FIREANGEL FA6111 Smoke Alarm User Manual

June 15, 2024
FireAngel

**FIREANGEL FA6111 Smoke Alarm User Manual

**

Optical smoke alarms FA6111, FA6115 and FA6120 are suitable for detecting slow shouldering fires. Like other smoke alarms, they can be subject to nuisance alarms from steam and should not be placed near bathrooms.

For the earliest warning, we recommend smoke and heat alarms are fitted in all rooms where the temperature is between 4°C and 38°C. Prolonged exposure to temperatures outside those stated above will reduce product life.

Heat alarm FA6215 is specified for Class A1 detection. Your heat alarm will sound a warning when the ambient temperature in a room is between 54°C and 65°C. For the best protection, heat alarms should always be installed as part of a complete fire protection system that includes smoke alarms.

Check with local building and fire regulations for your property, to ensure compliance.

The original English version of the manual, from which these translations were taken, has been independently approved. In case of discrepancy with translated parts, Firangi Safety Technology Limited confirms that the English guide is true and correct.

Note : This user manual is also available in large text and other formats. Please email: internationalsupport@fireangeltech.com for further information

POSITIONING

in which room should the alarm be installed? Smoke alarms FA6111, FA6115 and FA6120 are suitable for the landing, hallway, bedroom, living roman dining room
Heat alarm FA6215 is suitable for the kitchen, garage and loft
It is advisable to place an FA6111 Escape Light Alarm in a corridor along the escape route to light your path to safety.
Your smoke/heat alarm is suitable for use in mobile homes and caravans. This smoke/heat alarm is not intended for any non-residential, commercial or industrial application, nor for any other purpose than described

Where in the room should the alarm be installed?

Smoke alarms should be sited at least 300mm from light fittings and walls. Ideally as central as possible in the room
Smoke alarms should be positioned at no more than 600mm vertically below the highest point in the room. If positioning your smoke alarm on the wall, the top of the detection element must be between 150mm and 300mm below the ceiling, and at least 300mm from any neighboring wall
Install your heat alarm at a distance no greater than 5.3m from the farthest wall, no greater than 5.3m from a door to any room in which a fire might start and no greater than 5.3m from the next heat or smoke alarm. Heat alarms should be sited at least 300mm from light fittings and walls. Heat alarms should not be fitted on a wall.
Locations of alarms must be compliant with either BS 5839: Part 6 or relevant Buildingulations if in any doubt

INSTALLATION

Step 1:

FA6115 and FA6215 Replaceable battery alarms only

If the alarm requires AA batteries, remove the base plate from the alarm by twisting it anti-clockwise and insert the batteries (matching + to +). This will activate the alarm.
Replaceable battery
Note : For FA6120, the alarm must be installed on the baseplate to activate the alarm. For FA6111, FA6115 and FA6215, installing the batteries activates the alarm.

After activation, the red LED on the front of the alarm should flash once every 40 seconds (approx.) to show that the alarm is active.

The alarm test sound pattern will be: 3 beeps followed by a 1.5 second pause, then 3 beeps. The LED will flash once per second.

SMOKE ALARMS FA6111, FA6115 & FA6120

HEAT ALARM FA6215

Step 2

Baseplate Installation – all alarms: FA6111, FA6115, FA6215 and FA6120

  1. Drill holes into the ceiling (or wall) using the template below and secure the baseplate using the screws provided.

  2. Push and twist the alarm clockwise onto the baseplate

  3. Press the Test / button. The alarm will sound a reduced alarm volume. The FA6111 will also shine the escape light. To hear the alarm at full volume* double press the Test / button.

MAINTENANCE

  1. Test the alarm monthly (or as often as required by local authorities) Residents can
    test the alarm by pressing the central Test / button.
    MAINTENANCE

  2. . Vacuum your alarm every 3 months.

  3. Do not use cleaners or solvents

  4. Do not paint the alarm

  5. Replace the alarm every 10 years.
    MAINTENANCE

Do not use any other test method except the process described in this manual.

Do not tamper with the alarm as this could cause electric shock or malfunction.

LOW BATTERY WARNING

When the alarm battery is low, the alarm will ‘chirp’ and the Red operational LED will flash once every 40 seconds.

For FA6111, FA6115 and FA6215 Replaceable Battery Alarms
Battery Alarms

  1. Carefully turn the alarm anti-clockwise to remove the device from the baseplate

  2. Replace the battery immediately (within 30 days)

  3. Always test the alarm after replacing the batteries

FA6111, FA6115 or FA6215 alarms require 2 x AA batteries. Under normal use, the battery should last approximately three years for FA6111 and five years for FA6115 and FA6215. Use of a battery other than those recommended here may have a detrimental effect on the alarm: Energizer E91 Alkaline, Duracell AA MN1500 Alkaline, GP AA GN15A Alkaline, Energizer AA L91 Lithium.

For FA6120 Sealed Battery Alarms

  1. Carefully turn the alarm anticlockwise to remove the device from the baseplate.

  2. Replace the alarm immediately * (within 30 days).
    Carefully turn

    • If your alarm is still under warranty, contact Technical Support.

FAULT INDICATION

  1. if there is a fault, the alarm will ‘chirp’ twice and flash twice every 40 seconds.
    Replace the alarm

  2. If the alarm is still within warranty, contact Technical Support
    Technical Support

  3. If your alarm is no longer under warranty, replace immediately
    replace immediately.

System Status Indicators: If there is a fault your alarm will display the following fault indication patterns.

| Audible pattern| LED pattern| Action required
---|---|---|---
Low battery| 1 beep/40 seconds| 1 flash/40 seconds| FA6111, FA6115, FA6215: Replace the batteriesFA6120: Replace alarm within 30 days
Fault| 1 double beep/40 seconds| 1 double flash/40 seconds| May not signal alert – replace alarm immediately
End of Life| 1 triple beep/40 seconds| 1 triple flash/40 seconds| May not signal alert – replace alarm immediately

TROUBLESHOOTING GUIDE

If your smoke/heat alarm does not sound during testing:|

  • Check that your device is activated.
  • If testing after first installation, allow a few seconds for the alarm to settle.
  • To hear the alarm at full volume double press the Test /    button.
  • If the alarm has been silenced and is in low sensitivity mode it may not test. Wait 15 minutes then try again.
  • If the alarm is FA6111, FA6115 or FA6215, replace the battery.

---|---
If your smoke/heat alarm activates in the event of a known false alarm:|

  • Check the location of your device.
  • Clean the alarm.

If your smoke/heat alarm sounds unusual or ‘chirps’ intermittently:|

  • Check the location of your device.
  • Clean the alarm.
  • Check that your device is definitely the source of the chirping; make sure the noise isn’t coming from another alarm.

If you experience frequent unwanted alarms:|

  • Check the location of your device.
  • Clean the alarm.

If a fault or End of Life is indicated:|

  • Replace the alarm immediately.

If the light on the FA6111 fails to illuminate:|

  •  Check if the device is still within its warranty. If so, contact Technical Support, otherwise, replace the alarm immediately.

SILENCE FEATURE

In the event of a fire, your alarm will sound 3 beeps continuously and the LED flash once per second.* The FA6111 Escape Light Alarm will illuminate continuously.

  1. Press the Test / button

  2. The alarm will silence for 10 minutes and the red LED will continue to flash.
    alarm will silence

Smoke alarms can react to cooking fumes or other non emergency situations. Your alarm features ‘Silence’ technology. In the event of a known false alarm you can temporarily silence it by pressing the Test / button. The LED will continue to flash once every second to show that it is in Silence mode. Your alarm will automatically return to full sensitivity after 10 minutes.

NEVER IGNORE ANY ALARM. If an alarm is sounding, it is warning you of a potentially hazardous situation. Do not ignore it. Ignoring the alarm may result in injury or death. If your smoke or heat alarm activates and you are not absolutely certain of the source of fire, everyone out of the house immediately.

NOTE : For FA6215 Heat Alarms only; after sounding for 30 minutes, the audible alarm signal will increase the pause between alerts (by approx.12 seconds) in order to save power. The LED will continue to flash once every second.

