Conrad Electronic MK 9151N Level Sensing Relay Instruction Manual
- June 15, 2024
- Conrad Electronic
Table of Contents
MK 9151N Level Sensing Relay
Product Information
Specifications
- Model: VARIMETER Level Sensing Relay
- Model Numbers: IL 9151, SL 9151, MK 9151N
Function Diagrams
The product has two function diagrams:
-
Common control of output relays (with bridge X1-COM)
- X1 COM UH 0 Level MAX MIN 11-14, 21-24 X1 COM X2 (Open circuit
operation) 11-12, 21-22 tv MAX tv MIN 11-14, 21-24 X1 (Closed COM
circuit operation) 11-12, 21-22 tv MAX Common control of output
relays tv MIN M6956_b
- X1 COM UH 0 Level MAX MIN 11-14, 21-24 X1 COM X2 (Open circuit
-
Separate control of output relays (without bridge X1-COM)
- X1 COM UH 0 Level MAX MIN 21-24, 21-22 X1 COM X2 (Open circuit
operation) 11-14, 11-12 tvMIN tv MAX tv MAX tv MIN Translation of
the original instructions – 2 separate controllable output relays
for MIN and MAX level – Common controlled output relays for 2-point
hysteresis Approvals and Markings
- X1 COM UH 0 Level MAX MIN 21-24, 21-22 X1 COM X2 (Open circuit
Circuit Diagrams
The product has two circuit diagrams:
-
X1 COM X2 MIN MAX A1 A2 A1 A2 X1 X2 MIN COM MAX 12 11 14 22 21
24 12 22 14 11 24 21 M7556_b IL 9151.12, SL 9151.12 A1 11 21 MIN X1
COM X2 MAX A1 X1 MIN MAX 11 21 A2 X2 COM 12 14 22 24 22 24 12 14 A2
M8502 -
MK 9151N.12 Connection Terminals Terminal designation A1, A2
MIN, MAX, COM X1 – COM X2 – COM 11, 12, 14 21, 22, 24 Signal
description Auxiliary voltage AC oder DC Electrode connection
Selection operating mode via bridge Selection de-energized or
energized via bridge Contacts Rel. 1 Contacts Rel. 2
Product Usage Instructions
1-Point Level Control
The product supports 1-point level control which is suitable for
protection against overfilling and dry running on containers with a
free inlet/outlet. To configure this setup, you will need the
reference probe COM and the MAX probe located at the desired limit
level.
The output relay will switch over after the set delay time if
the fluid level exceeds or falls below the limit level, allowing
fluid to be pumped out or added.
Separate Output Control
If separate output control is desired, where each output relay
has a separate time delay, you need to set the unit to separate
control of the outputs and connect the MIN and MAX inputs to the
same probe. Please note that the resistance of the liquid is
divided on both input circuits, so the response value must be set
to double the desired value.
Time Delay and Wave Suppression
The product has a settable time delay of 0.2 to 20 seconds for
each probe circuit. This allows you to suppress early switching
caused by waves on the liquid. Additionally, time-dependent level
control can be realized. The delay works integrating and is active
when the liquid goes over as well as under the probe level.
Foam Differentiation
The wide setting range of the product allows for an optimum
setting to differentiate between foam and liquid. The response
value must be set to a value high enough that the unit reacts when
the liquid, but not when the foam reaches the probe. During the
setting procedure, the time delay should be set to the minimum
value.
FAQ
-
1. **Q: What is the purpose of the VARIMETER Level Sensing
Relay?**
A: The VARIMETER Level Sensing Relay is designed to monitor
fluid levels in containers and control output relays based on
predefined limits.
-
1. **Q: Can I control both MIN and MAX levels with separate
relays?**
A: Yes, the product supports separate control of output relays
for MIN and MAX levels.
-
1. **Q: How can I differentiate between foam and
liquid?**
A: The product has a wide setting range that allows for
differentiation between foam and liquid. The response value must be
set accordingly.
