 | Relay contact 2 input | K2 – Relay 2 output |
3 | Relay contact 3 input | K3 – Relay 3 output |
4 | Relay contact 4 input | K4 – Relay 4 output |
5 | GND | Relays common node |
6 | Not connected | Not connected |
7 | Not connected | Not connected |
8 | Not connected | Not connected |
6.8.3.2The inverter is preconfigured to the following RRCR power levels:
DRMs
Connector Pin1| DRMs
Connector Pin2| DRMs
Connector Pin3| DRMs
Connector Pin4| Active power| Cos(φ)
---|---|---|---|---|---
Short circuit with Pin5| | | | 0%| 1
| Short circuit with Pin5| | | 30%| 1
| | Short circuit with Pin5| | 60%| 1
| | | Short circuit with Pin5| 100%| 1
Active power control and reactive power control are enabled separately.
6.9 AFCI(Optional)
6.9.1 Arc-Fault Circuit Interrupter (AFCI)
In accordance with the National Electrical Code R, Article 690.11, the
inverter has a system for the recognition of electric arc detection and
interruption. An electric arc with a power of 300 W or greater must be
interrupted by the AFCI within the time specified by UL 1699B. A tripped AFCI
can only be reset manually. You can deactivate the automatic arc fault
detection and interruption (AFCI) via a communication product in “Installer”
mode if you do not require the function. The 2011 edition of the National
Electrical Code R, Section 690.11 stipulates that newly installed PV systems
attached to a building must be fitted with a means of detecting and
disconnecting serial electric arcs (AFCI) on the PV side.
6.9.2 Danger information
Danger of fire from electric arc
Only test the AFCI for false tripping in the order described below. Do not
deactivate the AFCI permanently.
If an “Error 200” message is displayed, the buzzer alarms, an electric arc occurred in the PV system. The AFCI has tripped and the inverter is in permanent shutdown.
The inverter has large electrical potential differences between its
conductors. Arc flashes can occur through air when high-voltage current flows.
Do not work on the product during operation.
When the inverter error 200, please follow the steps:
6.9.3 Operation step
6.9.3.1 Turn the DC & AC Disconnect to position “oFF”.
Wait for the display to go out.
6.9.3.2 Perform troubleshooting on the PV system:
Check all PV strings for the correct open-circuit voltage.
6.9.3.3 After the fault is rectified, restart the inverter:
Turn the DC & AC Disconnect to position “ON”.
7. Commissioning
Do not disconnect the DC connectors under load.
Improper operation during the wiring process can cause fatal injury to operator or unrecoverable damage to the inverter. Only qualified personnel can perform the wiring work.
Damage to the inverter due to moisture and dust penetration
Make sure the cable gland has been tightened firmly.
If the cable gland are not mounted properly, the inverter can be destroyed due to moisture and dust penetration. All the warranty claim will be invalid.
Requirements:
- The AC cable is correctly connected.
- The DC cable is correctly connected.
- The country is set correctly.
7.1 Start the inverter
7.1.1 Touch control
Touch | Description |
---|---|
Single touch | Switch display or Number +1 |
Double touch | Enter or confinmation |
Three touch | Previous menu |
Hold 5s | C o n f i r m c o u n t r y s e t t i n g o r Number recover default |
value
7.1.2 Country setting
Country setting
When the inverter start up,we need to select the right country,if we don’t
select any country, the inverter will run under AS/NZS4777.2 as default for
Australia,or run under VDE0126-1-1 for other region after 30s.
When inverter powered on, OLED will light automatically. Once the PV power is sufficient, OLED displays the following:
If we touch the touch button to scroll through the different countries the screen will constantly change.For example,if you want to choose Newzealand,touch the touch button until the OLED panel shows “Newzealand” as below:
Press the touch button for 5s the OLED shows the country , setting is completed.
7.2 General setting
7.2.1 Set inverter display language
This series inverter provides multi languages.
Single touch to switch different language.
Double touch to confirm you setting.
Set the language as described below:
7.2.2 Set inverter COM address
The default COM address is 1.We can change COM address as described below:
Single touch to switch display or make the number + 1.
Hold 5s ,the COM address become 001.
Double touch to confirm you setting.
7.2.3 Set inverter date & time
Single touch make the number 1.
Double touch to confirm you setting.
Hold 5s recover defaut value.
7.3 Advanced setting
7.3.1 Reset Country
Single touch to switch display or make the number + 1.
Double touch to confirm you setting.
The password of advanced setting is 123.
7.3.2 Export limitation setting
Single touch to switch display or make the number + 1.
Double touch to confirm you setting.
7.3.3 Reset factory
Perform this operation with caution because all configured parameters except the current date,time, and model parameters will be restored to their factory defaults.
Single touch to switch display or make the number + 1.
Double touch to confirm you setting.
7.4 Communications
7.4.1 RS485
This series inverter provides two RS485 ports. You can monitor one or more
inverters by
RS485.Another RS485 port is for smart meter(Export limitation functionality.).
7.4.2 USB-A
USB-A port is mainly for connecting monitor or firmware updage
Through USB connection,we can connect external optional monitor ,for example
:Shine
WIFI-X,Shine 4G-X, Shine LAN-X,ect.
And also you can quickly update the software by U disk.
We can monitor as below:
Make sure the on the front side, then insert the monitor,fasten the screw.
8. Start-up and shut down the Inverter
8.1 Start-Up the inverter
1. Connect the AC breaker of the inverter.
2.Turn on the dc switch, and the inverter will start automatically when the
input voltage is higher than 70 V.
8.2 Turn-off the Inverter
Do not disconnect the DC connectors under load.
Turn-off the inverter step:
1.Disconect the line circuit breaker from single-phases grid and prevent it
from being reactivated.
2.Turn off the dc switch.
3.Check the inverter operating status.
4.Waiting until LED, OLED have go out, the inverter is shut down.
9. Maintenance and Cleaning
9.1 Checking Heat Dissipation
If the inverter regularly reduces its output power due to high temperature,
please improve the heat dissipation condition. Maybe you need to clean the
heat sink.
9.2 Cleaning the Inverter
If the inverter is dirty, turn-off the AC breaker and DC switch ,waiting the
inverter shut down ,then clean the enclosure lid, the display, and the LEDs
using only a wet cloth. Do not use any cleaning agents (e.g. solvents or
abrasives).
9.3 Checking the DC Disconnect
Check for externally visible damage and discoloration of the DC Disconnect and
the cables at regular intervals.If there is any visible damage to the DC
Disconnect, or visible discoloration or damage to the cables, contact the
installer.
Once a year, turn the rotary switch of the DC Disconnect from the On position to the Off position 5 times in succession. This cleans the contacts of the rotary switch and prolongs the electrical endurance of the DC Disconnect.
10. EU Declaration of Conformity
With the scope of EU directives:
• 2014/35/EU Low Voltage Directive (LVD)
• 2014/30/EU Electromagnetic Compatibility Directive (EMC)
• 2011/65/EU RoHS Directive and its amendment (EU)2015/863
Shenzhen Growatt New Energy Technology Co. Ltd confirms that the Growatt inverters and accessories described in this document are in compliance with the above mentioned EU directives. The entire EU Declaration of Conformity can be found at www.ginverter.com.
11. Trouble shooting
Our quality control program assures that every inverter is manufactured to accurate specifications and is thoroughly tested before leaving our factory. If you have difficulty in the operation of your inverter, please read through the following information to correct the problem.
11.1 Error Messages displayed on OLED
An error message will be displayed on the OLED screen when a fault occurs. The
faults consist of system fault and inverter fault.
You may be advised to contact Growatt in some situation, please provide the
following information.
Information concerning the inverter:
- Serial number
- Model number
- Error message on OLED
- Short description of the problem
- Grid voltage
- DC input voltage
- Can you reproduce the failure? If yes, how?
- Has this problem occurred in the past?
- What was the ambient condition when the problem occurred?
Information concerning the PV panels:
- Manufacturer name and model number of the PV panel
- Output power of the panel
- Voc of the panel
- Vmp of the panel
- Imp of the panel
- Number of panels in each string
- If it is necessary to replace the unit, please ship it in the original box.
11.2 System fault
System fault (system faults are mainly caused by system instead of inverter, please check the items as instructed below before replacing inverter).
Error message | Description | Suggestion |
---|---|---|
Residual I High Error: 201 | Leakage current too high | 1.Restart the invert. |
2. If error message still exists, contact Growatt.
---|---|---
PV Voltage High Error: 202| The DC input voltage is exceeding
the maximum tolerable value.| 1. Disconnect the DC switch
immediately.
2. Check the voltage of each PV string with multimerter.
3. If the voltage of PV string is l o w e r t h a n 5 5 0
V, c o n t a c t Growatt.
---|---|---
PV Isolation Low Error: 203| Insulation problem| 1. Check if panel
enclosure ground properly.
2 . Ch e c k i f i n v e r t e r gro u n d properly.
3. Check if the DC breaker gets wet.
4. Check the impedance of PV (+) & PV (-) between ground (must be
more than 25 KΩ or 500 KΩ(VDE 0126)). If the error message
is d i s p l a y e d d e s p i t e t h e a b o v e checking passed,
contact Growatt.
AC V Outrange Error: 300| Utility grid voltage is out of permissible
range.| Please switch off DC switch.
Check AC wiring, especially neutral and ground wire.
Check grid voltage is complied with local grid standard.
Restart inverter, if problem still exist, Contact Growatt.
No AC connection Error: 302| No AC connection| Check AC wiring.
Check the status of AC breaker
PE abnormal Error: 303| Voltage of Neutral and PE above 30V.| 1.Check the
voltage of Neutral and PE.
2.Check AC wiring.
3.Restart inverter, if error message still exisits,contact Manufacturer
AC F Outrange Error: 304| Utility grid frequency out of permissible range.|
Please switch off DC switch.
Che ck AC wi r i ng, e s pe c i a l l y neutral and ground wire.
Check grid frequency is complied with local grid standard. Restart
inverter, if problem still exist, Contact Growatt.
Auto Test Failed Error: 407| Auto test didn’t pass.| Restart inverter,
repeat Auto Test, if problem still exist, contact Growatt.
---|---|---
11.3 Inverter warning
Warning code
|
Meanings
|
Suggestion
---|---|---
Warning202
|
DC SPD function abnormal
|
Warning 203
|
PV1 or PV2 Circuit short
|
Check the PV panel polarity.
Restart the inverter. If the warning still exist, please contact Growatt customer service to replace the POWER board.
Warning204
|
Dryconnect function abnormal
|
Warning 205
|
PV1 or PV2 boost broken
|
Restart the inverter. If the warning still exist, please contact Growatt customer service to replace the power board.
Warning207
|
USB over-current
|
1: Unplug the U disk or monitor.
2: Re-access U disk or monitor after shutdown.
3.If the error message still exists, contact manufacturer.
Warning 401
|
Inverter communicates with Meter abnormal
|
1: Check if the meter is on.
2: Check the inverter and the meter connection is normal .
Warning404
|
EEPROM abnormal
|
Restart the inverter. If the warning still exist, please contact Growatt customer service to replace the M3 board.
Warning405
|
Firmware version is not consistent
|
Uptate the right version firmware
11.4 Inverter fault
Error code
|
Meanings
|
Suggestion
---|---|---
Error: 200
|
AFCI fault
|
Error: 402
|
Output High DCI
|
Restart inverter, if problem still exist, Contact Growatt.
Error: 404
|
Bus sample fault
|
Restart inverter, if problem still exist, Contact Growatt.
Error: 405
|
Relay fault
|
Restart inverter, if problem still exist, Contact Growatt.
Error: 408
|
Over Temperature
|
If the ambient temperature of inverter is lower than 60°C, restart inverter, if error message still exists, contact Growatt.
Error: 409
|
Bus over voltage
|
Restart inverter, if problem still exist, Contact Growatt.
Error: 411
|
DSP communicates with M3 abnormal
|
Restart inverter, if problem still exist, contact Growatt.
Error: 414
|
EEPROM fault.
|
Restart inverter, if problem still exist, Contact Growatt.
Error: 417
|
The data sampled by the DSP and redundant M3 is not the same.
|
Restart inverter, if problem still exist, Contact Growatt.
Error: 420
|
GFCI fault.
|
Restart inverter, if problem still exist, or contact Growatt.
Error: 425
|
AFCI self-test fault
|
Restart inverter, if problem still exist, or contact Growatt.
12. Manufacturer Warranty
Please refer to the warranty card.
13 Decommissioning
13.1 Dismantling the Inverter
1. Disconnect the inverter as described in section8.
2. Remove all connection cables from the inverter.
Danger of burn injuries due to hot enclosure parts!
Wait 20 minutes before disassembling until the housing has cooled down.