SLEEP EASY™ FEATURE

ow battery ‘chirp’ occurs at night, the alarm can be silenced so it does not keep you fromleeping

  1. Press the Test / button.
    Press the Test

  2. The alarm will silence for 8 hours and the red LED will continue to flash.
    alarm will silence

  3. TAKE ACTION to replace the alarm or batteries THE NEXT DAY (see Low Batter yarning section)

TAKE ACTION

Take action as soon as possible to ensure protection in case of fire. Your alarm will still detect smoke (or heat) during the Sleep Easy mode but you must replace the alarm or batteries within 30 days

  • If your alarm is an FA6111, FA6115 or FA6215 and is signaling low batteries, replace the batteries as soon as possible. Once the batteries have been replaced, the Sleep Easyeature will be disabled for 30 days.
  • If your alarm is an FA6120 replace the alarm. If the device is still within warranty, contact our Technical Support team

NOTE : You can silence a low battery ‘chirp’ a maximum of 10 times. YOUR ALARM CANNOT BE SILENCED IF IT INDICATES A FAULT OR END OF LIFE (See ‘Fault Indication’).

WARRANTY & DISPOSAL

Firangi Safety Technology Limited warrants to the original purchaser that its enclosed smoke or heat alarm be free from defects in materials and workmanship under normal residential use and service for a period of 5 (five) years from the date of purchase (not including FA6111FA6115 or FA6215 replaceable batteries). Provided product is sent back to Firangi Safety Technology Limited with proof and date of purchase, Firangi Safety Technology Limited hereby warrants that during the 5 (five) year period commencing from the date of purchase Firangi Safchnology Limited, at its discretion, agrees to replace the unit free of charge. The warranty on placement FA6111, FA6115, FA6120 or FA6215 alarm, will last for the remainder of the period of the original warranty in respect of the alarm originally purchased – that is fr m the date of original purchase and not from the date of receipt of the replacement product. FireAngel Safeechnology Limited reserves the right to offer an alternative product similar to that being replaced if the original model is no longer available or in stock. This warranty applies to the original retail purchaser from the date of original retail purchase and is not transferable. Proof of purchase is required
This warranty does not cover damage resulting from accident, misuse, disassembly, abuse or lack of reasonable care of the product, or applications not in accordance with the user manual. It does not cover events and conditions outside of FireAngel Safety Technology Limited ‘control, such as Acts of God (fire, severe weather etc.). It does not apply to retail stores, service centers or any distributors or agents. FireAngel Safety Technology Limited will not recognise any changes to this warranty by third parties
FireAngel Safety Technology Limited shall not be liable for any incidental or consequential damages caused by the breach of any expressed or implied warranty. Except to the exhibited by applicable law, any implied warranty of merchantability or fitness for a particular purpose is limited in duration for 5 (five) years
This warranty does not affect your statutory rights. Except for death or personal injurireAngel Safety Technology Limited shall not be liable for any loss of use, damage, cost or expensrelating to this product or for any indirect, or consequential loss, damages or costs incurred by you or any other user of this product

DISPOSAL

Waste electrical products should not be disposed of with your other household waste. The alarm is ideally suited for disposal within the waste electronic and electrical equipment (WEEE) recycling scheme Please recycle where facilities exist. Check with your local authority, retailer or contact our Technical Support team for recycling/ disposal advice as regional variationapply. Replaceable batteries should be removed before disposal of the detector. Both batteries and the detector should be disposed of in line with current regulations. Do not attempt to open. Do not burn.

For Technical Support reference, please write the alarm batch number and install date below:

Batch number:
Batch number:

Install date:

FireAngel Safety Technology Limited. Email: (UK) technicalsupport@fireangeltech.com,
(DE) technik@fireangeltech.com, (FR) supporttechnique@fireangeltech.com, (NL) klantenservice@fireangeltech.com,
(INT) Internationalsupport@fireangeltech.com

0333
EN14604:2005
+AC:2008
Smoke alarm devices
FSTDOP21006

32
EN14604:2005
+AC:2008
Smoke alarm devices
FSTDOP21007 2

Model FA6215

KM 694292
BS 5446-2:2003

Company Lobo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>