Installation / User Manual
Micro Inverter (Integrated NS Protection Device)
(Built-in WIFI-G3)

Important Safety Instructions

This manual contains important instructions to follow during installation and maintenance of the Photovoltaic Grid-connected Inverter(Micro Inverter).To reduce the risk of electrical shock and ensure the safe installation and operation of the Micro Inverter the
following symbols appear throughout this document to indicate dangerous conditions and important safety instructions.
Specifications subject to change without notice – please ensure you are using the latest manual found at the manufacturer website.
WARNING:
This indicates a situation where failure to follow instructions may cause a serious hardware failure or personnel danger if not applied appropriately. Use extreme caution when performing this task.
NOTE:
This indicates information that is important for optimized Micro Inverter operation. Follow these instructions strictly.

Safety Instructions
DO NOT disconnect the PV module from the Micro Inverter without disconnecting the AC power.
Only qualified professionals should install and/or replace the Microinverters.
Perform all electrical installations in accordance with local electrical codes.
Before installing or using the Micro Inverter, please read all instructions and cautionary markings in the technical documents and on the Micro Inverter system and the solar-array.
Be aware that the body of the Micro Inverter is the heat sink and can reach a temperature of 80℃. To reduce risk of burns,do not touch the body of the Microinverter.
When the microinverter is working properly, please maintain a distance of at least 20cm from it.
DO NOT attempt to repair the Micro Inverter. If it fails, contact technical support to obtain an RMA number and start the replacement process. Damaging or opening the Micro Inverter will void the warranty.
Caution! The external protective earthing conductor is connected to the inverter protective earthing terminal through AC connector. When connecting, connect the AC connector first to ensure the inverter earthing then do the DC connections.
When disconnecting, disconnect the AC by opening the branch circuit breaker first but maintain the protective earthing conductor in the branch circuit breaker connect to the inverter ,then disconnect the DC inputs.
In any circumstance, do not connect DC input when AC connector is unplugged.
Please install isolation switching devices on the AC side of the inverter.

Radio Interference Statement
The equipment could radiate radio frequency energy and this might cause harmful interference to radio communications if not following the instructions when installing and using the equipment. But there is no guarantee that interference will not occur in a
particular installation. If this equipment causes harmful interference to radio or television reception,the following measures might resolve the issues:
A) Relocate the receiving antenna and keep it well away from the equipment.
B) Consult the dealer or an experienced radio / TV technical for help.
Changes or modifications not expressly approved by the party responsible for compliance may void the user’s authority to operate the equipment.
WiFi information
Frequency range:2.412~2.472GHz
WiFi maximum transmitting power:16 dBm ± 2dBm
Antenna:External Antenna
Antenna Gain:3.00dBi

The Meaning of Symbols

Can be OEM Trademark.
Caution, risk of electric shock.
Caution, risk of burn – Do not touch.
Caution, hot surface.
**** Symbol for the marking of electrical and electronics devices according

to Directive 2002/96/EC. Indicates that the device, accessories and the packaging must not be disposed as unsorted municipal waste and must be collected separately at the end of the usage. Please follow Local Ordinances or Regulations for disposal or contact an authorized representative of the manufacturer for information concerning the decommissioning of equipment.
| CE mark is attached to the solar inverter to verify that the unit follows the provisions of the European RED Directives.
| Refer to the operating instructions.
Qualified personnel| Person adequately advised or supervised by an electrically skilled person to enable him or her to perceive risks and to avoid hazards which
electricity can create. For the purpose of the safety information of this manual, a “qualified person” is someone who is familiar with
requirements for safety, refrigeration system and EMC and is authorized to energize,ground, and tag equipment, systems, and circuits in
accordance with established safety procedures. The inverter and endues system may only be commissioned and operated by qualified personnel.

Micro Inverter System Introduction

The Micro Inverter is used in utility-interactive grid-tied applications, comprised of three key elements:

  • Micro Inverter
  • SUN-MI-RELAY-01(Network and System Protection Device)
  • Router

This series Micro Inverter has built-in WIFI module so it can communicate with router directly.

M60 / 80 / 100G3
SUN-MI-RELAY-01(Network and System Protection Device): it is used to monitoring and disconnect the grid when sensing the grid voltage/frequeny is out of the allowed range. The relay kit also is able to reconnect grid when the grid condtions resume. It  must communicate with the built-in wifi module of the Micro Inverter, the Micro Inverter can work normally, otherwise the Micro Inverter can not work. The localhost of this relay kit is 10.10.101.254.

Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection
Device - Monitoring system

NOTE:
For the connection between SUN-MI-Relay-01( Network and System Protection Dev -ice) and Micro Inverter, the tool(screwdriver) is needed.
WARNING:
The Micro Inverter SUN-M60G3-EU-Q0, SUN-M80G3-EU-Q0, SUNM100G3-EU-Q0 shall not be put into operation without external relay kit SUN-MIRELAY-01.

Name Functions
**** COM The COM light indicates the communication status of the

microinverter and relay.
COM light flashes blue, Successfully communicated
**** AC/M| AC/M blue light flashes twice, Interconnection working status (relay is closed)
SET| Press and hold for 5 seconds, The relay resets, disconnects, and automatically closes after two minutes.
Press and hold for 10 seconds, The communication between the relay and the microinverter was disconnected, and communication resumed after two minutes.

Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection
Device - Monitoring system 2

Inverter Model| SUN-M60G3-EU-QO| SUN-M80G3-EU-QO| SUN- M100G3-EU-Q0
---|---|---|---
PV Input Voltage| 42.5V (20V-60V)
PV Array MPPT Voltage Range| 25V-55V
No. of MPP Trackers| 2
No. of Strings per MPP Tracker| 1

NOTE:
If the wireless signal in the area where the Micro Inverter is installed is weak, it is necessary to add a wifi signal booster at a suitable place between the router and the Micro Inverter.
This integrated system improves safety; maximizes solar energy harvest;increases system reliability, and simplifies solar system design, installation,maintenance, and management.

Microinverters Maximize PV Energy Production
Each PV module has individual Maximum Peak Power Tracking (MPPT) controls, which ensures that the maximum power is exported to the utility grid regardless of the performance of the other PV modules in the array.When PV modules in the array are affected by shade, dust, orientation,or any situation in which one module underperforms compared with the other units, the Micro Inverter ensures top performance from the array by maximizing the performance of each module within the array.

More Reliable than Centralized or String Inverters
The distributed Micro Inverter system ensures that no single point of system failure exists across the PV system.Microinverters are designed to operate at full power at ambient outdoor temperatures of up to 113℉ (45℃). The inverter housing is designed for outdoor installation and complies with the IP67 environmental enclosure rating.

Simple to Install
You can install individual PV modules in any combination of Module quantity, orientation, different type and power rate. The Ground wire (PE) of the AC cable is connected to the chassis inside of the Micro Inverter,potentially eliminating the installation of grounding wire (check local regulation).
Data collection adopts internal wifi,wireless router is needed near the Micro Inverter. When complete the installation of Micro Inverter,configure wireless router with internal wifi(refer to the wifi user manual).The data will be uploaded automatically.Users can monitor and manage the Micro Inverter through corresponding website or APP.

Micro Inverter Introduction

The Microinverters connect with the single-phase grid, and can also use multiple Microinverters in the form of single-phase grid to achieve three- phase grid.
For more information, please see the Technical Data page (P17) of this manual.

Model Number AC grid Max. # Per branch
SUN-M60G3-EU-Q0 50/60Hz,230V 8 for 25A breaker
SUN-M80G3-EU-Q0 50/60Hz,230V 6 for 25A breaker
SUN-M100G3-EU-Q0 50/60Hz,230V 5 for 25A breaker

Micro Inverter System Installation

A PV system using Microinverters is simple to install. Each Micro Inverter easily mounts on the PV racking, directly beneath the PV module(s). Low voltage DC wires connect from the PV module directly to the Micro Inverter, eliminating the risk of high DC
voltage.Installation MUST comply with local regulations and technical rules.

WARNING: Perform all electrical installations in accordance with local electrical codes.
WARNING: Be aware that only qualified professionals should install and/or replace Microinverters.
WARNING: Before installing or using an Micro Inverter,please read all instructions and warnings in the technical documents and on the Micro Inverter system itself as well as on the PV array.
WARNING: Be aware that installation of this equipment includes the risk of electric shock.
NOTE: Strongly recommend to install Surge protection Devices in the dedicated meter box.
NOTE: The product is suitable for residential, commercial and light industrial environments, not for industrial environments.

Required Parts and Tools from you
In addition to your PV array and its associated hardware, you will need the following items:

  • An or several AC connection junction boxes
  • Mounting hardware suitable for module racking
  • Sockets and wrenches for mounting hardware
  • Continuous grounding conductor and grounding washers
  • A Phillips screwdriver
  • A torque wrench

Parts list
Please check the following table, to see whether all the parts are included in the package:

Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection
Device - Parts list

  • Choose either Bus AC connector or Extension cable with European standard plug, can’t use them in the same project.

Installation Procedures
Step 1 – Install the AC branch circuit junction box

Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection
Device - Installation Procedures

a. Install an appropriate junction box at a suitable location on the PV racking system (typically at the end of a branch of modules).
b. Connect the open wire end of the AC cable into the junction box using an appropriate gland or strain relief fitting.
c. Connect the AC branch circuit junction box to the point of utility Grid Interconnection (Usually it is inside a distribution box).

Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection
Device - distribution

WARNING:
Wiring colour code can be different according local regulation,check all the wires of the installation before connecting to the AC cable to be sure they match. Wrong cabling can damage irreparably the microinverters,such an issue is not covered by the warranty.

Step 2 – Attach the Microinverters to the racking or the PV module frame
a. Mark the location of the Micro Inverter on the rack, with respect to the PV module and junction box or any other obstructions.
b. Mount one Micro Inverter at each of these locations using hardware recommended by your module racking vendor.

Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection
Device - Microinverters

The AC wire on the micro inverter is a TC-ER wire with a wire cross-section area of 1mm²(18AWG).
WARNING: Prior to installing any of the microinverters, verify that the utility voltage at the point of common connection matches the voltage rating on Micro Inverter label.
WARNING: Do not place the inverters (including DC and AC connectors) where exposed to the sun, rain or snow, even gap between modules.Allow a minimum of 3/4 (1.5cm.) between the roof and the bottom of the Micro Inverter to allow proper air flow.

Step 3 – Connect the microinverters in parallel
a. Check the Micro Inverter technical data page 5 for the maximum allowable number of Microinverters on each AC branch circuit.
b. As to parallel connection, please refer to page (P19-P20), use the T-connector, AC extension cable, Bus AC connector(If only one branch, just use the Extension cable with European standard plug) to connect the Micro Inverter in each branch.

Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection
Device - Male connector

Model| Wire Size| cable(mm)²| Torque value( max)| Max cable length
---|---|---|---|---
SUN-M60G3-EU-Q0| 12AWG| 2.5| 8.5Nm| Outside cable
(L+N+PE)20m
SUN-M80G3-EU-QO| 12AWG| 2.5| 8.5Nm
SUN-M100G3-EU-Q0| 12AWG| 2.5| 8.5Nm

WARNING:
DO NOT exceed maximum number of Microinverters in an AC branch circuit, as displayed on the page 5 of this manual.

NOTE:
Port marked with two-way arrow on T-type plug can only connect with extended cable and Port marked with one-way arrow on T-type plug can only connect with Micro Inverter.

Step 4 – Connect the wire open of branch end to the junction box.

Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection
Device - junction box

Step 5 – Connect Micro Inverter to the PV Modules

Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection
Device - Inverter

General Guidelines:
a. PV modules should be connected to DC input ports of a Micro Inverter.
b. In order to meet the relevant regulatory requirements, the cable length must be <3M.
Please consult the local power operator to make sure that the DC cable complies with local regulations.

NOTE:
When plugging in the DC cables, if AC already available,the Micro Inverter should immediately blink red light and will start work within the setting time (default 60 seconds).
If AC is not available,the red light will blink 3 times quickly and repeat after one second until AC is connected.

Micro Inverter System Operating Instructions

To operate the Micro Inverter PV system:

  1. Turn ON the AC circuit breaker on each Micro Inverter AC branch circuit.

  2. Turn ON the main utility-grid AC circuit breaker. Your system will start producing power after a one-minute waiting time.

  3. The units should start blinking red one minutes after turning on the AC circuit breaker.
    Then blue led blinking. This means they are producing power normally, the faster blinking of the blue led means more power generated.

  4. Configure the internal wifi module according to its user manual.

  5. The Microinverters will start to send performance data over wifi module to the network every 5 minutes.It enables customers to monitor performance data of each Micro Inverter through website and APP.

When AC power is applied but the Micro Inverter not started up, about 0.1 A current and 25VA power for each Micro Inverter may be measured by a power meter. This power is reactive power,not consume from utility grid.

Troubleshooting

Qualified personnel can use the following troubleshooting steps if the PV system does not operate correctly:

Status Indications and Error Reporting
Start up LED
One minute after DC power is first applied to the Micro Inverter,one short red blinks indicate a successful Micro Inverter startup sequence, be equal or greater than two short red blinks after DC power is first applied to the Micro Inverter indicate a failure during Micro Inverter setup.

Operation LED

Flashing Slow Blue – Producing small power
Flashing Fast Blue – Producing big power
Flashing Red – Not producing power
Red blinking two times – AC low-voltage or high-voltage
Red blinking three times – Grid failure

GFDI Error
A four time red LED indicates the Micro Inverter has detected a Ground Fault Detector Interrupter (GFDI) error in the PV system.
Unless the GFDI error has been cleared, the LED will remain four times blinking.

Other Faults
All other faults can be reported to the website and APP.

WARNING:
Never disconnect the DC wire connectors under load. Ensure that no current is flowing in the DC wires prior to disconnecting. An opaque covering may be used to cover the module prior to disconnecting the module.

Troubleshooting a non-operating Micro Inverter
There are two possible overall areas of trouble:
A. The Micro Inverter itself may be having problems.
B. The Micro Inverter itself is working fine but the communication between Micro Inverter and network has problem. The items below refer to Micro Inverter issues, not communicat -ion issues:

One quick way to tell whether the issue is the Micro Inverter or the communication problem:
Diagnosing from the network:
a. No-Data-Display: The website and APP don’t display any data.Check the network configuration.
b. Only display Micro Inverter is online but no data.This maybe because server is updating.

To troubleshoot a non-operating Micro Inverter, Follow the steps below in order:

  1. Verify the utility voltage and frequency are within ranges shown in the Technical Data section of this manual.
  2. Check the connection to the utility grid.Disconnect AC firstly,then disconnect DC and make sure the utility grid voltage can be measured at AC connector. Never disconnect the DC wires while the Micro Inverter is producing power. Re-connect the DC module connectors and watch for three short LED flashes.
  3. Check the AC branch circuit interconnection between all the microinverters. Verify each inverter is energized by the utility grid as described in the previous step.
  4. Make sure that any AC breaker are functioning properly and are closed.
  5. Check the DC connections between the Micro Inverter and the PV module.
  6. Verify the PV module DC voltage is within the allowable range shown in the Technical Data of this manual.
  7. If the problem still persists, please contact technical support.

WARNING:
Do not attempt to repair the Micro Inverter.If troubleshooting methods fail, please call for Technical Support

Replacement

Follow the procedure to replace a failed Micro Inverter
A. Disconnect the Micro Inverter from the PV Module, in the order shown below:

  1. Disconnect the AC by turning off the branch circuit breaker.
  2. Disconnect the AC connector of the Micro Inverter.
  3. Cover the module with an opaque cover.
  4. Disconnect the PV module DC wire connectors from the Micro Inverter.
  5. Remove the Micro Inverter from the PV array racking.

B. Install a replaced Micro Inverter to the bracket then remove the opaque cover.
Remember to observe the flashing LED light as soon as the new Micro Inverter is plugged into the DC cables.
C. Connect the AC cable of the replacement Micro Inverter.

Technical Data

WARNING: Be sure to verify the voltage and current specifications of your PV module match with those of the Micro Inverter. Please refer to the datasheet or user manual.
WARNING: You must match the DC operating voltage range of the PV module with the allowable input voltage range of the Micro Inverter.
WARNING: The maximum open circuit voltage of the PV module must not exceed the specified maximum input voltage of the inverter.

