MEAN WELL WDR-120 series 120W Single Output Industrial DIN RAIL Power Supply Owner’s Manual
- June 15, 2024
- MEAN WELL
Table of Contents
MEAN WELL WDR-120 series 120W Single Output Industrial DIN RAIL Power
Supply

Specifications
- Model : WDR-120-12
- DC Voltage: 12V
- Rated Current: 10A
- Current Range: 0 ~ 10A
- Rated Power: 120W
- Ripple & Noise (max.): 120mVp-p
- Voltage Adj. Range: 12 ~ 15V
- Line Regulation
- Load Regulation
- Setup, Rise, Hold Up Time: 2000ms, 70ms, 50ms/400VAC
- Voltage Range: 180 ~ 550VAC 254 ~ 780VDC
- Frequency Range: 47 ~ 63Hz
- Efficiency (Typ.): 89.5% / 400V
- AC Current: 0.7A/400VAC
- Inrush Current (max.) Cold Start: 50A
- Leakage Current:
Features
- Single and two phase wide input range 180 ~ 550VAC
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Built-in constant current limiting circuit
- Can be installed on DIN rail TS-35/7.5 or 15
- UL508(industrial control equipment)approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- 100% full load burn-in test
- Built-in DC OK relay contact
- 3 years warranty
GTIN CODE MW
Search: https://www.meanwell.com/serviceGTIN.aspx
SPECIFICATION
| MODEL | WDR-120-12 | WDR-120-24 | WDR-120-48 | 
|---|
OUTPUT
|  DC VOLTAGE|  12V| 24V| 48V
RATED CURRENT|  10A| 5A| 2.5A
CURRENT RANGE|  0 ~ 10A| 0 ~ 5A| 0 ~2.5A
RATED POWER|  120W| 120W| 120W
RIPPLE & NOISE (max.) **Note.2|  120mVp-p| 120mVp-p| 150mVp-p
VOLTAGE ADJ. RANGE|  12 ~ 15V| 24 ~ 29V| 48 ~ 58V
VOLTAGE TOLERANCE Note.3|  ±1.5%| ±1.0%| ±1.0%
LINE REGULATION|  ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION|  ±0.5%| ±0.5%| ±0.5%
SETUP, RISE, HOLD UP TIME**|  2000ms, 70ms, 50ms/400VAC           2000ms,
70ms, 10ms/230VAC at full load  
INPUT
|  VOLTAGE RANGE|  180 ~ 550VAC           254 ~ 780VDC
FREQUENCY RANGE|  47 ~ 63Hz
EFFICIENCY (Typ.)|  89.5% / 400V| 91% / 400V| 92% / 400V
AC CURRENT|  0.7A/400VAC           1.2A/230VAC
INRUSH CURRENT (max.)|  COLD START 50A
LEAKAGE CURRENT|  <3.5mA / 530VAC  
PROTECTION
|  **OVERLOAD|  105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after
fault condition is removed
****OVER VOLTAGE|  16 ~ 18V| 31 ~ 37V| 60 ~ 67V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE|  Shut down o/p voltage, recovers automatically after
temperature goes down
FUNCTION|  DC OK SIGNAL|  Relay contact rating(max.) : 30V / 1A
resistive
****ENVIRONMENT|  WORKING TEMP.|  -25 ~ +70℃ (Refer to “Derating
Curve”)
WORKING HUMIDITY|  20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY|  -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT|  ±0.03%/℃ (0 ~ 50℃)
VIBRATION|  Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,
Y, Z axes; Mounting clip: Compliance to IEC60068-2-6
SAFETY & EMC**
(Note 4)
|  SAFETY STANDARDS|  UL508, EAC TP TC 004 , BIS IS13252(Part1)(only for
12V,24V) approved, IEC62368-1 CB approved by SIQ; Design refer to BS
EN/EN62368-1, AS/NZS 62368.1(meet BS EN/EN60204-1)
WITHSTAND VOLTAGE|  I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC
OK:0.5KVAC
ISOLATION RESISTANCE|  I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/
70% RH
EMC EMISSION|  Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3
Class B, EAC TP TC 020
EMC IMMUNITY|  Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS
EN/EN55035, BS EN/EN61204-3, BS EN/EN61000-6-2 (BS EN/EN50082-2), heavy
industry level, EAC TP TC 020
**OTHERS|  MTBF|  1509.6K hrs min.       Telcordia SR-332
(Bellcore) ; 268.1K hrs min.       MIL-HDBK-217F (25℃)
DIMENSION|  40125.2113.5mm (WHD)
PACKING|  0.65Kg; 20pcs/14Kg/1.16CUFT
NOTE**|
- All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25℃ of ambient temperature.
- Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
- Tolerance : includes set up tolerance, line regulation and load regulation.
- The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
- Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quick may lead to increase of the set up time.
- The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer :For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
120W Single Output Industrial DIN RAIL Power Supply
Mechanical Specification

Block Diagram

DC OK Relay Contact
| Contact Close | PSU turns on / DC OK. | 
|---|---|
| Contact Open | PSU turns off / DC Fail. | 
| Contact Ratings (max.) | 
Derating Curve
Static Characteristics

File Name :WDR-120-SPEC 2022-12-02