REGENCY FIREPLACE PRODUCTS G800C Grandview Gas Fireplace Instruction Manual

June 15, 2024
REGENCY FIREPLACE PRODUCTS

G800C Grandview Gas Fireplace

Product Information

Specifications

  • Model: G800C Medium DV Gas Fireplace
  • Manufacturer: FPI FIREPLACE PRODUCTS INTERNATIONAL LTD.
  • Website: www.regency-fire.com
  • Installation and service must be performed by a qualified
    installer, service agency, or the gas supplier.

Product Usage Instructions

Safety Warnings

Failure to follow safety warnings exactly could result in
serious injury, death, or property damage. Please carefully read
and understand the following safety warnings:

  • Do not store or use gasoline or other flammable vapors and
    liquids in the vicinity of this or any other appliance.

  • Hot glass will cause burns. Do not touch the glass until
    cooled. Never allow children to touch the glass.

  • A barrier designed to reduce the risk of burns from the hot
    viewing glass is provided with this appliance and must be installed
    for the protection of children and other at-risk individuals.

  • The appliance gets hot while in operation. Do not touch it.
    Severe burns may result. Keep children, clothing, furniture,
    gasoline, and any other liquids with flammable vapors away.

  • Keep burner and control compartment clean. Refer to the
    installation and operating instructions accompanying the appliance
    for detailed cleaning instructions.

  • Carbon monoxide poisoning hazard: Ensure proper ventilation and
    follow all venting requirements.

Installation

To install the G800C Medium DV Gas Fireplace, please follow the
steps outlined below:

1. Gas Installation Checklist

Refer to page 9 of the manual for the Gas Installation
Checklist. Ensure that all the necessary requirements are met
before proceeding with the installation.

2. Installation Checklist

Refer to page 20 of the manual for the Installation Checklist.
Follow the checklist to ensure a proper and safe installation.

3. Locating Your Gas Fireplace

Refer to page 20 of the manual for detailed instructions on
where to locate your gas fireplace. Consider factors such as
clearance requirements, ventilation, and accessibility.

4. HeatWave Duct System Optional Kit #946-556

If you wish to install the optional HeatWave Duct System, refer
to page 20 of the manual for instructions on using the kit

946-556.

5. Venting Arrangements

Depending on your installation requirements, refer to the
relevant pages in the manual for venting arrangements using
horizontal termination, vertical termination, co-linear flex system
into a masonry chimney application, or co-linear flex system into
masonry fireplaces. Follow the instructions carefully to ensure
proper venting.

6. Unit Installation

Depending on your venting arrangements, refer to pages 60-62 of
the manual for detailed unit installation instructions with
horizontal or vertical termination. Follow the instructions step by
step for a successful installation.

FAQ (Frequently Asked Questions)

Q: Can I use this gas fireplace in a mobile home?

A: Yes, this gas fireplace can be installed in an aftermarket
permanently located, manufactured (U.S.A. only), or mobile home,
where not prohibited by local codes. Please ensure you follow all
installation requirements and use the type of gas indicated on the
rating plate.

Q: Are non-metallic venting systems compatible with this gas

fireplace?

A: No, non-metallic venting systems shall not interchange
components with another listed or unlisted metallic venting system.
Ensure you use the appropriate venting components as specified in
the manual.

Grandview® G800C Gas Fireplace

Owners & Installation Manual
MODEL: G800C Medium DV Gas Fireplace

www.regency-fire.com
Warning Fire or Explosion Hazard Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not touch any electrical switch: do not use any phone in your building.
Leave the building immediately. · Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s instructions. · If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.

Tested by:
920-182j

Installer: Please complete the details on the back cover and leave

Certified to/Certifié pour: ANSI Z21.88-2019

this manual with the homeowner.

Homeowner: Please keep these instructions for future reference.

FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4

11.08.22

To the New Owner:
Congratulations! You are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The GrandviewTM G800C has been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch. The GrandviewTM G800C has been approved by Intertek for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your Regency® Fireplace.
Front
! DANGER

HOT GLASS WILL CAUSE BURNS
DO NOT TOUCH GLASS UNTIL COOLED
NEVER ALLOW CHILDREN TO TOUCH GLASS

A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and must be installed for the protection of children and other at risk individuals.
CAUTION:
HOT WHILE IN OPERATION. DO NOT TOUCH. SEVERE BURNS MAY RESULT. KEEP CHILDREN, CLOTHING, FURNITURE, GASOLINE, AND ANY OTHER LIQUIDS WITH FLAMMABLE VAPOURS AWAY.

KEEP BURNER AND CONTROL COMPARTMENT CLEAN.

SEE INSTALLATION AND OPERATING INSTRUCTIONS ACCOMPANYING

APPLIANCE.

920-408

L’écran p contact a enfants e
ATT
Risque Ne pas Ne pas vêteme à distan S’assur Voir les l’appare

920-408
4.34.7 Instruction Plate For a glass-fronted gas appliance where the temperature of the glass viewing area outside surface exceeds the limits specified in Clause 5.14.4, the following graphic danger and statements shall be shown on a Class IIIA-2 Permanent Label. 4.34.6 Instruction Plate Each appliance shall bear a Class IIIB marking with letters on a contrasting background, located adjacent to the controlling device or in an equally conspicuous position where the instruction can be easily read.
April 22/14: Created draft Double sided Material: Synthetic Paper Size 5.965″ W x 5.71″ H Color: As shown in artwork
2 | Grandview® G800C Gas Fireplace

MANUFACTURED MOBILE HOME REQUIREMENTS
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE This Regency® product has been tested and listed by Intertek as a Direct Vent Wall Furnace to the following standards: Vented Gas Fireplace Heaters ANSI Z21.88-2019. This Direct Vent System Appliance must be installed in accordance with the manufacturer’s installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A. This appliance installation must comply with the manufacturer’s installation instructions and local codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A. This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as applicable to local codes. The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70. This appliance may only be installed in an aftermarket permanently located, manufactured (U.S.A only) or mobile home, where not prohibited by local codes. This appliance can only be used with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases. Ensure that structural members are not cut or weakened during installation.
This appliance may be installed in an aftermarket permanently located, manufactured (U.S.A. only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. A conversion kit is supplied with the appliance.
Grandview® G800C Gas Fireplace | 3

WARNING CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation: 1. Seal any unused openings in the venting system. 2. Inspect the venting system for proper size and horizontal pitch, as required in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54.1 and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. 3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. 4. Close fireplace dampers. 5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on
any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan. 6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously. 7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle. 8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with National Fuel Gas Code, ANSI Z223.1/NFPA. 9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace damper and any other gas-fired burning appliance to the previous conditions of use.
Other considerations: Non-metallic venting systems shall not interchange components with another listed or unlisted metallic venting system.
4 | Grandview® G800C Gas Fireplace

Owner’s Information
Copy of Safety Decal …………………………………………………………… 6 Decal Location …………………………………………………………………… 6 Unit Dimensions …………………………………………………………………. 8 Before You Start……………………………………………………………….. 11 Important Message ………………………………………………………….. 12 General Safety Information …………………………………………………. 12 To Turn Appliance On/Off……………………………………………………. 12 Optional Fan Operation ………………………………………………………. 12 Lighting the Pilot Using the Gas Control Knob Extender……………… 13 Proflame I Remote Control Operating Instructions ……………………. 14 Proflame I Remote Receiver Battery Replacement…………………….. 17 Operating Procedure for Remote Control ………………………………… 18 Safety Screen Removal ………………………………………………………. 19 Safety Screen Installation …………………………………………………… 19 Glass Door Removal ………………………………………………………….. 19 Glass Door Installation……………………………………………………….. 19
Installer’s Information
Gas Installation Checklist ……………………………………………………… 9 Installation Checklist………………………………………………………….. 20 Locating Your Gas Fireplace ………………………………………………… 20 HeatWave Duct System Optional Kit #946-556 ………………………… 20
Installation
Clearance / Framing and Venting Configurations ………………………. 21 Cool Wall Installation (Combustible Finishing)………………………….. 22 Non-Combustible Installation ………………………………………………. 22 Cool Wall installation/Cool Wall Conversion……………………………… 23 Cool Wall Clearances …………………………………………………………. 24 Cool Wall Mantel Clearances……………………………………………….. 25 Cool Wall Mantel Leg Clearances ………………………………………….. 25 Cool Wall Installation – Framing……………………………………………. 26 Chase Venting………………………………………………………………….. 27 Chase Vent Installation – Cool Wall ………………………………………. 28 Clean Front Installation (Non Cool Wall) – Clearances………………… 29 Clean Front Installation (Non Cool Wall)–Mantel Clearances ………. 30 Clean Front Installation (Non Cool Wall) – Mantel Leg Clearances…. 31 Clean Front Installation (Non Cool Wall) – Non Combustible
Requirements ………………………………………………………………… 31 Clean Front Installation – Framing (Non Cool Wall)……………………. 32 Clean Front Installation………………………………………………………. 33 Nailing Flange Instructions………………………………………………….. 33 Optional Clean Front Trim Install Instructions ………………………….. 33 Outside Finish Installation (Non Cool Wall) – Clearances …………….. 34 Outside Finish Installation (Non Cool Wall) – Mantel Clearances …… 35 Outside Finish Installation (Non Cool Wall) – Mantel Leg
Clearances…………………………………………………………………….. 35 Outside Finish Installation (Non Cool Wall)- Framing …………………. 36 Outside Finish – Finishing …………………………………………………… 37 Faceplate Install (Part # 761-922, 761-924, 761-926) ……………….. 38 Finishing Trim Install (Part # 761-928)…………………………………… 40 Unit Assembly Prior to Installation ………………………………………… 42 Nailing Flange Installation…………………………………………………… 43 Wall Board/Drywall Installation…………………………………………….. 44 Conversion to Top Vent………………………………………………………. 45 Vent Restrictor Installation ………………………………………………….. 47 Venting Introduction………………………………………………………….. 47 Exterior Vent Termination Requirements…………………………………. 48 4″ X 6-5/8″ (102 mmx 168 mm) Rigid Pipe – Cross Reference
Chart Only …………………………………………………………………….. 49 Venting Arrangements – Horizontal Termination – Rigid Pipe and
Direct Vent System (Flex) ………………………………………………… 53 Venting Arrangements – Vertical Termination – Rigid Pipe System
and Vertical Flex Kit to Same Limitations ………………………………. 54 Horizontal Terminations – Two 90°Elbows ………………………………. 55 Horizontal Terminations – Three 90o Elbows ……………………………. 55 Vertical Venting with Two 90o Elbows …………………………………….. 56 Vertical Venting with Three 90o Elbows ……………………………….. 56 Vertical Terminations Three 90° Elbows – Rigid Pipe 4″ x 6 – 5/8″
(102 mm x 168 mm) ……………………………………………………….. 57

table of contents
Venting Arrangements with Co-linear Flex System into a Masonry Chimney Application ………………………………………………………….. 58 Venting Arrangement – Vertical Terminations – Co-linear Flex
System Into Masonry Fireplaces ………………………………………… 59 Unit Installation with Horizontal Termination …………………………… 60 Unit Installation with Vertical Termination……………………………….. 61 Direct Vent System (Flex) Installation Procedures …………………….. 62 Vertical Termination 4″ x 6-7/8″ (102 mm x 175 mm) Venting
– Vertical Flex Vent Kit (Part #946-755)………………………………… 63 Vertical Flue Extension Kit (Part #946-756) …………………………….. 64 Ceiling Firestop / Firestop Spacer (Part #946-757)……………………. 64 Conversion from NG to LP using SIT Gas Valve ………………………… 65 Brick Panel installation ……………………………………………………….. 67 Enamel/Steel Panel Installation ……………………………………………. 68 Log Set Installation …………………………………………………………… 69 Crystal Tray Installation ……………………………………………………… 73 Driftwood Media Kit Installation……………………………………………. 74 Pilot Adjustment……………………………………………………………….. 76 S.I.T. 820 Valve Description…………………………………………………. 76 NG System Data ………………………………………………………………. 76 LP System Data ……………………………………………………………….. 76 Gas Pipe Pressure Testing …………………………………………………… 76 Aeration Adjustment………………………………………………………….. 77 Electrical Access and Installation ………………………………………….. 77 Optional Wall Thermostat (Part # 910-407)…………………………….. 78 Optional Remote Control (Part # 946-704) ……………………………… 78 Optional Wall Switch (Not Supplied by Regency)………………………. 78 Installing an Optional Wall Switch (Not Supplied by Regency) or
Thermostat (Part # 910-407 or 910-404/P)…………………………… 79 Wiring Diagram With and Without Thermostat/Remote Control……. 80 Installing the Optional Fan (Part 761-979)………………………………. 81 Fan Install After Unit Installation ………………………………………….. 82 Fan Wall Control Installation Kit (Part # 761-974) …………………….. 83 Optional On/Off Remote Kit Installation (Part # 946-704)…………… 85 Safety Screen Removal ………………………………………………………. 86 Safety Screen Installation …………………………………………………… 86 Glass Door Removal ………………………………………………………….. 86 Glass Door Installation……………………………………………………….. 86
Operating Instructions
Operating Instructions ……………………………………………………….. 87 First Fire …………………………………………………………………………. 87 Normal Operating Sounds of Gas Appliances …………………………… 87 Receiver Battery Replacement ……………………………………………… 88 DC Spark Igniter Battery Installation/Replacement……………………. 88 Copy of Lighting Plate Instructions ……………………………………….. 89
Maintenance
Maintenance Instructions ……………………………………………………. 90 General Vent Maintenance ………………………………………………….. 90 Log Replacement ……………………………………………………………… 90 Glass Gasket ……………………………………………………………………. 90 Door Glass………………………………………………………………………. 90 Glass Replacement ……………………………………………………………. 90 Valve Replacement ……………………………………………………………. 91 Gas Appliance Maintenance…………………………………………………. 92
Parts List
Main Assembly …………………………………………………………………. 93 Optional Accessories………………………………………………………….. 95 Warranty …………………………………………………………………….96
Grandview® G800C Gas Fireplace | 5

owner’s information

This is a copy of the label that accompanies each GrandviewTM G800C Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review. NOTE: Regency® units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.

Copy of Safety Decal

Duplicate S/N

536

Listed/Nom: Vented Gas Fireplace Heater / Foyer au Gaz à Évacuation Certified to/Certifié pour: ANSI Z21.88-2019

DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE Serial No./ No de série

C #: 4001172

MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE. Refer to Intertek’s Directory of Building Products for detailed information. Pour plus de détails , se reporter au Répertoire des produits de construction de Intertek.

