novus RS485 USB Converter Instruction Manual
- June 14, 2024
- Novus
Table of Contents
novus RS485 USB Converter Instruction Manual
SAFETY ALERTS
The symbols below are used in the device and throughout this manual to draw the user’s attention to important information related to device safety and use.
| |
---|---|---
CAUTION
Read the manual fully before installing and operating the device.|
CAUTION OR HAZARD
Risk of electric shock.| ATTENTION
Material sensitive to static charge. Check precautions before handling.
If the instrument is used in a manner other than that specified in this manual, the device’s safety protections may not be effective.
PRESENTATION
The USB-i485 Converte r is a cost-effective way to convert RS485 or RS422 industrial buses to a USB interface. When connected to a PC USB port the USB-i485 Converter is automatically detected and is installed as a native COM port, which is compatible with any existing serial communication application.
Multiple modules can be installed when using USB hubs thus allowing a hassle- free configuration of a multi serial system without any IRQ or DMA configuration.
1500 Vdc galvanic isolation between the USB port and RS485/RS422 protects the PC from spikes or possible misconnections in the communication bus.
The USB-i485 Converter can be configured for four-wire (Full Duplex) RS422 and RS485 or two-wire (Half Duplex) networks. When operating in two-wire RS485 the data transfer control is automatically done by the converter. Two independent and isolated RS485 networks can be supported by one USB-i485 Converter thus duplicating the possible number of remote devices.
DIMENSION
Fig. 01 – USB-i485 Converter
USB DRIVER INSTALLATION
The following installation steps may be slightly different depending on your PC configuration and Windows version. Follow the Wizard instructions and use the following steps and figures to select the correct installation options.
-
WINDOWS
a) Run the driver file available on our website.
b) Connect the module to a PC USB port. Windows® will detect the new hardware and will try to install it automatically.
c) After a few seconds, an installation error message will be displayed on the bottom right corner of the screen. This error has to do with the fact that Windows cannot recognize any device that has not been previously subscribed by Microsoft.
d) Open the Device Manager screen and search for the “F232R USB UART” device in the “Other Devices” category. Double-click it and click on the “Update Driver…” button.
e) Choose the “Browse my computer for driver software” option.
f) Select the “Drivers\Windows”. Let the “Include subfolders” selected.
g) If a window asking whether you want to install this driver pops up, choose to install.
h) Wait a few more seconds. A window displaying the installation success will be shown. -
LINUX
Since version 2.4.20, the necessary driver for the converter to work properly is already included in kernel.
Once you connect the converter to a PC USB port, the following modules should be loaded (they must be in the kernel list of modules):- ftdi_sio : (specific driver of the converter);
usbserial : (generic driver for USB-Serial conversion);
usbcore : (basic driver for USB devices).
- ftdi_sio : (specific driver of the converter);
-
MAC
See the documentation on the device page on our website. The Virtual Driver COM file provides information about how to perform the installation.
SERIAL PORT (COM PORT) ASSIGNMENT – WINDOWS
-
DETERMINATION
The serial port associated to the USB-1485 Converter is automatically determined by the operational system a few instants after the USB-1485
Converter connection. The user may easily identify or alter the COM port associated to the USB-1485 Converter accessing the Windows® “Device
Manager”:
Control Panel/System/Hardware/Device Manager/COM & LPT Ports
It’s also possible to open the “Device Manager” executing the following command: “devmgmt.msc”,
After opening the “Device Manager”, it’s possible to verify which is the Serial Port (COM) associated to the USB-1485 Converter. As it can be seen in Fig. 02, the USB-i485 Converter is associated to COM7.
Fig. 02 -COM Port Determination -
SELECTION
In case it’s necessary to modify the Serial Port (COM) associated to the USB-1485 Converter, select “USB Serial Port (COM X) where the USB-4485 Converter is connected. Access “Action Properties” and, in the “Port Definitions” tab, dick Advanced, as shown in Fig. 03. In case this tab does not appear, the driver was not installed correctly and the software must be reinstalled. in the “Advanced definitions for COMX window, change the parameter COM Port Number” for the desired COM, as shown in Fig. 04. Some serial ports may be marked as “In Use”. Only select one of these ports in case you are sure that it is not being used by another peripheral of your computer In some situations, the serial ports may be marked as in use even when the associated device is not installed anymore in the computer. In this case, it is safe to associate this port to the USB-1485 Converter.
Fig. 03- Accessing the COM port advanced configuration -
IMPORTANT RECOMMENDATION
To improve the communication of the USB interface, it is recommended the configuration of a Latency Timer. This parameter may be modified accessing “Advanced definitions for COMX” window, as shown in Fig. 03.
Later it’s possible to verify, as shown in Fig. 04. the “Latency Timer (ms)”, which must be altered to 4.
Fig. 04 -Advanced definitions for COM
CONNECTIONS
The appropriate connection to the USB-i485 Converter depends on the type of
serial network: RS422, 2-wire RS485 or 4-wire RS485. The
following figure shows a description of all USB-i485 Converter connection
terminals.
Fig. 05 – Device Connections
A shielded twisted-pairs cable is recommended for wiring the communication bus
from the converter to all network devices. The shield should be grounded
and/or connected to the common terminals of all devices. The minimum
recommended wire gauge is 24 AWG (0,2 mm2 ).
| Use of a wire connecting all devices common terminals is highly
recommended. Damage of the networked devices may
result if this recommendation is not followed.