0225266
Installation / Monitoring Technique
VARIMETER Level Sensing Relay IL 9151, SL 9151, MK 9151N
IL 9151
SL 9151
Function Diagrams
MK 9151N
Common control of output relays (with bridge X1-COM:
)
X1 COM
UH
0 Level
MAX MIN
11-14, 21-24
X1 COM X2 (Open circuit operation)
11-12,
21-22
tv MAX
tv MIN
11-14, 21-24
X1 (Closed
COM circuit
opXe2ration)11-12,
21-22
tv MAX
Common control of output relays
tv MIN
M6956_b
Separate control of output relays (without bridge X1-COM:
)
X1 COM
UH
0
Level MAX
MIN
21-24 21-22
X1 COM X2 (Open circuit operation)
11-14 11-12
tvMIN
tv MAX
tv MAX
tv MIN
Translation of the original instructions
· According to IEC/EN 60255-1 · 3 probe connections for 2-point and 1-point
level control · Also for use as moisture detector · High interference
resistance of the Measuring Circuit,
which is isolated from the mains · Max. wire length to the probes: 3000 m ·
Large setting range: 2 … 450 k
this permits differentiation between fluid and foam · Separately adjustable
response and release time delay
0.2 … 20 s for MIN- and MAX-level · Programmable for:
– 2 separate controllable output relays for MIN and MAX level – Common
controlled output relays for 2-point hysteresis
level control – Open circuit operation – Closed circuit operation · Measuring
Circuit for probes works with internally generated AC voltage (approx. 30 Hz),
electrolytic behaviour does not occur in the liquid · For auxiliary voltages
of 24 … 415 V AC or 24 V DC · LEDs for operation and state of contact · 2
changeover relays with 1 changeover contact each · IL 9151 and SL 9151 with
safe separation according to IEC/EN 61140, IEC/EN 60947-1 · Devices available
in 3 enclosure versions: IL 9151: Depth 59 mm, with terminals at the bottom
for
installation systems and industrial distribution systems according to DIN
43880 SL 9151, MK 9151N: Depth 98 mm, with terminals at the top for cabinets
with mounting plate and cable duct · IL / SL 9151: 35 mm width MK 9151N: 22.5
mm width
Approvals and Markings
- Only IL 9151, MK 9151N
Application
· Level monitoring and control for conductive liquids and powders, e.g. maximum and minimum filling levels, overfilling and protection against dry running
· Monitoring and control of the mixing ratio of conductive liquids · General resistance monitoring tasks, e.g. limit temperature detection
with PTC · Contact protection relay with time delay
21-24
21-22
X1 COM X2 (Closed circuit operation)
11-14
11-12
tvMIN
Seperate control of output relay
tv MAX
tv MAX
tv MIN
M6949_b
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
1
20.06.22 en / 583A
Circuit Diagrams
X1 COM X2
MIN MAX A1 A2
A1
A2
X1
X2
MIN COM
MAX
12 11
14
22 21
24
12
22
14 11 24 21 M7556_b
IL 9151.12, SL 9151.12
A1 11 21 MIN X1 COM X2 MAX
A1 X1 MIN MAX 11
21
A2 X2 COM
12 14 22 24
22 24 12 14 A2
M8502
MK 9151N.12
Connection Terminals
Terminal designation A1, A2 MIN, MAX, COM X1 – COM X2 – COM 11, 12, 14 21, 22, 24
Signal description Auxiliary voltage AC oder DC Electrode connection Selection operating mode via bridge Selection de-energized or energized via bridge Contacts Rel. 1 Contacts Rel. 2
Notes
1-point level control 1-point level control (see Figure) is especially
suitable for protection against overfilling and dry running on containers with
a free inlet/outlet. In this configuration, all that is required besides the
reference probe “COM” is the “MAX”, which must be located at the desired limit
level. The output relay switches over after the set delay time if the fluid
level exceeds or falls below the limit level, which permits fluid to be pumped
out or added.
Without bridge X1 – COM only relay “MAX” (contacts 21-22-24) switch, with
bridge X1 – COM both relays switch together. If for each output relay a
separate time delay is necessary, the unit has to be set to separate control
of the outputs and the “MIN” and “MAX” inputs are connected to the same probe.
Please note that the resistance of the liquid is divided up on both input
circuits. Therefore the response value must be setted to the double value.
If separate output control is selected with 1-point control for each output
relay the time delay can be setted separately.
Because of the settable time delay of 0.2 to 20 sec for each probe circuit, it
is possible to suppress early switching caused by waves on the liquid. Also
time depending level control can be realised. The delay works integrating and
is active when the liquid goes over as well as under the probe level.
The wide setting range allows easily an optimum setting so that the unit can
differentiate between foam and liquid. The response value must be set to a
value high enough, that the unit reacts when the liquid, but not when the foam
reaches the probe (for setting procedure the time delay is set to min. value).
Indicators
IL / SL 9151 Green LED: Yellow LED: Red LED:
MK 9151N Green LED: Yellow LED “MIN”: Red LED “MAX”:
On, when auxiliary supply connected On, when relay MIN active On, when relay
MAX active
On, when auxiliary supply connected On, when relay MIN active On, when relay
MAX active
Notes
All commercially available probes are suitable. The reference probe for level
measurement is generally located at the lowest point of the container and must
always be connected to the “COM” terminal. The container itself can be used as
a reference probe if it consists of conductive material.
