SM040KAMFA 3 Phase Modular Smart
SCALABLE UPS TO GUARANTEE
ULTIMATE POWER PROTECTION
SM020KAMFA/SM040KAMFA MODULAR UPS (3-PHASE) SERIES
The 3-Phase Modular UPS with N+X redundancy design and hot-swappable
modularity for mission-critical applications
Designed for server room and data center applications, the Modular UPS
(3-Phase) Series adopts double-conversion topology to provide seamless Pure
Sine Wave output. The modular UPSs support vertical addition of power modules,
and horizontal expansion by paralleling multiple systems to achieve even
higher capacity, allowing users to customize base on their business needs. The
N+1 redundancy design and replaceable modularity enhances the system
availability and avoids the risk of single point of failure.
SERIES FEATURES
-
Three-phase Design
-
Online (Double Conversion) UPS Topology
-
ECO Mode
-
High Density Design
-
Vertical Scalability
-
Flexible Installation Design
-
Color LCD with Touch Panel
-
UPS Parallel Expansion
-
Dual Inputs
-
Generator Compatible
-
Pure Sine Wave Output
-
Overload Protection
-
Maintenance Bypass Switch
-
Smart Battery Management (SBM)
-
Emergency Power Off (EPO) Port
-
SNMP/HTTP Remote Management Capability
-
PowerPanel Management Software
PRODUCT CALLOUTS
- Emergency Power OFF (EPO) Button
- LED Status Indicator
- LCD Display Panel
- Function Buttons
- Manual Bypass Breaker
- RS232
- RS485
- SNMP/HTTP Network Slot
- Parallel Board Slot
- Dry Contact
TECHNICAL SPECIFICATIONS
Model Name| SM020KAMFA|
SM040KAMFA
---|---|---
General
Phase| Three Phase
Form Factor| Modular
Energy Saving Technology| Online ECO Mode Efficiency > 97.5%
Hot Swappable Bypass Module| Yes
Normal Mode Efficiency (%)| 93%
Battery Mode Efficiency (%)| 92.5%
Parallel Expansion (Max. Units)| 2
Redundancy Design| Yes
Input
Dual Power Inputs| Yes
Backfeed Protection| Yes
Default Input Voltage Range (Bypass)| -20% ~ 15%
Overload Protection (Bypass)| 110~130% Load for 5 min, 130~150% Load for 1
min, >150% Load for 300ms
Rated Input Current (Bypass)| 55.6A (208V)| 111A (208V)
Default Frequency Tolerance (Bypass)| ± 5%| ± 10%
Configurable Frequency Tolerance (Bypass)| ± 1 %, ± 3 %, ± 5 %| ± 2.5 %, ± 5
%, ± 10 %, ± 20 %
Bypass to Inverter Switch Time (ms)| ≤1
Current Rating of Neutral Cable (Bypass) (A)| 1.7 x Input Rated Current
Input Connector| L1, L2, L3, N, G
Input Frequency (Hz)| 50, 60
Input Frequency Range (Hz)| 40 ~ 70
Nominal Input Voltage (Vac)| Line to Neutral (L-N): 120, 127 Vac, Line to Line
(L-L):208, 220
Input Voltage Range (Vac)| Line to Line (L-L): 124.8 ~ 260 Vac
Synchronization Window (Nominal) (Hz)| ± 2
Synchronization Window (Configurable)| ±0.5Hz ~ ±5Hz
THDI (%)| <4% (Full Linear Load)
Input Power Factor| 0.99
Output
Max Change Rate of Sync Frequency (Default) (Hz/sec)| 1
Change Rate Range of Sync Frequency (Configurable) (Hz/sec)| 0.1~5
Capacity (VA)| 20000| 40000
Capacity (Watts)| 20000| 40000
Neutral Current Capability (%)| 170
Non-Linear Load Capability (%)| 100
Output Connector| L1, L2, L3, N, G
Rated Output Voltage (Vac)| Line to Neutral (L-N):120, 127 Vac, Line to Line
(L-L):208, 220
Output Voltage Range (Vac)| ± 5%
Output Frequency (Hz ± %)| 50, 60
Power Factor| 1
Overload Protection (Line Mode)| 110% Load for 10 min, 125% Load for 1 min,
150% Load for 30 sec, >150% Load for 200ms
Crest Factor| 3 : 1
Harmonic Distortion (Linear Load)| THD<1.5%
Harmonic Distortion (Non-linear Load)| THD<6%
Short Circuit Protection| 300% 200ms
Synchronization Window (Nominal) (Hz)| ± 2
Synchronization Window (Configurable)| ±1Hz ~ ±5Hz
Battery
Compatible Battery Types| VRLA, AGM, Gel
Charger Voltage Tolerance (%)| ≤ 1 %
Recharge Power (%)| Default 10 % (Selectable from 1~20 % x UPS Capacity)
Ripple Current| ≤5% C10
Battery Solution| Extended Battery
Battery Voltage (V)| ±120
Compatible Extended Battery Module (EBM)| Yes
External Battery Quantity| 12V X 20pcs
Management & Communications
LCD Panel| Yes
LCD Types| Color LCD, LCD Touch Panel
LCD Information Display| Operation Type, Power Status, Battery Status, Load
Status, Fault & Warning, Other Information, Event & Log
LCD Setting & Control| Input & Output, Battery Setting, Language
LED Indicators| Power On, Line Mode, Battery Mode, Bypass Mode, Low Battery,
Overload, UPS Fault
Serial Port| RS232 x 1 + RS485 x 1 + Dry Contact x1
Emergency Power Off (EPO) Port| Yes
Power Management Software| PowerPanel Business (Recommended)
SNMP/HTTP Remote Monitoring| Yes – RMCARD205 included
Physical
Ingress Protection| IP20
Physical Size – UPS Module
Dimensions (WxHxD) (mm.)| 485.1 x 607.1 x 774.7| 485.1 x 942.3 x 774.7
Weight (kg.)| 60.69| 80.6
Shipping Dimensions
Dimensions (WxHxD) (mm.)| 632 x 784.4 x 1022.4| 632 x 1124 x 988.1
Weight (kg.)| 91.97| 121.97
Environmental
Operating Temperature (°C)| 0 ~ 40
Operating Temperature Note| Battery life is halved for every 50°F (10°C)
increase above 68°F (20°C)
Operating Relative Humidity (Non-condensing) (%)| 0 ~ 95
Maximum Air Exchange (m3/min)| 3.02
Operating Elevation (feet/meters)| ≤1000, Load Derated 1% per 100m from 1000m
and 2000m
Operating Elevation Note| At <=1,000m above sea level, de-rate power by 1% per
100m between 1,000m and 3,048m
Storage Temperature (°C)| -20 ~ 70
Storage Relative Humidity (Non-condensing) (%)| 0 ~ 95
Audible Noise at 1.0M from Surface of Unit (dBA)| 56
Battery Temperature Compensation| -3mV/ °C
Certifications
Certifications*| FCC Class A, UL1778, NOM, cTUVus, ICES-003
RoHS| Yes
*Certifications may vary according to different regions. Visit www.cyberpower.com for more information.
All specifications are subject to change without notice.
CyberPower and the CyberPower logo are trademarks of Cyber Power Systems,
Inc., and/or affliates, which are registered in many countries and regions.
All other trademarks are the property of their respective owners.
Copyright © 2022 Cyber Power Systems, Inc.
All rights reserved.
www.cyberpower.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>