sauermann KT 50 Mini Temperature Data Logger User Guide

June 16, 2024
sauermann

sauermann KT 50 Mini Temperature Data Logger

Product Information

Specifications

  • Model: KT 50 – KH 50
  • Languages: English, French, Spanish, Chinese
  • Functions: Data logger for HVAC – Temperature, Humidity
  • Display: Indicates dataset status, maximum and minimum values, alarm action type, and battery status
  • Dimensions: 40mm x 21.5mm
  • Connections: PC connection input and Micro-USB connector
  • Standard: EN12830 certified for food industry requirements
  • Recorder Function: Records values ​​at predefined intervals or operates continuously with loop recording
  • Mounting: Anti-theft necklace, batteries cover, magnetic fixing, locking sign of the batteries cover
  • Battery Replacement: Replace batteries when indicated on the screen and flashing LEDs
  • Maintenance: Avoid aggressive solvents and protect from cleaning products containing formalin
  • Precautions for Use: Always use the device as intended and  within specified parameters

Frequently Asked Questions

  • Q: Where can I find the customer service portal?
  • Q: What is the address of Sauermann Industries?
    • A: The address of Sauermann Industries is ZA Bernard Moulinet 24700 – Montpon – France. For more information, visit sauermanngroup.com

KISTOCK Data logger For HVAC – Temperature, Humidity

Specifications

Operating temperature, protection of the instruments and information about storage and the battery

  • *Operating temperature:** KT 50: from -40 to 70 °C / KH 50: from -20 to 70 °C
  • KT 50: IP65 / KH 50: IP20
  • Storage temperature: -20 to 50 °C
  • Battery power supply: 2 x CR2032 (lithium 3 V)

Display

  • °C: Temperature in degrees Celsius
  • °F: Temperature in degrees Fahrenheit
  • %RH: Relative humidity (KH 50)
  1. END: Dataset is finished
  2. REC: Records the values at the moment when this indicator appears / flashing: the dataset has not yet started
  3. FULL: Slow flashing: dataset is taking between 80 and 90% of storage capacity
    • Fast flashing: dataset is taking 90-100% of storage capacity
    • Constant: storage capacity filled up
  4. MAX/MIN: Displayed values correspond to maximum and minimum values of the channels
  5. Alarm action type: rising or falling action
  6. Flashing on the screen + flashing of LEDs:   means that the battery must be changed

Dimensions And Connections

Dimensions (mm)

sauermann-KT-50-Mini-Temperature-Data-Logger-FIG-4

Connections

sauermann-KT-50-Mini-Temperature-Data-Logger-FIG-5

EN12830 Standard

KT 50 models dedicated to food industry, meet with requirements of EN 12830 norm. This certification is required for transportation, storage and distribution of refrigerated, frozen and deep-frozen food, and ice cream Certification is done by an independent laboratory, COFRAC accredited.

  • The screen can be hard to read, and its display speed often slows down at temperatures lower than 0 °C. This has no effect on the accuracy of measurements.

Recorder fuction

The KISTOCK allows to record the values measured instantaneously, it records the values according to a predefined interval.
On the other hand, it is possible to operate continuously the KISTOCK thanks to a loop recording.

3 types of dataset start

The measurement dataset can be launched:

  • With a delayed start (with predefined date and time)
  • With the software
  • With OK key

6 types of dataset stop

You can stop your dataset:

  • According to a date and time (if it was started the same way)
  • According to a recording duration
  • According to a predefined number of recording points
  • If the storage capacity of the memory is full
  • With “Stop” option of the software
  • By holding “OK” key during about 5 seconds, if this function has been previously activated by the software.

Mounting

KISTOCK can be mounted in different ways, you can also move it or install it very easily.

  • Magnetic mounting (see photo)
  1. Necklace for anti-theft
  2. Batteries cover
  3. Magnetic fixing
  4. Locking sign of the batteries cover

Replace the batteries

With 500 days* battery life, KISTOCK ensure long-term measurements. To change the batteries:

  • Unlock the battery cover with a screwdriver or a coin.
  • Put the 2 batteries superimposing them (3 V CR2032 button batteries) with the + pole visible.
  • Put back the batteries cover: the sign of the batteries cover must be placed in front of the opened padlock.
  • Turn right the batteries cover: the sign on the batteries cover must be placed in front of the closed padlock.

Accessories

Please refer to the data sheet to get more information about available accessories.

Maintenance

  • please avoid any aggressive solvent. Please protect the device from any cleaning product containing formalin, that may be used for cleaning rooms or ducts.

Precautions for use

  • please always use the device in accordance with its intended use and within parameters described in the technical features in order not to compromise the protection ensured by the device.

*For a KT 50. Non-contractual value. Based on 1 measurement each 15 minutes at 25 °C. A correct operation of the device and the storage conditions must be respected.

More Information

Download the data sheet

sauermann-KT-50-Mini-Temperature-Data-Logger-FIG-7

Customer service portal Portail service clients

Use our Customer service portal to contact us: http://kimo- en.custhelp.com

Sauermann Industries

QSG – KT 50 – KH 50 – 27/11/2023 – Non-contractual document – We reserve the right to modify the characteristics of our products without prior notice.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals