solis S5-EH1P-L Hybrid Inverter Instruction Manual

June 14, 2024
solis

S5-EH1P-L Hybrid Inverter

Product Information

Specifications

  • Product Name: Solis S5-EH1P-L Hybrid Inverter

  • Manufacturer: Ginlong Technologies Co., Ltd.

  • Address: No. 57 Jintong Road, Binhai Industrial Park,
    Xiangshan, Ningbo, Zhejiang, 315712, P.R.China

  • Contact: Tel: +86 (0)574 6578 1806, Fax: +86 (0)574 6578
    1606

  • Version: Ver1.0

1. Introduction

1.1 Product Description

The Solis S5-EH1P-L Hybrid Inverter is a high-quality product
designed for use in Australia. It is manufactured by Ginlong
Technologies Co., Ltd.

1.2 Packaging

The inverter comes in a secure and durable packaging to ensure
safe delivery. Please check the contents of the package upon
receipt to ensure that all components are present.

2. Safety & Warning

2.1 Safety

Safety is of utmost importance when operating the Solis
S5-EH1P-L Hybrid Inverter. Please read and understand all safety
instructions provided in this manual before using the product.

2.2 General Safety Instructions

Follow these general safety instructions while using the
inverter:

  • Do not operate the inverter in wet or humid conditions.

  • Avoid exposing the inverter to extreme temperatures.

  • Ensure proper ventilation around the inverter to prevent
    overheating.

  • Do not open the inverter casing as it contains high-voltage
    components.

  • Keep children and unauthorized personnel away from the
    inverter.

2.3 Notice For Use

If you encounter any issues with the inverter, please find the
inverter’s serial number and contact Ginlong Technologies Co., Ltd.
for assistance. They will try to respond to your question as soon
as possible.

3. Overview

3.1 Screen

The inverter features a user-friendly screen that displays
important information and settings.

3.2 Keypad

The keypad allows you to navigate through the inverter’s menu
and make adjustments to its settings.

3.3 Terminal Connection

The inverter has terminal connections for easy installation and
connection to other components.

4. Installation

4.1 Select a Location for the Inverter

Choose a suitable location for installing the inverter. Ensure
that it is well-ventilated and protected from direct sunlight and
moisture.

4.2 Mounting the Inverter

Follow the provided instructions to securely mount the inverter
on a stable surface or wall.

4.3 PE Cable Installation

Connect the PE cable according to the provided guidelines to
ensure proper grounding of the inverter.

4.4 PV Input Cable Installation

Install the PV input cables following the recommended wiring
diagrams and guidelines provided by Ginlong Technologies Co.,
Ltd.

4.5 Battery Power Cable Installation

If applicable, connect the battery power cable to the inverter
as per the instructions provided.

4.12 Earth Fault Alarm

The inverter is equipped with an earth fault alarm system.
Follow the instructions in the manual to troubleshoot any earth
fault alarms.

4.13 LED Indicates

The inverter’s LED indicators provide important information
about its status. Refer to the manual for a detailed explanation of
the LED indications.

FAQ

Q: What should I do if I encounter a problem with the

inverter?

A: If you experience any issues with the inverter, please
contact Ginlong Technologies Co., Ltd. with the inverter’s serial
number for assistance.

Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712, P.R.China. Tel: +86 (0)574 6578 1806 Fax: +86 (0)574 6578 1606
Please adhere to the actual products in case of any discrepancies in this user manual. If you encounter any problem on the inverter, please find out the inverter S/N and contact us, we will try to respond to your question ASAP.

Solis S5-EH1P-L Hybrid Inverter
Instruction Manual
(ForAustralia) Ver1.0
Ginlong Technologies Co., Ltd.

Contents

1. Introduction ………………………………………………………………………………………………………………………………
1.1 Product Description ……………………………………………………………………………………………………………… 1.2 Packaging …………………………………………………………………………………………………………………………………
2. Safety & Warning ………………………………………………………………………………………………………………
2.1 Safety ………………………………………………………………………………………………………………………………………… 2.2 General Safety Instructions …………………………………………………………………………………………………
2.3 Notice For Use …………………………………………………………………………………………………………………………
3. Overview ……………………………………………………………………………………………………………………………………
3.1 Screen ………………………………………………………………………………………………………………………………………… 3.2 Keypad ………………………………………………………………………………………………………………………………………
3.3 Terminal Connection ………………………………………………………………………………………………………………
4. Installation …………………………………………………………………………………………………………………………………
4.1 Select a Location for the Inverter …………………………………………………………………………………… 4.2 Mounting the Inverter …………………………………………………………………………………………………………
4.3 PE Cable Installation ………………………………………………………………………………………………………… 4.4 PV Input Cable Installation ……………………………………………………………………………………………… 4.5 Battery Power Cable Installation ……………………………………………………………………………………
4.6 AC Cable Installation …………………………………………………………………………………………………………… 4.7 Communication Cable Installation ………………………………………………………………………………… 4.8 Meter Installation …………………………………………………………………………………………………………………… 4.9 External Residual Current Device(RCD) ………………………………………………………………… 4.10 Inverter monitoring connection ………………………………………………………………………………… 4.11 Max over current protection device (OCPD) …………………………………………………………
4.12 Earth Fault Alarm ……………………………………………………………………………………………………………… 4.13 LED Indicates ………………………………………………………………………………………………………………………
5. Commissioning & Shutdown …………………………………………………………………………………
5.1 Preparation of Commissioning ……………………………………………………………………………………… 5.2 Commissioning Procedure ……………………………………………………………………………………………… 5.3 Shutdown procedure …………………………………………………………………………………………………………
6. Operation …………………………………………………………………………………………………………………………………
6.1 Initial Display ……………………………………………………………………………………………………………………………
6.2 Main Menu ……………………………………………………………………………………………………………………………… 6.3 Information ……………………………………………………………………………………………………………………………… 6.4 Settings ……………………………………………………………………………………………………………………………………
6.5 Advanced Info ………………………………………………………………………………………………………………………… 6.6 Advanced Settings – Technicians Only …………………………………………………………………………
7. Maintenance ………………………………………………………………………………………………………………………… 8. Troubleshooting ………………………………………………………………………………………………………………… 9. Specifications ……………………………………………………………………………………………………………………… 10. Appendix …………………………………………………………………………………………………………………………………

01 01 02 03 03 03 05 06 06 06 06 07 07 09 11 12 15 20 22 27 33 33 34 34 35 36 36 36 45 46 46 48 48 51 53 58 81 82 88 97

1. Introduction
1.1 Product Description
The Solis S5-EH1P-L Series is designed for residential hybrid systems, which can work with batteries to optimize self-consumption. The unit can operate in both off- and on-grid modes. The Solis S5-EH1P-L Series has 5 different models: S5-EH1P3K-L, S5-EH1P3.6K-L, S5-EH1P4.6K-L, S5-EH1P5K-L, S5-EH1P6K-L

1. Introduction
1.2 Packaging
Please ensure that the following items are included in the packaging with your machine:

Inverter x1

Back plate x1

Fastening screw x3

AC grid terminal x1

Reminder light Display
Key
Figure 1.1 Front side view

AC backup terminal x1

DC connector x2

RJ45 connector x1

Battery Cable x2

CAN cable x1

RS485 Meter cable x1 (For Eastron Meter)

Eastron Meter x1

CT x1

Terminal cover x1

Connector x1

Battery Temperature Sensor x1 (Optional )

If anything is missing, please contact your local Solis distributor.

Manual User manual x1

Figure 1.2 Bottom side view

.01.

.02.

2. Safety & Warning
2.1 Safety
The following types of safety instructions and general information appear in this document as describedbelow:
DANGER: “Danger” indicates a hazardous situation which if not avoided, will result in death or serious injury.
WARNING: “Warning” indicates a hazardous situation which if not avoided, could result in death or serious injury.
CAUTION: “Caution” indicates a hazardous situation which if not avoided, could result in minor or moderate injury.
NOTE: “Note” provides tips that are valuable for the optimal operation of your product.
WARNING: Risk of fire Despite careful construction, electrical devices can cause fires.
Do not install the inverter in areas containing highly flammable materials or gases. Do not install the inverter in potentially explosive atmospheres.
2.2 General Safety Instructions
WARNING: Only devices in compliance with SELV (EN 69050) may be connected to the RS485 and USB interfaces.
WARNING: Please don’t connect PV array positive (+) or negative (-) to ground, it could cause serious damage to the inverter.
WARNING: Electrical installations must be done in accordance with the local and national electrical safety standards.
WARNING: Do not touch any inner live parts until 5 minutes after disconnection from the utility grid and the PV input.
.03.

2. Safety & Warning
WARNING: To reduce the risk of fire, over-current protective devices (OCPD) are required for circuits connected to the inverter. The DC OCPD shall be installed per local requirements. All photovoltaic source and output circuit conductors shall have isolators that comply with the NEC Article 690, Part II. All Solis single phase inverters feature an integrated DC switch. CAUTION: Risk of electric shock, do not remove cover. There is no user serviceable parts inside, refer servicing to qualified and accredited service technicians.
CAUTION: The PV array supplies a DC voltage when they are exposed to sunlight.
CAUTION: Risk of electric shock from energy stored in capacitors of the Inverter, do not remove cover for 5 minutes after disconnecting all power sources (service technician only). Warranty may be voided if the cover is removed without authorization . CAUTION: The surface temperature of the inverter can reach up to 75 (167 F). To avoid risk of burns, do not touch the surface of the inverter while it’s operating. Inverter must be installed out of the reach of children.
NOTE: PV module used with inverter must have an IEC 61730 Class A rating.
WARNING: Operations below must be accomplished by licensed technician or Solis authorized person.
WARNING: Operator must put on the technicians’ gloves during the whole process in case of any electrical hazards.
WARNING: AC BACKUP Port of S5-EH1P-L Series is not allowed to connect to the grid.
.04.

2. Safety & Warning
WARNING: The S5-EH1P-L Series does not support parallel (three- and single- phase) operation on the AC-BACKUP port. Connecting multiple units in parallel will void the warranty.

×××
3 Phase LOAD

××
1 Phase LOAD

×
Generator

WARNING: Please refer to the specification of the battery before configuration.
2.3 Notice For Use
The inverter has been constructed according to the applicable safety and technical guidelines. Use the inverter in installations that meet the following specifications ONLY: 1. Permanent installation is required. 2. The electrical installation must meet all the applicable regulations and standards. 3. The inverter must be installed according to the instructions stated in this manual. 4. The inverter must be installed according to the correct technical specifications.

.05.

3. Overview
3.1 Screen
Solis S5-EH1P-L Series adopts 7 inch color screen, it displays the status, operating information and settings of the inverter.
3.2 Keypad
There are four keys in the front panel of the inverter (from left to right): ESC, UP, DOWN and ENTER keys. The keypad is used for:
Scrolling through the displayed options (the UP and DOWN keys); Access and modify the settings (the ESC and ENTER keys).

Figure 3.2 Keypad
3.3 Terminal Connection
Solis S5-EH1P-L Series inverter is different from normal on-grid inverter, please refer to the instructions below before start connection.

Dry Contact Port (reserved)

DRM Connection

COM Port

Figure 3.3 Front Panel Display
WARNING: Please refer to the specification of the battery before configuration.
.06.

4. Installation
4.1 Select a Location for the Inverter
To select a location for the inverter, the following criteria should be considered: Exposure to direct sunlight may cause output power derating. It is recommended to avoid installing the inverter in direct sunlight. It is recommended that the inverter is installed in a cooler ambient which doesn’t exceed 104/40.

4. Installation
Install on a wall or strong structure capable of bearing the weight of the machine (18.3kg). Install vertically with a maximum incline of +/- 5 degrees, exceeding this may cause output power derating. To avoid overheating, always make sure the flow of air around the inverter is not blocked. A minimum clearance of 300mm should be kept between inverters or objects and 500mm clearance between the bottom of the machine and the ground.

300mm

300mm

300mm

300mm

300mm

500mm

500mm

Figure 4.1 Recommended Installation locations
WARNING: Risk of fire Despite careful construction, electrical devices can cause fires.
Do not install the inverter in areas containing highly flammable materials or gases. Do not install the inverter in potentially explosive atmospheres. The mounting structure where the inverter is installed must be fireproof.
.07.

Figure 4.2 Inverter Mounting clearance
Visibility of the LEDs and LCD should be considered. Adequate ventilation must be provided.
NOTE: Nothing should be stored on or placed against the inverter.
NOTE: This inverter complies with IEC 62109-2 clause 13.9 for earth fault alarm monitoring. If an Earth Fault Alarm occurs, the fault code “PV-ISO PRO 01/02” will be displayed on the inverter screen / the LED indicator “Alarm” will light up.
.08.

4. Installation
4.2 Mounting the Inverter
Dimensions of mounting bracket:

102

21

6.8

70

140

318

333

11.8 6.8

140

31
31
Figure 4.3 Inverter wall mounting
Once a suitable location has be found accordingly to 4.1 using figure 4.3 and figure 4.4 mount the wall bracket to the wall. The steps to mount the inverter are listed below: 1. Select the mounting height of the bracket and mark the mounting holes.
For brick walls, the position of the holes should be suitable for the expansion bolts.

.09.

4. Installation
Suitable fixing screws Bracket
Locking screw Figure 4.4 Fix bracket on the wall WARNING: The inverter must be mounted vertically. 2.Lift up the inverter (be careful to avoid injury), and align the back bracket on the inverter with the convex section of the mounting bracket. Hang the inverter on the mounting bracket and make sure the inverter is secure (see Figure 4.5)
Figure 4.5 Wall Mount Bracket .10.

4. Installation
4.3 PE Cable Installation
An external ground connection is provided at the right side of inverter. Prepare OT terminals: M4. Use proper tooling to crimp the lug to the terminal. Connect the OT terminal with ground cable to the right side of inverter. The torque is 2Nm.
Figure 4.6 Connect the external grounding conductor

4.4 PV Input Cable Installation

4. Installation

Before connecting inverter, please make sure the PV array open circuit voltage is within the limit of the inverter.
Before connection, please make sure the polarity of the output voltage of PV array matches the”DC+”and”DC-“symbols.

Please use approved DC cable for PV system.

1. Select a suitable DC cable and strip the wires out by 7±0.5mm. Please refer to the table below for specific specifications.

7±0.5mm

Cable type
Industry generic PV cable model:PV1-F

Cross sectionmm²

Range

Recommended value

4.0~6.0 12~10AWG

4.012AWG

Figure 4.7

2. Take the DC terminal out of the accessory bag, turn the screw cap to disassemble it, and take out the waterproof rubber ring.

Positive terminal

Negative terminal Nut

Figure 4.8

Waterproof collar

.11.

.12.

4. Installation

3. Pass the stripped DC cable through the nut and waterproof rubber ring. Positive terminal Negative terminal

Figure 4.9
4. Connect the wire part of the DC cable to the metal DC terminal and crimp it with a special DC terminal crimping tool.

Positive terminal Negative terminal

Squeeze

Figure 4.10

5. Insert the crimped DC cable into the DC terminal firmly, then insert the waterproof rubber ring into the DC terminal and tighten the nut.

Positive terminal Negative terminal

After you hear a “click”, pull gently to check for a firm engagement. Click

Tighten
Figure 4.11 .13.

4. Installation
6. Measure PV voltage of DC input with multimeter, verify DC input cable polarity.


  • Figure 4.12 7. Connect the wired DC terminal to the inverter as shown in the figure, and a slight “click” is heard to prove the connection is correct.
    Click
    Figure 4.13
    CAUTION: If DC inputs are accidently reversely connected or inverter is faulty or not working properly, it is NOT allowed to turn off the DC switch. Otherwise it may cause DC arc and damage the inverter or even lead to a fire disaster. The correct actions are: Use a clip-on ammeter to measure the DC string current. If it is above 0.5A, please wait for the solar irradiance reduces until the current decreases to below 0.5A. Only after the current is below 0.5A, you are allowed to turn off the DC switches and disconnect the PV strings. In order to completely eliminate the possibility of failure, please disconnect the PV strings after turning off the DC switch to aviod secondary failures due to continuous PV energy on the next day. Please note that any damages due to wrong operations are not covered in the device warranty.
    .14.

4. Installation
4.5 Battery Power Cable Installation
4.5.1 Normal battery cable installation
NOTE: External battery switch must be installed between the battery and inverter for safe maintenance purpose if the battery does not have built-in DC breaker. The battery switch must have a rated current greater than or equal to 80A/125A (80A for 3K~3.6K Models, 125A for 4.6K~6K Models). Connect the Battery cable to the inverter and make sure the positive and negative poles are correct. A “Click” sound means fully connection and fasten the cables with the terminal protection cover as indicated in Figure 4.14.
Figure 4.14 Installation of Terminal Protection Cover To remove the battery connection, please ensure the system is powered off and then remove the terminal protection cover. When disconnect the battery cables, please press the button as indicated in the figure while pulling out the cable.
Button
Figure 4.15 NOTE: Before connecting the battery, please carefully read the user manual of the battery and perform the installation exactly as the battery manufacturer requests.
.15.

4. Installation
4.5.2 Extended battery cable installation
If the battery cable size is required to be changed by the battery manufactuer, please refer to following content for the cable preparation. Otherwise, you may skip these steps.

A A-1 A-2

B C-1 C-2

D

Figure 4.16

A:Connector Body A-1: Barrel sealing (Not included when no sealing requirement) A-2: O-Ring (Not included when no sealing require ment)
B: Barrel(Only for cable size 16mm² ) C: Grommet(Not included when no sealing requirement)
C-1: For 16mm²
C-2: For 25mm² D: Back Shell

Step 1: Wire cutting and stripping (Apply for 10mm² & 16mm² Cable) Stripping conductor: 18±1mm

Conductor

Insulation Figure 4.17

.16.

4. Installation
Step 2: Un-assemble Grommet and Back shell over the cable as shown.

Grommet

Back shell

Correct direction: The chamfer in the rear position

Wrong direction: The chamfer at the front position
Figure 4.18 Step 3: Put the barrel and the cable conductor into the lug.
When 16mm² cable apply, assembly barrelinto lug firstly as shown

Then put the conductor into the lug

Tie closely in here Figure 4.19

.17.

4. Installation
Step 4: Crimping the lug as shown. Crimping heigth is 7.5+0/-0.2mm

Gap is 1.0 mm Ref. Crimping length is 7.5 ± 0.5 mm
Figure 4.20

Cable size 16mm² 25mm²

Cable range 8.10±0.20mm 10.20±0.20mm

Crimping heigth 7.5+0/-0.2mm

Table 4.1

Cable pullout force 1000N Min. 1200N Min.

Recommended crimping tool: Manual hydraulic crimping Die:25 mm²

Figure 4.21

.18.

4. Installation
Step 5: Install grommet and back shel. Assemble the grommet onto the connector body firstly

No gap

Then assemble back shell onto the connector body and tighten

Figure 4.22

4. Installation
4.6 AC Cable Installation
There are two AC terminals and the assembly steps for both are the same. TakeouttheACconnectorpartsfromthepackaging.

Describe Cable diameter Traverse cross sectional area Exposure Length

Numerical value 10~14mm 6~8mm² 9mm

Table 4.2

1. Disassemble the AC connector. Strip the AC wires about 9mm.

22mm

9mm

2. Set the parts on the cable. A

Figure 4.23

27mm

B CD E

Figure 4.24 3. Crimp wires screw twisting torque 0.8+/-0.1N·m.

9mm
A: Locker B: Body C: Seal body D: Claw E: Nut

Figure 4.25

.19.

.20.

4. Installation
4. Push Housing into Body.
Click
Figure 4.26 5. Insert Seal and Clamp Finger into socket ,then tighten the nut , torque 4+/-0.5N·m.
Figure 4.27 6. The same installation for both cable end plug and socket connectors. 7. Mating plug andsocket: Push the plug into the socket completely, then rotate the locker according to the direction instructed by the marks on thelocker.
Figure 4.28 NOTE: Before mating the plug and socket, please double check both AC Grid and AC Backup connectors. Do not connect the grid cables to the AC Backup port or connect the backup load cables to the AC Grid Port. Otherwise, it may leads to malfunction or damage. .21.

4. Installation
4.7 Communication Cable Installation
4.7.1 Communication Port Definition

Picture

Port

CAN Port

RS-485 Meter Port
DRM Port

COM Port

Function
1. Used for CAN communication between inverter and lithium battery BMS. 2. (Optional) Used for battery temperature sensor connection when lead-acid battery is used.
1. Used for RS485 communication between inverter and the compatible smart meter. It is necessary to realize the normal hybrid control logics.
1. (Optional) To realize Demand Response or Logic interface function, this function may be required in UK and Australia.
1. (Optional) Used for Solis Data Logger Connection. 2. (Optional) Used for Modbus RTU communication with a 3rd party external device.
Table 4.3

4.7.2 CAN Port Connection 4.7.2.1 CAN Communication with Lithium Battery
1. A 3m length pre-made CAN cable is provided in the accessory package with one end marked with “To CAN” and the other end marked with “To Battery”.

To CAN

To Battery
Figure 4.29 2. Insert the RJ45 terminal on the end of the CAN cable (Marked with “To CAN”) to the CAN port at the bottom of the inverter and fasten the swivel nut. 3. Connect the other end marked with “To Battery” to the battery.
.22.

4. Installation

NOTE:

Before connecting CAN cable with the battery, please check whether the

communication pin sequence of the inverter and the battery match;

If it does not match, you need to cut off the RJ45 connector at one end of the

CAN cable and adjust the pin sequence according to the pin definitions of

both inverter and battery. Pin definition of the inverter CAN Port is following

RJ45terminal

EIA/TIA 568B.

12345678

CAN-H on Pin 4: Blue CAN-L on Pin 5: Blue/White

CAN-L CAN-H

4.7.2.2 Battery Temperature Sensor Connection for Lead-acid Battery (Optional)
NOTE: Battery temperature sensor can be optionally used with lead-acid battery for inverters to accurately detect the battery ambient temperature and adjust voltage compensation based on the customer-defined coefficient. It is an optional accessory which may not be provided with the inverter package. If lead-acid battery is used and battery temperature sensor is needed, please contact your distributor or Solis sales to purchase individually.
1. Insert the RJ45 terminal end to the CAN port at the bottom of the inverter and fasten the swivel nut. (Cable length: 1 meter)
2. Fasten the temperature sensor ring onto the battery module. If no suitable fastening terminal can be found on the battery module, the sensor ring can be attached to the positive or negative pole of the battery module.

Figure 4.30

.23.

4. Installation
4.7.3 RS485 Meter Port Connection
4.7.3.1 RS485 Meter Connector Assemble Steps
A 2-pin connector with 5m RS485 cable for meter communication can be found in the package. If extending the RS485 cable, please ensure the distance is within 100m and twisted shielded RS485 cable should be used to prevent signal interference. Red wire is RS485A Black wire is RS485B

A. Connection Part B. Rotatory Ring C. Main Body D. Sealing Ring E. Fasten Nut Figure 4.31

RS485A

RS485B

Figure 4.32
4.7.3.2 Compatible Smart Meter RS485 Connection

Compatible Smart Meter Model SDM120CT (Default) SDM120M SDM630MCT SDM630
ACR10R16DTE
ACR10R16DTE4

Meter RS485 Pin Definition Pin 9 ­ RS485B, Pin 10 ­ RS485A Pin 9 ­ RS485B, Pin 10 ­ RS485A Pin 13 ­ RS485B, Pin 14 ­ RS485A
B ­ RS485B, A ­ RS485A RJ45 Port on the meter Pin 7 ­ RS485B, Pin 8 ­ RS485A Pin 21 ­ RS485A, Pin 22 ­ RS485B

Table 4.4

.24.

4. Installation
4.7.4 DRM Port Connection (Optional)
4.7.4.1 For Remote Shutdown Function
Solis inverters support remote shutdown function to remotely control the inverter to power on and off through logic signals. The DRM port is provided with an RJ45 terminal and its Pin5 and Pin6 can be used for remote shutdown function.

Signal Short Pin5 and Pin6 Open Pin5 and Pin6

Table 4.5

Function Inverter Generates Inverter Shutdown in 5s

Rj45 plug

1–8

RJ45terminal

Correspondence between the cables and the stitches of plug, Pin5 and Pin6

12345678

of RJ45 terminal is used for the logic interface, other Pins are reserved.

Pin 1: Reserved; Pin 2: Reserved

12345678

Pin 3: Reserved; Pin 4: Reserved

Switch_input1 Switch_input2 Pin 5: Switch_input1; Pin 6: Switch_input2

DRM(logic interface)

Pin 7: Reserved; Pin 8: Reserved

Figure 4.33 Strip the insulation layer and connect to RJ45 plug
4.7.4.2 For DRED Control Function (For AU and NZ Only)
DRED means demand response enable device. The AS/NZS 4777.2:2020 required inverter need to support demand response mode(DRM). This function is for inverter that comply with AS/NZS 4777.2:2020 standard. A RJ45 terminal is used for DRM connection.

Pin

Assignment for inverters capable of both charging and discharging

Pin

Assignment for inverters capable of both charging and discharging

1

DRM 1/5

5

RefGen

2

DRM 2/6

6

Com/DRM0

3

DRM 3/7

7

V+

4

DRM 4/8

8

V-

Table 4.6

.25.

4. Installation

NOTE: Solis hybrid inverter is designed to provide 12V power for DRED.

RJ45 plug 1–8

RJ45terminal 12345678

12345678

Correspondence between the cables and the stitches of plug Pin 1: white and orange ; Pin 2: orange Pin 3: white and green Pin 4: blue Pin 5: white and blue Pin 6: green Pin 7: white and brown Pin 8: brown

Figure 4.34 Strip the insulation layer and connect to RJ45 plug

4.7.5 COM Port Connection (Optional)
COM Port can be used for either Solis Data Logger connection or 3rd party monitoring/control device with Modbus RTU communication.
4.7.5.1 Solis Data Logger Installation
1. Remove the watertight cap from the COM port. 2. Insert the Solis Data Logger to the COM port to match the joint.

Match the joint Figure 4.35
3. Rotate the black ring on the Solis Data Logger in clockwise to secure the connection. NOTE: Do not rotate the main body of the Solis Data Logger. It may damage the logger and the inverter COM port.
.26.

4. Installation
Figure 4.36
4.7.5.2 Third party monitoring/control device connection
If a third party monitoring/control device need to be connected directly to the inverter, the COM port can be used with a special connector to extend the RS485A and RS485B pins, please contact Solis local service team or Solis sales for this special connector.
Figure 4.37 Modbus RTU protocol is supported by Solis inverters. To acquire latest protocol document, please contact Solis local service team or Solis sales.
4.8 Meter Installation
CAUTION: Make sure the AC cable is totally isolated from AC power before connecting the Smart Meter and CT. A Smart Meter with the CT in product box is compulsory for hybrid system installation. It can beused to detect the grid voltages and current directions, provide the operating condition of the hybridinverter via RS485 communications.
.27.

4. Installation

NOTE:
1. The Smart Meter with CT is already configured ; please do not change any settings on the Smart Meter.
2. One Smart Meter can be used with only one hybrid inverter.

The Solis S5-EH1P-L Series inverter is able to connected Acrel meters or Eastron meters to fuilfill the control logic of the self-consumption mode, export power control, monitoring, etc. Acrel 1ph meter (With CT): ACR10R-D16TE (Optional) Acrel 3ph meter (With CT): ACR10R-D16TE4 (Optional) Eastron 1ph meter (Direct Insert): SDM120M (Optional) Eastron 1ph meter (With CT): SDM120CT Eastron 3ph meter (Direct Insert): SDM630 (Optional) Eastron 3ph meter (With CT): SDM630MCT (Optional) Below 4.8.1 section describes the connection diagram of 1ph meter Eastron SDM120CT and Acrel ACR10R-D16TE. Below 4.8.2 section describes the connection diagram of 3ph meter Eastron SDM630MCT and Acrel ACR10R-D16TE4.

NOTE:
Please note that the CT orientation must be correct, otherwise the system will not work properly.

Grid side K L

Compatible Smart Meter Model SDM120CT (Default) SDM120M SDM630MCT SDM630
ACR10R16DTE
ACR10R16DTE4

Meter RS485 Pin Definition Pin 9 ­ RS485B, Pin 10 ­ RS485A Pin 9 ­ RS485B, Pin 10 ­ RS485A Pin 13 ­ RS485B, Pin 14 ­ RS485A
B ­ RS485B, A ­ RS485A RJ45 Port on the meter Pin 7 ­ RS485B, Pin 8 ­ RS485A Pin 21 ­ RS485A, Pin 22 ­ RS485B

Table 4.7

.28.

4. Installation
4.8.1 Single phase meter installation

.29.

RS485 Meter COM

PV strings CB CB
Battery

RS485 Meter
S5-EH1P-L

Back-up L N PE
L N PE Grid

Distribution box CB
RCD CB
RCD

Power cable

PE N L Load_a

Note: If the CT is installed in the wrong direction, the Hybrid Inverter can’t work normally.

Pin 9 ­ RS485A – Black Pin 10 ­ RS485B – Red
Critical Load
L N PE

34
8 9 10 SDM120M
567 12 1:White 2:Black

L N GRID PE

Grid side K L
CT direction towards to grid

Figure 4.38 (Eastron SDM120CT)

RS485 Meter COM

PV strings CB CB
Battery

S5-EH1P-L S5-EH1P-L

Back-up L N PE
L N PE Grid

Distribution box CB RCD
CB
RCD

Critical Load
L N PE

Power cable

PE N L

Note: If the CT is installed in the wrong direction, the Hybrid Inverter can’t work normally.

Load_a

Figure 4.39 (Acrel ACR10R-16DTE)

N L

RJ45 Port

1 2 3 41312 Meter

5 6 7 8 9 10212223 White Black

CT

L

N GRID

PE

Grid side K L
CT direction towards to grid

4. Installation

.30.

4. Installation
4.8.2 Three phase meter installation

.31.

PV strings CB CB
Battery

RS485 Meter
S5-EH1P-L

Back-up L N PE
L N PE Grid

Distribution box CB
RCD

CB

RS485

RCD

Critical Load
L N PE

Power cable

PE N L Load_a

Note: If the CT is installed in the wrong direction, the Hybrid Inverter can’t work normally.

Figure 4.40 (Eastron SDM630MCT)

BA

CT Wires Left: Black Right: White

9 10 11 12 13 14 15 16 17 18 19 20
Meter

Voltage Sampling

Power

1 2 3 4 5 6 7 8

CT3 CT2
CT1

L3 L2 L1 GRID N
PE

Grid side K L
CT direction towards to grid

PV strings S5-EH1P-L
Battery

Back-up L N PE
La N PE Grid

Distribution box RCD
RS485
RCD

Critical Load:3kw
L N PE

N

Lc Lb

N

La

La

1 2 3 4 1312
Meter

A B 5 6 7 8 9 10 212223
RS485

CTc

Lc

CTb

Lb

CTa

La GRID

N

PE

RCD

RCD

PE N L

Power cable

Load_a

PE

N La Lb Lc

Load_b

Note: If the CT is installed in the wrong direction, the Hybrid Inverter can’t work normally.
Figure 4.41 (Acrel ACR10R-16DTE4)

PE N Lc Load_c
Grid side K L
CT direction towards to grid

4. Installation

.32.

4. Installation
4.9 External Residual Current Device(RCD)
All series of Solis inverters are integrated with an internal residual current device to protect against any potential d.c component and a.c component of residual current. Therefore, all Solis inverters, due to the design, are not able to feed in DC fault current to the system which fully complies with IEC60364-7-712. If an external RCD is required to be installed by local regulations, Solis recommends installing a Type-A RCD with a threshold current higher than 100mA.
4.10 Inverter monitoring connection
The inverter can be monitored via Wi-Fi or GPRS. All Solis communication devices are optional. For connection instructions, please refer to the Solis Monitoring Device installation manuals.

Smart phone monitoring

GPRS monitoring

Wi-Fi monitoring

Router

Wi-Fi monitoring

Wi-Fi box

Internet

Web server

PC monitoring

Figure 4.42 Wi-Fi orGPRScommunication function

4. Installation
4.11 Max. over current protection device (OCPD)
To protect the inverter’s AC grid connection conductors, Solis recommends installing AC breakers that will protect againt overcurrent. The following table defines OCPD ratings for these inverters.

Inverter S5-EH1P3K-L S5-EH1P3.6K-L S5-EH1P4.6K-L S5-EH1P5K-L S5-EH1P6K-L

Rated voltage(V)
230 230 230 230 230

Rated output current (Amps)
13.1 15.7 20.0 21.7 26.1

Table 4.8 Rating of grid OCPD

Current for protection device (A)
20 20 30 30 40

4.12 Earth Fault Alarm
Solis inverters fully comply with IEC62109-2 in terms of earth fault alarm (PV insulation detection and protection). When the earth fault on PV side happens, the yellow alarm indicator will flash and the alarm code “PVISO-PRO” will show up on the LCD screen.
Inverter should be installed in a high traffic area to ensure the alarm to be noticed. The inverter can’t start to generate until the earth fault is resolved. Please refer to the troubleshooting section of this manual to resolve the earth fault or contact Solis service team for help. For the earth fault happened on battery inputs, customer shall install external alarm and monitoring device to comply AS/NZS 5139.

.33.

.34.

4. Installation
4.13 LED Indicators
There are three LED indicators on the RHI inverter (Red, Green, and Orange) which indicate the working status of the inverter.

Light POWER OPERATION
ALARM

Status

Description

ON

The inverter can detect DC power.

OFF

No DC power.

ON

The inverter is fully operational.

OFF

The inverter has stopped operating.

FLASHING

The inverter is initializing.

ON

Fault condition is detected.

OFF

No fault condition detected.

FLASHING

Either the grid or solar cannot be detected.

Table 4.9 Status Indicator Lights

5. Commissioning
5.1 Preparation of Commissioning
Ensure all the devices are accessible for operation, maintenance and service. Check and confirm that the inverter is firmly installed. Space for ventilation is sufficient for one inverter or multiple inverters. Nothing is left on the top of the inverter or battery module. Inverter and accessories are correctly connected. Cables are routed in safe place or protected against mechanical damage. Warning signs and labels are suitably affixed and durable.
5.2 Commissioning Procedure
5.2.1 Recommended Installation
1. Measure DC voltage of PV strings and battery and ensure the polarity is correct.


  • 2. Measure AC voltage and frequency and ensure they are within local standard.

3. Switch on the external AC breaker to power on the LCD of the inverter.

.35.

.36.

5. Commissioning

4. Enter advanced settings (do not repeat this step for all subsequent operations).

0.00kW 0.00kW

0.00kW

2.526 KWH
0.00kW

SMeettninugs

Information

2015-02-23 19 35

Settings

Advanced Information

Advanced Settings

SPeatstsinwgosrd

Step 1

2015-02-23 19 35

Please Input The Current Password

0

0

1

0

Step 2

YES= NO=

ESC

UP

DOWN

ENT

Step 3

5. Select the local grid standard code.

Advanced Settings
Select Standard ON/OFF Calibrate
Reset Password Restart HMI
Storage Energy Set

2015-02-23 19 35
Export Power Set HMIUpdate DSPUpdate
BaudRate RS485 Special Settings

ESC

UP

DOWN

ENT

Step 1

SetleticntgSs tandard

Select Standard: 4777_A

2015-02-23 19 35

YES= NO=
Step 2

5. Commissioning

Region Standard Code Name OV-G-V1 OVGV1-T OV-G-V2 OVGV2-T UN-G-V1 UNGV1-T UN-G-V2 UNGV2-T OV-G-F1 OVGF1-T OV-G-F2 OVGF2-T UN-G-F1 UNGF1-T UN-G-F2 UNGF2-T Startup-T Restore-T Recover-VH Recover-VL Recover-FH Recover-FL Start- VH Start-VL Start-FH Start-FL

Australia A
4777-A
265V 1.5S 275V 0.1S 180V 10S 70V 1.5S 52HZ 0.1S 52HZ 0.1S 47HZ 1.5S 47HZ 1.5S 60S 60S 253V 205V 50.15Hz 47.5Hz 253V 205V 50.15Hz 47.5Hz

Australia B
4777-B
265V 1.5S 275V 0.1S 180V 10S 70V 1.5S 52HZ 0.1S 52HZ 0.1S 47HZ 1.5S 47HZ 1.5S 60S 60S 253V 205V 50.15Hz 47.5Hz 253V 205V 50.15Hz 47.5Hz

Australia C New Zealand

4777-C

4777-N Setting Range

265V 1.5S 275V 0.1S 180V 10S 70V 1.5S 55HZ 0.1S 55HZ 0.1S 45HZ
5S 45HZ
5S 60S 60S 253V 205V 50.15Hz 47.5Hz 253V 205V 50.15Hz 47.5Hz

265V 1.5S 275V 0.1S 180V 10S 70V 1.5S 55HZ 0.1S 55HZ 0.1S 45HZ 1.5S 45HZ 1.5S 60S 60S 253V 196V 50.15Hz 47.5Hz 253V 196V 50.15Hz 47.5Hz

230-276V 1-2S
230-276V 0.1-2S 38-230V 10-11S 38-230V 1-2S
50-55HZ 0.1-2S
50-55HZ 0.1-2S 45-50HZ 1-6S 45-50HZ 1-6S 10-600S 10-600S
230-276V 115-230V 50-52Hz 47-50Hz 230-276V 115-230V 50-52Hz 47-50Hz

Table 5.1

.37.

.38.

5. Commissioning

6. Check the backup supply settings. If you don’t have a backup circuit on the backup port, disable it. Otherwise, keep it as enable and refer to section 4.6 for the installation process of AC backup connector.

Advanced Settings

2015-02-23 19 35

Steotrtiangges Energy Set

2015-02-23 19 35

Select Standard ON/OFF Calibrate
Reset Password Restart HMI
Storage Energy Set

Export Power Set HMIUpdate DSPUpdate
BaudRate RS485 Special Settings

Control Parameter Battery Select Meter Set
Storage Mode Select Battery Wakeup

ESC

UP

DOWN

ENT

Step 1

CSeotntitnroglsParameter

2015-02-23 19 35

Backup Supply Backup Votage
Current Direction Battery Current Charge Limitation

Disable Floating Charge 055.0V

230.0V Equalizing Charge 000.0V

Charge Batter y Overoltage 060.0V

000.0A Battery Undervoltage042.0V

000.0A Voltage Droop

Disable

Discharge Limitation000.0A

Step 2

SET= DONE=

ESC

UP

DOWN

ENT

Step 3

5. Commissioning

7. Select the battery option and set battery SOC The default setting for overdischarge SOC is 20%, force charging SOC is 10%, force charge current limit is 100A. If other setting is needed please follow 6.6.6.2 for detail. PS. If you don’t have battery connected, set it to “No Battery”.

Advanced Settings
Select Standard ON/OFF Calibrate
Reset Password Restart HMI
Storage Energy Set

2015-02-23 19 35
Export Power Set HMIUpdate DSPUpdate
BaudRate RS485 Special Settings

Steotrtiangges Energy Set
Control Parameter Battery Select Meter Set
Storage Mode Select Battery Wakeup

2015-02-23 19 35

ESC

UP

DOWN

ENT

Step 1

Step 2

BSaetteinrgysSelect

2015-02-23 19 35

Battery Module: B-BOX LV

OverDischg SOC 020%

BSaetteinrgysSelect

Step 3

2015-02-23 19 35

ForceCharge SOC 004% ForceChg PLmt 300.0W Power limit On From Gird

YES= NO=

ESC

UP

DOWN

ENT

Step 5

YES= NO=

ESC

UP

DOWN

ENT

Step 4

.39.

.40.

5. Commissioning

Brand BYD

Model Box Pro 2.5-13.8

Setting Select “B-BOX”

LG Energy RESU 3.3/6.5/10/13 (CEI 0-21) Solution

Select “LG Chem”

Pylontech Dyness

US2000(CEI 0-21)/US3000(CEI 0-21)/ ForceL1(CEI 0-21)/ForceL2(CEI 0-21)/ Phantom-S/US2000C/US3000C/UP5000
Powerdepot/Powerbox/B4850

Select “Pylon” Select “Dyness”

Puredrive AOBOET WECO Green Soluna Highstar Freedom KODAK FOX UZ Energy GSL

48V-100Ah AOBOET Uhome-LFP 6.8kWh 5K3-R20 Home E11 4K PACK HSD5870 Freedom Won Lite FL5.2 LV5200 L051100-A 48V-100Ah

Select “Puredrive” Select “AoBo” Select “WECO” Select “Green” Select “Soluna” Select “Highstar” Select “Freedom” Select “KODAK” Select “FOX” Select “CATL” Select “GSL”

ZETARA POWER

51.2V-100Ah

Select “ZETARA”

Battery Select

NOTE: Only battery models in the list can be selected.

NOTE: For the latest compatible battery list, please refer to Solis company website.

.41.

5. Commissioning

8. Select the storage work mode. Recommended settings – Self-Use Mode. This mode can maximize the use of photovoltaic power generation directly for household electricity, or store it in batteries and use it for household electricity.If the other mode need to be used, please follow 6.6.6.4.

Advanced Settings
Select Standard ON/OFF Calibrate
Reset Password Restart HMI
Storage Energy Set

2015-02-23 19 35
Export Power Set HMIUpdate DSPUpdate
BaudRate RS485 Special Settings

Steotrtiangges Energy Set
Control Parameter Battery Select Meter Set
Storage Mode Select Battery Wakeup

2015-02-23 19 35

ESC

UP

DOWN

ENT

Step 1

Steotrtiangges Mode Select

2015-02-23 19 35

Mode:
Self Use

SeltftiUngsse Mode

Step 2
ON OFF

2015-02-23 19 35

Step 3

TSiemtteinogfsuse for Self use

2015-02-23 19 35

Optimal Income: Stop

Charge Limit:

050.0A

Discharge Limit: 050.0A

HH MM HH MM

Charge Time: Discharge Time: Charge Time: Discharge Time: Charge Time: Discharge Time:

22:00—-08:00 08:00—-22:00 00:00—-00:00 00:00—-00:00 00:00—-00:00 00:00—-00:00

HH MM
Total Time: 10:00 Total Time: 14:00 Total Time: 00:00 Total Time: 00:00 Total Time: 00:00 Total Time: 00:00

NEXT= DONE=

ESC

UP

DOWN

ENT

Step 5

YES= NO=

ESC

UP

DOWN

ENT

Step 4

CSehtatirngginsg from gird for Self use

2015-02-23 19 35

Allow Not Allow

YES= NO=

ESC

UP

DOWN

ENT

Step 6

NOTE: See step 6, if “Charge from grid for self use” is set to “Not Allow”, the inverter will not force charge the battery and the battery could potentially go to sleep mode.
.42.

5. Commissioning

8. Please check in the accessory package and confirm the meter type first. If the default meter is Acrel ACR10R16DTE, please select the meter type as “1PH Meter”. If the default meter is Eastron SDM120CT, please select the meter type as “Eastron 1PH Meter”. If another meter is used, please refer to section 6.6.6.3.1 to select the meter type. Please set the “meter placement” as “Grid”. If other configuration is used, please refer to section 6.6.6.3.2.

Advanced Settings
Select Standard ON/OFF Calibrate
Reset Password Restart HMI
Storage Energy Set

2015-02-23 19 35
Export Power Set HMIUpdate DSPUpdate
BaudRate RS485 Special Settings

Steotrtiangges Energy Set
Control Parameter Battery Select Meter Set
Storage Mode Select Battery Wakeup

2015-02-23 19 35

ESC
SMeettteinr gSset

UP

DOWN

ENT

Step 1

2015-02-23 19 35

SMeettteinr gSselect

Step 2

2015-02-23 19 35

Meter Select Meter Placement

Meter Type:
1Ph Meter

ESC
SMeettteinr gSselect

YES= NO=

UP

DOWN

ENT

Step 3

2015-02-23 19 35

Meter Type:
Eastron 1Ph Meter

YES= NO=

ESC

UP

DOWN

ENT

Step 4

SMeettteinr gPslacement

2015-02-23 19 35

Install on:
Grid

YES= NO=

ESC

UP

DOWN

ENT

Step 5

YES= NO=

ESC

UP

DOWN

ENT

Step 6

5. Commissioning

9. Switch on the inverter DC switch. 10. Switch on battery breaker. 11. Verify the readings in “Information” pages.
MSeettninugs

0.00kW 0.00kW

0.00kW

2.526 KWH
0.00kW

Information

2015-02-23 19 35

Settings

Advanced Information Advanced Settings

Step 1

SInefottrinmgastion

2015-02-23 19 35

Solar Power 00000W

Solar Voltage1 000.0V

Solar Voltage2 000.0V

Grid Voltage 000.0V

Battery Voltage 000.0V

Backup Voltage 000.0V

DRM NO.

08

Solar Current1 000.0A

Solar Current2 000.0A

Grid Power

+00000W

Grid Frequency 00Hz

Charg Power +00000W

ESC

1/4

UP

DOWN

ENT

Step 3

SInefottrinmgastion

BMS Information

Module Type No Battery

Battery Voltage 00.00V

Battery Current 000.0A

Charge Limit 000.0A

Discharge Limit 000.0A

SOC Value

000%

SOH Value 000%

BMS Status Normal

ESC

3/4

UP

DOWN

Step 5

2015-02-23 19 35
ENT

Step 2

Information

2015-02-23 19 35

Total Energy0000000kWh Device StatusGenerating

This Year 0000000kWh Battery StatusNormal

Last Year 0000000kWh Backup StatusNormal

This Month 0000kWh

Grid Status OffGridMode

Last Month 0000kWh

Today

0000.0kWh

Yesterday 00000.0kWh

Inverter SN FFFFFFFFFFFFFFF

ESC

2/4
UP

DOWN

ENT

Step 4

ISnefottrimngastion

2015-02-23 19 35

Grid Meter

PV Inverter Meter

Meter Voltage 000.0V

Meter Voltage 000.0V

Meter+ Current00.00A

Meter+ Current00.00A

Meter Power +000000W Meter Power +000000W

Meter Energy 0000.00kWh Meter Energy 0000.00kWh

Input Energy 0000.00kWh Input Energy 0000.00kWh

Output Energy 0000.00kWh Output Energy 0000.00kWh

ESC

4/4

UP

DOWN

ENT

Step 6

.43.

.44.

5. Commissioning
5.3 Shutdown procedure
1. Turn off the AC isolator at the grid connection point. 2. Turn off the DC switch of the inverter. 3. Turn off the DC switch between inverter and battery. 4. Waiting for the LCD of inverter to turn off and the system shutdown is completed.
.45.

6. Operation

Pressing the ESC key calls back
the previous menu

Monthly Energy

ESC ESC

Main interface

Pressing the ENTER key to switch
to the submenu

ENTER

main menu information UP/DOWN
settings UP/DOWN advanced info. UP/DOWN advanced settings

Figure 6.1 Operation Overview

6.1 Initial Display
When powering up the inverter for the first time, it is required to set the language. Press “ENT” to select.

SettLinagnsguage

2015-02-23 19 35

English

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.2 Set Language

.46.

6. Operation
After setting the language, press “ESC” to access the main page.

0.00kW 0.00kW

0.00kW

2.526 KWH
0.00kW

Figure 6.3 Main Page
On the main page, Press “ESC” : View the yield data on a monthly bar charts. Then use “UP” and “DOWN” to change the date and “ENT” to move the cursor. Press “UP” or “DOWN”: View different status on the top left of the main page. Press “ENT”: Enter the main menu.

Solar Power: When solar power is generatedan arrow indicates the direction of the power flow and the value is shown above the arrow.
Battery: When the battery is connected successfully, it will display “CAN OK”,meanwhile,battery SOC, arrow and value of power flow is shown. Otherwise, it will display “CAN Fail”.
Non-Critical Loads: Loads connected to the AC Grid port which will shutdown if the grid is in malfunction.

Smart Meter: When the smart meter is connected successfully,

2.526

KWH

it will display “RS485 OK”, otherwise “RS485 Fail”.

Critical Loads: Loads connected to the AC Backup port which will be supported by battery and solar even if the grid is in malfunction.

Grid: The arrow and value indicate the export/import power of the hybrid system.

.47.

6.2 Main Menu
There are four submenu in the Main Menu: 1. Information 2. Settings 3. Advanced Information 4. Advanced Settings
MSeettninugs
Information

6. Operation
2015-02-23 19 35

Settings

Advanced Information

Advanced Settings

ESC

UP

DOWN

ENT

Figure 6.4 Main Menu

6.3 Information
In the “Information” section, operating data and information can be viewed. Three pages of information can be checked by press “UP” or “DOWN”. The example display is shown in the following Figure 6.5, 6.6 and 6.7. Values are for reference only.

ISnefottrimngastion

2015-02-23 19 35

Solar Power 00000W

Solar Voltage1 000.0V

Solar Voltage2 000.0V

Grid Voltage 000.0V

Battery Voltage 000.0V

Backup Voltage 000.0V

DRM NO.

08

Solar Current1 000.0A

Solar Current2 000.0A

Grid Power

+00000W

Grid Frequency 00Hz

Charg Power +00000W

ESC

1/4

UP

DOWN

ENT

Figure 6.5 Information Page 1

.48.

6. Operation

Information

2015-02-23 19 35

Total Energy0000000kWh Device StatusGenerating

This Year 0000000kWh Battery StatusNormal

Last Year 0000000kWh Backup StatusNormal

This Month 0000kWh

Grid Status OffGridMode

Last Month 0000kWh

Today

0000.0kWh

Yesterday 00000.0kWh

Inverter SN FFFFFFFFFFFFFFF

ESC

2/4
UP

DOWN

ENT

Figure 6.6 Information Page 2

ISnefottrimngastion

BMS Information

Module Type No Battery

Battery Voltage 00.00V

Battery Current 000.0A

Charge Limit 000.0A

Discharge Limit 000.0A

SOC Value

000%

SOH Value 000%

BMS Status Normal

ESC

3/4
UP

2015-02-23 19 35

DOWN

ENT

Figure 6.7 Information Page 3

.49.

6. Operation

ISnefottrimngastion

2015-02-23 19 35

Grid Meter

PV Inverter Meter

Meter Voltage 000.0V

Meter Voltage 000.0V

Meter+ Current00.00A

Meter+ Current00.00A

Meter Power +000000W Meter Power +000000W

Meter Energy 0000.00kWh Meter Energy 0000.00kWh

Input Energy 0000.00kWh Input Energy 0000.00kWh

Output Energy 0000.00kWh Output Energy 0000.00kWh

ESC

4/4

UP

DOWN

ENT

Figure 6.8 Information Page 4

NOTE: Meter Power/Grid Power: Positive value indicates exporting power to the grid, negative value indicates importing power from the grid Charge Power: Positive value indicates charging, negative value indicates discharging.

NOTE: Information for “PV Inverter Meter” is only available when two Eastron meters are used and Meter Placement is selected as “Grid+PV Meter”. Details please consult Solis service department.

.50.

6. Operation

6.4 Settings
In the “Settings” section, Time/Date, Slave address and language can be modified.

Settings

2015-02-23 19 35

Set Time/Date Set Address Set Language

Figure 6.9 Setting

6.4.1 Set Time/Date
Set the time and date on the inverter. Must set this according to local time as it affects the daily yield calculation. (If Solis monitoring system is used, must set the correct time zone of the system, otherwise datalogger will update the inverter time based on the time zone of the system.) Press “UP” and “DOWN” to change the value. Press “ENT” to mover the cursor. Press “ESC” to save the change.

Set Time/Date

2015-02-23 19 35

YY

MM

DD

2015 –

2

– 23

HH

MM

20 :

53

NEXT= DONE=

ESC

UP

DOWN

ENT

Figure 6.10 Set Time

.51.

6. Operation

6.4.2 Set Address
Set the slave address of the inverter. The default address is 01.

SettAindgdsress

2015-02-23 19 35

Slave Address01

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.11 Set Address

6.4.3 Set Language
Set system language. Chinese and English are available.

SettLinagnsguage

2015-02-23 19 35

English

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.12 Set Language

.52.

6. Operation
6.5 Advanced Information
Detailed information can be viewed in this section: 1. Alarm Message 2. Running Message 3. Version 4. Communication Data. 5. Daily Energy 6. Monthly Energy 7. Yearly Energy 8. Total Energy. 9. Warning Message 10. Inspection
ASdevttainngcsed Information

2015-02-23 19 35

Alarm Message Running Message
Version Communication Data
Daily Energy Monthly Energy

Yearly Energy Total Energy Warning Message
Inspection

Figure 6.13 Advanced Information
6.5.1 Alarm Message
40 pages of latest alarm messages (5 per page). Alarm message shows the alarm that will lead to inverter shutdown.

Alarm Message
Message
NO-Grid NO-Grid NO-Grid NO-Grid NO-Grid

Date/Time
02-23 19:35 02-23 19:34 02-23 19:34 02-23 19:24 02-23 18:22
01/40

2015-02-23 19 35
Date
0000 0000 0000 0000 0000

.53.

ESC

UP

DOWN

ENT

Figure 6.14 Alarm Message

6. Operation

6.5.2 Running Message
This function is for maintenance person to get running message such as internal temperature, Standard NO. etc.(Values are for reference only).

RSeutntinnignsg Message

DC Bus Voltage

410.7V

Reactive Power Ratio +1.00

Output Power Limit 100%

Control Word Status 0000H

Inverter Temperature +0031.6degC

Standard

G59/3

Grid Filter NO.

00

Ground Voltage

000.0V

Battery Enable

Disable

2015-02-23 19 35

ESC
Figure 6.15 Running Message

6.5.3 Version
Inverter model number and software version can be viewed in this section.
Values are for reference only..

Version

Model

F8

Software Ver.140000

2015-02-23 19 35

2015-02-23 19 35

ESC
Figure 6.16 Model Version and Software Version

.54.

6. Operation

6.5.4 Communication Data
Internal communication data can be viewed in this section. For maintenance person only. Values are for reference only.

Communication Data
01-10 86 61 A1 00 01 50 8A 06 1E 00 11-20 D5 05 1E 00 00 00 00 00 00 00 21-30 00 00 00 00 00 00 00 00 00 00 31-40 09 02 00 00 00 00 B8 10 C0 00 41-50 20 5C 80 01 00 00 43 00 07 02 51-60 01 00 04 00 6D 04 E6 05 01 00 61-70 DC 05 1E 00 59 06 1E 00 D4 03 71-80 10 27 00 00 00 00 00 00 00 00 81-90 00 00 00 00 00 00 60 00 00 00

2015-02-23 19 35

ESC
Figure 6.17 Communication Data

6.5.5 Daily Energy
The screen shows the daily energy detail of the inverter.

Daily Energy

Daily Energy[kW]

60 50 40 30 20 10 00
00:00

03:00

ESC

06:00

09:00

UP

12:00

15:00

2015-02-23

DOWN

2015-02-23 19 35

18:00

21:00

00:00

ENT

Figure 6.18 Daily Energy

6. Operation

6.5.6 Monthly Energy
The screen shows the inverter monthly energy detail of different month.

MSeotntitnhglys Energy

2015-02-23 19 35

600

Monthly Energy[kWh]

500 400 300

200

100

000 05
ESC

10

15

20

25

2015-02-23 : 071.2kWh

UP

DOWN

ENT

Figure 6.19 Monthly Energy

6.5.7 Yearly Energy
The screen shows the inverter yearly energy detail of different year.

YSeattrilnygEsnergy

Yearly Energy[MWh]

3.0 2.5 2.0 1.5 1.0 0.5 0.0
01

00.51

02

03

ESC

2015-02-23 19 35

04

05

06

07

08

09

10

11

12

2015

UP

DOWN

ENT

Figure 6.20 Yearly Energy

.55.

.56.

6. Operation

6.5.8 Total Energy
The screen shows the inverter total energy detail.

TSoettatilnEgnsergy

2015-02-23 19 35

3.0

2.5

Totally Energy[MWh]

2.0

1.5

1.0

0.5

0.0

00.01

2006

2007

2008

2009

2010

2 0 11

2012

2013

2014

2015

Figure 6.21 Total Energy

6.5.9 Warning Message
10 pages of latest warning messages (5 per page). Warning message shows the warning that is abnormal but will not lead to inverter shutdown.

WSeatrtnininggs Message Message

Date/Time NO message.

2015-02-23 19 35
Data

ESC

UP

DOWN

ENT

Figure 6.22 Warning Message

.57.

6. Operation
6.6 Advanced Settings – Technicians Only
NOTE: This function is for authorised technicians only. Improper access and operation may result in abnormal results and damage to the inverter. Password required ­ restricted access ­ authorised technicians only Un-authorised access may void the warranty. (Password”0010″)

Select Advanced Settings from main menu, the LCD screen show the password is needed:

PSaesttsinwgosrd

2015-02-23 19 35

Please Input The Current Password

0

0

1

0

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.23 Enter Password

The default password is “0010”. Please press “down” to move the cursor, press “up” to select the number. After enter the correct password the Main Menu will display a screen and be able to access to the following information.
1. Select Standard 2. ON/OFF 3. Calibrate 4. Reset Password 5. Restar HMI 6. Storage Energy Set 7. Export Power Set 8. HMI Update 9. DSP Update 10. BaudRate RS485 11. Special Settings

.58.

6. Operation

Advanced Settings
Select Standard ON/OFF Calibrate
Reset Password Restart HMI
Storage Energy Set

2015-02-23 19 35
Export Power Set HMIUpdate DSPUpdate
BaudRate RS485 Special Settings

Figure 6.24 Advanced Settings

6.6.1 Select Standard
This function is used to select corresponding grid standards.

SelteticntgSs tandard

2015-02-23 19 35

Select Standard:
4777_A

YES= NO=
Figure 6.25 Select Standard Press the UP/DOWN keys to select the standard “4777_A”, “4777_B”,” 4777_C” and “4777_N” for compliance with AS/NZS4777.2:2020. The standard “AS4777-15” is for AS/NZS4777.2:2015.
NOTE: To check the firmware version, select the standard and you will find ‘firmware version’ parameter. A2 is the current version that comply with AS/NZS 4777.2:2020.
.59.

6. Operation

The default protection settings and setting range for different regions are showing below:

Region Standard Code Name OV-G-V1 OVGV1-T OV-G-V2 OVGV2-T UN-G-V1 UNGV1-T UN-G-V2 UNGV2-T OV-G-F1 OVGF1-T OV-G-F2 OVGF2-T UN-G-F1 UNGF1-T UN-G-F2 UNGF2-T Startup-T Restore-T Recover-VH Recover-VL Recover-FH Recover-FL Start- VH Start-VL Start-FH Start-FL

Australia A
4777-A
265V 1.5S 275V 0.1S 180V 10S 70V 1.5S 52HZ 0.1S 52HZ 0.1S 47HZ 1.5S 47HZ 1.5S 60S 60S 253V 205V 50.15Hz 47.5Hz 253V 205V 50.15Hz 47.5Hz

Australia B
4777-B
265V 1.5S 275V 0.1S 180V 10S 70V 1.5S 52HZ 0.1S 52HZ 0.1S 47HZ 1.5S 47HZ 1.5S 60S 60S 253V 205V 50.15Hz 47.5Hz 253V 205V 50.15Hz 47.5Hz

Australia C New Zealand

4777-C

4777-N Setting Range

265V 1.5S 275V 0.1S 180V 10S 70V 1.5S 55HZ 0.1S 55HZ 0.1S 45HZ
5S 45HZ
5S 60S 60S 253V 205V 50.15Hz 47.5Hz 253V 205V 50.15Hz 47.5Hz

265V 1.5S 275V 0.1S 180V 10S 70V 1.5S 55HZ 0.1S 55HZ 0.1S 45HZ 1.5S 45HZ 1.5S 60S 60S 253V 196V 50.15Hz 47.5Hz 253V 196V 50.15Hz 47.5Hz

230-276V 1-2S
230-276V 0.1-2S 38-230V 10-11S 38-230V 1-2S
50-55HZ 0.1-2S
50-55HZ 0.1-2S 45-50HZ 1-6S 45-50HZ 1-6S 10-600S 10-600S
230-276V 115-230V 50-52Hz 47-50Hz 230-276V 115-230V 50-52Hz 47-50Hz

Table 5.1

.60.

6. Operation

6.6.2 ON/OFF
This function is used to start or stop the generation of the inverter.

OSeNt/tiOngFsF

2015-02-23 19 35

ON OFF STOP

YES= NO=

ESC

UP

DOWN

ENT

6.6.3 Calibrate

Figure 6.26 Set ON/OFF

Warranty or maintenance may result in resetting total generating data, this function allow the maintenance personnel to amend the total generating data of replacement inverter to the original one.
By using our data monitoring hardware, the data on monitoring website can automatically synchronize with the preset total generating power of inverter.

Calibrate

2015-02-23 19 35

Total Energy Power Parameter

YES= NO=
Figure 6.27 Calibrate

.61.

6. Operation

TotalEnergy ATdojtuasl tEingertgoyt:al0g0e0n00er5a6tkinWghpower

2015-02-23 19 35

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.28 Total Energy

PowerParameter APdojwusetrinPgartao:tal1g.0e0n0erating power

2015-02-23 19 35

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.29 Power Parameter

.62.

6. Operation

6.6.4 Reset Password
Reset Password: In this page, user can reset the inverter password, but the admin password is always valid.

RSetsteintgPsassword

2015-02-23 19 35

Please Input New Password

X

X

X

X

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.30 Reset Password

6.6.5 Restart HMI
This function is to reboot the LCD screen.

6.6.6 Storage Energy Set

This section contains working mode setting, battery control setting, etc.

Steotrtiangges Energy Set

2015-02-23 19 35

Control Parameter Battery Select

Meter Set

Storage Mode Select

Battery Wakeup

Figure 6.31 StorageEnergyset

.63.

6. Operation
6.6.6.1 Control Parameter
Enter the Control Parameter menu as shown below: Don’t change the settings without the permission of technicians.

CSeotntitnroglsParameter

2015-02-23 19 35

Backup Supply Backup Votage
Current Direction Battery Current

Disable Floating Charge 055.0V 230.0V Equalizing Charge 000.0V Charge Batter y Overoltage 060.0V 000.0A Battery Undervoltage042.0V

Charge Limitation 000.0A Voltage Droop

Disable

Discharge Limitation000.0A

SET= DONE=

ESC

UP

DOWN

ENT

Figure 6.32 Control Parameter
6.6.6.2 Battery Select
This product is compatible with multiple battery models. Please refer to the latest compatible battery list on Solis company website.

WARNING: Inverter must be installed with compatible battery models. Any defect, damage or collateral loss due to using a non-compatible battery is not in the scope of inverter warranty or compensation. Please refer to the battery compatible list on Solis company website for information on latest compatible battery models.

For above compatible battery modules, Only three parameters need to be defined: OverDischg SOC (10%~40%, default 20%) –Inverter will not discharge the battery when the OverDischg SOC is reached.
Battery self-discharge is unavoidable,SOC may go lower than the limit if the battery can’t get charged for a long period of time.
ForceCharge SOC (5%~OverDischg SOC, default 10%) –To prevent the battery going into sleep mode, when the ForceCharge SOC is reached, inverter will charge the battery using the power from either PV or Grid. * ForceChg Limit (0A~100A, default 100A) –Determine the battery charge current limit when inverter operates in force charge status.

.64.

6. Operation
Battery Module:
B-BOX LV

Figure 6.33 Battery Select

BSaettienrgysSelect

2015-02-23 19 35

OverDischg SOC 020%

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.34 Over Discharge SOC.

BSaettienrgysSelect

2015-02-23 19 35

ForceCharge SOC 004% ForceChg PLmt 300.0W Power limit On From Grid

.65.

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.35 ForceCharge SOC

6. Operation

NOTE: 5G products support lead-acid battery. Select “Lead-Acid” in the “Battery Select” and configure the following parameters according to different lead-acid batteries.

LSeeattdinAgcsid Battery

2015-02-23 19 35

Battery Capacity: 100Ah Equalizing Voltage: 56.4V Floating Voltage: 53.5V Overdischg Voltage: 44.5V Floating Current: 04.0A Force Charg Voltage: 43.8V

I_Max Discharge: 060.0A ForceChg PLmt:

300.0W

I_Max Charge: 010.0A Temp.Compensation: 072mV/degC

AMB.Temp.Lower: +05degC

AMB.Temp.Upper: +45degC

Power Limit On:

From Gird

SET= DONE=

ESC

UP

DOWN

ENT

Lead Acid Battery (Values are examples Only)
1. Battery Capacity: Define the capacity of the battery. 2. Equalizing Voltage: Define the voltage for Equalizing/Absorption charge. 3. Floating Voltage: Define the voltage for floating charge. 4. Floating Current: Define the current for floating charge. 5. Overdischg Voltage: Define the voltage that stops discharging the battery. 6. Force Charg Voltage: Define the voltage that forces to charge the battery
to prevent a dead battery. 7. ForceChg Limit:Define the battery charge current limit in force charge
status. 8. I_Max Discharge: Define the max discharge current for the battery. 9. I_Max Charge: Define the max charge current for the battery. 10. Temp.Compensation: Define the temperature compensation parameter
for the battery. 11. AMB.Temp.Lower/Upper: Define the temperature range when the
temperature compensation is effective.

After configuration, save and send. If battery temperature sensor is connected, select “Warm”. If battery temperature sensor is not connected, select based on actual condition for fixed compensation Cold: 5 degC Warm: 25 degC Hot: 40 degC

.66.

6. Operation

LSeeattdinAgcsid Battery

2015-02-23 19 35

Environment Temp:
Warm

YES= NO=

ESC

UP

DOWN

ENT

WARNING: Lead-acid battery is not recommended for general customers as it requires experienced installers and technicians who can fully understand the battery parameters and configure the settings and installations correctly. Due to the inconformity between battery cells, damages will be less likely to be avoided. Solis is not responsible for any potential damages caused by the use of lead-acid batteries.

.67.

6. Operation

6.6.6.3 Meter Set

These settings are used to select the meter types and meter installed locations based on the actual configuration.

MSeettteinr gSset

2015-02-23 19 35

Meter Select

Meter Placement

ESC
6.6.6.3.1 Meter Select
MSeettteinr gSselect

YES= NO=

UP

DOWN

ENT

Figure 6.36 Meter Set

Meter Type:
1Ph Meter

2015-02-23 19 35

YES= NO=

ESC

UP

DOWN

Figure 6.37 Meter Select Meter Model Acrel 1ph meter (With CT): ACR10R-D16TE (Optional)

Acrel 3ph meter (With CT): ACR10R-D16TE4 (Optional) Eastron 1ph meter (Direct Insert): SDM120M (Optional) Eastron 1ph meter (With CT): SDM120CT

Eastron 3ph meter (Direct Insert): SDM630 (Optional) Eastron 3ph meter (With CT): SDM630MCT (Optional) No meter is connected

ENT
Meter Type Options “1ph meter” “Acrel 3ph meter” “Eastron 1ph meter” “Eastron 1ph meter” “Eastron 3ph meter” “Eastron 3ph meter” “No Meter”
.68.

6. Operation
6.6.6.3.2 Meter Placement
Grid: Meter is installed at the grid connection point. Load: Meter is installed at the load branch circuit. Grid+PV Inverter: One meter is connected at the grid connection point, the other meter is connected at the AC output port of an extra PV inverter. (Eastron Meter supported).

MSeettteinr gPslacement

2015-02-23 19 35

Install on:
Grid

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.38 Meter Placement
6.6.6.4 Storage Mode Select
There are 4 working modes available. 1. Self Use Mode 2. Feed in Priority Mode 3. Backup Mode 4. Off Grid Mode

Steotrtiangges Mode Select

Mode:
Self Use

2015-02-23 19 35

Figure 6.39 Storage Mode Select .69.

6. Operation

Mode 1: Self-Use Mode Logic(Maximize the usage of PV) PV Power Using Priority: Load>Battery>Grid Load Support Priority: PV>Battery>Grid Battery Charging Power comes from PV. (If “Charging From Grid” is allowed, it can also come from Grid) If “Time of Use” is “Run”, the logic will follow the charging/discharging settings and time settings as defined in “Time of Use”. For those undefined period of time, it will still follow the Self-Use logic.
Time of use for Self use Path: Advanced Settings->Storage Energy Set->Storage Mode Select-> Self-Use Mode->ON->Time of use for Self use

TSiemtteinogfsuse for Self use

2015-02-23 19 35

Optimal Income: Stop

Charge Limit:

050.0A

Discharge Limit: 050.0A

HH MM HH MM

Charge Time:

22:00—-08:00

Discharge Time: 08:00—-22:00

Charge Time:

00:00—-00:00

Discharge Time: 00:00—-00:00

Charge Time:

00:00—-00:00

Discharge Time: 00:00—-00:00

HH MM
Total Time: 10:00 Total Time: 14:00 Total Time: 00:00 Total Time: 00:00 Total Time: 00:00 Total Time: 00:00

NEXT= DONE=

ESC

UP

DOWN

ENT

Figure 6.40
Charging from gird self use Path: Advanced Settings->Storage Energy Set->Storage Mode Select-> Self-Use Mode->ON->Charging from gird for Self use

CSehtatirngginsg from gird for Self use

2015-02-23 19 35

Allow Not Allow

YES= NO=

ESC

UP

DOWN

Figure 6.41

ENT
.70.

6. Operation

Mode 2: Feed In Priority Mode Logic(Feed the excess PV to Grid in order to gain subsidies) PV Power Using Priority: Load>Grid>Battery Load Support Priority: PV>Battery>Grid Battery Charging Power comes from PV. (If “Charging From Grid” is allowed, it can also come from Grid) If “Time of Use” is “Run”, the logic will follow the charging/discharging settings and time settings as defined in “Time of Use”. For those undefined period of time, it will still follow the Feed in Priority logic.
Time of use for Feed for priority Path: Advanced Settings->Storage Energy Set->Storage Mode Select-> Feed in Priority Mode->ON->Time of use for Feed for priority

TSiemtteinogfsuse for Feed for priority

2015-02-23 19 35

Optimal Income: Stop

Charge Limit:

050.0A

Discharge Limit: 050.0A

HH MM HH MM

Charge Time: Discharge Time: Charge Time: Discharge Time: Charge Time: Discharge Time:

22:00—-08:00 08:00—-22:00 00:00—-00:00 00:00—-00:00 00:00—-00:00 00:00—-00:00

HH MM
Total Time: 10:00 Total Time: 14:00 Total Time: 00:00 Total Time: 00:00 Total Time: 00:00 Total Time: 00:00

NEXT= DONE=

ESC

UP

DOWN

ENT

Figure 6.42
Charging from gird for Feed for priority Path: Advanced Settings->Storage Energy Set->Storage Mode Select-> Feed in Priority Mode->ON->Charging from gird for Feed for priority

CSehtatirngginsg from gird for Feed for priority

2015-02-23 19 35

Allow Not Allow

.71.

YES= NO=
Figure 6.43

6. Operation

Mode 3: Backup Mode Logic(Keep the Battery at a certain SOC and only use it during power outage) Backup Mode Logic: Keep the Battery at a certain SOC and only use it during power outage. Backup SOC Setting Range: From Battery “Overdischarge SOC” to 100% PV Power Using Priority: Battery>Load>Grid Load Support Priority: PV>Grid>Battery Battery Charging Power comes from PV. (If “Charging From Grid” is allowed, it can also come from Grid) * The “Backup Mode” is not applicable for Lead-acid batteries. Charging from gird for Backup mode Path: Advanced Settings->Storage Energy Set->Storage Mode Select->Backup Mode->
ON->Backup SOC->Charging from gird for Backup mode

CSehtatirngginsg from gird for Backup mode

2015-02-23 19 35

Allow Not Allow

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.44

.72.

6. Operation

Mode 4: Off-Grid Mode Logic(For Off-grid use and AC-Grid Port Disconnected) OverDischg SOC for Off-Grid Setting Range: From Battery “Forcecharge SOC” to 100% PV Power Using Priority: Load>Battery Load Support Priority: PV>Battery Battery Charging Power comes from PV.

Off Grid Mode Path: Advanced Settings->Storage Energy Set->Storage Mode Select ->Off-Grid Mode-> ON->Off Grid Mode

SOeffttGinrgids Mode

2015-02-23 19 35

OverDischg SOC for Off Grid: 030%

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.45

6.6.6.5 Battery Wakeup
This function should be activated only after the installation.In the case of a low battery voltage shutdown, the inverter will shut-down. This setting can be enabled, so when the inverter detects PV or grid it wakes up the battery. This function conflicts with the battery reverse polarity protection( If the installer connects cables with wrong polarity,the inverter can protect itself from damage).To avoid the possible damage during installation,do not active battery wakeup function before finishing the first commissioning.

.73.

6. Operation

6.6.7 Export power Set

This function is to set the export power control. 1. ON/OFF. 2.Backflow Power. 3.Failsafe ON/OFF Setting 2&3 are only valid when Setting 1 is set to “ON” “ON/OFF” is to enable/disable the export power control function
“Backflow Power” is to set the max allowed export power at the meter location “Failsafe ON/OFF” is a protection method to prevent excess export power when meter communication fails

ESxepttoinrgt spower Set

2015-02-23 19 35

ON/OFF BackflowPower FailSafe ON/OFF

ESC

UP

DOWN

ENT

Figure 6.46 Export power Set

NOTE: The export power control function comply with Section 6.3 of AS/NZS4777.2:2020. Inverter doesn’t have the generation control limit function as in Section 6.2 of AS/NZS4777.2:2020.

6.6.7.1 ON/OFF
Enable/Disable the function.
ON/OFF

2015-02-23 19 35

ON OFF

YES= NO=
Figure 6.47 ON/OFF .74.

6. Operation

6.6.7.2 Backflow Power
Determine the allowed backfeed power. (System export to the grid)

BSaetctkinflgosw Power

2015-02-23 19 35

Backflow Power 0W

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.48 Backflow Power

6.6.7.3 FailSafe ON/OFF
When this Failsafe function is ON, the inverter will shutdown once it loses communication with the meter in case of any backflow power exceeding the limit.

FSaeitltSinagfes ON/OFF

2015-02-23 19 35

ON OFF

YES= NO=
Figure 6.49 FailSafe ON/OFF

.75.

6.6.8 HMI Update
This function is used to update HMI software. Values are for reference only.
HMIUpdate

6. Operation
2015-02-23 19 35

The Current Version:F0

CANCE= UPDATE SYSTEM=

ESC

UP

DOWN

ENT

Figure 6.50 HMI Update

6.6.9 DSP Update
This function is used to update DSP software. Values are for reference only.
DSPUpdate

2015-02-23 19 35

The Current Version:00

CANCE= UPDATE SYSTEM=

ESC

UP

DOWN

ENT

Figure 6.51 DSP Update

.76.

6. Operation
6.6.10 BaudRate RS485
This function is to change the internal communication Baudrate.

BSaeuttdinRgaste RS485

2015-02-23 19 35

Baud Rate Parity Data bits Stop bits

9600 None
8 1

YES= NO=

ESC

UP

DOWN

ENT

Figure 6.52 BaudRate RS485

WARNING: This function is for maintenance personnel only, wrong operation will prevent the inverter from working properly.

6.6.11 Special Setting
There are two special settings: 1. AFCI Set 2. EPS Mode
SpeettciniaglsSetting

AFCI Set EPS Mode

2015-02-23 19 35

YES= NO=
Figure 6.53 Special Setting .77.

6. Operation

6.6.11.1 AFCI Set

Inverters have the built-in AFCI function which can detect the arc fault on the DC circuit and shut down the inverter to prevent a fire disaster.

AFCI Set

2015-02-23 19 35

AFCI ON/OFF OFF AFCI Level. 00

2015-02-23 19 35

ESC

UP

DOWN

ENT

Figure 6.54 AFCI Set

WARNING: The “AFCI Level” is reserved for technicians ONLY. Do not change the sensitivity otherwise it will lead to frequent false alarms or malfunctions. Manufacturer is not responsible for any further damages caused by unauthorized modifications.

WARNING: The setting corresponds to the current status as well which can be used to inspect the ON/OFF state of the AFCI function.

.78.

6. Operation

During the normal operation, if an DC arc is detected, the inverter will shut down and give out the following alarm:

ARC-FAULT

2015-02-23 19 35

Restart Press ESC 3s

Figure 6.55 ARC-FAULT
Installer needs to thoroughly inspect the DC circuit to ensure all the cables arecorrectly fastened. Once the DC circuit issue has been fixed or it is confirmed to be OK, press “ESC” for 3s and wait for the inverter to restart.

6. Operation
6.6.11.2 EPS Mode
EPS Mode needs to work with external Solis NPS switching box to achieve ATS switching function. When grid is available, only the Grid Port is enabled and load is supported through NPS box by the grid. When grid is lost, Grid Port will be disabled and after the “Switching Time”, the Backup Port will be enabled and then load is supported through NPS box by the Backup Port. *It gives up the UPS function of the backup port and manually set the switching time. This mode must work with the Solis NPS switching Box. Otherwise it may cause some unexpected control mistakes.

ESPetStinMgosde
EPS En/Disable: Enable Switcing Time: 01.00s EPS OvDis SOC: 020%

2015-02-23 19 35

SET= DOWN=

ESC

UP

DOWN

ENT

Figure 6.56 EPS Mode

.79.

.80.

7. Maintenance
Solis S5-EH1P-L Series inverter does not require any regular maintenance. However, cleaning the heatsink will help inverter dissipating heat and increase the lifetime of inverter. The dirt on the inverter can be cleaned with a soft brush.
CAUTION: Do not touch the surface when the inverter is operating. Some parts may be hot and cause burns. Turn OFF the inverter (refer to Section 5.2) and let it cool down before you do any maintenance or cleaning of inverter. The LCD and the LED status indicator lights can be cleaned with cloth if they are too dirty to be read. NOTE: Never use any solvents, abrasives or corrosive materials to clean the inverter.
.81.