NATURAL GAS: Model G800C-NG

Minimum supply pressure 5.0″ WC/C.E. (1.25kPa)

Manifold pressure high 3.8″ WC/C.E. (0.94kPa)

Manifold pressure low 1.1″ WC/C.E. (0.27kPa)

Orifice size

42 DMS

Minimum input

15,000 Btu/h (4.4 kW)

Maximum input

27,000 Btu/h (7.91 kW)

Altitude

0-4500 ft/pi (0-1372 m)

APPAREIL FONCTIONNANT AU GAZ NATUREL Modèle G800C-NG Pression d’alimentation minimale Pression manifold – haute Pression manifold – basse Taille de l’orifice Débit calorifique minimal Débit calorifique maximal Altitude

PROPANE GAS: Model G800C-LP

Minimum supply pressure 11″ WC/C.E. (2.74kPa)

Manifold pressure high 10.5″ WC/C.E. (2.61kPa)

Manifold pressure low 2.9″ WC/C.E. (0.72kPa)

Orifice size

53 DMS

Minimum input

14,500 Btu/h (4.25 kW)

Maximum input

26,500 Btu/h (7.77 kW)

Altitude

0-4500 ft/pi (0-1372 m)

APPAREIL FONCTIONNANT AU GAZ PROPANE Modèle G800C-LP Pression d’alimentation minimale Pression manifold – haute Pression manifold – basse Taille de l’orifice Débit calorifique minimal Débit calorifique maximal Altitude

536

Minimum Clearances to Combustibles / Rear Vent–Clean Finish

Dégagements minimaux par rapport aux matériaux combustibles

D C
A

F B

E
DOOR SEAL: Please check that the door is
properly sealed

0″ Clearance to

combustibles from /

Top, sides, bottom and rear of unit

Mantel Clearances from

Fireplace Opening /

(A) 20-1/2″ (521 mm) at max. depth

Side Wall Clearance

from Fireplace Opening /

B) Min. 26-1/2″ (673mm)(on one side)

Ceiling from Top of

Fireplace Opening:

C) Min. 36-1/2″ (927 mm)

Mantel Depth:

D) Max. 19″ (483 mm)

Alcove Clearances:

E) Min. Width 84″ (2134 mm),

F) Max. Depth 36″ (914 mm)

Minimum Vent Clearances:

Horizontal Top

2″ (51 mm)

Horizontal Side 1-1/2″ (38 mm)

Horizontal Bottom 1-1/2″ (38 mm)

Vertical Vent

1-1/2″ (38 mm)

(See Instruction Manual for detailed instructions)

This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1.

This appliance must be installed in accordance with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States, or when such a standard is not applicable,

ANSI/NCSBCS A225.1/NFPA 501A, Manufactured Home Installations Standard or ANSI A119.2 ou NFPA 501C Standard for Recreational Vehicles

This appliance is only for use with the type of gas indicated on the rating plate and may be installed in an aftermarket, permanently located, manufactured (mobile) home where not prohibited by local codes. See

owner’s manual for details. This appliance is not convertible for use with other gases, unless a certified kit is used. (Kit #761-977). Fan Part # 761-979.

Installer l’appareil selon les codes ou règlements locaux, ou, en l’absence de tels règlements, selon les codes d’installation ANSI Z223.1. Installer l’appareil selon la norme 24 CFR, Part 3280, Manufactured Home

Construction and Safety Standard. Si ces normes ne sont pas pertinentes, utilisez la norme ANSI/NCSBCS A225.1/NFPA 501A, Manufactured Home Installations Standard, ou ANSI A119.2 ou NFPA 501C

Standard for Recreational Vehicles. Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil peut être installé dans une maison préfabriquée ou mobile (É.-U.

seulement) installée à demeure si les règlements locaux le permettent. Voir la notice de l’utilisateur pour plus de renseignements. Cet appareil ne peut pas être utilisé avec d’autres gaz sauf si une trousse de

conversion certifiée est fournie.

This vented gas fireplace heater is not for use with air filters. FOR USE WITH GLASS DOORS CERTIFIED WITH THE APPLIANCE ONLY

Ne pas utiliser de filtre à air avec ce foyer au gaz à évacuation. POUR UTILISATION UNIQUEMENT AVEC LES PORTES EN VERRE CERTIFIÉES AVEC L’APPAREIL

For Use Only with Barrier (Part #761-038/P )

Utiliser uniquement avec l’écran ( n ° 761-038/P )

Electrical supply/Alimentation électrique 115VAC, 1.5A, 60Hz.
VENTED GAS FIREPLACE HEATER – NOT FOR USE WITH SOLID FUELS. CATEGORY I

FPI Fireplace Products International Ltd. Delta, BC, Canada

FOYER AU GAZ À ÉVACUATION – NE PAS UTILISER AVEC UN COMBUSTIBLE SOLIDE. CATÉGORIE I

Made in Canada/ Fabriqué au Canada

EP5011169

CANADIAN ENERGY PERFORMANCE VERIFIED
RENDEMENT ÉNERGÉTIQUE
VÉRIFIÉ

CSA P.4.1 Fireplace Efficiency (FE) /Efficacité énergétique des foyers (EEF) CSA P.4.1 Natural Gas / Gaz naturel 54.17% Propane Gas / Gaz propane 53.64%

920-168d

Part #: 920-168d

CFoolrouthr:eESvetaryttehionfgMblaascskaocnhgurseeyttesx,cienpsttwalhlaattiiosnhighlighted is DprientcedarledL. ocation

Sainzed: rFeiplea@ir1m00u%st9b.1e17d”Wonxe 6b.0y45a”Hplumber or gas fitter licensed in the Commonwealth of

DO NOT REMOVE DECAL FROM UNIT.

NMoavs. s1a/1c9hu: Cserettaste. d Draft

Jan 6, 2020: Removed reference to CSA standard

Mar. 17/21: Updated CSA/ANSI date
SFeoprtt.h1e6/S2t1a:Utepodaf tMe aPs.4s.a1cdhautasetts, flexible con-

Jnaenc2to5r/2s2s:hAadlldneodtCeaxtceegoerdy316 inches in length.
July 4/22: Changed wording

For the State of Massachusetts, the appli-
ances individual manual shut-off must be a t-handle type valve.

Remove bottom cover–decal will be on the floor of the unit

The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where
the gas appliance is installed.

6 | Grandview® G800C Gas Fireplace

owner’s information

5.08: Modifications to NFPA-54, Chapter 10

MA Code – CO Detector
(for the State of Massachusetts only)

(2) Revise 10.8.3 by adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1. Detailed instructions for the installation of the venting system design or the venting system components; and

2. A complete parts list for the venting system design or venting system.

(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipmentat the completion of the installation.
Grandview® G800C Gas Fireplace | 7

19″ 481mm NON COOL WALL 16 7/8″ 429mm COOL WALL

owner’s information
Unit Dimensions
4″ 101mm

18″ 457mm

35

7 8

913mm

OUTSIDE FINISH

32

5 8

827mm

CLEAN FRONT

6

5 8

170mm

18

7 8

480mm

17

1 2

446mm

11

1 4

287mm

GAS INLET

7

5 8

195mm

32

1 2

823mm

FIREPLACE OPENING

33

7 8

862mm

OUTSIDE FINISH

30

7 8

29

7 8

759mm

648mm

1 2

CLEAN FRONT

783mm

25

37

1 2

953mm

1

5 8

41mm

1

5 8

41mm

42

7 8

1088mm

ELECTRICAL INLET

7

1 2

192mm

11

1 4

287mm

1

37

3 4

959mm

32mm

1 4

1

924mm

3 8

36

892mm

1 8

35

(7 23287987”m”m)
734mm

39mm

1 2

34

5 8

880mm

34

3 4

883mm

Finishing Trim

Faceplate

Note: Gas connection is from the left hand side of the appliance & electrical connection on right hand side of the appliance. A metal receptacle box is supplied/installed with the appliance to make all 120 volt electrical connections.
ALL PICTURES / DIAGRAMS SHOWN THROUGHOUT THIS MANUAL ARE FOR ILLUSTRATION PURPOSES ONLY. ACTUAL PRODUCT MAY VARY DUE TO PRODUCT ENHANCEMENTS.
8 | Grandview® G800C Gas Fireplace

dimensions

Gas Installation Checklist

This general checklist does not contain all pertinent installation details or specifics and does not supersede the guidelines in this manual. Your Regency dealer/installer should use it in conjunction with manual instructions. Please follow all local codes and jurisdictions in authority.

Customer:

Date Installed:

Install Address:

Location of Fireplace:

Serial No:

Installer:

Model No:

Site Requirements

YES NO

If applicable, are the insulation, vapour barrier, and drywall present if installed on an outside wall or chase?
Does the area have a solid continuous base to support the unit? Will the area accommodate the size of the applliance and all clearances? Are the gas and electrical roughed into the area where the unit is being installed?
In City & Grandview series cool wall applications, is the chase enclosure sealed to prevent heat from escaping? All hot air from the unit must exit via the mandatory ventilation openings. In City & Grandview applications, Is the chase enclosure vented with the mandatory heat ventilation openings? See manual for details. If applicable, is the masonry/factory built freplace in its original condition with no modifications?
If applicable, have the hearth requirements been met?
Unit Setup

YES NO

If applicable, are the standoffs and top nailing flange extensions installed and at the correct depth to accommodate finishing material? See manual for details. If applicable, is the fireplace level and secured, meeting framing clearances? See manual for details. If applicable, is the unit converted to top or rear vent per manual instructions, and the insulation discarded?
Venting

YES NO

Are the venting components approved for the unit installed? Does the venting configuration comply with venting diagrams? Is venting installed and secured, and are clearances for the vent pipe and termination cap maintained? If applicable, was a 1/4″ rise maintained for every foot of horizontal run? Was the termination installed and sealed? Is the direct vent termination at the highest point in the vent assembly? If applicable, are both chimney liners continuous from flue collars to termination? Electrical and Wiring

YES NO

Is the appliance connected to the household’s 110/120v per local codes? Check local codes for receptacle placement. Were the connections in the fireplace tested with a circuit tester? Is the appliance properly grounded? If applicable, is the supplied electrical/gang box affixed to the wall to facilitate the mounting of the receiver/battery box ? Gas

YES NO

Does the supply pressure meet the requirements shown on the rating plate? Was a conversion performed? Was a leak check performed and manifold pressures verified? Is the shut-off valve installed and easily accessible to the customer?

Grandview® G800C Gas Fireplace | 9

installation
Finishing If applicable, is only noncombustible material installed in the noncombustible areas? Do clearances meet installation and manual requirements? Do the mantels and/or projections comply with the installation manual? If applicable, was the solid fuel fireplace warning plate installed? Appliance Media Setup Do commands from the remote or wall switch light the pilot and main burner? Are the burner media/log set, glass door, and screen installed per instructions in the manual? Was the air shutter on the proper setting after running the unit for 20 minutes? If applicable, were the surround and trims installed according to the manual? Was the operation of the fan, lights (if installed), and flame modulation checked? Customer Tutorial and Presentation Is the customer confident operating the new gas appliance and aware of all the features on the remote? Confirm that the rating and lighting plates are attached to the appliance. Do not remove. Was the customer informed of the location of the rating and lighting plates? Was accessing unit controls in a power outage explained to the customer? Are the model and serial numbers and the date of installation of the unit written in the manual and on the checklist? Were the warranty and unit registration reviewed with the customer? Comments:

YES NO YES NO YES NO

10 | Grandview® G800C Gas Fireplace

Before You Start
Safe installation and operation of this appliance requires common sense, however, we are required by the ANSI Standards to make you aware of the following:
INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.

YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME AREA AS THE APPLIANCE. TODDLERS, YOUNG CHILDREN AND OTHERS MAY BE SUSCEPTIBLE TO ACCIDENTAL CONTACT BURNS. A PHYSICAL BARRIERS IS RECOMMENDED IF THERE ARE AT RISK INDIVIDUAL IN THE HOUSE. TO RESTRICT ACCESS TO A FIREPLACE OR STOVE, INSTALL AN ADJUSTABLE SAFETY GATE TO KEEP TODDLERS, YOUNG CHILDREN AND OTHER AT RISK INDIVIDUALS OUT OF THE ROOM AND AWAY FROM HOT SURFACES.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
A BARRIER DESIGNED TO REDUCE THE RISK OF BURNS FROM THE HOT VIEWING GLASS IS PROVIDED WITH THIS APPLIANCE AND SHALL BE INSTALLED FOR THE PROTECTION OF CHILDREN AND OTHER AT-RISK INDIVIDUALS
ANY SAFETY SCREEN, GUARD, OR BARRIER REMOVED FOR SERVICING THE APPLIANCE, MUST BE REPLACED PRIOR TO OPERATING THE APPLIANCE.
IF THE BARRIER BECOMES DAMAGED, THE BARRIER SHALL BE REPLACED WITH THE MANUFACTURER’S BARRIER FOR THIS APPLIANCE.

owner’s information

Grandview® G800C Gas Fireplace | 11

owner’s information

Important Message
Save These Instructions
The G800C Direct Vent Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual first. Consult the “authority having jurisdiction” to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fireplace is installed in compliance with manufacturer’s instructions and all applicable codes.
General Safety Information
1. The appliance installation must conform with local codes or, in the absence of local codes, with the current National Gas Codes or ANSI Z223.1 Installation Codes.
2. The appliance when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes with the current National Electrical Code, ANSI/NFPA 70.
3. See general construction and assembly instructions. The appliance and vent should be enclosed.

13. Do not slam shut or strike the glass door.
14. Under no circumstances should any solid fuels (wood, paper, cardboard, coal, etc.) be used in this appliance.
15. The appliance area must be kept clear and free of combustible materials, (gases and other flammable vapours and liquids).
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
To Turn Appliance On/Off
1. Ensure pilot is lit. This appliance will not operate if the pilot is not lit. Follow the lighting instructions in manual to light pilot.
2. Locate the on/off switch located at the bottom right hand corner of the appliance.
3. Flick the switch to turn on or off the appliance.

Optional Fan Operation
1 If the optional fan has been installed, the speed of the fan can controlled by using the controller.
2. To control the speed of the fan, locate the fan speed controller located either on the underside of the firebox marked FAN with a dial and or the wall.
If installed on the underside of the firebox, the screen will need to be removed. See instructions in this manual. If wall mounted simply use the dial to control the speed of the fan.
Note:The fan may take 15-30 minutes to turn on as this appliance has a fan thermo disc. If the fan speed controller is turned to the ON position, the fan will turn on automatically when heated and turn OFF automatically when cooled down.

4. This appliance must be connected to the specified vent and termination cap to the outside of the
building envelope. Never vent to another room or inside a building. Make sure that the vent is
fitted as per Venting instructions.

5. Inspect the venting system annually for blockage and any signs of deterioration.

6. Venting terminals shall not be recessed into a wall or siding.

7. Any safety glass removed for servicing must be replaced prior to operating the appliance.

8. To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fireplace.
9. Wear gloves and safety glasses for protection while doing required maintenance.

ON/OFF Switch

10. Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination.

= ON

= OFF

11. Under no circumstances should this appliance be modified. Parts that have to be removed for servicing should be replaced prior to operating
this appliance.

12. Installation and any repairs to this appliance should be done by a qualified service person. A professional service person should be called to inspect this appliance annually. Make it a
practice to have all of your gas appliances
checked annually.

