Intelligent Power Supply KNX bus/Auxiliary Voltage
Instruction Manual

Intelligent Power Supply KNX bus/Auxiliary Voltage

elsner Intelligent Power Supply KNX bus Auxiliary Voltage -
fig1

Device structure

  1. Input voltage VIN

  2. Bus voltage VBUS

  3. Telegram traffic

  4. Output current IOUT
    green: IOUT < 640 mA
    orange: IOUT is 640…900 mA
    red: IOUT > 900 mA (Overload) 5 Temperature
    green: Temperature is 0…75 °C
    red: Temp. is out of this range

  5. KNX bus reset red: Restart of the KNX bus line is running

  6. Programming LED red: Programming Mode active
    A Supply voltage terminals
    B Reset button
    C Programming button
    D Aux output connector
    E KNX TP connector

Intelligent Power Supply KNX bus/Auxiliary Voltage
Installation instructions

Safety and operating instructions

Product manual and product file (ETS 5 application) can be downloaded from the Elsner Elektronik website on www.elsner-elektronik.de in the “Service” menu.
Installation, testing, operational start-up and troubleshooting should only be performed by an authorised electrician.
DANGER!
Risk to life from live voltage (mains voltage)!
There are unprotected live components inside the device.

  • Inspect the device for damage before installation. Only put undamaged devices into operation.
  • Comply with the locally applicable directives, regulations and provisions for electrical installation.
  • Immediately take the device or system out of service and secure it against unintentional switchon if risk-free operation is no longer guaranteed.

Use the device exclusively for building automation and observe the operating instructions. Improper use, modifications to the device or failure to observe the operating instructions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition and after conclusion of all installation and operational start-up tasks, and only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions.

Description

The intelligent Power Supply KNX PS640-IP 2U with extensive diagnostic and alarm functionality powers one line of a KNX system with 30 V DC and has an additional unchoked voltage output to provide auxiliary power. Both outputs are overload-proof and short circuit protected. LEDs indicate the state of the power supply and the KNX TP line.
The KNX TP line can be reset via object and via push-button press. For diagnostics, input state, KNX bus voltage, output current, device temperature and times of operation (total/since last startup) are monitored. Alarms inform about measurement values leaving the normal working range or the configured threshold range. Up to eight different alarms can be pre-defined.
KNX PS640-IP 2U is able to send info telegrams on request, periodically and after certain events. Details (number/duration) on output failures like short circuits, overloads and over-threshold events are accessible. Info telegrams also inform on returning to normal working condition after device startup, after a KNX bus restart and after a short circuit. Heartbeat telegrams indicate proper functioning.
Scope of delivery

  • Power Supply System
  • KNX terminal and auxiliary voltage terminal (white/yellow)

Buttons and LEDs description

Input voltage VIN [off] Vin is 195…265 V AC
Input voltage VIN red Vim is out of this range
Bus voltage VBUS green VBUS is 28…31 V DC
Bus voltage VBUS red VBUS is out of this range
Telegram traffic green (blinking) Telegram traffic < 80 %
Telegram traffic red Telegram traffic > 80 %

Installation

Installation location and preparation

  • Installation only in dry locations. Protect the device from moisture, dirt and damage
  • Accessibility of the device for operation and visual inspection must be provided
  • The housing of the device must not be opened
  • For mounting use an appropriate equipment according to IEC60715
  • Installation only in distribution boards and enclosed housings. Installation only on a 35 mm DIN rail (TH35). Terminals and metal parts under current must be completely covered. It must be not possible to remove the cover without aid of a tool. Contact protection must be provided through the control cabinet

Connection
Connect the KNX bus line as for common KNX bus connections with a KNX bus cable, to be stripped and plugged into the KNX TP connector. Do not damage electrical insulations when connecting

Maintenance

The device needs no maintenance. If necessary, the device can be cleaned with a dry cloth

Disposal

After use, the device must be disposed of or recycled in accordance with the legal regulations. Do not dispose of it with the household waste!

Technical data

The product conforms to the conditions of the EU Directives.

Power input:

Mains voltage| 230V ∼±15%, 50Hz
Leakage loss (open-circuited)| 1.2 W
Leakage loss (normal)| 4.7 W
Power consumption (normal)| 23 W
Power consumpt. (max., overload)| 42 W
Housing:|
Plastic PA66 housing, Housing colour white| RAL 9018
Dimensions (H × W × D), 2 modules at 18 mm| 94 mm × 36 mm × 71 mm
Mounting (IEC60715) 35 mm top-hat rail| (TH35)
Mains voltage connection Screw terminals (max. torque 0.4 Nm)| 0.3…2.5 mm²
KNX bus connection KNX TP connector (red/black), screwless, for single-core cable| Ø 0.6…0.8 mm
AUX output connection KNX TP connector (white/yellow), screwless, for single- core cable| Ø 0.6…0.8 mm
Weight| 185 g
Environmental conditions:
Operating temperature| -5…+45 °C
Storage temperature| -20…+70 °C
Ambient humidity (non-condensing)| 5…93 %
Power output:
KNX output voltage| 28…31 V  SELV
AUX output voltage| 28…31 V   SELV
Rated current| 640 mA
Maximum current (total output)| 1.2 A
Mains failure bridging time| > 100 ms
Efficiency at nominal load| 82%
Disconnection time after failure| 10 s
Electrical safety:
Pollution degree (IEC60664)| 2
Protection class (IEC61140)| II
Overvoltage category (IEC60664)| III

08.06.2021
Technical changes and errors excepted.
Elsner Elektronik GmbH
www.elsner-elektronik.de
Service: +49 (0) 7033 / 30945-250

Documents / Resources

| elsner Intelligent Power Supply KNX bus/Auxiliary Voltage [pdf] Instruction Manual
Intelligent Power Supply KNX Bus Auxiliary Voltage, Intelligent Power Supply KNX Bus, Auxiliary Voltage, Intelligent Power Supply, Power Supply, KNX Bus Power Supply, Auxiliary Voltage Power Supply
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals