RAB EZPAN 1X4 LED Flat Panel Battery Back-Up
Product Information
Specifications
- Model: EZPAN 1X4, EZPAN 2×2, EZPAN 2×4
- Application: Indoor recessed ceiling
- Mounting: Suitable for 9/16 or 15/16 flat tee-grid in insulated and non-insulated ceilings
- Safety Rating: Suitable for damp locations
Product Usage Instructions
Installation Instructions
RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and the hazards involved.
Safety Instructions
- Make certain power is OFF before installing or maintaining fixture. No user serviceable parts inside.
- Risk of fire or electric shock. Suitable for damp locations.
- Suitable for 9/16 or 15/16 flat tee-grid in both insulated ceilings and non-insulated ceilings. Access above ceiling required.
- Do not handle energized fixture when hands are wet, when standing on wet or damp surfaces, or in water.
- Fixture to be independently supported to building structure.
Recessed Ceiling Mounting
- Firmly bend the pre-installed Grid Clips up and out.
- Rotate and slide the Fixture as required to fit through the Tee-Grid Bar and place it as indicated by the directional arrow.
- Secure the Fixture to the Tee-Grid Bar.
- Support the Fixture to the building structure by Support Wires (supplied by others) through the Grid Clip Hole.
- Make sure that the orientation of the Splice Box and Access Plate faces an accessible tile to make electrical splices.
- Loosen Access Plate Screw and remove the Access Plate. Knock out appropriate Conduit Knockouts on the Access Plate to route input conduit.
- Connect wires as shown in wiring diagram. Push all wires back into the Splice Box. Use appropriate UL approved wire connectors as required by code to complete wiring. Be careful not to pinch wires.
FAQ
Q: Can this fixture be used in outdoor applications?
A: No, this fixture is suitable only for indoor recessed ceiling applications.
Q: What type of ceiling grids is this fixture compatible with?
A: This fixture is compatible with 9/16 or 15/16 flat tee-grid in both insulated and non-insulated ceilings.
Q: Is above ceiling access required for installation?
A: Yes, above ceiling access is required for installation.
Q: How should I support the fixture to the building structure?
A: The fixture should be independently supported to the building structure using support wires (supplied by others) through the Grid Clip Hole.
INSTALLATION INSTRUCTIONS
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or
- email: marketing@rablighting.com
Model
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and
all applicable local codes. Proper grounding is required for safety. THIS
PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE
BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND
THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining
fixture. No user serviceable parts inside.
SAFETY INSTRUCTIONS
- WARNING: Risk of fire or electric shock. Suitable for damp locations.
- WARNING: Suitable for 9/16” or 15/16” flat tee-grid in both insulated ceilings and non-insulated ceilings. Access above ceiling required. WARNING: Do not handle energized fixture when hands are wet, when standing on wet or damp surfaces, or in water.
- WARNING: Vapor barrier must be suitable for 90° C.
- WARNING : Fixture to be independently supported to building structure.
RECESSED CEILING MOUNTING
The fixture is suitable only for INDOOR RECESSED CEILING application. Above ceiling access required. To mount in an insulated or non-insulated ceiling – 9/16” or 15/16” exposed Flat Tee Grid Ceiling follow the steps below.
- Firmly bend the pre-installed Grid Clips (up and out as shown in Fig. 1).
- Rotate and slide the Fixture as required to fit through the Tee-Grid Bar and place it as indicated by the directional arrow as shown in Fig. 2. Secure the Fixture to the Tee-Grid Bar.
- Support wires are required by Installation Codes. Support the Fixture to the building structure by Support Wires (supplied by others) through the Grid Clip Hole as shown in Fig. 3.
- Make sure that the orientation of the Splice Box and Access Plate faces an accessible tile to make electrical splices.
- Loosen Access Plate Screw and remove the Access Plate. Knock out appropriate Conduit Knockouts on the Access Plate to route input conduit. Use appropriate conduit connectors as required by code (Fig. 4).
- Connect wires as shown in wiring diagram. Push all wires back into the Splice Box. Use appropriate UL approved wire connectors as required by code to complete wiring. Be careful not to pinch wires. WARNING: To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
- Replace Access Plate and tighten Access Plate Screw.
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V through 277V, 50 or 60 Hz. For 0-10V dimming follow the wiring directions as shown in Fig 5
- Connect the Black fixture lead to the LINE supply lead.
- Connect the White fixture lead to the COMMON supply lead.
- Connect the GROUND wire from fixture to supply ground
- Connect the purple fixture lead to the (V+) DIM lead.
- Connect the pink fixture lead to the (V-) DIM lead
- Cap the yellow fixture lead, if present. Do NOT connect. NOTE: Do not connect DIM V+ (purple)/ DIM V- (pink) to line voltage or supply ground.
LIGHTCLOUD® ENABLED MODELS
Lightcloud-enabled models require a Lightcloud Gateway and should be placed within 100’ of another Lightcloud device. Support at 1.844.LIGHTCLOUD or logging into the Web App at control.lightcloud.com.
LED Indicator:
- Blinking Red = Looking for a network
- Solid Green = Connected to network
NOTE: (see Fig. 6)
To test, double-click the Reset Button for on/off. Double-click Reset Button
and hold for dimming cycles. Hold Reset Button for 10 seconds to reset the
network.
LIGHTCLOUD WIRING
WARNING: Lightcloud-enabled fixtures require constant power and should
not be placed down circuit from any switching devices.
Universal voltage driver permits operation at 120V through 277V, 50 or 60 Hz.
Follow the wiring directions as shown in Fig 7.
- Connect the Black fixture lead to the LINE supply lead.
- Connect the White fixture lead to the COMMON supply lead.
- Connect the GROUND wire from fixture to supply ground.
- LIGHTCLOUD-enabled models DO NOT have external 0-10V dimming wires.
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
CLEANING
CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized.
- Clean polystyrene lens & fixture with non-abrasive cleaning solution.
- Do not open fixture to clean the LEDs. Do not touch the LEDs.
TROUBLESHOOTING
- Check the line voltage at fixture. Refer to wiring directions.
- Is the fixture grounded properly?
BATTERY BACKUP MODELS
WIRING
CAUTION: THIS IS A BATTERY BACKUP FIXTURE for standby lighting. Voltage
could be present in Battery. To prevent high voltage from being present on
output leads, inverter connector must be open. Do not join inverter connector
until installation is complete and AC power is supplied to the emergency
ballast.
Note: Make sure that the necessary branch circuit wiring is available. An
unswitched AC source of power is required. The emergency ballast must be fed
from the same branch circuit as the AC ballast (Fig. 8).
Do not use any supply voltage other than 120V-277V.
- Connect the UNSWITCHED black fixture lead to the HOT supply lead.
- If using an unswitched circuit, connect both black leads together.
- If using a switched circuit, connect SWITCHED black lead to the switch.
- Connect the COMMON fixture lead to the COMMON supply lead.
- For 0-10V Dimming, connect DIM (+) purple lead and DIM (-) pink lead to 0-10V dimmer connections on the driver.
- Connect the GROUND wire from fixture to supply ground.
- All unused leads must be capped and insulated.
- After installation is complete, supply AC power to the emergency ballast and join the inverter connector.
- At this point, power should be connected to both the AC ballast and the emergency ballast, the Charging Indicator Light should illuminate indicating the battery is charging.
- A short duration discharge test may be conducted after the emergency ballast has been charging for one hour. Charge for 24 hours before conducting a 90-minute discharge test. Refer to OPERATION.
OPERATION
- When AC power is applied, the charging indicator light is illuminated, indicating that the battery is being charged.
- When power fails, the emergency driver automatically switches to emergency power (internal battery), operating at reduced output. The emergency driver supplies 12W of power in emergency mode for a minimum of 90 minutes.
- When AC power is restored, the emergency driver automatically returns to charging mode.
MAINTENANCE
Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:
- Visually inspect the charging indicator light monthly. It should be illuminated.
- Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
- Conduct a 90-minute discharge test once a year. Fixture would provide reduced illumination for a minimum of 90 minutes.
Battery Backup Setting
PRODUCT| WATTAGE| DIP SWITCH POSITION (12W)
EZPAN 1X4| 17|
1 = O
2 = On
EZPAN1X4| 30, 40
EZPAN 2X2| 17
EZPAN 2X2| 30, 40
EZPAN 2X4| 30, 40, 50