---|---
RS485 or RS422 devices from different vendors or of different models may
identify the communication terminals using distinct notation. The
following table shows some of this notations and its equivalence to the
USB-i485 Converter.
USB-i485 CONNECTION IDENTIFICATION | Rx+ ou Tx+ | Rx- ou Tx- |
---|
POPULAR RS485 AND RS422 CONNECTION IDENTIFICATION
| D| D
D1| D0
B| A
D+| D-
Table 01 – Identification
-
HALF-DUPLEX RS485 HALF-DUPLEX (2 WIRES)
To set this mode of operation, the MOD terminal (pin 4) must be left unconnected.
This is the usual RS485 connection. A single twisted pair is used for data transmission and reception. Multiple RS485 devices are connected in a
single bus, as shown in the next figure. Devices from different vendors may use different names for the data signal terminals.
In the following figure, different identification schemes are presented for each device, with the proper connection to the USB-i485 Converter.
RS485 devices can be connected to either bus 1 or 2.
Fig. 06 – Half-Duplex RS485 (2 wires)
The common terminal (GND – pin 5) must be connected to the corresponding terminals of all network devices, to ensure the same potential in all
devices. If a common wire is not connected to all devices, all must be properly grounded according to the manufacturer recommendation. For the
USB-i485 Convert, the proper grounding terminal is pin 5 (GND).
The need to install termination resistors depends on the total length of the communication bus and the communication speed (Baud Rate). The
USB-i485 Convert has built-in termination resistors, which can be installed by wiring terminals RT1 (8) or RT2 (3) as shown in dashed lines in the last figure.
For additional information in grounding, common wire and termination resistors, read the document RS485 & RS422 Basic, available on our
website : www.novusautomation.com for download. -
FULL-DUPLEX RS485 FULL-DUPLEX (4 WIRES)
To set this mode of operation, the MOD terminal (pin 4) must be connected to terminal GND (pin 5).
In this mode two pairs of wires are used. Data from the USB-i485 Convert to the networked devices are transmitted through one pair, and the other pair carries data from the devices to the USB-i485 Convert. Multiple devices are connected as shown in the next figure.
Fig. 07 – Full-Duplex RS485 (4 wires)
The common terminal (GND – pin 4) must be connected to the corresponding terminals of all network devices, to ensure the same potential in all devices. If a common wire is not connected to all devices, all must be properly grounded according to the manufacturer recommendation. For the USB-i485 Converter, the proper grounding terminal is pin 5 (GND).
The need to install termination resistors depends on the total length of the communication bus and the communication speed (baud rate). The USB-i485 Converter has a built-in termination resistor, which can be installed by wiring terminal RT2 (3) as shown in dashed lines in the last figure.
For additional information in grounding, common wire and termination resistors, read the document RS485 & RS422 Basic, available on our -
RS422
Full-Duplex RS485 specification supersedes RS422. The same connection instructions shown for Full-Duplex RS485 apply for RS422 connection.
CONFLICTS WITH OTHER USB DEVICES UNDER WINDOWS
Installation of the USB driver for the USB-i485 converter may result in
conflicts with existing USB devices in the computer (mouse or other Serial/USB
devices, for example). In this case, follow the procedure below to restore
functionality of the affected device:
o to the Windows Control Panel and open the USB-i485 Converter properties in:
Control Panel / System / Hardware / Device Manager / Ports (COM & LPT)
Select the desired “USB Serial Port” device, click with the right mouse button and select “Properties”. Select “Port Settings” and click on the “Advanced…” button. Uncheck the “Serial Enumerator” option:
Fig. 08 – Serial Enumerator
TECHNICAL SPECIFICATIONS
Computer Interface | USB V1.1 Plug and Play |
---|---|
Operational system virtual serial port driver | Windows: Windows 10, |
8, 7, Vista, XP, Server 2008, Server 2003, 98, ME, 2000, CE; MAC;Linux 2.4.20
or above.
Field Interfaces| RS485 Half Duplex (dual buses); RS485 Full
Duplex;RS422.
Data Rate| From 300 bps to 250 kbps.
Maximum RS485/RS422 cable length| 1200 m
Maximum number of devices in the RS485 network| Maximum number of
devices in the RS485 network (unit load devices – 12 k ): Half Duplex: 2 x 32
devices;Full Duplex: 32 devices.
Power| From the USB post. Consumption: <100 mA.
Isolation| 1500 Vcc (1 minute) from USB interface and the RS485/RS422
interface.
RS485/RS422 bus protection| ±60 Vcc, 15 kV ESD
USB Connection| Mini-B connector.A 1.5 m cable with plugs mini-B and A
is provided with the device.
RS485/422 Connector| Screw terminal type accepting 1.5 mm² (16 AWG)
wires.
Operating Environment| 0 to 50 °C, 10 to 90 % relative humidity, non-
condensing.
Communication protocol| Jumper selected RS485 / RS422.
Flow Control| Automatic flow control for RS485 Half Duplex.
Internal Terminating Resistors| 120 Ohms internal resistors
termination enabled by jumpers.
LEDs| Transmission and reception of data.
ABS Housing| 70 x 60 x 18 mm.
Certifications| CE
Table 02 – Technical Specifications
CE Mark
This is a Class A product. In a domestic environment, this product may cause
radio interference in which case the user may be required to take adequate
measures.
1.888.610.7664 www.calcert.com sales@calcert.com
References
- Calcert
- NOVUS Automation Inc. - Controllers, Thermostats, Data Loggers, Solid State Relays, Sensors, Transmitters, SCADA, Data Acquisition and Temperature Controllers
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>