M60G3/80G3/100G3 Microinverter Datasheet

Model| SUN-M60G3 -EU-QO| SUN-M80G3 la -EU-QO| SUN-M100G3 -EU-QO
---|---|---|---
Input Data (DC)
Recommended input power(STC)| 210-420W(2 Piece)| 210-560W(2 Piece)| 210-700W(2 Piece)
Maximum input DC voltage| | 60V|
MPPT Voltage Range| | 25-55V|
MPPT Full Power Voltage Range(V)| 30V-55V| 33V-55V| 40V-55V
Min.DC input voltage(V)| | 20V|
Max DC short circuit current| | 19.5Ax2|
Max input current| | 1 3Ax2|
Output Data (AC)| |
Rated output Power| 600W| 800W| 1000W
Max.AC Output Apparent Power| 600VA| 800VA| 1000VA
Rated AC output current| 2.7A| 3.5A| 4.4A
Max.AC Output Current| 2.7A| 3.5A| 4.4A
Nominal voltage / range| | 230V/ 0.85Un-1.1Un|
Nominal frequency| | 50/60Hz|
Extended frequency / range| | 45-55Hz / 55-65Hz|
Power factor| | 1|
Maximum unit per branch| 8| 6| 5
Max. allowed altitude operating| | 2000m|
Max.inverter backfeed current to the array| | OA|
Max output fault current
Efficiency| | 10A|
CEC weighted efficiency| 95%
Peak inverter efficiency| 96.5%
Static MPPT efficiency| 99%
Night time power consumption| 50mW
Mechanical Data
Ambient temperature range| -40 C — 65 C ,>45 C derating
Dimensions(WxHxD mm)| 212W X 190H X 40D (Without mounting bracket and cable)
Weight (kg)| 2.8
Cooling| Natural cooling
Enclosure environmental rating| IP67
Protective class| Class I
Topology| Isolated HF Transformer
Features|
---|---
Compatibility| Compatible with 60,72 cell PV modules
Communication|  WiFi
Compliance| EN50549,VDE0126,VDE4105,IEC62109,CE,INMETRO
Warranty| 10 Years

  • Note : 15years warranty (only installed in Germany and Austria)

Technical Data

Model:SUN-MI-RELAY-01 Network and System Protection Device

AC Intput Data(Inverter)
Nominal Voltage| 220V/230V
Nominal Frequency| 50/60Hz
Max AC Current| 12A
Nominal AC Current| 12A
Matching Inverter| Micro Inverter
AC Output Data(Grid)
Nominal Voltage| 220V/230V
Nominal Frequency| 50/60Hz
Max AC Current| 12A
Nominal AC Current| 12A
General Data
Ambient Temperature Range| -40-65°C, >45°C derating
Humidity| 0%-100% RH
Cabinet Size (WxHxD)
111mm95mm37.7mm| (Excluding Connectors and Brackets)
Weight| 340g
Enclosure Environmental Rating| IP67
Communication| Wireless/Wifi
Safety EMC / Standard| IEC/EN61000-6-1/3, IEC/EN 62109-1, IEC/EN 62109-2,VDE- AR-N 4105
WiFi information:
Frequency range| 2.412-2.472GHz
WiFi maximum transmitting power| 17dBm ± 1.5dBm
Antenna| External Antenna
Antenna Gain| 3dBi

Wiring Diagram

Sample Wiring Diagram Three Phase

Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection
Device - Fig 1

Sample Wiring Diagram Single Phase

Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection
Device - Fig 2

Monitoring Platform

This series Micro Inverter has built-in WIFI modular which is able to connect router directly. For WIFI configuration, please check the manual of“Built-in WIFI modular Micro Inverter WIFI configuration Manual”
Web monitoring address:
https://pro.solarmanpv.com; (for Solarman distributor account)
https://home.solarmanpv.com (for Solarman end user account)
For mobile phone monitoring system, scan the QR code to download the APP.
Also you can find it by searching “solarman business” in App store or Google Play store, and this App is for distributor/installer.
Find it by searching “solarman smart” in App store or Google Play store and choose “solarman smart”, this app is for plant owner.

https://download.solarmanpv.com/qrdownload/index.html?target=c

https://download.solarmanpv.com/qrdownload/index.html?target=b

How to connect the SUN-MI-RELAY-01 to the Micro Inverterr via web

  1. Turn on the wireless network of your PC or smartphone.

  2. Select network of SUN-MI-RELAY-01 (network name: RE_398526017) and the default password of the network is listed on the nameplate of PWD:“5c4db8d6”.Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - Inverterr via web

  3. Open a browser and enter 10.10.101.254. Both username and password are “admin”.
    (Recommended browser: IE 8+, Chrome 15+, Firefox 10 + ).Conrad Electronic
Built in WIFI G3 Micro Inverter Integrated NS Protection Device -
passwordIf can’t access the 10.10.101.254 for a long while, please disconnect the AC and then waiting for 5S and try again.

