Dwyer TID Series Temperature-Process Indicator Instruction Manual
- June 4, 2024
- Dwyer
Table of Contents
TID Series Temperature-Process Indicator
Instruction Manual
Specifications – Installation and Operating Instructions
The affordable Series TID allows users to monitor temperature or a process
value.
Temperature ranges are available from -58 to 302°F using one of our PTC or NTC
thermistors. Process values can be displayed from -999 to 999 counts using a
4-20 mA signal from one of our various transmitters. The process indicator has
an adjustable span and zeroes on the 4-20 mA models.
Installation
Note: The unit must be mounted away from vibration, impacts, water, and
corrosive gases.
- Cut hole in panel 2.80 x 1.14 in (71 x 29 mm).
- Apply silicone (or rubber gasket) around the perimeter of the hole to prevent leakage.
- Insert the unit into the hole of the panel.
- Slide removable fitting clips onto the unit from the back until secure to the panel.
- Remove the back cover to the wire unit.
- A wiring diagram is displayed on the top of the unit.
SPECIFICATIONS
Range: -58 to 302°F (thermistor); -999 to 999 counts (4-20 mA).
Input: PTC/NTC thermistor or 4-20 mA.
Power Requirements: 115 VAC, 230 VAC, 24 VAC/DC.
Accuracy: > 1%.
Display: 3-digits; red, green or blue display.
Resolution: 1° or 0.1 count.
Front Panel Rating: IP64 (NEMA 3R).
Output: 5/12 VDC (model dependent).
Weight: 2.3 oz (65 g).
Compliance: CE, cURus.
LIST OF PARAMETERS (CURRENT MODELS ONLY)
| Description| Units| Range
Lc
He
P1
H5| Value for 4 mA input
Value for 20 mA input
Decimal point
Access code| Range
Range
Selection Numeric| -999 to 999
-999 to 999
No/yes
0 to 99
Parameter Descriptions
Lc = Value for 4 mA input
If P1 = Yes the value is displayed with a decimal point
Hc = Value for 20 mA input
If P1 = Yes the value is displayed with a decimal point
P1 = Decimal Point
If P1= Yes LC, Hc, and probe values are displayed with a decimal point
H5 = Access code to parameters
Parameter Programming
- Press SET for 8 seconds. The Access code value 00 is shown on the display (the unit comes with a code set at 00 from the factory).
- With the UP and DOWN arrows, code can be set to user needs.
- Press SET to enter the code. If the code is correct, the first parameter label is shown on the display (Lc).
- Move to the desired parameter with the UP and DOWN arrow keys.
- Press SET to view the value on the display.
- The value can be modified with the UP and DOWN arrows.
- Press ENTER to enter the value and exit.
- Repeat until all necessary parameters are modified.
- Press SET and DOWN at the same time to quit programming or wait one minute and the display will automatically exit programming mode.
Note: The keyboard code can be reset to ZERO by turning off the controller and turning it on again while keeping the SET key depressed.
Display Message
The display normally shows the temperature of the probe. In case of error the
following messages are shown:
- Er = Memory error
- 00 = Open probe
- — = Short circuit probe