12 | Grandview® G800C Gas Fireplace

owner’s information

Lighting the Pilot Using the Gas Control Knob Extender

1. Remove the knob extender from its cradle located on the firebox floor in front of the gas valve. See below.

Cradle

Extender Knob

2. Slide the extender knob over the pilot/on/off knob located on the gas valve. See below. On/off/pilot knob on gas valve

Extender knob slid over on/off/pilot knob on gas valve

3. Follow instructions on how to light the pilot in this manual or the lighting plate located on the underside of the unit. 4. Once the pilot is lit, remove the extender knob and put it back into the cradle for future use.
Grandview® G800C Gas Fireplace | 13

owner’s information

Proflame I Remote Control Operating Instructions

IMPORTANT:The Proflame Transmitter 1 is an integrated part of the

Proflame 1 System, which consists of these elements:

·

Proflame 1 Transmitter, to be used in conjunction with:

·

Integrated Fireplaces Control (Proflame 1 DFG)

The Proflame 1 Transmitter provides for controlling the following hearth

appliance functions:

Main Burner On/Off

Main Burner flame modulation (6 levels)**

Thermostat and Smart thermostat functions

Accent light modulation (6 levels)**

Comfort Fan speed modulation (6 levels)**

** This feature is not available on all models.

TECHNICAL DATA REMOTE CONTROL

Supply Voltage

4.5V (three 1.5V AAA batteries)

Ambient temperature ratings
Radio Frequency

0 – 50oC (32 – 122oF) 315 MHZ

WARNING:THETRANSMITTER AND RECEIVER ARE RADIO FREQUENCY DEVICES. PLACING THE RECEIVER IN OR NEAR METAL MAY SEVERELY REDUCETHE SIGNAL RANGE.

The Proflame Transmitter uses a streamline design with a simple button layout and informative LCD display (Fig. 1). A Mode Key is provided to index between the features and a Thermostat Key is used to turn on/off or index through Thermostat functions (Fig. 1 & 2). Additionally, a Key Lock feature is provided (Fig. 22).

ATTENTION!
– Turn “OFF” the main gas supply of the appliance during installation or maintenance of the Receiver device.
– Turn “OFF” main gas supply to the appliance prior to removing or reinserting the batteries.

– In case of remote control malfunction, turn off the IFC device using the “ON/OFF” main switch.

– For installation / maintenance, switch off the IFC device removing main power supply plug.

Figure 1: Proflame Transmitter

OPERATING PROCEDURE
Pairing the remote control to remote receiver/battery holder (if required)
Install the 4 AA batteries into the receiver battery bay. Note the polarity of the battery and insert into the battery bay as indicated on the battery cover (+/-). Place the 3 position slider switch in the “Remote” position.. Press the PRG button located on the top right hand corner of receiver, see the receiver instruction(). The Receiver will “beep” three (3) times to indicate that it is ready to synchronize with a Transmitter. Install the 3 AAA type batteries in the Transmitter battery bay, located on the base of the Transmitter. (fig. 3) With the batteries already installed in the Transmitter, push the On button. The Receiver will “beep” four times to indicate the Transmitter’s command is accepted and sets to the particular code of that Transmitter. The system is now initialized.
(
)The receiver may be independent or integral to the IFC hearth appliance control module. The receiver instruction may not be independent when part of the IFC.

Figure 2: Transmitter LCD Display Note: May not be exactly as shown as hand- held may be silver or black.

14 | Grandview® G800C Gas Fireplace

Figure 3: Battery Compartment

owner’s information

Temperature indication Display

Room Thermostat (Transmitter Operation)

With the system in the “OFF” position, press the Thermostat Key and the Mode Key at the same time. Look at the LCD screen on the transmitter to verify that a C or F is visible to the right of the room temperature display (Figures 4 & 5).

The Remote Control can operate as a room thermostat. The thermostat can be set to a desired temperature to control the comfort level in a room. To activate this function, press the Thermostat Key (Fig. 1). The Lcd display on the Transmitter will change to show that the room thermostat is “ON” and the set temperature is now displayed (Fig. 9). To adjust the set temperature, press the Up or Down Arrow Keys until the desired set temperature is displayed on the LCD screen of the Transmitter.

Figure 4: Remote Control display in Farenheit.

Figure 5: Remote Control display in Celsius.

Turn on the Appliance
With the system OFF, press the ON/ OFF Key on the Transmitter. The Transmitter display will show some other active Icons on the screen. At the same time the Receiver will activate the appliance. A single “beep” from the Receiver will confirm reception of the command.
Figure 6: Remote Control display

Figure 9

Figure 10

KEY LOCK
This function will lock the keys to avoid unsupervised operation. To activate this function, press the MODE and UP Keys at the same time (fig.1281). To de- activate this function, press the MODE and UP Keys at the same time.

Turn off the Appliance
With the system ON, press the ON/OFF Key on the Transmitter. The Transmitter LCD display will only show the room temperature (Fig. 6). At the same time the Receiver will turn off the appliance. A single “beep” from the Receiver confirms reception of the command.

Figure 18

Grandview® G800C Gas Fireplace | 15

owner’s information
LOW BATTERY POWER DETECTION Transmitter
The life span of the remote control batteries depends on various factors: quality of the batteries used, the number of ignitions of the appliance, the number of changes to the room thermostat set point, etc. When the Transmitter batteries are low, a Battery Icon will appear on the LCD display of the Transmitter (Fig.1292) before all battery power is lost. When the batteries are replaced this Icon will disappear.
Figure 19
ENABLE / DISABLE functions on the Proflame I remote only. 1. Remove one battery from the remote. 2. Press and hold both the ON/OFF and the MODE button at the same time. 3. Reinstall the battery (removed in Step 1) while still holding both buttons (keep holding both buttons and
once all batteries are installed then release the MODE button only). 4. The screen will show CFG. 5. Use the up or down arrow button to program out the function on the remote.
16 | Grandview® G800C Gas Fireplace

owner’s information

Proflame I Remote Receiver Battery Replacement

Remote Receiver Battery Replacement

How to replace/add the batteries on remote receiver.

Note:4 AA batteries are mandatory in the remote receiver to operate appliance when using remote control.

The remote receiver will be located on the bottom right hand side of appliance next to the fan speed controller. The safety screen will need to be removed

to gain access to this remote receiver.
pl

pl by

g

phi ps

STEP 1

Move both the left/right slides as shown below.

The battery compartment will be pushed out slightly, to allow to easily extract it

STEP 2

Extract the battery compartment from the remote receiver/battery holder

Replace 4 x AA batteries and insert the battery compartment back into remote receiver/battery holder

STEP 3

Keeping the battery compartment pressed in, close the left slide

Close the right slide

STEP 4 Reinstall wall cover plate with 2 Phillips head screws.

Grandview® G800C Gas Fireplace | 17

operating instructions

Operating Procedure for Remote Control

Functionality of the Receiver
The receiver is supplied by four AA batteries (see Fig. 3). The receiver accepts commands via radio signals sent from the transmitter. The receiver sends commands by the wire harness to the multifunctional gas control. When the system is turned on, an acoustic signal (beep) is generated to indicate that the receiver is ready to receive commands from the remote control.
Turn on the Appliance
When the ON/OFF key is pressed, the LED on the transmitter illuminates and the remote control is switched on. At the same time, the receiver connects the thermopile to the gas valve millivolt coil and the appliance main burner turns on in the high position. A single acoustic signal from the receiver confirms the reception of the command.

Low Battery Detection (Receiver)
The duration of the remote control batteries depends on many factors: the quality of the batteries used, the number of ignitions of the appliance, etc. If the receiver batteries are low, a triple acoustic signal is emitted by the receiver when it receives a command from the transmitter. This is an alert of a low battery condition before battery power is lost altogether. As soon as the depleted batteries are replaced, the acoustic signal from the receiver confirms the reception of the ON/OFF command from the transmitter.
Backup Function
If the batteries of the receiver are low, the appliance can be switched on manually by moving the threeposition slider switch on the receiver to the ON position.

CAUTIONS

WARNINGS

Warnings and Cautions
· Fire hazard. Can cause severe injury or death.
· The receiver causes the ignition of the fireplace. The fireplace can turn on suddenly. Keep away from the burner, especially when operating the BACKUP switch.
· Property damage hazard. Excessive heat can cause property damage.
· The fireplace can stay ignited for many hours. Take care to turn off the fireplace if it is unattended by adults. Do not leave the remote control where children can reach it.

Turn Off the Appliance
If the appliance and the remote control are switched on and the ON/OFF key is pressed, the remote control is turned off. At the same time, the receiver removes power from the gas valve millivolt coil and the appliance main burner turns off. A double acoustic signal from the receiver confirms the reception of the command.

ON REMOTE OFF

18 | Grandview® G800C Gas Fireplace

Safety Screen Removal
1. Slide screen up.
2. Slide screen right.
3. Lower screen down.

owner’s information
Glass Door Removal
1. To remove the glass door – place both hands on either side of the latch. Pull forward then up to unlock, repeat on opposite side.
Important: After releasing the latches, support the weight of the door.
Latch locations
2. With both latches released, support the door with both hands and tilt out to approximately a 60 degree angle.
3. Lift the door up and out of lower slots to remove.

4. Swing screen outwards while
keeping the screen
level and remove.

Safety Screen Installation
1. To install the safety screen–Reverse steps above.

Glass Door Installation
1. To install the door–Reverse steps above. Grandview® G800C Gas Fireplace | 19

installer’s information

Installation Checklist
1. Locate appliance a) Room location (Refer to “Locating Your Gas fireplace” section) b) Clearances to Combustibles (Refer to “Clearances” section) c) Mantle Clearances (Refer to “Combustible Mantel Clearances” section) d) Framing & Finishing Requirements (Refer to “Framing & Finishing” section) e) Venting Requirements (Refer to “Venting” section)
2. Assemble Top Standoffs and Top Facing Support and Side Nailing Strips (Refer to “Unit Assembly Prior to Installation” Section). NOTE: Must be done before installing unit into place.
IMPORTANT: If installing the fan kit or changing this from rear vent to top vent, this must be completed prior to installing the appliance into the framed opening.
3. Install vent (Refer to “Venting” sections).
4. Make gas connections. Test the pilot. Must be as per Diagram (Refer to “Pilot Adjustment ” section).
Convert to propane if desired (Refer to “Gas Line Installation” and “Conversion Kit from NG to LPG” sections).

This includes:
1. Clocking the appliance to ensure the correct firing rate (rate noted on label 27,000 Btu/h for natural gas and propane), after burning appliance for 15 minutes.
2. If required, adjusting the primary air to ensure that the flame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
Locating Your Gas Fireplace
1. When selecting a location for your fireplace, ensure that the clearances are met.
2. The appliance must be installed on a flat, solid, continuous surface For example a wood, metal or concrete floor or in a raised (on the wall) application. The appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.
3. The G800C Gas Fireplace can be installed in a recessed position or framed out into the room as in A, B, C and D. See Diagram 1.

4. This appliance is Listed for bedroom installations using the standard Remote (millivolt thermostat system). Some areas may have further requirements, check local codes before installation.
5. The G800C Gas Fireplace are approved for alcove installations, see “Clearances” section for details.
6. We recommend that you plan your installation on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have an authorized inspector, dealer, or installer review your plans before installation.
HeatWave Duct System Optional Kit #946-556
The HeatWave Air Duct Kit increases the effectiveness of your fireplace by dispersing warm air from the fireplace to remote locations in the same room or other rooms in your home.
Up to two kits may be installed on the fireplace.
Please Note: Only 1 HeatWave kit may be operated at one time. This includes the internal blower option as well.

5. Make electrical connections to receptacle supplied with unit (recommended).
6. Install standard and optional features. Refer to the following sections:

The HeatWave Duct Kit has different
clearance and framing requirements, check the HeatWave manual for details.

a. Standard Glass Door b. Rear to top vent conversion
c. Coolwall conversion
d. Fan Installation (Optional) e. Nailing flange installation f. Electrical access/120 volt power installation
by others
g. Wall Mount On/OFf Switch + Receiver Installation
h. Coolwall Clearances/Framing/Finishing i. Clean Front Clearance/ Framing/Finishing j. Outside Finish Clearance/ Framing/
Finishing
k. LP Conversion (optional) l. Inner Panels or Brick Panels (Must install one
of the options) m. Media (Glass crystals) n. Log Set Installation o. HeatWave Kit

Diagram 1
A) Flat on Wall B) Flat on Wall Corner C) Recessed into Wall/Alcove D) Corner

7. Final check.

20 | Grandview® G800C Gas Fireplace

installation
Clearance / Framing and Venting Configurations
The G800C is designed to allow for unique installation options–depending on the desired finish. Please review the options and follow the specific clearance, framing, and finishing options for that application. The applications are as follows: Cool Wall Installation-Clean Front & Outside Finish: combustible materials can be installed right up to the fireplace opening with this option. Non Combustible Installation-Clean Front & Outside Finish Applications: non-combustible required when installing materials right to the fireplace opening with this option. See descriptive diagrams on the next page. Note: The topics listed below can be found in the pages that follow.
Cool Wall Installation (Combustible Finishing)…………………………………………….. 16 Non- Combustible Installation …………………………………………………………………. 16 Cool Wall installation/Cool Wall Conversion………………………………………………… 17 Cool Wall Clearances ……………………………………………………………………………. 18 Cool Wall Mantel Clearances………………………………………………………………….. 19 Cool Wall Mantel Leg Clearances …………………………………………………………….. 19 Cool Wall Installation – Framing………………………………………………………………. 20 Chase Venting…………………………………………………………………………………….. 21 Chase Vent Installation – Cool Wall …………………………………………………………. 22 Clean Front Installation (Non Cool Wall) – Clearances…………………………………… 23 Clean Front Installation (Non Cool Wall)–Mantel Clearances …………………………. 24 Clean Front Installation (Non Cool Wall) – Mantel Leg Clearances……………………. 25 Clean Front Installation (Non Cool Wall) – Non Combustible Requirements………… 25 Clean Front Installation – Framing (Non Cool Wall)………………………………………. 26 Clean Front Installation…………………………………………………………………………. 27 Nailing Flange Instructions…………………………………………………………………….. 27 Optional Clean Front Trim Install Instructions …………………………………………….. 27 Outside Finish Installation (Non Cool Wall) – Clearances ……………………………….. 28 Outside Finish Installation (Non Cool Wall) – Mantel Clearances ……………………… 29 Outside Finish Installation (Non Cool Wall) – Mantel Leg Clearances ………………… 29 Outside Finish Installation (Non Cool Wall)- Framing ……………………………………. 30 Outside Finish – Finishing ……………………………………………………………………… 31 Faceplate Install ………………………………………………………………………………….. 32 Finishing Trim Install ……………………………………………………………………………. 34 Unit Assembly Prior to Installation …………………………………………………………… 36 Nailing Flange Installation……………………………………………………………………… 37
Grandview® G800C Gas Fireplace | 21

installation
Cool Wall Installation (Combustible Finishing)
Cool Wall Install: · Vented chase · Combustible material can be used all around the fireplace · Combustible framing

Clean Front
Clean Front
Non-Combustible Installation
Standard Install: · Non-vented chase · Non-combustible board required · Combustible framing

Outside Finish w/ Finishing Trim

Clean Front
22 | Grandview® G800C Gas Fireplace

Outside Finish w/ Faceplate

Cool Wall installation/Cool Wall Conversion
1. Remove six (6) screws to remove top panel.

installation
4. Insert a large slotted screwdriver into the slot in between front and back tabs–bend the three (3) tabs up 90° towards the front. DO NOT REMOVE TABS

2. Remove insulation from top of unit and discard.

5 . Bend the rear three (3) tabs up 90° towards the back of the unit.