On the level “MIN” and “MAX” the other probes are installed and connected to
the corresponding inputs of IL 9151. It is also possible to connect only one
probe.
2-point level control The 2-point control is selected when a liquid should be
kept between “MIN” and “MAX” level. 2 operation modes can be selected:
Without bridge X1 – COM: Separate control of output relays for “MIN” and “MAX”
level
With bridge X1 – COM: Common control of both output relays
When the relays are separately controlled each output relay is operated by the
corresponding probe circuit. For each level the time delay can be set
separately (tvMIN and tvMAX).
When the relays are controlled together, these work like a relay with 2
changeover contacts as follows:
If the liquid rises above the “MAX” level the output relays switch over after
the delay time of tvMAX and start e.g. a pumpt to sink the liquid. If the
level goes under the “MAX” level the output relays remain activated until the
“MIN” level is reached. Now the output relays switch back after the time delay
of tvMIN and stop the pump. The whole process starts again when the level
reaches the “MAX” probe.
2
20.06.22 en / 583A
Technical Data Input
Technical Data General Data
Setting range of the
fluid resistance:
2 … 450 k (response value)
Setting:
On logarithmically divided absolute scale
Switching point hysteresis: Approx. 4 % (at 450 k)
… 15 % (at 2 k) of the set value
Voltage and temperature
influence:
< 2 % of the set value
Max. cable length to the
probes:
Set value
Cable length
(at 100 nF/km)
450 k
50 m
100 k
200 m
35 k
500 m
10 k
1500 m
5 k
3000 m
Max. sensing voltage:
Approx. AC 10 V
(internally generated)
Max. sensing current:
Approx. AC 1.5 mA
(internally generated)
Response and release times
tvMIN, tvMAX:
0.2 … 20 s for both output relays separate settable
Setting on logarithmically-divided
absolute scale
Auxiliary Circuit
Auxiliary voltage UH:
AC 24, 42, 110, 230 V DC 24 V
Voltage range of UH
AC:
0.8 … 1.1 UN
DC:
0.85 … 1.25 UN
Nominal power consumption
AC:
Approx. 2 VA
DC:
Approx. 1 W
Frequency range:
45 … 400 Hz
Output
Contacts
IL / SL 9151.12, MK 9151N.12: 2 x 1 changeover contact
Thermal current Ith:
4 A
Switching capacity
IL / SL 9151:
To AC 15
NO contact:
5 A / AC 230 V
IEC/EN 60947-5-1
NC contact:
2 A / AC 230 V
IEC/EN 60947-5-1
To DC 13:
2 A / DC 24 V
IEC/EN 60947-5-1
MK 9151N:
To AC 15
NO contact:
3 A / AC 230 V
IEC/EN 60947-5-1
NC contact:
1 A / AC 230 V
IEC/EN 60947-5-1
To DC 13:
1 A / DC 24 V
IEC/EN 60947-5-1
Electrical life
IL / SL 9151:
IEC/EN 60947-5-1
To AC 15at 1 A, AC 230 V: 2 x 105 switching cycles
MK 9151N:
IEC/EN 60947-5-1
To AC 15 at 1 A, AC 230 V: 1.5 x 105 switching cycles
Short circuit strength
max. fuse rating:
4 A gG / gL
IEC/EN 60947-5-1
Mechanical life:
30 x 106 switching cycles
Operating mode:
Continuous operation
Temperature range:
Operation:
– 20 … + 60 °C
Storage:
– 25 … + 70 °C
Altitude:
2000 m
Clearance and creepage
distances
Rated rated impulse voltage voltage /
pollution degree
IEC 60664-1
IL / SL 9151:
Input / Auxiliary Circuit: Input / output circuit:
6 kV / 2 (at UH = DC 24 V: 1kV) 6 kV / 2
MK 9151N:
Input / Auxiliary Circuit: Input / output circuit:
4 kV / 2 (at UH = DC 24 V: 1 kV) 4 kV / 2
Auxiliary / output circuit
A1-A2 (AC):
4 kV / 2
EMC
Electrostatic discharge:
8 kV (air)
IEC/EN 61000-4-2
HF irradiation
80 MHz … 2.7 GHz:
10 V / m
IEC/EN 61000-4-3
Fast transients:
2 kV
IEC/EN 61000-4-4
Surge voltages
Between
wires for power supply:
1 kV
IEC/EN 61000-4-5
Between wire and ground:
2 kV
IEC/EN 61000-4-5
HF wire guided:
10 V
IEC/EN 61000-4-6
Interference suppression:
Limit value class B
EN 55011
Degree of protection
Housing:
IP 40
IEC/EN 60529
Terminals:
IP 20
IEC/EN 60529
Housing:
Thermoplastic with V0 behaviour
according to UL subject 94
Vibration resistance:
Amplitude 0.35 mm,
frequency 10 … 55 Hz, IEC/EN 60068-2-6
Climate resistance:
20 / 060 / 04
IEC/EN 60068-1
Terminal designation:
EN 50005
Wire connection:
IL / SL 9151:
2 x 2.5 mm2 solid or
2 x 1.5 mm2 stranded ferruled
DIN 46228-1/-2/-3/-4
Min. cross section:
0,6 mm
Insulation of wires
or sleeve length:
10 mm
MK 9151N:
1 x 4 mm2 solid or
1 x 2.5 mm2 stranded ferruled or
2 x 1.5 mm2 stranded ferruled
DIN 46228-1/-2/-3/-4
Min. cross section:
0.5 mm2
Abisolierlänge der Leiter:
8 mm
Wire fixing:
IL / SL 9151:
Flat terminals with self-lifting
clamping piece
IEC/EN 60999-1
MK 9151:
Box terminal with wire protection
Fixing torque:
0.8 Nm
Mounting:
DIN rail
IEC/EN 60715
Weight
IL 9151:
Approx. 165 g
SL 9151:
Approx. 192 g
MK 9151N:
Approx. 180 g
Dimensions
Width x height x depth IL 9151: SL 9151: MK 9151N:
35 x 90 x 59 mm 35 x 90 x 98 mm 22.5 x 90 x 98 mm
CCC-Data
Nominal voltage UN: MK 9151N:
AC 24, 42, 110, 230 V DC 24 V
Switching capacity To AC 15 NO contact:
1.5 A / AC 230 V IEC/EN 60947-5-1
Technical data that is not stated in the CCC-Data, can be found
nfo in the technical data section.
3
20.06.22 en / 583A
Standard Type
IL 9151.12 2 … 450 k AC 230 V 0.2 … 20 s
Article number:
0049135
· Settable response value: 2 … 450 k
· ·
Auxiliary voltage UH: Response and release
AC delay: 0.2
230 V … 20 s
· 2 output relays with 1 changeover contact each
· With safe separation
· Width:
35 mm
Application Example
12 11 14 22 21 24
A1
12 14
22 24
A2
11
21
MIN MAX COM X1 X2
SL 9151.12 2 … 450 k AC 230 V 0.2 … 20 s
Article number:
0051552
· Settable response value: 2 … 450 k
· ·
Auxiliary voltage UH: Response and release
AC delay: 0.2
230 V … 20 s
· 2 output relays with 1 changeover contact each
· With safe separation
· Width:
35 mm
Niveau
M6634_b
IL 9151, SL 9151 with safe separation according to IEC/EN 61140, IEC/EN
60947-1
MK 9151N.12 2 … 450 k AC 230 V 0.2 … 20 s
Article number:
0054100
· Settable response value: 2 … 450 k
· ·
Auxiliary voltage UH: Response and release
AC delay: 0.2
230 V … 20 s
· 2 output relays with 1 changeover contact each
· Width:
22.5 mm
Variants MK 9151N.12/001: MK 9151N.12/002:
Time delay, when level drops under setting value Time delay, when level rises over setting value
Ordering example for variants
12 11 14 22 21 24
A1
12 14
22 24
A2
11
21
MIN MAX COM X1 X2
K1
K2
M11101
MK 9151 N .12 /00_ 2 … 450 k
AC 230 V 0.2 … 20 s
Response and release delay Auxiliary voltage Response value Variant, if
required Contacts Type
Application as contact protection relay, e.g. for two reed contact switches (K1, K2).
Accessories OA 5640:
5
Standard probe Article number: 0016045
21
M5670
140
Stainless steel immersion electrode, Temperature range: 0 … + 60 °C, Weight:
Approx. 0.1 kg Wire connection: 1.5 mm2 stranded wire with sleeve without
plastic collar Stripping length: 10 mm Fixing torgue: 0.6 Nm
16
E.Dold&SöhneGmbH&Co.KG·D-78120Furtwangen · Bregstraße 18 · Phone +49 7723 654-0 · Fax +49 7723 654356
dold-relays@dold.com·www.dold.com
4
20.06.22 en / 583A
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>