3. Screw off all projecting cable glands.
4. Lift the inverter off the bracket and unscrew the bracket screws.
13.2 Packing the Inverter
If possible, always pack the inverter in its original carton and secure it
with tension belts. If it is no longer available, you can also use an
equivalent carton. The box must be capable of being closed completely and made
to support both the weight and the size of the inverter.
13.3 Storing the Inverter
Store the inverter in a dry place where ambient temperatures are always
between -25°C and +60°C.
13.4 Disposing of the Inverter
Do not dispose of faulty inverters or accessories together with household waste. Please accordance with the disposal regulations for electronic waste which apply at the installation site at that time. Ensure that the old unit and, where applicable, any accessories are disposed of in a proper manner
14. Technical Data
14.1 Specification
Model
Specifications
|
MIC 600TL-X
|
MIC 750TL-X
|
MIC 1000TL-X
|
MIC 1500TL-X
---|---|---|---|---
Input data(DC)
Max. recommended PV power(for module STC)
|
840W
|
1050W
|
1400W
|
2100W
Max. DC voltage
|
500V
Start voltage
|
50V
Nominal voltage
|
360V
MPP voltage range
|
50V-500V
MPP voltage range at Full Power
|
55V-450V
|
65V-450V
|
85V-450V
|
130V-450V
No. of MPP trackers
|
1
No. of PV strings per MPP trackers
|
1
Max. input current per MPP trackers
|
13A
Max. short-circuit current per MPP trackers
|
16A
DC overvoltage category
|
Category II
Output data(AC)
AC nominal power
|
600W
|
750W
|
1000W
|
1500W
Max. AC apparent power
|
600VA
|
750VA
|
1000VA
|
1500VA
Nominal AC voltage/range*
|
230V/180~280V
AC grid frequency/range
|
50-60Hz/44-55Hz;54-65Hz
Max. output current
|
2.9A
|
3.6A
|
4.7A
|
7.1A
Inrush current
|
<10A
Max output fault current
|
66A
Max output overload protection
|
10A
|
10A
|
10A
|
10A
Backfeed current
|
0A
P o we r fa c t o r ( @ n o m i n a l power)
|
0.99
Adjustable power factor
|
0.8leading… 0.8lagging
---|---
THDi
|
<3%
AC grid connection type
|
Single phase
AC overvoltage category
|
Category III
Efficiency
Max. efficiency
|
96.5%
|
97.4%
|
97.4%
|
97.4%
Euro-eta
|
96.0%
|
96.5%
|
96.5%
|
97.0%
Protection devices
DC reverse-polarity protection
|
Integrated
DC switch
|
Integrated
DC Surge protection
|
Type III
Insulation resistance monitoring
|
Integrated
AC surge protection
|
Type III
AC short-circuit protection Integrated
Ground fault monitoring
|
Integrated
Grid monitoring
|
Integrated
Anti-islanding protection
|
Integrated
Residual-current monitoring
unit
|
Integrated
General data
Dimensions (W / H / D) in mm
|
274254138
Weight
|
6.0 kg
Operating temperature range
|
–25 °C … +60 °C
Noise emission (typical)
|
≤ 25 dB(A)
Altitude
|
4000m
Internal consumption at night
|
<0.5W
Topology
|
transformerless
Cooling
|
Natural convection
Protection degree
|
IP65
Relative humidity
|
0~100%
DC connection
|
VP-D4/MC4(Optional)
AC connection
|
AC connector
Interfaces
Display
|
OLED+LED
---|---
RS485/USB
|
Integrated
WIFI/GPRS/4G/LAN/ RF
|
Optional
Warranty:5/10 years
|
Yes/ Optional
Model
Specifications
|
MIC 2000TL-X
|
MIC 2500TL-X
|
MIC 3000TL-X
|
MIC 3300TL-X
---|---|---|---|---
Input data(DC)
Max. recommended PV power(for module STC)
|
2800W
|
3500W
|
4200W
|
4290W
Max. DC voltage
|
550V
Start voltage
|
80V
Nominal voltage
|
360V
MPP voltage range
|
65V-550V
MPP voltage range at Full Power
|
170V-450V
|
200V-500V
|
250V-500V
|
270V-500V
No. of MPP trackers
|
1
No. of PV strings per MPP trackers
|
1
Max. input current per MPP trackers
|
13A
Max. short-circuit current per MPP trackers
|
16A
DC overvoltage category
|
Category II
Output data(AC)
AC nominal power
|
2000W
|
2500W
|
3000W
|
3300W
Max. AC apparent power
|
2000VA
|
2500VA
|
3000VA
|
3300VA
Nominal AC voltage/range*
|
230V/180~280V
AC grid frequency/range
|
50-60Hz/44-55Hz;54-65Hz
Max. output current
|
9.5A
|
11.9A
|
14.3A
|
14.3A
Inrush current
|
<10A
Noise emission (typical)
|
≤ 25 dB(A)
---|---
Altitude
|
4000m
Internal consumption at night
|
<0.5W
Topology
|
transformerless
Cooling
|
Natural convection
Protection degree
|
IP65
Relative humidity
|
0~100%
DC connection
|
VP-D4/MC4(Optional)
AC connection
|
AC connector
Interfaces
Display
|
OLED+LED
RS485/USB
|
Integrated
WIFI/GPRS/4G/LAN/ RF
|
Optional
Warranty:5/10 years
|
Yes/ Optional
- The AC Voltage Range may vary depending on specific country grid standard. All specifications are subject to change without notice.
