MEAN WELL WDR-120 series 120W Single Output Industrial DIN RAIL Power Supply Owner’s Manual

June 15, 2024
MEAN WELL

MEAN WELL WDR-120 series 120W Single Output Industrial DIN RAIL Power

Supply

 WELL-WDR-120-series-120W-Single-Output-Industrial-DIN-RAIL-Powe-Supply-
PRODUCT

Specifications

  • Model : WDR-120-12
  • DC Voltage: 12V
  • Rated Current: 10A
  • Current Range: 0 ~ 10A
  • Rated Power: 120W
  • Ripple & Noise (max.): 120mVp-p
  • Voltage Adj. Range: 12 ~ 15V
  • Line Regulation
  • Load Regulation
  • Setup, Rise, Hold Up Time: 2000ms, 70ms, 50ms/400VAC
  • Voltage Range: 180 ~ 550VAC 254 ~ 780VDC
  • Frequency Range: 47 ~ 63Hz
  • Efficiency (Typ.): 89.5% / 400V
  • AC Current: 0.7A/400VAC
  • Inrush Current (max.) Cold Start: 50A
  • Leakage Current:

 Features

  • Single and two phase wide input range 180 ~ 550VAC
  • Protections: Short circuit / Overload / Over voltage / Over temperature
  • Cooling by free air convection
  • Built-in constant current limiting circuit
  • Can be installed on DIN rail TS-35/7.5 or 15
  • UL508(industrial control equipment)approved
  • BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
  • 100% full load burn-in test
  • Built-in DC OK relay contact
  • 3 years warranty

GTIN CODE MW

Search: https://www.meanwell.com/serviceGTIN.aspx

SPECIFICATION

MODEL WDR-120-12 WDR-120-24 WDR-120-48






OUTPUT

| DC VOLTAGE| 12V| 24V| 48V
RATED CURRENT| 10A| 5A| 2.5A
CURRENT RANGE| 0 ~ 10A| 0 ~ 5A| 0 ~2.5A
RATED POWER| 120W| 120W| 120W
RIPPLE & NOISE (max.) **Note.2| 120mVp-p| 120mVp-p| 150mVp-p
VOLTAGE ADJ. RANGE| 12 ~ 15V| 24 ~ 29V| 48 ~ 58V
VOLTAGE TOLERANCE Note.3| ±1.5%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE, HOLD UP TIME**| 2000ms, 70ms, 50ms/400VAC           2000ms, 70ms, 10ms/230VAC at full load





INPUT

| VOLTAGE RANGE| 180 ~ 550VAC           254 ~ 780VDC
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 89.5% / 400V| 91% / 400V| 92% / 400V
AC CURRENT| 0.7A/400VAC           1.2A/230VAC
INRUSH CURRENT (max.)| COLD START 50A
LEAKAGE CURRENT| <3.5mA / 530VAC


PROTECTION

| **OVERLOAD| 105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
****
OVER VOLTAGE| 16 ~ 18V| 31 ~ 37V| 60 ~ 67V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION| DC OK SIGNAL| Relay contact rating(max.) : 30V / 1A resistive
****
ENVIRONMENT| WORKING TEMP.| -25 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting clip: Compliance to IEC60068-2-6
SAFETY & EMC**

(Note 4)

| SAFETY STANDARDS| UL508, EAC TP TC 004 , BIS IS13252(Part1)(only for 12V,24V) approved, IEC62368-1 CB approved by SIQ; Design refer to BS EN/EN62368-1, AS/NZS 62368.1(meet BS EN/EN60204-1)
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61204-3, BS EN/EN61000-6-2 (BS EN/EN50082-2), heavy industry level, EAC TP TC 020
**OTHERS| MTBF| 1509.6K hrs min.       Telcordia SR-332 (Bellcore) ; 268.1K hrs min.       MIL-HDBK-217F (25℃)
DIMENSION| 40125.2113.5mm (WHD)
PACKING| 0.65Kg; 20pcs/14Kg/1.16CUFT
NOTE**|

  1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25℃ of ambient temperature.
  2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
  3. Tolerance : includes set up tolerance, line regulation and load regulation.
  4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
  5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quick may lead to increase of the set up time.
  6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer :For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

120W Single Output Industrial DIN RAIL Power Supply

Mechanical Specification

 WELL-WDR-120-series-120W-Single-Output-Industrial-DIN-RAIL-Powe-
Supply-01

Block Diagram

 WELL-WDR-120-series-120W-Single-Output-Industrial-DIN-RAIL-Powe-
Supply-02

DC OK Relay Contact

Contact Close PSU turns on / DC OK.
Contact Open PSU turns off / DC Fail.
Contact Ratings (max.)

Derating Curve