3. Slide out tab as shown to remove–recycle part.

6. Flip top panel 180° and reinstall to top of unit with four(4) screws in locations shown below.

Grandview® G800C Gas Fireplace | 23

installation

Cool Wall Clearances

The clearances listed below are minimum distances unless otherwise stated.

A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

Caution Requirements
The top, back and sides of the fireplace are defined by standoffs. The metal ends of the standoff may NOT be recessed into combustible construction.

WARNING
Fire hazard is an extreme risk If these clearances (air space) to combustible materials are not adhered to. It is of greatest importance that this fireplace and vent system be installed only in
accordance with these instructions.

G800C Clearance Requirements–Cool Wall Installations

Clearance:

Cool Wall – Clean Front

Measured From:

A: Mantel Height (min.)

**0″

Top of Fireplace Opening

B: Sidewall

6″ (152 mm)

Side of Fireplace Opening

C: Ceiling

47-1/2″ (1207 mm)

Top of Fireplace Opening

D: Mantel Depth (max.)

14″ (356 mm)

Front of Fireplace Opening

E: Alcove Width

84″ (2134 mm)

Wall to Wall (Minimum)

F: Alcove Depth

36″ (914 mm)

Front to Back Wall (Maximum)

G: Convection Air Outlet

66″sq (426 cm2)

Top/Front of Enclosure

H: Convection Air Outlet Opening Offset

0-2″ (51 mm)

*Top of Chase Enclosure

K: Chase Enclosure (Min.)

80″ (2032 mm)

From Base of Appliance Floor

L: Clearance to Sprinkler Head (Min.)

36″ (914 mm)

Perpendicular From Chase Grill

Notes:

0″

No Hearth Required

IMPORTANT – *A minimum of 66 square inches of open area, not lower than 0″-2″ from top of enclosure, required for all cool wall installations — this can be achieved by having an open area in front. See manual for details. ** An extra 3/4″ (19mm)of mantel height is required when using a faceplate.

The HeatWave Duct Kit has different
clearance and framing requirements, check the HeatWave manual for details.

H G

C

K

D

F

A

L
Chase grill

Sprinkler

Side view

E
E
F
Alcove 24 | Grandview® G800C Gas Fireplace

Minimum Vent Clearances to Combustibles

Horizontal Top Horizontal Side Horizontal Bottom Vertical Vent

2″ (51 mm) 1-1/2 ” (38 mm) 1-1/2″ (38 mm) 1-1/2″ (38 mm)

installation
Cool Wall Mantel Clearances
Due to the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing are shown in the diagram below.
Mantel Clearances
14 12 10 8 6 4 2

0

14″ 10

Combustible

5 0
Inches

7″
B C
A
To Floor

2″
Top of Fireplace Opening

Mantel Clearances G800C
From Top of Fireplace Opening

A

B

C

32-1/2″ (826 mm)

10″ (254 mm)

5″ (127 mm)

Note: Ensure the paint that is used on the mantel and the facing is “High Quality” or the paint may discolour.
Note: If Faceplate or Finishing Trim is being installed, leave 3-3/8″ clearance from from top of fireplace opening for installation and removal.

Cool Wall Mantel Leg Clearances

TopView

2″ (51mm)

MMaanntteell lleegg Mantel leg

Side opening of fireplace

32-3/4″ (832mm) overall fireplace width Clean finish

1-3/4″ (44mm)

3″ (76mm)

6″ (152 mm) Allowable mantel leg
projection

5″ (127 mm)

See framing dimensions on next page.

Grandview® G800C Gas Fireplace | 25

installation

Cool Wall Installation – Framing

Framing Dimensions Description

M N* O P
Q
R S (Rear Vent) S (Top Vent) T U V W

Framing Width Framing Height Framing Depth Corner Facing Wall Width Corner Facing Wall Width Framed Chase Ceiling Enclosure Vent Centerline Height – Rear Vent Centerline Height – Top Gas Connection Height Gas Connection Inset Gas Connection Width Clearance to Corner of Unit

Cool Wall 36-1/2″ (927mm)

Cool Wall with Finishing Trim or Faceplate
37-1/2″ (952mm) 43″ (940 mm) 16-7/8″ (427 mm) 42-1/2″ (1035 mm)
60″ (1524 mm)
80″ (2032 mm) 29″ (737 mm) 44″ (1118 mm) 1-1/2″ (38 mm) 6-3/8″ (162 mm)
3″ (76 mm) 2-3/4″ (70 mm)

  • Important: Framing height requires consideration of the hearth height. Dimension N = N + the thickness of the installed hearth.
    Note: The 2 standoffs at the rear of the appliance may be removed as these are not required in this application. Ensure that any screws that are removed are reinstalled. The 2 standoffs can eb recycled/discarded.

R

Combustible header
N M

Top Vent

Rear Vent

O
S S

P W

Q
Corner=Top Vent Only
IMPORTANT: Corner applications are vented from the top only – rear venting cannot be used.

T VU

26 | Grandview® G800C Gas Fireplace

installation
Chase Venting
Note: The enclosure opening cannot be any lower than 0-2″ (0-51 mm) from the top of the enclosure for all installations. Minimum height of enclosure from base of appliance is 80″ (2032 mm).
A minimum 66 in2 opening in the enclosure is required to maintain safe operating temperatures. This can be achieved in a number of ways including the examples shown below.
Warning: DO NOT cover or place objects in front of the air outlet(s).

Regency Chase Vent

Custom chase vent

Reveal at the chase top

Grandview® G800C Gas Fireplace | 27

installation
Chase Vent Installation – Cool Wall
Framed Opening must be at least 2-3/8″ (60mm) tall, and at least 33-3/8″ (848mm) wide to accomodate the Chase vent. The top of the Chase vent opening must be 2″ (51 mm) or less from the top of the chase enclosure. Fasten the Chase vent with screws and construction adhesive. If the optional Regency chase vent is not being used, a minimum 66in2 (426cm2) opening in the enclosure is required to maintain safe operating temperatures. This can be achieved in a number of ways including a reveal at the top of the chase.

Max. 2″

Side View
Ceiling Top of chase enclosure

Max. 2″

Ceiling

28 | Grandview® G800C Gas Fireplace

installation

Clean Front Installation (Non Cool Wall) – Clearances

The clearances listed below are minimum distances unless otherwise stated.

A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

Caution Requirements
The top, back and sides of the fireplace are defined by standoffs. The metal ends of the standoff may NOT be recessed into combustible construction.

WARNING
Fire hazard is an extreme risk if these clearances (air space) to combustible materials are not adhered to. It is of greatest importance that this fireplace and vent system be installed only in accordance with these
instructions.

G800C Clearance Requirements

Clearance:

Dimension

A: Mantel Height (min.)

11-1/2″ (292 mm)

B: Sidewall

25″ (635 mm)

C: Ceiling

36-1/2″ (927 mm)

D: Mantel Depth (max.)

19″ (483 mm)

E: Alcove Width

84″ (2134 mm)

F: Alcove Depth

36″ (914 mm)

Notes:

0″

Measured From: Top of Fireplace Opening
Side of Fireplace Opening Top of Fireplace Opening Front of Fireplace Opening
Wall to Wall (Minimum) Front to Back Wall (Maximum) No Hearth Required

The HeatWave Duct Kit has different
clearance and framing requirements, check the HeatWave manual for details.

C D
A

Minimum Vent Clearances to Combustibles

Horizontal Top Horizontal Side Horizontal Bottom Vertical Vent

2″ (51 mm) 1-1/2 ” (38 mm) 1-1/2″ (38 mm) 1-1/2″ (38 mm)

F

E
E
F Alcove

Grandview® G800C Gas Fireplace | 29

installation
Clean Front Installation (Non Cool Wall)–Mantel Clearances
Due to the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing are shown in the Diagram on the right. Note: Ensure the paint that is used on the mantel and the facing is “High Quality” or the paint may discolour.
Mantel Clearances
18 16 14 12 10 8 6 4 2

0

24 19″
12 0
Inches

Combustible

12″
7″
BC

Non-Combustible

D

Material Min.11-1/2″H (292mm) Material Max. 2″D (51mm)

A
To Floor

Top of Fireplace Opening

Mantel Clearances G800C
From Top of Fireplace Opening

A

B

C

D

32-1/2″ (826 mm)

20-1/2″ (597 mm)

15-1/4″ (470 mm)

11-1/2″ (292 mm)

30 | Grandview® G800C Gas Fireplace

Clean Front Installation (Non Cool Wall) – Mantel Leg Clearances

installation

TopView
Side opening of fireplace

Allowable mantel leg projection (38mm)

4-1/4″ (108mm)

2″ (51mm)

*3322–13//24″”((882362mmmm) ) OverallOFvireerpallal FceireWpiladcthe (wCildetahn Finish)

Mantel Leg Mantel leg

1-1/2″ (38mm)

5″
3″ (76mm)

6-7/8″ (175mm)

Clean Front Installation (Non Cool Wall) – Non Combustible Requirements

37-1/2″ [953mm] No Combustible Materials in this Area

11-1/2″ [292 mm]

NO FACING OR FINISHING MATERIAL
IN THIS AREA

30-7/8″ [784 mm]

3″ [76mm]

32-3/4″ 832mm

3″ [76mm]

1-5/8″ (41 mm)

See framing dimensions on next page.

Grandview® G800C Gas Fireplace | 31

installation

Clean Front Installation – Framing (Non Cool Wall)

Framing Dimensions M N* O P (Top Vent Only) Q (Top Vent Only) R S (Rear Vent) S 1 (Top Vent) T U V W

Description Framing Width Framing Height Framing Depth – Top Vent Corner Facing Wall Width Corner Facing Wall Width Framed Chase Ceiling Vent Centerline Height – Rear Vent Centerline Height – Top Gas Connection Height Gas Connection Inset Gas Connection Width Clearance to Corner of Unit Non- combustible Height

G800C – Non Cool Wall 37-1/2″(953 mm) 43″ (1092 mm) 19-1/4″ (489 mm) 46-1/2″ (1181 mm) 65-3/4″ (1670 mm) 62″ (1575 mm) 29″ (673 mm) 44″ (1118 mm) 1-1/2″ (38 mm) 6-3/8″ (162 mm) 3″ (76 mm) 2-3/4″ (70 mm) 11-1/2″ (292 mm)

  • Important: Framing height requires consideration of the hearth height. Dimension N = N + the thickness of the installed hearth.

R

Combustible header
N M

Top Vent

Rear Vent

O S1S
S

P W
Q
Corner=Top Vent Only IMPORTANT: Corner applications are vented from the top only – rear venting cannot be used.

T VU

32 | Grandview® G800C Gas Fireplace

Clean Front Installation
The finishing material can be brought to the edge of the fireplace opening. Do NOT finish beyond the opening, doing so will prevent the screen from being attached and removed. The Optional Clean Front Trim (Part # 761-929) is available to prevent this from happening. See Section: Clean Front trim install instruCtions for details.
Nailing Flange Instructions
1. Bend framing tabs 90° backward to create the framing standoff.
Framing Tab

installation

Optional Clean Front Trim

Optional Clean Front Trim Install Instructions
(Part # 761-929)

1. Loosen the four (4) screws that at-
tach the right and left nailing flanges to the unit.

2. Slide the left and right tiling flanges onto the front of the fireplace. Use the slots to center with the screw securing
the Nailing Flanges.

max.

3. Tighten screws down.

4. Slide the Bottom Tiling Flange against
the bottom of the fireplace. Secure with a screw on each side.

5. Finishing material can now be pressed
against the flat edge created by the Clean Front Trim.

Grandview® G800C Gas Fireplace | 33

installation

Outside Finish Installation (Non Cool Wall) – Clearances

The clearances listed below are minimum distances unless otherwise stated.
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

Caution Requirements
The top, back and sides of the fireplace are defined by standoffs. The metal ends of the standoff may NOT be recessed into combustible construction.

WARNING
Fire hazard is an extreme risk if these clearances (air space) to combustible materials are not adhered to. It is of greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

G800C Outside Finish Clearance Requirements

Clearance:

Dimension

Measured From:

A: Mantel Height (min.)

10″ (254 mm)

Top of Fireplace Opening

B: Sidewall

25″ (635 mm) one side only Side of Fireplace Opening

C: Ceiling

36-1/2″ (927 mm)

Top of Fireplace Opening

D: Mantel Depth (max.)

12″ (305 mm)

Top of Fireplace Opening

E: Alcove Width

84″ (2134 mm)

Wall to Wall (Minimum)

F: Alcove Depth

36″ (914 mm)

Front to Back Wall (Maximum)

Notes:

0″

No Hearth Required

C
D F
A

Minimum Vent Clearances to Combustibles

Horizontal Top Horizontal Side Horizontal Bottom Vertical Vent

2″ (51 mm) 1-1/2 ” (38 mm) 1-1/2″ (38 mm) 1-1/2″ (38 mm)

E

E
F
Alcove 34 | Grandview® G800C Gas Fireplace

installation
Outside Finish Installation (Non Cool Wall) – Mantel Clearances
Due to the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing are shown in the diagram below.
Mantel Clearances
14 12 10 8 6 4 2

0

24 12 0
Inches

Combustible

12″ 7″

1″

B

C

D

Non-Combustible Material Min. 10″ H (254mm)

A
To Floor

Top of Fireplace

Mantel Clearances G800C
From Top of Fireplace Opening

A
34″ (754 mm)

B
19″ (483 mm)

C
15″ (381 mm)

D
10″ (254 mm)

Note: Ensure the paint that is used on the mantel and the facing is “High Quality” or the paint may discolour.

**The non combustible board supplied with the appliance is 11-1/2″ (292mm) high. This may be cut to size if desired.

Outside Finish Installation (Non Cool Wall) – Mantel Leg Clearances

TopView

Side opening of fireplace

4-1/4″ (108mm)

1-1/2″ (38 mm)

35-7/8″ (912 mm) Overall Fireplace Width (Outside Finish)

6-7/8″ (175mm)
Allowable mantel leg projection

LMeagntel Mantel Leg
3″ (76 mm)

Grandview® G800C Gas Fireplace | 35

installation

Outside Finish Installation (Non Cool Wall)- Framing

Framing Dimensions Description

Outside Finish

Outside finish with Finishing Trim or Faceplate

M

Framing Width

36-1/2″ (927 mm)

37-1/2″ (953 mm)

N*

Framing Height

O

Framing Depth

43″ (1092 mm) 19-1/4″ (489 mm)

P (Top Vent Only)

Corner Facing Wall Width

46-1/2″ (1181 mm)

Q (Top Vent Only) R

Corner Facing Wall Width Framed Chase Ceiling

65-3/4″ (1670 mm) 62″ (1575 mm)

S (Rear Vent)

Vent Centerline Height – Rear

29″ (673 mm)

S1 (Top Vent)

Vent Centerline Height – Top

44″ (1118 mm)

T

Gas Connection Height

1-1/2″ (38 mm)

U

Gas Connection Inset

6-3/8″ (162 mm)

V

Gas Connection Width

3″ (76 mm)

W

Clearance to Corner of Unit

2-3/4″(70 mm)

Non-combustible Height

10″ (254 mm)

  • Important: Framing height requires consideration of the hearth height. Dimension N = N + the thickness of the installed hearth.

R

Combustible header
N M

Top Vent

Rear Vent

O

S1S

S

P W
Q
Corner=Top Vent Only IMPORTANT: Corner applications are vented from the top only – rear venting cannot be used.
36 | Grandview® G800C Gas Fireplace

T VU

Outside Finish – Finishing
Finishing Material may be brought to the top and side edges of the fireplace, as shown below.

installation

Grandview® G800C Gas Fireplace | 37

installation
Faceplate Install (Part # 761-922, 761-924, 761-926)
Faceplate – Finishing: The finishing material can be brought to the top of the fireplace. A 1/2″ gap must be maintained on the sides to allow the Faceplate to be installed. The finishing material must not protrude past the front face of the fireplace. Follow the steps below to install.
See section: Nailing flange install for Nailing Flange Depth settings.

1. Bend the four mounting tabs on the outer box Front 90° forward. There are two tabs per side.

2. Bend the tabs on the left and right nailing flanges 90° forward.There are twotabs per nailing flan.ge These tabs are used to stop finishing material from interfering with the faceplate mounts.

Mounting Tabs 38 | Grandview® G800C Gas Fireplace

Top and Side Nailing Flange Tabs

Faceplate – Finishing: A 1/2″ gap must be maintained on the sides of the fireplace to allow the Face Plate to be installed and removed.
Do NOT finish past the front face of the fireplace.
Top View
3 ” (19 mm) 4

Mounting Tab Folded forward

Framing

Face Plate

Nailing Flange folded forward

installation
Nailing Flange Tabs folded forward
Mounting Tabs folded forward

Install the faceplate by resting the arms on the Face Plate on top of the mounting tabs. Adjust left and right to center the Face Plate. NOTE: Do not touch the faceplate without clean, soft, gloves. Dirt or oils can be transferred onto the finish and become permanent.
Critical Finishing Gap
Grandview® G800C Gas Fireplace | 39

installation
Finishing Trim Install (Part # 761-928)
The Finishing Trim can be installed to upgrade the look of the fireplace or to cover facing material edges.
1. Lay the parts on a soft surface painted side down. 2. Insert the tab on the left side into the slot on the top. 3. Fold the tabs down to secure. 4. Insert the tab on the top into the slot on the right. 5. Fold the tab down to secure.
See section: NAILING FLANGE INSTALL FOR NAILING FLANGE DEPTH SETTINGS.

Left Side Right Side

Finishing Trim Install Instructions: 1. Bend the four tabs on the outer box front forward. There are two tabs per side.
These tabs are the mounts for the faceplate or finishing trim.
2. Bend the two tabs on the top nailing flange down.
3. Bend the tabs on the left and right nailing flanges forward. There are two tabs per nailing flange.

40 | Grandview® G800C Gas Fireplace

Top and Side Nailing Flange Tabs

Finishing Trim – Finishing:
A 1/2″ gap must be maintained on the sides and top of the fireplace to allow the Finishing Trim to be installed and removed. The finishing trim has adjustment for material to protrude up to 1/4″ past the front of the finishing trim.
Install the faceplate by resting the arms on the finishing trim on the top of the mounting tabs.
Adjust left and right to center the finishing trim.

installation

Side View

Top Nailing Flange Tabs folded down

Nailing Flange Tabs folded forward

Mounting Tabs folded forward

Critical Finishing Gap

Top View

3″ 4

Mounting Tab Folded forward

Finishing Trim

Nailing Flange folded forward

Grandview® G800C Gas Fireplace | 41

installation
Unit Assembly Prior to Installation After the framing has been built, the nailing Flanges will need to be set depending on the depth of finishing material being used. Up to 1-1/4″ total material thickness can be used, including the backing material. The depth of finishing material can be adjusted in 1/4″ increments.
1. Determine the required depth setting for the materials being used.
2. Once the setting has been chosen, install the Left and Right Nailing Flanges with 2 screws on each Flange.

Left Nailing Flange Right Nailing Flange Standoff Deflector
Top Nailing Flange

Nailing Flange Parts

Finishing Material Depth

1-1/4″ 1″

3/4″ 1/2″

Flush 1/4″ Setting

Front of Fireplace

42 | Grandview® G800C Gas Fireplace

Nailing Flange Installation 3. Screw one screw into the rear hole on each Side Nailing Flange. 4. Install the Top Nailing Flange with 4 screws.
Top Nailing Flange

installation

5. Slot the Standoff Deflector onto the back screws, then secure the with a screw through the remaining front hole on each flange.
Standoff Deflector

CLEAN FRONT
Backing Material (Drywall etc.)
Finishing Material
Flush Finishing Material

OUTSIDE FINISH
Distance to combustible material varies with
install

Backing Material (Drywall etc.) Finishing Material
Total Material Maximum Depth: 1-1/4″
Grandview® G800C Gas Fireplace | 43

installation
Wall Board/Drywall Installation
WARNING! Risk of Fire! Comply with all minimum clearances to combustibles as specified. Finishing Instructions: It is important to follow the framing and finishing instructions to ensure proper placement of fireplace into the surrounding framing/finishing materials. Wall board materials 1/2 in. thick are specified in this installation manual to properly align with the optional finishing methods offered with this appliance. The G800C may be finished to the appliance opening with 1/2 inch thick drywall or non combustible material depending on the application and requirements. The nailing flanges allow for adjustments of up to 1-1/4″ thickness of material. · Ensure that the back and side clearances are maintained. WARNING! Risk of Fire! Maintain specified air space clearances to combustibles. Inadequate air space could cause overheating and fire. The appliance is designed to be used with 1/2 in. wall sheathing materials such as drywall, plywood, wood composites, or non-combustible materials. Thicker materials may be used. Refer to facing and finishing details in this manual. Facing Material · Facing and/or finishing materials must never overhang into the glass opening. · Facing materials may be combustible or non-combustible WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum clearances. Comply with all minimum clearances to combustibles as specified in this manual. Overlapping materials could ignite and will interfere with proper operation. PAINTING If desired finishing includes a painted wall, 100% acrylic latex, oil-based or standard acrylic paints may be used. Follow paint manufacturer’s instructions for paint and primer application.
NO SCREW ZONE
44 | Grandview® G800C Gas Fireplace

installation

Conversion to Top Vent
Note: This conversion must be done prior to the unit being placed in position.

Important: Loosen bottom screws only and slide inner and outer collar up and off unit.

The unit comes equipped as a rear vent unit. These instructions are to be used, only if the unit is going to be top vented.

Remove outer collar

1. Remove six (6) screws in locations shown below to remove vent cover plate.

Remove screws

Vent cover plate

Diagram 3

Loosen

Diagram 1

4. From the top of the unit–remove the top cover plate by removing the two (2) top screws and loosening the two (2) bottom screws. Slide cover plate up and off to remove.

2. Using a magnetic drill bit–remove the two (2) top screws and loosen two(2) bottom screws to remove outside collar from the back of the unit. See Diagram 3.
3. Remove the four (4) top screws and loosen the two (2) bottom screws to remove in the inner collar from the back of the unit. See Diagram 3.
Note: Tale care not to drop any screws into the unit.

Diagram 4 – Top of Unit 5. Remove the insulation from the top of the unit as shown and discard.

Diagram 2 – Back of Unit

Diagram 5

Grandview® G800C Gas Fireplace | 45

installation

6. Remove the Exhaust Cover Plate marked: DISCARD, and discard plate.
7. Remove the four (4) top screws and loosen the two (2) bottom screws to remove in the inner cover plate from the top of the unit.

9. Install the top cover plate (removed from the top in Step 4) to the back of the unit. Slide the plate onto the two (2) loosened screws and tighten all 4 screws.

10. Install inner collar (removed from the back in Step 3) to the top . Slide collar onto loosened screws and tighten all six (6) additional screws.
11. Install outer collar (removed from the back in Step 2) to top of unit. Slide
Diagram 6 8. Install the inner cover plate removed from the top in Step 7–to the back
of the unit. Slide the plate onto the two (2) loosened screws and tighten all six (6) screws.
collar onto two (2) loosened screws and tighten all four (4) additional screws. 12. Reinstall vent cover plate (removed in Step 1) with six (6) screws.
Diagram 7 46 | Grandview® G800C Gas Fireplace

Vent Restrictor Installation
1. Determine the venting configuration. Note: The Set 1/Set 2 vent restrictor plate is installed from the factory to Set 1 (2″ open). Set 3 uses a separate restrictor plate, which is found in the manual package.
2. Go to venting arrangements section (in the manual) to determine if a vent restrictor setting is required. (If required, proceed to Step 3).
3. Loosen the two screws that secure the top heat deflector and remove top heat deflector (diagram 1).
4. Align the vent restrictor plate (found in the manual package) to the required vent restrictor position as per the Diagrams shown.
5. Once the vent restrictor plate is in the required position, secure with 2 1/4″ x 1/2″ screws. Ensure all screws are tight, but do not over tighten.
4. Align the vent restrictor plate (found in the manual package) to the required vent restrictor position as per the Diagrams shown.
5. Once the vent restrictor plate is in the required position, secure with 2 1/4″ x 1/2″ screws. Ensure all screws are tight, but do not over tighten.

installation
Diagram 1: Top heat deflector

Restrictor plate for Set 1, Set 2 (Part # 761-060F)
Set 0 Fully Open

Restrictor plate for Set 3 (Part # 761-143F)
Set 1 2″ Open Factory Setting

Diagram 2: Vent restrictor located on top exhaust assembly
Venting Introduction
The G800C uses the “balanced flue” technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These flue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it’s own separate vent system. Common vent systems are prohibited.

Set 2 1-3/4″ Open

Set 3 1-1/4″ Open

Grandview® G800C Gas Fireplace | 47

installation
Exterior Vent Termination Requirements

Minimum Clearance Requirements

USA2

A Clearance above grade, veranda, porch, deck, or balcony

12″ (30 cm)

B Clearance to window or door that may be opened C Clearance to permanently closed window

9″ (23 cm) *

D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61cm) from the center line of the terminal (check with the local code)
E Clearance to unventilated soffit F Clearance to outside corner: with AstroCap Termination Cap.
Clearance to outside corner: with all other approved Termination Caps.
G Clearance to inside corner: with AstroCap Termination Cap Clearance to inside corner: with all other approved Termination Caps.
H Clearance to each side of center line extended above meter/regulator assembly J Clearance to service regulator vent outlet

24″ (60 cm)
19″ (48 cm) 13″ (33 cm) 13″ (33 cm) 11″ (28 cm) 11″ (28 cm)

K Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance L Clearance to a mechanical air supply inlet 3′ (91 cm) above if within 10′ (3 m) horizontally.

9″ (23 cm) 36″ (91 cm)

M Clearance above paved sidewalk or a paved driveway located on public property

N Clearance under veranda, porch, deck, or balcony

1 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both

dwellings

Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor

a *

Clearance in accordance with local 3 feet (91cm) within a height of 15

installation codes and the requirements of the gas feet (4.5m) above the meter / regulator assembly

supplier

b 3 feet (91cm) above – if within 10 feet (3m) horizontally

48 | Grandview® G800C Gas Fireplace

installation

4″ X 6-5/8″ (102 mmx 168 mm) Rigid Pipe – Cross Reference Chart Only

Components from different Manufacturers may not be mixed. Not all Rigid Pipe components are available directly from FPI. Non-metallic venting systems shall not interchange components with another listed or unlisted metallic vent system.
Note: Olympia Ventis DV is only approved for certain models. See list of approved models in cross-reference chart.

Description
6″ Pipe Length-Galvanized 6″ Pipe Length-Black 7″ Pipe Length-Galvanized 7″ Pipe Length-Black 9″ Pipe Length-Galvanized 9″ Pipe Length-Black 12″ Pipe Length-Galvanized 12″ Pipe Length-Black 18″ Pipe Length-Galvanized 18″ Pipe Length-Black 24″ Pipe Length-Galvanized 24″ Pipe Length-Black 36″ Pipe Length- Galvanized 36″ Pipe Length-Black 48″ Pipe Length-Galvanized 48″ Pipe Length- Black 60″ Pipe Length-Galvanized 60″ Pipe Length-Black

Simpson Direct Vent Pro®
46DVA-06 46DVA-06B N/A N/A 46DVA-09 46DVA-09B 46DVA-12 46DVA-12B 46DVA-18 46DVA-18B 46DVA-24 46DVA-24B 46DVA-36 46DVA-36B 46DVA-48 46DVA-48B 46DVA-60 46DVA-60B

*Selkirk Direct TempTM
4DT-6 4DT-6B N/A N/A 4DT-9 4DT-9B 4DT-12 4DT-12B 4DT-18 4DT-18B 4DT-24 4DT-24B 4DT-36 4DT-36B 4DT-48 4DT-48B 4DT-60 4DT-60B

*American Metal Products® Amerivent Direct N/A N/A 4D7 4D7B N/A N/A 4D12 4D12B 4D18 4D18B 4D24 4D24B 4D36 4D36B 4D48 4D48B N/A N/A

*Metal-FabTM Sure Seal
4D6 4D6B N/A N/A N/A N/A 4D12 4D12B 4D18 4D18B 4D24 4D24B 4D36 4D36B 4D48 4D48B N/A N/A

*Security

*ICC Excel

Secure- Vent® Direct

SV4L6 SV4LB6 N/A N/A N/A N/A SV4L12 SV4LB12 SV4LA SV4LA SV4L24 SV4LB24 SV4L36 SV4LB36 SV4L48 SV4LB48 N/A N/A

TC-4DL6 TC-4DL6B N/A N/A TC-4DL9 TC-4DL9B TC-4DL1 TC-4DL1B TC-4DL18 TC-4DL18B TC-4DL2 TC-4DL2B TC-4DL3 TC-4DL3B TC-4DL4 TC-4DL4B N/A N/A

*Olympia Ventis DV***
VDV-0406 VDVB-0406 N/A N/A VDV-0409 VDVB-0409 VDV-0412 VDVB-0412 VDV-0418 VDVB-0418 VDV-0424 VDVB-0424 VDV-0436 VDVCB-0436 VDV-0448 VDVB-0448 N/A N/A