MIC 600TL-X is only available in Germany.
14.2 DC &AC connector info
DC connector
|
VP-D4/ MC4(opt)
---|---
AC connector
|
EN030-2028-1001 VPAC06EP-3S(SC) VPAC06EW-3P(SC4)
14.3 Torque
Enclosure lid screws
|
12kgf.cm
---|---
AC terminal
|
6kgf.cm
Signal terminal
|
4kgf.cm
Safety screw
|
12kgf.cm
Additional ground screws
|
12kgf.cm
Max output fault current
|
66A
---|---
Max output overload protection
|
16A
Backfeed current
|
0A
P o we r fa c t o r ( @ n o m i n a l power)
|
0.99
Adjustable power factor
|
0.8leading… 0.8lagging
THDi
|
<3%
AC grid connection type
|
Single phase
AC overvoltage category
|
Category III
Efficiency
Max. efficiency
|
97.4%
|
97.6%
|
97.6%
|
97.6%
Euro-eta
|
97.0%
|
97.0%
|
97.1%
|
97.1%
Protection devices
DC reverse-polarity protection
|
Integrated
DC switch
|
Integrated
DC Surge protection
|
Type III
Insulation resistance monitoring
|
Integrated
AC surge protection
|
Type III
AC short-circuit protection
|
Integrated
Ground fault monitoring
|
Integrated
Grid monitoring
|
Integrated
Anti-islanding protection
|
Integrated
Residual-current monitoring unit
|
Integrated
General data
Dimensions (W / H / D) in mm
|
274254138
Weight
|
6.0kg
|
6.2kg
Operating temperature range
|
–25 °C … +60 °C
14.4 Accessories
In the following table you will find the optional accessories for your product. If required, you can order these from GROWATT NEW ENERGY TECHNOLOGY CO.,LTD or your dealer.
Name
|
Brief description
---|---
Shine WIFI-X
|
WIFI monitor with USB interface
Shine 4G-X
|
4G monitor with USB interface
Shine Link-X
|
RF monitor with USB interface
Shine LAN-X
|
LAN monitor with USB interface
Shipped to a Growatt service centre for repair, or repaired on-site, or exchanged for a replacement device of equivalent value according to model and age.
The warranty shall not cover transportation costs in connection with the return of defective modules . The cost of the installation or reinstallation of the modules shall also be expressly exclude as are all other related logistical and process costs incurred by all parties in relation to this warranty claim.
Contact 16
If you have technical problems about our products, contact the GROWATT Serviceline. We need the following information in order to provide you with the necessary assistance:
►Inverter type
►Serial number of the inverter
►Event number or display message of the inverter
►Type and number of PV modules connected
►Optional equipment
Shenzhen Growatt New Energy Co., Ltd
4-13/F,Building A,Sino-German(Europe) Industrial Park, Hangcheng Ave,Bao’an District, Shenzhen, China
15. Compliance Certificates
Certificates
With the appropriate settings, the unit will comply with the requirements
specified in the following standards and directives (dated: April/2020):
Model
|
Certificates
---|---
MIC 600-3300TL-X
|
CE , IEC 62109,IEC62116/61727,IEC60068/61683, VDE0126-1-1,EN 50549,C10/11,Inmetro
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>