elsner 71320 Thermostaat Voor Fan Instruction Manual

June 16, 2024
elsner

elsner 71320 Thermostaat Voor Fan

Product Information

Specifications

  • Model: KNX eTR 102 FC
  • Colour Options: 71320 (white), 71322 (black)
  • Power Supply: 230 V
  • KNX Interface: SELV (Safety Extra Low Voltage)

Scope of Delivery

The package includes the following items:

  • KNX eTR 102 FC unit
  • Mounting materials

Installation

Caution: Electrical Voltage! Installation and operation should only be carried out by a qualified electrician.

The device should only be used as a fixed installation and after completing all installation and commissioning work, and only in the intended environment. Any misuse, modifications to the device or failure to follow these instructions will void any warranty rights.

Product Usage Instructions

Front View

  1. Blower levels area with 3 touch surfaces
  2. Temperature area with 2 touch surfaces and temperature display
  3. Mode area with 2 touch areas:

A: Switch between automatic/manual mode
LED on: Automatic mode active
On/Off: Temperature controller on/off

FAQ

  • Q: Where can I find the manual and KNX application?
  • A: The manual and KNX application can be found at www.elsner-elektronik.de.
  • Q: What precautions should I take when using this device?
  • A: Please ensure that the installation and operation are carried out by a qualified electrician. Use the device only as a fixed installation and in the intended environment.
  • Q: What should I do if I encounter any issues with the device?
  • A: If you experience any issues, refer to the user manual for troubleshooting steps. If the problem persists, contact customer support for further assistance.

Safety and operating instructions

CAUTION! Live voltage!
Installation and commissioning may only be handled by an electrician.

  • Only operate devices if they are free from damage.
  • Comply with country-specific standards, directives, specifications and provisions for electrical installation.
  • Switch off the voltage to the system during installation.
  • Observe the regulations and standards applicable to SELV circuits during installation and wiring of the KNX connection.
  • The device may only be operated as a fixed-site installation when assembled and after the conclusion of all installation and operational start-up tasks and only in the surroundings designated for it.
  • Improper use, modifications to the device or failure to observe this manual will void any warranty and guarantee claims.

Description

Room Temperature Controller for Fan Coil A/C

  • The room temperature controller for the KNX building bus system automatically controls air conditioning with fan coil units. It has touch-sensitive buttons with which the room climate settings can be manually readjusted.
  • The fan speed (1-3), the setpoint temperature (value, touch buttons +/-) and the mode (automatic on/off, air conditioning on/off) can be set. LEDs show the current settings.
  • The brightness and switch-off behaviour of the LEDs can be adjusted.
  • A temperature sensor is integrated in the unit, which can be used for control.
  • To obtain a mixed value, the unit can receive another measured value via the bus and process it with its value to obtain an overall temperature.
  • The automatic room climate control includes a PI controller for heating and cooling (one- or two-stage).
  • This control contains parameters specifically for air conditioning with fan coil systems (systems with fans).
  • The room temperature controller can also be used as an extension unit, i.e.
  • it transmits the manual inputs to another control device in the KNX system, which then takes over the control.
  • Communication objects can be linked in integrated AND and OR logic gates.

Scope of delivery

  • Push button with mounting
  • 4 screw anchors 4 × 20 mm, 4 flat head screws 3 × 25 mm
  • KNX plug-in terminal

Installation

  • The Room Temperature Controller is made for wall mounting.
  • The device can be mounted directly on plaster or in a device socket according to DIN EN IEC 60670-1/DIN 49073 and other sockets, e.g. Swiss inlet box.
  • If the device is installed in a socket, this socket must not contain cabling with 230 V.
  • To avoid falsifying the temperature value, use a wind-proof socket and also seal the inlet pipes against draughts.
  • When selecting an installation location, ensure that the measurement results are affected as little as possible by external influences. Possible sources of interference include:
    • Direct sunlight
    • Warming or cooling of the building structure on which the sensor is mounted, e.g. due to sunlight, heating or cold water pipes
    • Drafts from windows and doors
    • Connection lines and ducts which lead from warmer or colder areas to the sensor
  • Permanent measurement variations can be corrected in the ETS (offset).

Fig. 3 Front view

  1. Blower levels“ area with 3 touch surfaces
  2. Temperature“ area with 2 touch surfaces and temperature display
  3. Mode“ area with 2 touch areas
    A: Switch between automatic/ manual mode
    LED on: Automatic active
    On/Off: Temperature controller on/off
    LED on: controller active

elsner-71320-Thermostaat-Voor-Fan-FIG-4

Fig. 4 Back view with mounting
4/5 Screw holes. Fastening with 2 screws in opposite holes is sufficient.
For wall mounting, use a fixing material suitable for the ground!

Fig. 5 Back view without mounting

  • KNX plug-in terminal +/- for connection when mounted on a socket
  • Programming LED
  • Programming button (recessed)
  • Spring-loaded terminals KNX bus for mounting directly on the wall
  • Temperature sensor

Fig. 6 Open/close device

  • Remove the front panel from the mounting: Move the front panel a few millimetres upwards to release the lock. The two parts can be easily separated.
  • Mount the front panel on the mounting:
  • Place the front panel slightly above the centre position so that it hooks in and slides it down.

elsner-71320-Thermostaat-Voor-Fan-FIG-7

Fig. 7, 8 Installation directly on the wall

  • Remove the red-black KNX plug-in terminal, it is not required.
  • Connect the bus +/- connecting wires to the spring-loaded terminals on the front panel.
  • The wires are pushed into the connection openings.
  • To pull it out, press the spring down, e.g. with a screwdriver.

Fig. 9 Installation on a socket

  • If there is a cavity behind the device, e.g. when using a socket, you can use the red/black KNX plug-in terminal for connection.

Maintenance

  • Fingerprints on the glass panel are best removed with a cloth moistened with water or a microfiber cloth.
  • Do not use an abrasive cleaning agent or aggressive cleansing agents.

Disposal
After use, the device must be disposed of under the legal regulations. Do not dispose of it with household waste!
Conformity
The product conforms to the conditions of the EU Directives.

General

  • Casing Genuine glass, plastic:
  • Colours (similar): RAL 9003 (white) and RAL 9005 (black)
  • Degree of protection: IP20
  • Size (W × H): 81.5 mm x 81.5 mm
  • Mounting depth: 12 mm
  • Total weight: ≈ 65 g
  • Ambient temperature: -5…+45 °C
  • Ambient humidity (RH) (non-condensing): 5…95 %
  • Storage temperature: -25…+70 °C
  • Overvoltage category: III
  • Pollution degree: 2

KNX bus

  • Medium: TP1-256
  • Configuration mode: S-Mode
  • Group addresses max: 254
  • Assignments max: 254
  • Communication objects: 82
  • Nominal voltage: 30 V SELV
  • Power consumption: ≤ 25 mA
  • Connection KNX plug-in terminal Conductor diameter Stripping length: 0.6…0.8 mm s 5 mm
  • Connection spring-loaded terminals Conductor cross-section solid and fine-stranded conductors fine-stranded conductors with ferry-less Stripping length: 0.2…0.75 mm² 0.25…0.34 mm² 7…9 mm
  • Duration after bus voltage restoration until data is received: ≈ 5 s

Sensor

  • Temperatur-Messbereich: -5…+60 °C

CONTACT

  • Elsner Elektronik GmbH
  • Sohlengrund 16
  • 75395 Ostelsheim
  • Deutschland
  • www.elsner-elektronik.de.
  • Service: +49 (0) 7033 / 30945-250

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>