ALFA ELECTRIC AVC300.432 Air Conditioner For Electrical Enclosures Indoor Application User Manual
- June 13, 2024
- ALFA ELECTRIC
Table of Contents
CONTROL TYPE | ARTICLE CODE |
---|---|
Digital thermostat with alarms | ARC300.432 |
FEATURES | Unit |
Power supply | V |
Cooling capacity EN14511 | A35-A35 |
A35-A50 | W |
Absorbed electric power EN14511 | A35-A35 |
A35-A50 | W |
Rated current | A |
Motor circuit breaker / Delayed pre fuse (advised) | A |
Electrical connection | – |
Air flow rate (free blow) | enclosure |
Operating temperature | ambient |
(+68 | + 122) |
enclosure | °C (°F) |
Refrigerant | – |
**** Protection degree EN60529/1 | ambient |
enclosure | – |
degree)
Design| casing| –| Galvanised sheet steal
cover| –| Galvanised sheet steel powder coated RAL7035
Weight| kg| 65
Conformity / Certifications| –| CE
WARNING
- Safety of AIR CONDITIONER is warranted only by proper use of these instruction which must be kept.
- Installation must be done by qualified personnel only after enclosure power supply disconnecting.
- Before any operation, switch off the power supply.
- The appliance is classified as not accessible to the general public
- The air conditioner is not to be used by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction.
- Children being supervised not to play with the air conditioner.
- The air conditioner must be installed in accordance with national wiring regulations
- Upstream of the electrical connection, an efficient disconnection system must be provided in compliance with the standard
- Internal and external components of electrical enclosure don’t have to affect the proper installation of air conditioner.
- Inside of electrical enclosure there must not be components that could affect the proper ventilation.
- Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary weight of installed AIR CONDITIONER.
- Installation position of AIR CONDITIONER must be selected to ensure good ventilation. Take care that any internal/external components of enclosure don’t obstruct air passage. (see section 2.2 GENERAL CHECKS BEFORE INSTALLATION)
- The heat loss of the components installed inside of the electrical enclosure must be lower than useful cooling power of the AIR CONDITIONER.
- AIR CONDITIONER must be handled in upright position and protected against accidental tipping over.
- Do not modify the AIR CONDITIONER structure if it is not specified in these instruction or associated instructions.
- During transportation of enclosures with installed air conditioner a proper bracket must be used to support the cooling unit weight.
- Install only original spare parts and accessories.
- Protection against access to live parts must be warranty by installer.
- The supply connector of the AIR CONDITIONER must only be connected and disconnected when electrical enclosure is electrically disconnected.
- Follow all technical data shown in this manual
INSTALLATION
PRODUCT HANDLING
AIR CONDITIONER ARC series must be handled in upright position and
protected against accidental tipping over.
The air conditioner handling, when unpacked, can be done thanks to lifting eye
bolt. Air conditioners ARC series are fitted with lifting eye bolts.
Check the proper fixing of eye bolts before lift the air conditioner.
GENERAL CHECKS BEFORE INSTALLATION
****Before the installation make sure that the cabinet is disconnected from
the electrical supply.
GENERAL CHECKS
electrical enclosure must be disconnected form power supply
electrical data shown on rating label pasted on air conditioner side must be
guaranteed
Electrical enclosure must be sized according to air conditioner dimensions and
weight.
Electrical enclosure must have at least IP54 protection degree
Internal and external components of electrical enclosure don’t have to affect
the proper installation of air conditioner
The installation site must be free from excessive dirt, aggressive ambient
conditions and moisture.
The installation site must be free from hot air flows
The internal side of electrical enclosure must be free from dirt and moisture
The environment temperature must be within the range specified on label pasted
on air conditioner side
Inside of electrical enclosure there must not be components that could affect
the proper ventilation
the enclosure positioning with installed air conditioner must be carefully
selected to ensure good ventilation (clearance between the air conditioner and
the near walls must be at least 500 mm in each side).
Proper disposing of condensate discharge
FITTING
-
Make the fixing hole on the enclosure as is shown in the drilling template
VIEW FROM EXTERNAL OF ELECTRICAL ENCLOSURE
Deburr all sharp edges to avoid accidental injuries -
Apply the gasket (included in fixing kit) on the back panel of the air conditioner;
-
Lift the air conditioner by lifting eyebolt and place on the enclosure roof
-
Mount the air conditioner on the electrical cabinet according to the drilling template with adequate M6 screws and washers against unscrewing (notincluded in mounting kit)
-
Connect an adequate hose to the condensate drain pipe like is shown by picture below
**** Air conditioner produces condensate because the moist air inside of the enclosure meets cold heat exchanger (evaporator) and then it becomes water; water production decreases during air conditioner working because enclosure air becomes dry.
The condensate must be properly evacuated to avoid accidental damage to
the electrical enclosure
The enclosure must be IP 54 protected, if enclosure is not airtight,
condensate production could increase.
**** The enclosure IP54 degree is guaranteed only if the air conditioner is
proper mounted.
ELECTRICAL CONNECTION
WIRING DIAGRAM
ELECTRICAL INSTALLATION
The electrical installation must be carried out by a qualified
electrician who is responsible for compliance with the applicable standards
and regulations.
Air conditioner is factory wired for 460VAC input voltage, if needed it
can be changed at 400VAC. Select the proper wiring according to mains voltage
where unit is installed.
**** Input voltage selection can be carried out by male connector proper
wiring. Supply male connector is included in mounting kit and it is factory
wired as is shown in picture below.
- Bridge from blank pole to pole 6 means input voltage set at 460VAC
- In case of mains voltage at 400VAC the bridge must be shifted from pole 6 to pole 4
-
After supply voltage selection, male connector can be wired with main cable.
Before the installation make sure that the cabinet is disconnected from the electrical supply.
Wire male plug with an adequate cable as is shown by picture, phases order shown on male connector must be kept
Cable section must be at least 1,5mm2
The male plug is fitted with spring terminals: -
Push the spring with a screwdriver and then insert the wire.
-
Check the proper wire insertion.
-
Insert male connector inside of 7 poles female connector placed on the bottom of the air conditioner.
**** When air conditioner is installed on electrical enclosure, female connector is accessible only from inside the enclosure.
The supply (1) and signal (2) connectors are placed on the bottom of the air conditioner
-
Insert signal connector (included in installation kit, refer to picture below) inside of 4 poles female connector placed on the bottom of the air conditioner.
ALARM OUTPUT/DIGITAL INPUT
ARC300.432 is fitted with an electronic controller which permits alarm
output and digital input signals.
Alarm output
Alarm output is activated according to alarm parameters (for example in
case of enclosure temperature higher than ALU value, digital input not
activated… See PARAMETERS at 4.2 DIGITAL THERMOSTAT INSTRUCTION section)
Alarm output is a dry contact.
Digital input
WARNING: proper functions of air conditioner are allowed only if
digital input is activated. (closed contact between poles 13-14).
Digital input can be a door limit switch or a generic external dry contact.
Plug for signals is factory wired with a bridge between 13-14 poles. Bridge
can be removed to wire a door limit switch.
Connect signal plug with signal female connector placed on the bottom of the
air conditioner, near of power supply connector.
STARTING AND ADJUSTMENT
GENERAL DESCRIPTION
ALFA ELECTRIC air conditioners are especially designed for dissipation of
heat loss inside electrical enclosures with IP54 protection degree.
Air circulation inside the enclosures allows to keep enclosure air volume
isolated from external ambient air, it preserves the inside of the enclosure
against dirt and humidity which are present in the external air.
ARC series must be installed only on the roof of electrical enclosure
After finishing assembly of the conditioner, wait approx. 30 min. before
starting it (the oil must collect in the compressor to ensure lubrication and
cooling).
The air conditioner operates automatically, that is to say, after insertion,
the evaporator fan operates continuously making the air inside the cabinet
circulate. This way a uniform distribution of temperature inside the cabinet
itself is attained. The built-in thermostat drives compressor and condenser
fan according to set point value and other parameters (See PARAMETERS at 4.2
DIGITAL THERMOSTAT INSTRUCTION section for references)
Compressor and condenser fan start after a delay set on thermostat (see
parameter AC on parameters list for references) to permit a minimum interval
between the compressor stop and the following restart.
During proper operations, the compressor and condenser fan turn OFF when
internal enclosure temperature decreases under set point value.
DIGITAL THERMOSTAT INSTRUCTION
WARNING : the air conditioner is designed to operate at 35 ° C cabinet temperature. If the set point is changed the performance of the unit will vary.
- Regulating thermostat is fixed on side of air conditioner.
- Thermostat could be set into a range from 20°C up to 50°C. Follow thermostat instructions for parameter changing.
SET
| To display target set point; in programming mode it selects a parameter or
confirm an operation.
---|---
| (DEF) To start a manual defrost
| To see the max. stored temperature; in programming mode it browses the
parameter codes or increases the displayed value.
| To see the min stored temperature; in programming mode it browses the
parameter codes or decreases the displayed value.
| To switch the instrument off, if onF = oFF.
| To switch the light, if oA1 = Lig
KEY COMBINATIONS:
| To
lock & unlock the keyboard.
---|---
| To
enter in programming mode
****| To return to the room temperature display
LED FUNCTION DESCRIPTION:
LED | MODE | FUNCTION |
---|---|---|
ON | Compressor enabled | |
Flashing | Anti-short cycle delay enabled | |
ON | Defrost enabled | |
ON | An alarm is occurring | |
ON | Continuous cycle is running | |
ON | Energy saving enabled | |
ON | Light on | |
ON | Auxiliary relay on | |
ON | Measurement unit | |
Flashing | Programming phase |
MAX & MIN TEMPERATURE MEMORIZATION
How to see the min temperature
- Press and release the ▼ key.
- The “Lo” message will be displayed followed by the minimum temperature recorded.
- By pressing the ▼ key again or by waiting 5s the normal display will be restored.
How to see the max temperature
- Press and release the ▲ key.
- The “Hi” message will be displayed followed by the maximum temperature recorded.
- By pressing the ▼ key again or by waiting 5s the normal display will be restored.
How to reset the max and min temperature recorded
- Hold press the SET key for more than 3s, while the max. or min temperature is displayed. (rSt message will be displayed)
- To confirm the operation the “rSt” message starts blinking and the normal temperature will be displayed.
HOW TO SEE THE SET POINT
- Push and immediately release the SET key: the display will show the Set point value;
- Push and immediately release the SET key or wait for 5 seconds to display the probe value again.
HOW TO CHANGE THE SETPOINT
- Push the SET key for more than 2 seconds to change the Set point value;
- The value of the set point will be displayed and the “°C” or “°F” LED starts blinking;
- To change the Set value push the ▲ or ▼ arrows within 10s.
- To memorise the new set point value push the SET key again or wait 10s.
HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:
- Enter the Programming mode by pressing the SET + ▼ keys for 3s (the “°C” or “°F” LED starts blinking).
- Select the required parameter. Press the SET key to display its value
- Use ▲ or ▼ to change its value.
- Press SET to store the new value and move to the following parameter.
To exit: Press SET + ▲ or wait 15s without pressing a key.
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.
HOW TO LOCK THE KEYBOARD
- Keep pressed for more than 3 s the ▲ + ▼ keys.
- The POF message will be displayed and the keyboard will be locked. At this point it will be possible only to see the set point or the MAX o Min temperature stored
- If a key is pressed more than 3s the POF message will be displayed.
HOW TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the ▲ + ▼ keys, till the Pon message will be displayed.
THE ON/OFF FUNCTION
With onF = oFF, pushing the ON/OFF key, the instrument is switched off. The
OFF message is displayed. In this configuration, the regulation is disabled.
To switch the instrument on, push again the ON/OFF key.
WARNING: Loads connected to the normally closed contacts of the relays
are always supplied and under voltage, even if the instrument is in standby
mode.
PARAMETERS
Regulation
Hy: Differential: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential
for set point. Compressor
Cut IN is Set Point + differential (Hy). Compressor Cut OUT is when the
temperature reaches the set point.
Ot: Thermostat probe calibration: (-12.0÷12.0°C; -120÷120°F) allows to
adjust possible offset of the thermostat probe.
AC: Anti-short cycle delay: (0÷50 min) minimum interval between the
compressor stop and the following restart.
CH: Type of action: CL = cooling; Ht = heating.
rES: Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point
display. dLy Display delay: (0 ÷20.0m; risul. 10s) when the temperature
increases, the display is updated of 1 °C/1°F after this time.
IdF: Interval between defrost cycles: (0÷120h) Determines the time
interval between the beginning of two defrost cycles.
MdF: (Maximum) length for defrost: (0÷255min) (0=no defrost) When P2P =
n, (not evaporator probe: timed defrost) it sets the defrost duration, when
P2P = y (defrost end based on temperature) it sets the maximum length for
defrost.
ALU: MAXIMUM temperature alarm: (SET÷110°C; SET÷230°F) when this
temperature is reached the alarm is enabled, after the “ALd” delay time.
ALL: Minimum temperature alarm: (-50.0 ÷ SET°C; -58÷230°F when this
temperature is reached the alarm is enabled, after the “ALd” delay time.
i1P: Digital input polarity: oP: the digital input is activated by
opening the contact; CL: the digital input is activated by closing the
contact.
i1F: Digital input configuration: EAL = external alarm: “EA” message is
displayed; bAL = serious alarm “CA” message is displayed. PAL = pressure
switch alarm, “CA” message is displayed; dor = door switch function; dEF =
activation of a defrost cycle; AUS =to switch on the second relay if oA1 =
AUS; Htr = kind of action inversion (cooling –heating); FAn = not set it; ES =
Energy saving.
did: (0 ÷ 255 min) with i1F= EAL or i1F = bAL digital input alarm delay:
delay between the detection of the external alarm condition and its
signalling.
with i1F= dor: door open signalling delay
with i1F = PAL: time for pressure switch function: time interval to calculate
the number of the pressure switch activation.
PbC: Type of probe: it allows to set the kind of probe used by the
instrument: PbC =
PBC: probe, ntc = NTC probe.
dP3: Third probe display- no available
.dP4: Fourth probe display- no available
DIGITAL INPUT (ENABLED WITH P3P = N)
The free voltage digital input is programmable in different configurations
by the “i1F” parameter.
Door switch input (i1f = dor)
It signals the door status and the corresponding relay output status
through the odc parameter:
no= normal (any change);, Fan= fan OFF; CPr= Compressor OFF, F_C= Compressor
and fan OFF.
Since the door is opened, after the delay time set through parameter did, the
door alarm is enabled, the display shows the message dA and the regulation
restarts is rtr = yES. The alarm stops as soon as the external digital input
is disabled again. With the door open, the high and low temperature alarms are
disabled.
Digital inputs polarity
The digital input polarity depends on the i1P parameter.
i1P=CL: the input is activated by closing the contact.
i1P=OP: the input is activated by opening the contact
GENERIC ALARM (i1F = EAL)
As soon as the alarm input is activated (for example enclosure temperature
higher than ALU value) the unit will wait for did time delay before signalling
the EAL alarm message. The outputs status doesn’t change. The alarm stops just
after the alarm input is deactivated.
SERIOUS ALARM MODE (i1F = bAL)
When the alarm input is activated (for example enclosure temperature higher
than ALU value), the unit will wait for did delay before signalling the CA
alarm message. The relay outputs are switched OFF. The alarm will stop as soon
as the alarm input is dectivated.
ALARM SIGNALS
Message | Cause | Putputs |
---|---|---|
“P1” | Room probe failure | Compressor output acc. to par. “Con” and “COF” |
“P3” | Third probe failure | Outputs unchanged |
“P4” | Fourth probe failure | Outputs unchanged |
“HA” | Maximum temperature alarm | Outputs unchange.d |
“ LA “ | Minimum temperature alarm | Outputs unchange.d |
“HA2” | Condenser high temperature | It depends on the “Ac2” parameter |
“LA2” | Condenser low temperature | It depends on the “bLL”parameter |
“dA” | Door open | Compressor according to rrd |
“EA” | External alarm | Output unchanged. |
“CA” | Serious external alarm (i1F=bAL) | All outputs OFF. |
“CA” | Pressure switch alarm (i1F=PAL) | All outputs OFF |
“rte” | Real time clock alarm | Alarm output ON; Other outputs |
unchanged; Defrosts according to par. “ l d F “ Set real
time clock has to be set
rtF| Real time clock board failure| Alarm output ON; Other outputs
unchanged; Defrosts according to par. “ l d F “ ****
Contact the service
DEFAULT SETTING VALUES
Label| Name| Range| °C/°F|
---|---|---|---|---
Set| Set point| LS÷US| 31.0| —
Hy| Differential| 0,1÷25.5°C/ 1÷ 255°F| 4.0| Pr1
Ot| Thermostat probe calibration| -12÷12°C /-120÷120°F| 0.0| Pr1
AC| Anti-short cycle delay| 0 ÷ 50 min| 3| Pr1
CH| Kind of action| CL=cooling; Ht= heating| cL| Pr1
rES| Resolution| in=integer; dE= dec.point| dE| Pr1
IdF| Interval between defrost cycles| 1 ÷ 120 hours| 8| Pr1
MdF| (Maximum) length for defrost| 0 ÷ 255 min| 0| Pr1
ALU| MAXIMUM temperature alarm| Set÷ 110.0°C; Set÷230°F| 50.0| Pr1
ALL| Minimum temperature alarm| -50.0°C÷Set/ -58°F÷Set| -50.0| Pr1
i1P| Digital input polarity| oP=opening;CL=closing| oP| Pr1
i1F| Digital input configuration| EAL, bAL, PAL, dor; dEF; Htr, AUS|
dor| Pr1
did| Digital input alarm delay| 0÷255min| 0| Pr1
PbC| Kind of probe| Ptc; ntc| ntc| Pr1
dP3| Third probe display| —| noP| Pr1
dP4| Fourth probe display| —| noP| Pr1
SPARE PARTS LIST
ABREVIATION | DESCRIPTION | CODE |
---|---|---|
M1 | Compressor | COMPRNJ6226ZX |
M2 | Evaporator fan | VCENT220D230V |
M3 | Condenser fan | VCENT250D230V |
C 1 | Evaporator fan capacitor | CON2UFS2M8F |
C 3 | Condenser fan capacitor | CON5UFS2M8F |
TR | Electronic regulating thermostat | TERMDIG1S1D2R |
TA | Anti-ice safety thermostat | TERM.ALL.COND |
K1 | Contactor | CONTAT9A3P |
ACCESSORIES
**** Accessories are not included in air conditioner package, if needed, they can be ordered according following codes:
DESCRIPTION | CODE |
---|---|
Filter | KFR.03P |
FILTER
Filter Installation
Filter can be easily installed in retrofit.
Place the filter on the air conditioner cover as is shown by picture below.
Place the hooks inside of housings placed on the cover.
Push the filter to the bottom until the hooks are right placed.
Filter removal
Carry out the operations in reverse order according to filter installation.