Adjustable Length 3″-10″-Galvanized N/A

N/A

Adjustable Length 3″-10″-Black

N/A

N/A

Adjustable Length 7)-Galvanized

N/A

N/A

Adjustable Length 7″-Black

N/A

N/A

Extension Pipe 8-1/2″-Galvanized

46DVA-08A

N/A

Extension Pipe 8-1/2″-Black

46DVA-08AB

N/A

Adjustable Length 12″-Galvanized N/A

N/A

Adjustable Length 12″-Black

N/A

N/A

Extension Pipe 16″-Galvanized

46DVA-16A

N/A

Extension Pipe 16″-Black

46DVA-16AB

N/A

N/A N/A 4D7A 4D7AB N/A N/A 4D12A 4D12A N/A N/A

4DAL 4DALB N/A N/A N/A N/A N/A N/A N/A N/A

N/A

TC-4DLT

N/A

N/A

TC-4DLTB

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

SV4LA12

TC-4dLSI

N/A

SV4LBA12

TC-4dLSIB

N/A

N/A

N/A

N/A

N/A

N/A

N/A

45º Elbow-Galvanized 45º Elbow-Black 45º Elbow Swivel-Galvanized 45º Elbow Swivel-Black 90º Elbow-Galvanized 90º Elbow-Black 90º Elbow, Swivel-Galvanized 90º Elbow, Swivel-Black 90º Starter Elbow, Swivel-Galvanized Adaptor*

46DVA-E45

4DT-EL45

46DVA-E45B

4DT-EL45B

See 46DVA-E45 N/A

See 46DVA-E45B N/A

46DVA-E90

4DT-EL90S

46DVA-E90B

4DT-EL90SB

See 46DVA-E90 N/A

See 46DVA-E90B N/A

N/A

N/A

N/A

N/A

4D45L 4DT-EL45B N/A N/A 4DT-EL90S 4DT-EL90SB N/A N/A N/A N/A

N/A N/A 4D45L 4D45LB N/A N/A 4D90L 4D90LB 4D90A 4D90L

N/A N/A SV4E45 SV4EB45 N/A SV4EBR90-1 SV4E90-1 wSV4EB90-1 N/A N/A

TE-4DE45 TE-4DE45B N/A N/A TE-4DE90 TE-4DE90B N/A N/A N/A N/A

VDV-EL0445 VDVB-EL0445 N/A N/A VDV-EL0445 VDVB-EL0445 N/A N/A N/A VDV-UAA04

Ceiling Support Cathedral Support Box Wall Support/Band Offset Support Wall Thimble-Black Wall Thimble Cover/Ceiling Support Firestop Spacer Trim Plate- Black * Not available from Regency

N/A 46DVA-CS 46DVA-WS 46DVA-ES 46DVA-WT 46DVA-DC 46DVA-FS N/A

4DT-CS 4DT-CSS 4DT-WS/B 4DT-OS 4DT-WT N/A 4DT-FS 4DT-TP

4DSP 4DRSB 4DWS N/A 4DWT N/A 4DFSP 4DFPB

4DFSP 4DRS 4DWS N/A 4DWT N/A 4DFS 4DcP

SV4SD SV4CSB SV4BM SV4SU SV4RSM SV4PF SV4BF SV4LA

TM4-RDS TM4-SDS TM-SWS TM-SOS N/A N/A TM-4CS TM-4TP

VDV-SCR04 VDV-CSS04 VDV-WS04 N/A VDV-WPT04 N/A VDV-FS04 VDV-WTC04

Grandview® G800C Gas Fireplace | 49

installation

Description

Simpson Direct Vent Pro®

Attic Insulation Shield 12″

46DVA-IS

Attic Insulation Shield – Cold Climates 36″ N/A

*Selkirk

*American Metal

Direct TempTM Products®

Amerivent Direct

N/A

4DAIS12

N/A

4DAIS12

*Metal-FabTM Sure Seal
4DIS N/A

*Security Secure- Vent®
SV4RSA N/A

*ICC Excel Direct
N/A TM-4AS

*Olympia Ventis DV***
VDV-AIS04 N/A

Basic Horizontal Termination Kit (A) Horizontal Termination Kit (B) Vertical Termination Kit

46DVA-KHA N/A N/A

4DT-HKA 4DT-HKB 4DT-VKC

4DHTK2 4DHTK1 4DHTK

4DHTKA 4DHTKB 4DHTK

SV-SHK SV-HK SV-FK

TM4-HTK TM4-HTK N/A

VDV-KW04 VDV-K04 N/A

High Wind Vertical Cap High Wind Horizontal Cap
Horizontal Square Termination Cap Vertical Termination Cap Storm Collar

46DVA-VCH N/A
46DVA-HC 46DVA-VC 46DVA-SC

N/A N/A
4DT-HHC 4DT-HVC 4DT-SC

N/A N/A
4DHC 4DVC 4DSC

N/A N/A
4DHT 4DVT 4DSC

N/A N/A
SV4CHC-1 SV4CGV-1 SV4FC

TM-4VT TM-4DHT
TM-4HT N/A TM-SC

VDV-VCHW04 N/A
VDV-HC04 N/A VDV-SC04

Flashing – Flat Roof Adjustable Flashing 0/12-6/12 Adjustable Flashing 6/12-12/12
Vinyl Siding Standoff Vinyl Siding Shield Plate

46DVA-FF 46DVA-F6 46DVA-F12
46DVA-VSS N/A

N/A 4DT-ST14 4DT-ST36
4DT-VS 4DT-VSP

N/A 4D12S 4D36S
N/A N/A

N/A 4DF 4DF-12
4DVS N/A

N/A SV4STC14 SV4STC36
SV4VS SV4VS

N/A TF-4FA TF-4FB
TM-VSS N/A

N/A VDV-F0406 VDV-SSO
N/A N/A

Snorkel Termination 14″ Snorkel Termination 36″

46DVA-SNK14

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

TM-4ST14 N/A TM-4ST36 N/A

Wall Firestop

46DVA-WFS

N/A

N/A

N/A

N/A

TM-4TR

VDV-FS04

  • Not available from Regency
    ***Olympia Ventis DV application for the following units only when using 4″ x 6-5/8″ vent system: B36XTE, B36XTCE, all City Series 40 models, CV72E/CB72E (power-vented models only), G600C, G600C-1, G600EC, G800C, G800C-1, G800EC, P36, P36E, and RC500E.

FPI 946-506/P **510-994 640-530/P

Vent Guard (Optional) for AstroCap Rigid Pipe Adaptor (Must use with all rigid piping) Riser Vent Terminal

946-205 946-208/P 946-523/P 946-206

Vinyl Siding Shield for Riser Vent Terminal Vent Guard (Optional) for Riser Vent Terminal AstroCap Horizontal Cap Vinyl Siding Standoff for AstroCap

**The rigid pipe adaptor is not required on the C34, C34E, U39, U39E, H15, H27, H35 & RC500E. Note: When using Metal-Fab Sure Seal Rigid Piping – please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).

Offset Pipe Selection: Use this table to determine offset pipe lengths.

Pipe Length (L)

4″ x 6-5/8″ Venting

Run (X)

Rise (Y)

For specific instructions on venting components – visit the manufacturers website listed below.

0″ (0mm)

4-7/8″ (124mm)

13-7/8″ (340mm)

Simpson Direct Vent Pro: www.duravent.com

6″ (152mm)

8″ (203mm)

16-1/2″ (419mm)

Selkirk Direct-Temp: www.selkirkcorp.com

9″ (229mm)

10-1/8″ (257mm)

18-5/8″ (473mm)

American Metal Products: www.americanmetalproducts.com

12″ (305mm)

12-1/4″ (311mm)

20-3/4″ (527mm)

Metal-Fab Sure Seal: www.mtlfab.com

24″ (610mm)

20-5/8″ (524mm)

29-1/8″ (740mm)

Security Secure Vent: www.securitychimneys.com

36″ (914mm)

29″ (737mm)

37-1/2″ (953mm)

Industrial Chimney Company: www.icc-rsf.com

48″ (1219mm)

37-7/16″ (951mm)

45-15/16″ (1167mm)

Olympia Ventis DV: www.olympiachimney.com

Note: Horizontal runs of vent must be level, or have a 1/4″ rise for every 1 foot of run towards the termination. Never allow the vent to run downward – this could cause high temperatures and may present a possible fire hazard.

50 | Grandview® G800C Gas Fireplace

Olympia Ventis DV: www.olympiachimney.com

installation
Venting Arrangements for Horizontal Terminations – Flex Vent or Rigid Pipe 4″ x 6-5/8″
The Diagrams show all allowable combinations of vent runs with 4″ x 6-5/8″ venting using the Regency direct vent system or rigid vent system. A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes. For horizontal terminations the Regency Direct Vent Flex System may be used for installations with a maximum continuous vent maximum horizontal length of 3ft (0.9m). Note: Must use optional rigid pipe adaptor (Part # 510-994) when using Rigid Pipe vent systems. · Maintain clearance to combustibles. · Horizontal vent must be supported every 3 feet. · Firestops are required at each floor level and whenever passing through a wall.

Vertical Height (Feet)
Rigid 44-“(1.1m) Flex 44″(1.1m)
3

Horizontal (Feet)

2

4

6

8

0

12

10

8

6

Set #1

4

2 Max. 36″(0.9m)
0
Top Vented Set #1 (2″ open) up to 2′ horizontal Factory Setting – no restrictor required greater than 2′ horizontal

18″ (0.5m)
Rear Vented Factory Setting – No Restrictor Required

Grandview® G800C Gas Fireplace | 51

installation

Rigid Pipe Venting Systems – Horizontal or Vertical Terminations

The minimum components required for a basic horizontal termination are:

1 Horizontal Termination Cap 1 90o Elbow 1 Rigid Pipe Adaptor 1 Wall Thimble 1 Length of pipe to suit wall thickness
(see chart)
Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap. For siding other than vinyl furring strips may be used, instead of the vinyl siding standoff, to create a level surface to mount the vent terminal. The Terminal must not be recessed into siding. Measure the wall thickness including furring strips.
If a Vinyl Siding Standoff is required (it must be used with vinyl siding), measure to outside surface of wall without siding and add 2 inches.

Flat Wall Installation

Wall Thickness (inches)

Vent Length Required (inches)

4″ (102mm) – 5-1/2″ (140mm)

6″ (152mm)

7″ (178mm) – 8-1/2″ (216mm)

9″ (229mm)

10″ (254mm) – 11-1/2″ (292mm)

12″ (305mm)

9″ (229mm) – 14-1/2″ (368mm)

11″ (279mm) – 14-5/8″ (371mm) Adj. Pipe

15″ (381mm) – 23-1/2″ (597mm)

17″ (432mm) – 24″ (610mm) Adj. Pipe

Corner Installation

Wall Thickness (inches)

Vent Length Required (inches)

3-1/4″ (83mm) – 6-3/4″ (171mm)

11″ (279mm) – 14-5/8″ (371mm) Adj. Pipe

7-3/4″ (197mm) – 16-1/4″ (413mm)

17″ (432mm) – 24″ (610mm) Adj. Pipe

7-1/4″ (184mm) – 8-3/4″ (222mm)

6″ (152mm) + 12″ (305mm) 9″ (229mm) + 9″ (229mm)

4-1/4″ (108mm) – 5-3/4″ (146mm)

6″ (152mm) + 9″ (229mm)

Vertical Termination
Cap Storm Collar
Flashing
Ceiling Firestop
Pipe Length

Vinyl Siding Standoff (Optional)

Horizontal Termination
Cap

Wall Thimble
Adj.Pipe Length 11″ – 14-5/8″
90o Elbow

Alternate
Horizontal Termination
Caps

24″ Pipe Length
Rigid Pipe Adaptor

WARNING: Do not combine venting components from different venting systems.
However use of the AstroCapTM and FPI Riser is acceptable with all systems.
This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with DuraVent Direct Vent, Selkirk Direct-Temp, Ameri Vent Direct venting, Olympia Ventis DV and Security Secure Vent systems. Use of these systems with the Rigid Pipe Adaptor is deemed acceptable and does not affect the Intertek WHI listing of components.

The FPI AstroCapTM and FPI Riser Vent terminal are certified for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent , American Metal Products, Olympia Ventis DV, Security Secure Vent®, AmeriVent Direct Vent. AstroCapTM is the proprietary trademark of FPI Fireplace Products
International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.

52 | Grandview® G800C Gas Fireplace

installation
Venting Arrangements – Horizontal Termination – Rigid Pipe and Direct Vent System (Flex)
(Propane & Natural Gas)
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o elbow (two 45o elbows equal one 90o elbow). Note: Must use optional rigid pipe adaptor (Part # 510-994) when using Rigid Pipe venting systems.

Horizontal (Feet)

2

4

6

8

10

12

14

16

18

20

0

18

16

14

Set #2 (1-3/4″)

12

Vertical Height (Feet)

10
Set #1-2″ open
8

Set #0-Fully Open

6

4

44″ (1118mm)

2

Minimum

Height

Requirement

0

· Maintain clearances to combustibles.
· Horizontal vent must be supported every 3 feet. · Firestops are required at each floor level and whenever passing through a wall.

All Rigid Pipe Systems 4″ inner diameter 6-5/8″ outer diameter
FPI Flex Vent 4″ inner diameter 6-7/8″ outer diameter
A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
Note: FPI Direct Vent Flex System Part #:946-513 (2 foot), 946-515 (4 foot)and 946-516 (10 foot) are only approved for horizontal terminations.

Grandview® G800C Gas Fireplace | 53

installation
Venting Arrangements – Vertical Termination – Rigid Pipe System and Vertical Flex Kit to Same Limitations
(Propane & Natural Gas)
The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90o elbows, with rigid pipe vent systems for Propane and Natural Gas.

Vertical Height (Feet)

Horizontal (Feet)

0

2

4

6

8

10

12

38

36

34 Set #3 (1-1/4″ open)

32

CPI mode

30

recommended

Set #2 (1-3/4″ open)

28

26 24

22

20

18

16

Set #1 (2″ open)

14 12

10 8

6

4

44″ (1118mm)

2

Minimum

Height

0

Requirement

· Vent must be supported at offsets. · Firestops are required at each floor level and whenever passing through a wall. · Maintain clearances to combustibles.
Note: Must use optional rigid pipe adaptor when using rigid vent systems (Part

510-994).

54 | Grandview® G800C Gas Fireplace

Horizontal Terminations – Two 90°Elbows

One 90o elbow = Two 45o elbows.

H1

Option V A) 0′ Min. B) 1′ Min. C) 2′ Min. D) 3′ Min. E) 4′ Min. F) 5′ Min.

H + H1 2′ Max. 3′ Max. 4′ Max. 5′ Max. 6′ Max. 7′ Max.

With these options, maximum total pipe length is 30 feet with minimum
of 6 feet total vertical
and maximum 8 feet total horizontal. Please note mini-
mum 1 foot between 90o elbows is re-
quired.