  4.  Browser jumps to “ Status ” page, the basic information is listed there.Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - information

  5. Click to enter the “Quick Set” page and click the “Search” button to start searching for network hotspots near the NS protection device.Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - hotspots

  6. Click to select your micro-inverter’s WLAN hotspot and enter the inverter hotspot password.Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - WLAN hotspot

  7. The default password of the AP network is 12345678 if there’s no nameplate that includes PWD:XXXXXXXX on the inverter body. If there’s nameplate that includes PWD:XXXXXXXX on the inverter body then the AP network password is the “XXXXXXXX”.Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - AP network passwordConrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - connection

  8. Click to enter the Status page,You can view the current connection information on the Device information page.if you need help,Please contact Deye’s official after-sales service or authorized service provider.Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - provider

How to connect the Micro Inverter to the router via web

  1. Turn on the wireless network of your PC or smartphone.

  2. The default password of the AP network is 12345678 if there’s no nameplate that includes PWD:XXXXXXXX on the inverter body. If there’s nameplate that includes PWD:XXXXXXXX on the inverter body then the AP network password is the “XXXXX
    XXX”: for example, the default password of AP network is “5c4db4d8” of the inverter SN:2302202012.Conrad Electronic Built in WIFI G3 Micro Inverter
Integrated NS Protection Device - via webAlso, the default password can be changed. If forgetting the modified password, please contact service@deye.com.cn for help.

  3. Open a browser and enter 10.10.100.254. Both username and password are “admin”. (Recommended browser: IE 8+, Chrome 15+, Firefox 10 + ).Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - Chrome

  4. Browser jumps to “ Status ” page, the basic information is listed there.Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - wireless network

  5. Turn to “Wizard” page, click “Refresh” to search the wireless network. Select the target network and click “Next” .Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - network

  6. Enter the password and click Next.Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - Enter the password

  7. Users can select any options below to enhance the security and click Next.Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - enhance

  8. If the setup is successful, the following page will pop up and click OK to reboot the micro inverter.Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - loggeer

  9. Connect to loggeer AP network again, then log in to 10.10.101.254 by Browser, and check the system info of “Status” page. After the network setting is done, the remote server A or B should be “connected”.Conrad Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device - solarman

  10. When it shows “connected” which means this Micro Inverter has connected solarman platform successfully. Generally speaking, it will be online after 10-15 min after configuration successfully at the first time.

How to connect in APP

  1. Registration
    Open the app of SOLARMAN Smart and register an account.
    Click “Register” and create your account here.Conrad Electronic Built in
WIFI G3 Micro Inverter Integrated NS Protection Device - How to connect in
APP

  2. Create a Plant
    Click “Add Now” to create your plant.
    Please fill in plant basic info and other info here.Conrad Electronic Built
in WIFI G3 Micro Inverter Integrated NS Protection Device - Create a
Plant

  3. Add a Logger
    Optional 1: Enter the logger SN manually.
    Optional 2: Click the icon in the right and scan the QR code to enter logger SN.
    You can find logger SN on the carton packaging or on the logger body.Conrad
Electronic Built in WIFI G3 Micro Inverter Integrated NS Protection Device -
Add a Logger

  4. Network Configuration
    After the logger is added, please configure the network to ensure normal operation.
    Go to “Plant Details”-“Device List”, find the target SN and click ” Device Networking”.
    If showing”online” which means the datalogger of the inverter connects the solarman platform successfully. Then you will be able to check the plant info on the platform.

EU Declaration of Conformity

**** within the scope of the EU directives

  • Radio Equipment Directive 2014/53/EU (RED)
  • Restriction of the use of certain hazardous substances 2011/65/EU)(RoHS)

NINGBO DEYE INVERTER TECHNOLOGY CO.,LTD confirms herewith that the products described in this document are in compliance with the fundamental requirements and other relevant provisions of the above mentioned directives. The entire EU Declaration of Conformity can be found at www.deyeinverter.com.

Please scan the QR code to download the certification.

https://www.deyeinverter.com/download/#microinverter-4

References

Read User Manual Online (PDF format)

Loading......