Filter mat cleaning
The filter mat can be cleaned with compressed air or water and without
aggressive washing detergent.
Filter mat cleaning or replacement depends to environmental dirt. Check the
filter mat status periodically.
WARRANTY
WE Alfa Electric
Division of:
ALFA PLASTIC s.a.s.
Via Della Valle, 39 – 20048 CARATE BRIANZA (MI)
Tel. +39 (0362) 903.539 – Fax +39 (0362) 975.133
Mail: info@alfaelectric.com
www.alfaelectric.com
guarantees that the product is free from any quality defects.
The product is guaranteed for a period of 12 months from the date of delivery, provided it operates under the following conditions:
- value of power supply indicated in the data plate is completely respected;
- requirements specified on user’s manual are completely respected;
- cabinet temperature is not higher or lower than its rated temperature;
- ambient temperature is not higher or lower than its rated temperature;
- the product is mounted on cabinets with a minimum IP54 protection level;
- the product is mounted on cabinets that not requiring higher cooling power than expected;
- the product is clearly identifiable by serial number.
The warranty does not apply if :
- the cooling circuit has been modified about type and quantity of refrigerant or composition;
- the unit operates in acid or corrosive ambient;
- the unit has been modified without ALFAPLASTIC consent.
This warranty shall become null as soon as the product is altered or modified
in its structure or in circuits. The terms of this warranty (commencement and
termination dates) are not modified by any repair or replacement of products.
For every part that results defective during the period of this warranty,
ALFAPLASTIC shall repair or replace it. Any others charges arising from
removal, handling and installation of the products shall not be refunded by
ALFAPLASTIC. Like is specified on user’s manual, installation, handling, the
correct earthing in accordance with all current standards are under the
responsibility of costumer. In the event of any damage caused by a defective
product shall apply the EEC85.374 standard. The malfunction must be
communicated in writing to ALFAPLASTIC. Warranty is void if the costumer is
not in good standing with the payments
LEGAL RAPRESENTATIVE
FIORATTI P
UE DECLARATION OF CONFORMITY
WE Alfa Electric
Division of:
ALFA PLASTIC s.a.s.
Via Della Valle, 39 – 20841 CARATE BRIANZA (MB)
Tel. +39 (0362) 903.539 – Fax +39 (0362) 975.133
Mail: info@alfaelectric.com
www.alfaelectric.com
DECLARE THAT THE AIR CONDITIONER FOR ELECTRICAL CABINETS
AVC, AVE, ARC SERIES
DO COMPLY WITH THE FOLLOWING DIRECTIVES
2006/42/CE MACHINERY DIRECTIVE (17 May 2006)
2014/35/UE LOW VOLTAGE DIRECTIVE (26 February 2014)
2014/30/UE EMC DIRECTIVE (26 February 2014)
2011/65/UE ROHS DIRECTIVE (8 June 2011)
STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE
EN 60335-2-40:2003; A1; A2 (IEC 60335-2-40: 2002; A1; A2)
EN 60335-1: 2010; A11; A13; A14; A1; A2 (IEC 60335-1; A1; A2)
OTHER STANDARDS APPLIED
EN 55014-1: 2017
EN 55014-2: 2015
EN IEC 61000-3-2: 2019
EN 61000-3-3: 2013
EGAL RAPRESENTATIVE FIORATTI P.
Customer Support
Document: UMA-CDZ-ARC300.432-02 | Date | Name |
---|
Description Original user’s manual for air conditioner ARC300 series
Language: English| ISSUE| 30/10/2020| Ascheri M.
REV. 01| 30/03/2021| Ascheri M.
REV. 02| 19/05/2021| Ascheri M.
REV. 03| |
Division of:
ALFAPLASTIC s.a.s.
Via Della Valle, 39 – 20841 Carate Brianza (MB) Italy
Tel. +39 (0362) 903.539 Fax. +39 (0362) 975.133
Mail: info@alfaelectric.com
www.alfaelectric.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>