G) 6′ Min.

8′ Max

No Vent Restrictor Installed *Required when using rigid venting

Lengths do not include elbow indicated.

installation

H

V

Horizontal Terminations – Three 90o Elbows
H1

V1

One 90o elbow = Two 45o elbows.

Option A) B) C) D) E) F) G)

V
0′ Min. 1′ Min. 2′ Min. 3′ Min. 4′ Min. 5′ Min. 6′ Min.

H V + V1 1′ Max. 1′ Min. 2′ Max. 3′ Min. 2′ Max. 5′ Min. 2′ Max. 7′ Min. 3 Max. 9′ Min. 4′ Max. 10′ Min. 5′ Max. 11′ Min.

H + H1 2′ Max. 3′ Max. 4′ Max. 5′ Max. 6′ Max. 7′ Max. 8′ Max.

With these options, max. total pipe length is 30 feet with min. of 12 feet total vertical and max. 9 feet total horizontal.
Please note min. 1 foot between 90o elbows is required.

H)

7′ Min. 6′ Max. 12′ Min.

9′ Max.

No Vent Restrictor Installed *Required when using rigid venting

Lengths do not include elbow indicated.

H V

  • Grandview® G800C Gas Fireplace | 55

installation
Vertical Venting with Two 90o Elbows

One 90o elbow = Two 45o elbows.

Option A)

V

H

0′ Min. 2′ Max.

V + V1 W i t h t he s e o p t io ns ,

1′ Min.

maximum total pipe length is 30 feet with minimum

B)

1′ Min. 4′ Max. 3′ Min. of 7 feet total vertical and

C)

2′ Min. 5′ Max.

4′ Min.

maximum 8 feet total horizontal.

V1

D)

3′ Min. 6′ Max. 5′ Min.

Please note mini-

E)

4′ Min. 7′ Max. 6′ Min. mum 1 foot between

F)

5′ Min. 8′ Max.

7′ Min.

90o elbows is required.

Lengths do not include elbow indicated. *Required when using rigid venting

H

V

Vertical Venting with Three 90o Elbows

One 90o elbow = Two 45o elbows.

Option A) B) C) D) E) F) G)

V
0′ Min. 1′ Min. 2′ Min. 3′ Min. 4′ Min. 5′ Min. 6′ Min.

H + H1 2′ Max. 2′ Max. 3′ Max. 4′ Max. 5′ Max. 6′ Max. 7′ Max.

V + V1 2′ Min. 3′ Min. 4′ Min. 6′ Min. 7′ Min. 8′ Min. 9′ Min.

With these options, maximum total pipe length is 30 feet with minimum of 10 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.

H)

7′ Min. 8′ Max. 10′ Min.

Lengths do not include elbow indicated. *Required when using rigid venting

V1 H1

H

V

56 | Grandview® G800C Gas Fireplace

installation
Vertical Terminations Three 90° Elbows – Rigid Pipe 4″ x 6 – 5/8″ (102 mm x 168 mm)

One 90o elbow = Two 45o elbows.

Option V A) 0′ Min. B) 1′ Min. C) 2′ Min. D) 3′ Min. E) 4′ Min. F) 5′ Min. G) 6′ Min. H) 7′ Min.

H + H1 V + V1

2′ Max. 2′ Min. With these options, max.

2′ Max.

3′ Min.

total pipe length is 30 feet with min. of 10 feet total

3′ Max. 4′ Min. vertical and max. 8 feet

4′ Max. 6′ Min. total horizontal.

5′ Max. 7′ Min.

6′ Max.

8′ Min.

Please note min. 1 foot between 90o

7′ Max. 9′ Min. elbows is required.

8′ Max. 10′ Min.

No Vent Restrictor Installed *Required when using rigid venting

Lengths do not include elbow indicated.

V1 H1

H

V

Grandview® G800C Gas Fireplace | 57

installation
Venting Arrangements with Co-linear Flex System into a Masonry Chimney Application
IMPORTANT: As shown below, the unit can only be vented from the top, not from the rear.

THE APPLIANCE MUST NOT BE CONNECTED TO A CHIMNEY FLUE SERVING A SEPARATE SOLID FUEL
BURNING APPLIANCE.

Masonry chimneys may take various contours which the flexible liner will accommodate. However, keep the flexible liner as straight as possible, avoid unnecessary bending.
The Air Intake pipe must be attached to the inlet air collar of the termination cap.

This appliance is designed to be attached to
two 3″ (76mm) co-linear aluminium flex running the full length of the chimney. See the Venting Arrangements on next page for minimum and maximum heights.

Required Parts:

Part #
946-529
948-305 946-563

Description
Co-linear DV Vertical Termination Cap 3″ Flex – 35 ft. Co-Axial to Co-Linear Adapter Kit which contains the following: Co-linear Flex Adapter Outer Pipe Inner Pipe Adapter

Alternate Approved Caps
46dva-VC Vertical Termination Cap 46dva-VCH High Wind Cap 46dva-GK 3″ Co- linear Adapter with flashing

Co-linear DV Vertical Termination
Cap # 946-529
A maximum of two certified
joiner kits may be used
per length. #948-305 (35 ft)
Exhaust Flue
Outer Pipe with Kit# 946-563

NOTE:
See detailed venting arrangements, vertical terminations, co-linear flex system into masonry fireplaces in this manual.

Pipe Length

Rigid Pipe Adapter # 510-994
Top exit only. Cannot be vented from the rear.

90 Degree Elbow Inner Pipe Adapter with Kit# 946-563

Flex Liner
Air Intake Co-Linear
Flex Adapter with Kit# 946-563

58 | Grandview® G800C Gas Fireplace

installation
Venting Arrangement – Vertical Terminations – Co-linear Flex System Into Masonry Fireplaces
FOR BOTH RESIDENTIAL & MANUFACTURED HOMES IMPORTANT: As shown below, the unit can only be vented from the top, not from the rear. Restrictor at Set #1 (2″/51 mm open)

30

30

30

2′ max. 44″ 6′ max.
Combined min. of 8′ Combined max. of 30′

Vertical Height (feet)

30′ Max.

Vertical Height (feet)

30′ Max.

Vertical Height (feet)

8′ Min.

8′ Min.

2′ max.

44″

44-3/4″

Horizontal Distance (Feet)

Horizontal Distance (Feet)

Horizontal Distance (Feet)

Grandview® G800C Gas Fireplace | 59

installation

Unit Installation with
Horizontal Termination
Install the vent system according to the manufacturer’s instructions included with the components.
1. Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the unit. Rough in the gas preferably on the right side of the unit and the electrical (junction block is on the left side) on the left.
2. Direct Vent pipe and fittings are designed with special twist-lock connections to connect the venting system to the appliance flue outlet. A twist-lock appliance adaptor is an available option that must be used in conjunction with the Simpson Dura-Vent Direct Vent system.
3. Put a bead of Mill-Pac inside the outer section of the adapter and on the inner collar. Slip the adapter over the existing inner and outer flue collar and fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier). Level the fireplace and fasten it to the framing using nails or screws through the nailing strips.
4. Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.
Notes: a) Twist-lock procedure: Four indentations, located on the female ends of pipes and fittings, are designed to slide straight onto the male ends of adjacent pipes and fittings, by orienting the four pipe indentations so they match and slide in to the four entry slots on the male ends, Diagram 1. Push the pipe sections completely together, then twistlock one section clockwise approximately one-quarter turn, until the two sections are fully locked. The female locking lugs will not be visible from the outside, on the Black Pipe or fittings. They may be located by examining the inside of the female ends.

b) Horizontal runs of vent must be supported every three feet. Wall straps are available for this purpose.
5. Mark the wall for a 10″ x 10″ square hole. The center of the square hole should line up with the centerline of the horizontal pipe. Cut and frame the 10 inch square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of noncombustible material, i.e. masonry block or concrete, a 7″(178mm) dia. (7-1/2″(191mm) dia. for flex) hole is acceptable.
Note: With Dura-Vent, the minimum height is achieved by installing a 90o elbow directly to the rigid pipe adaptor.
Notes:
a) The horizontal run of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fire.
b) The location of the horizontal vent termination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. For External Vent Terminal Locations, see Exterior Vent Termination Location.
c) Snorkel Terminations: For installations requiring a vertical rise on the exterior of the building, 14-inch and 36inch tall Snorkel Terminations are available, as well as the standard Riser Vent. Follow the same installation procedures as used for standard Horizontal Termination. NEVER


Note: Riser Vent is only for use in above grade terminations.
Diagram 3
*Diagrams 3 & 4: As specified in CGA B149 Installation Code. Local codes or regulations may require different clearances.
install the snorkel upside down. 6) The arrow on the vent cap should be
pointing up. Insure that the 1-1/2” clearances to combustible materials are maintained (Diagram 4). Install the termination cap. Below Grade Installation If the Snorkel Termination must be installed below grade, i.e. basement application, proper drainage must be provided to prevent water from entering the Snorkel Termination. Refer to Diagram 4. Do not attempt to enclose the Snorkel within the wall, or any other type of enclosure.

Diagram 1

NOTE: For best results and optimum performance with each approved venting system, it is highly recommended to apply “MillPac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty.
60 | Grandview® G800C Gas Fireplace

Diagram 2
*As specified in CGA B149 Installation Code. Local codes or regulations may require different clearances.

Diagram 4
NOTE: For Snorkel terminations in ABOVE grade installations, follow national or local code requirements.

installation

Diagram 5
The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.
Note: If installing termination on a siding covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding.
7. Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall Thimble over the vent pipe.
8. Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the vent cap assembly. It is important that the vent pipe extends into the vent cap sufficient distance so as to result in a minimum pipe overlap of 1-1/4 inches. Secure the connection between the vent pipe and the vent cap by attaching the two sheet metal strips extending from the vent cap assembly into the outer wall of the vent pipe. Use the two sheet metal screws provided to connect the strips to the pipe section. See Diagram 6.

Unit Installation with Vertical Termination

1. M a i n t a i n t h e 1 – 1 / 4 ”

clearances (air spaces)

to

combustibles when passing

through ceilings, walls, roofs,

enclosures, attic rafter, or other

nearby combustible surfaces.

Do not pack air spaces with

insulation. Check for the

maximum vertical rise of the

venting system and the

maximum horizontal offset

limitations.

Diagram 1

2. Set the gas appli-

ance in its desired

location. Drop a plumb bob down from the ceiling to

plumber’s tape connected

the position of the to wall strap

appliance flue exit, wall and mark the loca- strap tion

45o Elbows

where the vent

will penetrate the ceiling. Drill a small

Firestop Spacer

hole at his point.

Diagram 2

Next, drop a plumb bob from the roof to the

hole previously drilled in the ceiling, and mark

the spot where the vent will penetrate the roof.

Determine if ceiling joists, roof rafters or other

framing will obstruct the venting system. You

may wish to relocate the appliance or to offset,

as shown in Diagram 2 to avoid cutting load

bearing members.

4. Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow connections are in the fully twist-locked position and sealed.
5. Cut a hole in the roof centered on the small drilled hole placed in the roof in Step 2. The hole should be of sufficient size to meet the minimum requirements for clearance to combustibles of 1-1/2″. Slip the flashing under the shingles (shingles should overlap half the flashing) as per Diagram 4.
Diagram 4: The upper half of the flashing is installed under the roofing material and not nailed down until the chimney is installed. This allows for small adjustments. 6. Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3 feet, to avoid excessive stress on the elbows, and possible separation. Wall straps are available for this purpose (Diagram 2).
Galvanized pipe is desirable above the roof line due to its higher corrosion resistance. Continue to add pipe sections through the flashing until the height of the vent cap meets the minimum height requirements specified in Diagram 5 or local codes. Note that for steep roof pitches, the vertical height must be increased.

Diagram 6
9. Install wall thimble in the center of the 10″ square and attach with wood screws (Diagram 7).
Diagram 7

NOTE: For best results and optimum performance with each approved venting system, it is highly recommended to apply “MillPac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty. 3. A Firestop spacer must be installed in the floor
or ceiling of every level. To install the Firestop spacer in a flat ceiling or wall, cut a 10 inch square hole. Frame the hole as shown in Diagram 3 and install the firestop.
Diagram 3

Diagram 5

Roof Pitch

Minimum Vent Height

Feet

Meters

flat to 7/12

2

0.61

over 7/12 to 8/12

2

0.61

over 8/12 to 9/12

2

0.61

over 9/12 to 10/12 2.5

0.76

over 10/12 to 11/12 3.25

0.99

over 11/12 to 12/12 4

1.22

over 12/12 to 14/12 5

1.52

over 14/12 to 16/12 6

1.83

over 16/12 to 18/12 7

2.13

over 18/12 to 20/12 7.5

2.29

over 20/12 to 21/12 8

2.44

Grandview® G800C Gas Fireplace | 61

installation

A poor draft, or down drafting can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the vent height may solve the problem.
7. Ensure vent is vertical and secure the base of the flashing to the roof with roofing rails, slide storm collar over the pipe section and seal with a mastic.

Note: To make the installation
more aesthetically pleasing, we recommend framing out a square to mount the terminal to.

Outside Wall
Furring Strips

8. Install the vertical termination cap by twistlocking it.

Note: Any closets or storage spaces, which the vent passes through must be enclosed.
Offset Chart

that the termination is not recessed into the siding.
2. Level the fireplace and fasten it to the framing using nails or screws through the nailing strips.

3. Assemble the vent assembly by applying Mill Pac to the 4″(100mm) inner collar of the termination and slipping the 4″(100mm) liner over it at least 1-3/8″ (35mm). Fasten with the 3 screws (drilling pilot holes will make this easier). Apply Mill Pac to the 6-7/8″(175mm) flex pipe and slip it over the 6-7/8″ outer collar of the vent terminal at least 1-3/8″(35mm) and fasten with the 3 screws.

Direct Vent System (Flex) Installation Procedures

NOTE:Horizontal sections must be supported at intervals not exceeding 3 feet (0.9 meter). (Flame picture and performance will be affected by sags in the liner).
4. Separate the 2 halves of the wall thimble and securely fasten the one with the tabs to the outside wall making sure that the tabs are on top and bottom. Fasten the other thimble half to the inside wall. The thimble halves

slip inside each other and can be adjusted for 2 x 4 or 2 x 6 walls. The liners must slip over the collars a minimum of 1-3/8″. 5. Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up (there are markings on the cap that show which way is up). This will position the termination cap with proper down slope for draining water. Fasten the cap to the outer wall with the 4 supplied screws.
6. Pull the centre 4″(100mm) liner and outer 6-7/8″(175mm) liner out enough to slip over the flue collars of the fireplace. (You may wish to cut the liner shorter to make it more workable.) Do not bend liner more than 90o.
7. Apply Mill Pac over the fireplace inner collar and slip the 4″(100mm) liner down over it and attach with 3 supplied screws.
8. Do the same with the 6-7/8″(175mm) liner.
9. Apply a bead of silicone between the thimble and termination and around the outer edge of the terminal at the wall in order to keep the water out.
IMPORTANT: Do not locate termination hood where excessive snow or ice buildup may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.

1. Locate the unit in the framing, rough in the gas (preferably on the right side of the unit) and the electrical (Junction block is on the left side) on the left. Locate the centerline of the termination and mark wall accordingly.
Cut a 10″(254mm) hole in the wall (inside dimension).

4″ dia. flue pipe with spring spacer

2 x 4 or 2 x 6 Termination Cap

Note: A 1-1/2″(38mm) clearance around the liner must be maintained except that only a 1″ (25mm) clearance is needed at the termination end. We recommend framing a 10″(254mm) x 10″(254mm) (inside dimensions) hole to give structural rigidity for mounting the termination.
Note: If installing termination on a siding covered wall, furring strips must be used to ensure
62 | Grandview® G800C Gas Fireplace

6-7/8″ dia air intake

Screws
(4 per connection)

Screws (3 per connection)

Wall Thimble 2 pieces (10″ Outer

Diameter)

installation

Vertical Termination 4″ x 6-7/8″ (102 mm x 175 mm) Venting – Vertical Flex Vent Kit

(Part #694/86-V7E5N5T)ING VERTICAL

(9 6 55)

1. Maintain the 1-½” (38 mm) clearance (air space) to combustibles when passing through ceilings, walls, floors, enclosures, attic rafters or other nearby combustibles. Do not pack air spaces with insulation. Check Venting sections for the maximum vertical rise of the venting system and the maximum horizontal offset limitations. Ensure that you maintain clearances around enclosures, walls, below or above floors, floor joists, etc. Each appliance has different clearance requirements (top,sides,bottom). See specific appliance manual for details.
2. Set the appliance in its desired position. Drop a plumb bob down from the ceiling/floor joist to the position of the appliance flue exit and mark the location where the vent will penetrate the ceiling. Drill a small hole at this point. Next drop a plumb bob from the roof to the hole previously drilled at the ceiling level and mark the spot where the vent will penetrate the roof.
3. Cut a hole in the roof centered on the small hole placed in the roof in the previous steps. The hole should be a minimum of 10-¼ (260 mm) inches. The hole may be round and or square.
4. Slip the flashing under the shingles and line up flashing so it is centered to the hole (shingles should overlap half of the flashing) as per Diagram 1.
Diagram 1: The upper half of the flashing is installed under the roofing material and not nailed down until the chimney is installed.
This allows for small adjustments.

11. Secure inner flex pipe to pipe adaptor by using Mill-Pac over the adaptor. Slide the inner pipe over adaptor and secure with 3 screws.

12. Repeat Step 11 to secure outer flex.

13. Slide the finished length up towards the flashing ensuring the length of

pipe is a minimum of 2 feet (0,61 m) measured from the top of the roof.

Level the chimney and secure using the roof support provided with kit to

bottom side of the roof as shown using a minimum of 2 screws per side-

see Diagram 3b. See Diagram 4 for roof pitch and height requirements.

See Diagram 3a for securing method if 2 ft. (0,61 m) is insufficient and

additional lengths are required, this may be purchased separately. See

Simpson Duravent components list in the instruction manual for part

numbers.
Termination Cap

Termination Cap

Storm Collar Flashing

Storm Collar Flashing

Roof Support

Roof Support / Brace

Ceiling Firestop

Ceiling Firestop Enclosure

Ceiling Firestop Flex Pipe

Support to prevent sagging

Elbow Support

Ceiling Firestop Flex Pipe

Diagram 1

5. A ceiling firestop/firestop spacer must be installed when passing through

each floor or ceiling level. To install the ceiling firestop/firestop spacer in

a flat ceiling or floor joist cut a 10- ¼ (260 mm) inch square hole. Frame

the hole as show in Diagram 1 and install the ceiling firestop. Slide the top

attic insulation spacer onto the top of the attic insulation shield/firestop –

See Diagram 1a. Secure with 4 screws/nails. If more than one is required,

these can be purchased separately.

Termination Cap

Storm Collar
Note: The ceiling firestop/firestop spacer may be Flashing cut down to size if this

shield is too high for the application.

Firestop spacer to prevent

-1/4 60

Diagram 2

debris Roof support from falling into the ceiling firestop

Ceiling firestop

Enclosure

Ceiling firestop

Diagram 2a

Ceiling firestop

6. Determine the overall height of the chimney from the top of the appliance to the underside of the flashing. If required cut the flexible inner and outer pipe to the desired length up to a maximum of 20 feet (6.1 m).

7. Put a bead of Mill-Pac around the 4 inch (102 mm) collar on the appliance and slide the inner flex pipe over the inner collar of the appliance and secure with a minimum of 3 screws.

8. Install 4 inch spacers around 4 inch (102 mm) flex.

9. Repeat Step 7 to install the outer pipe to the outer collar of the appliance

Note: If an offset is necessary in the attic or floor joists it is important to support the vent pipe every 3 feet (0.91 m) to avoid excessive stress and sagging of the vent pipe. Wall straps are provided (3 in total) for this purpose. All round/plumbers strapping may also be used if further supports are required.

10. Attach the rigid pipe section to the adaptor by using Mill-Pac on the inner/ outer pipe. Use 3 screws to secure outer pipe.

Diagram 3
Termination Cap
Storm Collar Flashing

Diagram 3a

Roof support
Diagram 3b

Diagram 4

Roof Pitch

Minimum Vent Height

flat to 7/12

Feet Meters

Ceilin2g firestop

0.61

over 7/12 to 8/12 Enclosure 2

over 8/12 to 9/12

2

0.61 0.61

over 9/12 to 10/12

2.5

0.76

over 10/12 to 11/12 over 11/12 to 12/12

Ceilin3g .f2ire5stop 4

0.99 1.22

over 12/12 to 14/12

5

1.52

over 14/12 to 16/12

6

1.83

over 16/12 to 18/12

7

2.13

over 18/12 to 20/12

7.5

2.29

over 20/12 to 21/12

8

2.44

14. Put a bead of caulking on the exterior between the outer pipe and flashing to prevent water from penetrating the chimney system.

15. Slide storm collar over pipe length until it reaches the flashing.

16. Install termination cap by twist locking it.

17. Secure the flashing to the roof using screws

Note: Any closets or storage spaces which the vent passes through must be enclosed.
Grandview® G800C Gas Fireplace | 63

installation

Vertical Flue Extension Kit (Pa(rt #9464-67-57566))
20 foot (6.1 m) Flex pipe Extension (Used in conjunction with the 946-755 Vertical Flex kit and 948-367/P flex to flex adaptor).
1. Stretch out both inner 4″ (102 mm) and outer 6 7/8″ (175 mm) pipe up to -1/4 60 a maximum of 20 feet.

4″ (102 mm) inner pipe 20ft. (6.1 m)
10 spring spacers

Note :The inner and outer pipes may be cut if only a short length is required.

Termination Cap

2Ae. aSIcnclehsiditlaeifnlolgloosurfpitreoreirrnsftgcloeepsxil/pifnpiargeicpseleetrosvopevales.rporTauoacnneidndrs4amta”llul(lts1htt0heeb2wemcaeinmyilsid)ntaoginlwlenfindreertswhptheoipep4en/f”irappesaispstsoeshpi.nogwspntah.croeur gihn 3ais.npifnaADlancpitaeepcgrrleyrocainlomaintlolgab1rteoh,oareafdfntltoodhopoefirnoMfjslfoetitialxshlltlePa, tdachauacetttpicacateerionri1lsui0anun- gnldad¼ftiitrsoheilnneispctshopthpheise.erqilSmdu4/la”ifedirr(teeee1sr0htth2oooelpfemtt,(ohmsfperea)eam4intD”tenici(ae1itgir0nraf2salseummxlsah1mptioaoip)w)n.e SefrcoumrethweithV4erstcicraelwtse/rnmaiilnsa. Itfiomnokreit tohvaenrotnhee ffirleexstoapdaisprteeqr ueirnesdu,rtihnegstehcaat nthe beinpnuerrchflaesxepdipseepoavraetrelalyp.s the collar by at least 1-3/8″ (35 mm). Fasten with
3 screws.
4. ApplTyhaebceeaildinogf fMireilsl Ptoapc/fiarerostuonpdstphaecpeer rmimaeytebreocfutht edo6w-7n/8to” (s1iz7e5 imf tmhe) outerschoiellladriosfttohoehfilguhe faodrathpetearpapnlidcastliiopnit. over the 6-7/8″ (175 mm) outer flex pipe from the vertical termination kit ensuring that the outer flex pipe overlaps the collar by at least 1-3/8″ (35 mm). Fasten with the 3 screws.
5. Repeat steps to secure the other end of the flex adapter using the flex kit.

Ceiling firestop

Storm Collar Flashing

flex adaptor

Roof support firestop 3 wall straps

6-7/8″ (175 mm) outer flex pipe 20 ft (6.1 m)

Ceiling firestop Enclosure
Ceiling firestop

6. See Vertical Vent installation instructions for installation of the complete vent system.
Note: If an offset is necessary in the attic or floor joists it is important to sup-port the vent pipe every 3 feet (0.91 m) to avoid excessive stress and sagging of the vent pipe. Wall straps are provided (3 in total) for this purpose.
1
All round/plumbers strapping may also be used if further supports are required.
Ceiling Firestop / Firestop Spacer (Part #946-757)

NOTE

Used in conjunction with the 946-755 Vertical Flex Kit and the 946-756 Vertical Flex Extension Kit/Horizontal Power Vent Kit.
A ceiling firestop/firestop spacer must be installed when passing through each floor or ceiling level. To install the ceiling firestop/firestop spacer in a flat ceiling or floor joist, cut a 10- ¼ inch square hole, frame it as show in Diagram 1, and install the ceiling firestop. Slide the top attic insulation spacer onto the top of the attic insulation shield/firestop (see Diagram 1a). Secure with 4 screws/nails. If more than one firestop is required, these can be purchased separately.
· The ceiling firestop/firestop spacer may be cut down to size if the shield is too high for the application.

-1/4 60
Diagram 1

Termination Cap
Storm Collar Flashing
Ceiling firestop
Firestop spacer to prevent debrRiosoffrsoupmporftafilrleinsgtoipnto the ceiling

Ceiling firestop Enclosure

Diagram 1a

Ceiling firestop

64 | Grandview® G800C Gas Fireplace 1

Conversion from NG to LP using SIT Gas Valve

installation

THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !

Each Kit contains one LP Conversion Kit

Conversion Kit #761-977 Contains:

Qty. Part #

Description

1

904-947 Burner Orifice #53 LP

(PO5-12)

1

904-529 5/32″ Allen Key

1

918-590 Decal “Converted

to LPG”

1

908-528 Red “LP” label

1

910-037 LP Injector (Pilot

Orifice)

1

920-183 Instruction Sheet

Installation of LP Conversion Kit:
1. Shut off the gas and electrical supply.
2. Remove the safety screen.
3. Remove the glass door
.
4. Remove the logs, glass, and any other media.
5. Remove the two log supports
and log grate assembly by removing 2 screws and sliding the tray forward to remove.
*(See specific instructions in unit manual.)

7. Remove the pilot retainer clip below the pilot cap.
Pilot retainer clip
8. Pull off the pilot cap to expose the pilot orifice.

10. Re-install pilot cap and pilot retainer clip. 11. Remove burner orifice with a 3/8″
wrench. Use another wrench to hold on to the elbow behind the orifice. Discard orifice. 12. Reinstall new burner orifice LPG stamped #53 and tighten.
13. Turn control knob to the “OFF position. Locate the Hi/Lo knob on the gas valve. See diagram below.

  1. Remove the black protection cap by hand from the hi-low knob (Fig.1).

Diagram 1: Remove the left and right screws. 6. Remove three screws then remove the
burner assembly.
Diagram 2: Slide burner assembly to the right–then remove.

9. Unscrew the pilot orifice with the Allen key; then replace with the LPG pilot orifice, provided in the kit.

Fig. 1

Fig.2

  1. Insert a 5/32” or 4mm Allen wrench into the hexagonal key-way of the screw (Fig. 2), rotate it counterclockwise until it is free and extract it.
    Installer Notice:

These instructions must remain with the appliance.

Grandview® G800C Gas Fireplace | 65

installation
16) Check that the screw is clean and if necessary remove dirt.
17) Flip the screw (Fig. 3).

Fig.3

  1. Using the Allen wrench as shown in Fig.4, rotate the screw clockwise until snug, do not overtighten.

Fig.4
WARNING! Do not over tighten the screw.
Recommended to grip the wrench by the short side.

  1. Verify that if the conversion is from NG to LPG, the screw must be re- assembled with the red o-ring visible (Fig. 5).

Red o-ring visible

LPG Configuration

  1. Attach the label “This unit has been converted to LPG” near or on top of the serial # decal.
  2. Replace yellow “NG” label with red “LPG” label.
  3. Reinstall burner assembly.
  4. Adjust aeration accordingly–see manual for details. Aeration must be set to 5/16″ (8 mm) for LP.
  5. Reverse steps 4­1.
  6. Check for gas leaks.
  7. Check inlet and outlet pressures.
  8. Check operation of flame control.

Fig.5
20) Re-assemble the black protection cap (Fig. 6).

Fig. 6 21) Reverse steps 6 – 1.
WARNING! Also check that the pilot and main burner injectors are appropriate for
the gas type.
66 | Grandview® G800C Gas Fireplace 2

installation

Brick Panel installation
Note: Do not install the firebed grate, media, vermiculite, embers, and logs until the brick panels are installed.
· Brick panels will discolor a little during normal operation. This is normal and should not be considered a defect.

6. Install the right side panel–the angled corner should be located facing the bottom rear of the fireplace when installing.
NOTE: Shorter row of bricks should be positioned at the bottom of back and side panels.

1. Remove screen and glass door, if installed.
2. Loosen two screws in locations shown below. Slide upper baffle towards the back wall and then remove from unit.

3. Loosen 2 screws on pilot assembly in locations shown below. Slide pilot shield towards the back of the unit and remove from unit.

7. With panel in position, secure it with the brick clip removed in step 5 and retighten screw.
8. Repeat Steps 5-7 on the left side.

4. Install back panel carefully. Tilt panel forward from the top and rest the bottom of the panel on the firebox floor. Tip top back until it also rests on the firebox back wall.

9. Slide the bottom panel carefully underneath the burner and push to the back until it contacts the back panel.

5. Loosen screws and remove brick clip.

tooltip
1
3

2 4

Item Part # Description

1

N/A

Inside Top of Firebox

2

N/A

Panel

3

761-049 Brick Clip

4

904-519 Screw

10. Reinstall the upper baffle. 11. Reinstall the pilot shield removed in step 3.
Grandview® G800C Gas Fireplace | 67

installation

Enamel/Steel Panel Installation

For Black Enamel Panels: · Black enamel panels must be inspected for scratches and dimples
prior to installation. All claims are to be recorded at this time. Claims for damage after installation will