8. Troubleshooting

The inverter has been designed in accordance with international grid tied standards for safety, and electromagnetic compatibility requirements. Before delivering to the customer the inverter has been subjected to several test to ensure its optimal operation and reliability.
In case of a failure the LCD screen will display an alarm message. In this case the inverter may stop feeding energy into the grid. The alarm descriptions and their corresponding alarm messages are listed in Table 8.1:

When faults occur, the “Fault” state will be shown on the main screen. Follow the steps below to check what fault occurs.

Steps: Enter Down Advanced Information Enter Alarm Message.

Step1: Press ENTER.

Step2: Press DOWN to select Advanced Information, then press ENTER.

MSeettninugs

2015-02-23 19 35

Information

Settings

Advanced Information

Advanced Settings

ESC

UP

DOWN

ENT

Step3: Press DOWN to select Alarm Message, then press ENTER.

SAdevttainngcsed Information

2015-02-23 19 35

Alarm Message Running Message
Version Communication Data
Daily Energy Monthly Energy

Yearly Energy Total Energy Warning Message
Inspection

.82.

8. Troubleshooting

Message Name Off
LmtByEPM
LmtByDRM LmtByTemp LmtByFreq
LmtByVg
LmtByVar
LmtByUnFr Standby StandbySynoch GridToLoad

Information Description Control device to shutdown
The device’s output is under controlled
DRM Function ON Over temperature power limited Frequency power limited

Troubleshooting Suggestion
1. Turn on the device in the ON/OFF Setting.
1. Confirm whether the inverter is connected to an external EPM/meter to prevent reverse current.
2. Confirm whether the inverter is controlled by an external third-party device.
3. Confirm whether the power setting of the inverter power control is limited.
4. Verify settings in section 6.6.7 and check your meter readings.
1. No need to deal with it.
1. No need to deal with it, the device is in normal operation.

The device is in the Volt-Watt mode

1. Due to the requirements of local safety regulations, when the grid voltage is high, the Volt-watt working mode is triggered, which generally does not need to be dealt with.
2. Inverter factory test errors causing this mode to open, if you need to close, you can close this mode in LCD, set the process: Main menu Advanced Settings Password 0010 STD mode settings Working Mode Working mode: NULL Save and exit.

The device is in the Volt-Var mode of operation

1. Due to the requirements of local safety regulations, when the grid voltage is high, the Volt-watt working mode is triggered, which generally does not need to be dealt with.
2. Inverter factory test errors causing this mode to open, if you need to close, you can close this mode in LCD, set the process: Main menu Advanced Settings Password 0010 STD mode settings Working Mode Working mode: NULL Save and exit.

Under frequency limit
Bypass run Off grid status to On grid status Grid to load

1. No need to deal with it.

.83.

8. Troubleshooting

Message Name

Information Description

Troubleshooting Suggestion

Surge Alarm
OV-G-V01 UN-G-V01 OV-G-F01 UN-G-F01 G-PHASE G-F-GLU NO-Grid OV-G-V02 OV-G-V03 IGFOL-F OV-G-V05 OV-G-V04 UN-G-V02 OV-G-F02 UN-G-F02
NO-Battery
OV-Vbackup
Over-Load

On-site grid surge
Grid voltage exceeds the upper voltage range Grid voltage exceeds the lower voltage range Grid frequency exceeds the upper frequency range Grid frequency exceeds the lower frequency range Unbalanced grid voltage Grid voltage frequency fluctuation No grid
Grid transient overvoltage
Grid transient overvoltage
Grid current tracking failure Grid voltage RMS instantaneous overvoltage fault Grid voltage exceeds the upper voltage range Grid voltage exceeds the lower voltage range Grid frequency exceeds the upper frequency range Grid frequency exceeds the lower frequency range
Battery is not connected
Inverting overvoltage
Load overload fault

1. Grid side fault, restart the device. If it is still not eliminated, please contact the manufacturer’s customer service.
1. Confirm whether the power grid is abnormal. 2. Confirm that the AC cable is properly
connected. 3. Restart the system and check if the fault
persists.
1. Restart the system, confirm if that the fault continues.
1. Confirm whether the power grid is abnormal. 2. Confirm that the AC cable is properly
connected. 3. Restart the system and check if the fault
persists.
1. Check on information page 1 ­ Verify the battery voltage is within standards.
2. Measure battery voltage at plug. 1. Check whether the backup port wiring is normal 2. Restart the system, confirm that the fault continues. 1. Backup load power is too large, or some inductive load startup power is too large, need to remove some backup load, or remove the inductive load on the backup.
.84.

8. Troubleshooting

Message Name BatName-FAIL CAN Fail
OV-Vbatt

Information Description

Troubleshooting Suggestion

Wrong battery brand selection CAN Fail

1. Confirm whether the battery model selection is consistent with the actual one.
1. Can failure is a failure of communication between inverter and battery. Check cable conditions. Check to ensure you have it plugged in on the CAN port of the battery and inverter. Check that you are using the right cable. Some batteries require a special battery from the battery manufacturer.

Battery undervoltage detected

1. Verify battery voltage is within standards. Measure battery voltage at inverter connection point. Contact your battery manufacturer for further service.

UN-Vbatt

Battery overvoltage detected

1. Restart the system and check if the fault persists.If it is still not eliminated, please contact the manufacturer’s customer service.

Fan Alarm

Fan alarm

OV-DC01 (1020 DATA:0001)
OV-DC02 (1020 DATA:0002)
OV-BUS (1021 DATA:0000)
UN-BUS01 (1023 DATA:0001)
UNB-BUS (1022 DATA:0000)
UN-BUS02 (1023 DATA:0002)
DC-INTF. (1027 DATA:0000)

DC 1 input overvoltage
DC 2 input overvoltage
DC bus overvoltage
DC bus undervoltage
DC bus unbalanced voltage Abnormal detection of DC bus voltage DC hardware overcurrent (1, 2, 3, 4)

OV-G-I

A phase RMS value

(1018 DATA:0000) overcurrent

OV-DCA-I (1025 DATA:0000)
OV-DCB-I (1026 DATA:0000)
GRID-INTF. (1030 DATA:0000)

DC 1 average overcurrent
DC 2 average overcurrent AC hardware overcurrent (abc phase)

1. Check if the internal fan is working correctly or jammed.
1. Check if the PV voltage is abnormal 2. Restart the system, confirm that the fault
continues
1. Restart the system, confirm that the fault continues.
1. Check if the DC wires are connected correctly without loose connection. 1. Confirm that the grid is abnormal. 2. Confirm that the AC cable connection is not
abnormal. 3. Restart the system, confirm that the fault
continues.
1. Restart the system, confirm that the fault continues.

.85.

8. Troubleshooting

Message Name

Information Description

DCInj-FAULT

The current DC component

(1037 DATA:0000) exceeds the limit

IGBT-OV-I (1048 DATA:0000)

IGBT overcurrent

OV-TEM (1032 DATA:0000)

Module over temperature

RelayChk-FAIL (1035 DATA:0000)

Relay failure

UN-TEM (103A DATA:0000)

Low temperature protection

PV ISO-PRO01 (1033 DATA:0001)
PV ISO-PRO02 (1033 DATA:0002)
12Power-FAULT (1038 DATA:0000)
ILeak-PRO01 (1034 DATA:0001)
ILeak-PRO02 (1034 DATA:0002)
ILeak-PRO03 (1034 DATA:0003)
ILeak-PRO04 (1034 DATA:0004)
ILeak_Check (1039 DATA:0000)

PV negative ground fault
PV positive ground fault
12V undervoltage failure
Leakage current failure 01 (30mA) Leakage current failure 02 (60mA) Leakage current failure 03 (150mA)
Leakage current failure 04
Leakage current sensor failure

GRID-INTF02 (1046 DATA:0000)

Power grid disturbance 02

Troubleshooting Suggestion 1. Confirm that the grid is abnormal. 2. Confirm that the AC cable connection is not
abnormal. 3. Restart the system, confirm that the fault
continues. 1. Restart the system, confirm that the fault continues. 1. Check whether the surrounding environment
of the inverter has poor heat dissipation. 2. Confirm whether the product installation
meets the requirements. 1. Restart the system, confirm that the fault continues. 1. Check the working environment temperature of the inverter. 2. Restart the system to confirm if the fault continues.
1. Check whether the PV strings have insulation problems. 2. Check whether the PV cable is damaged.
1. Check current leakage to ground. Verify your grounding. Verify all wires are in good condition and not leaking current to ground.
1. Confirm whether the grid is seriously distorted. 2. Check whether the AC cable is connected
reliably.

OV-Vbatt-H/ OV-BUS-H (1051 DATA:0000)

Battery overvoltage hardware failure / VBUS

1. Check if the battery circuit breaker is tripping. 2. Check if the battery is damaged.

.86.

8. Troubleshooting

Message Name Information Description

Troubleshooting Suggestion

OV-ILLC (1052 DATA:0000)

LLC hardware overcurrent

INI-FAULT (1031 DATA:0000)
DSP-B-FAULT (1036 DATA:0000)
AFCI-Check (1040 DATA:0000)

AD zero drift overlink
The master-slave DSP communication is abnormal
AFCI self-test failure

ARC- FAULT (1041 DATA:0000)

AFCI failure

1. Check whether the backup load is overloaded. 2. Restart the system, confirm that the fault
continues.
1. Restart the system, confirm that the fault continues.
1. Verify connections are tight within your PV system. Arc fault settings can be changed in advanced settings if further adjustment is necessary.

Table 8.1 Fault message and description

NOTE: If the inverter displays any alarm message as listed in Table 8.1; please turn off the inverter and wait for 5 minutes before restarting it . If the failure persists, please contact your local distributor or the service center.
Please keep ready with you the following information before contacting us.
1. Serial number of Solis Single Phase Inverter; 2. The distributor/dealer of Solis Single Phase Inverter (if available); 3. Installation date. 4. The description of problem (i.e. the alarm message displayed on the LCD and the status
of the LED status indicator lights. Other readings obtained from the Information submenu (refer to Section 6.2) will also be helpful.); 5. The PV array configuration (e.g. number of panels, capacity of panels, number of strings, etc.); 6. Your contact details.

.87.

9. Specifications

Technical Data Input DC (PV side) Recommended max. PV power Max. input voltage Rated voltage Start-up voltage MPPT voltage range Full load MPPT voltage range Max. input current Max. short circuit current Max. inverter backfeed current to the array MPPT number/Max input strings number Battery Battery Type Battery Voltage range Battery Capacity Maximum Charging Power Maximum Charge/discharge current Communication Output AC(Back-up) Rated output power Max. apparent output power Back-up switch time Rated output voltage Rated frequency Rated output current THDv(@linear load) Input AC (Grid side) Input voltage range Max. input current Frequency range

S5-EH1P3K-L

S5-EH1P3.6K-L

4800W 100-520V

600V 330V 120V 90-520V
15.0A/15.0A 22.5A/22.5A
0A 2/2

5700W 120-520V

Li-ion / Lead-acid 42 – 58V
50 – 2000Ah 3kW 62.5A CAN

3kW 4.5 kVA, 10SEC
<20ms 1/N/PE, 230 V
50Hz 13.5 A <2%

20.5 A

187-265V 45-55 Hz

25.0 A

.88.

9. Specifications

Technical Data Output AC(Grid side) Rated output power Rated apparent output power Max. apparent output power Operation phase Rated grid voltage The grid voltage range Rated grid frequency AC grid frequency range Rated grid output current Inrush current Max. output fault current Max. output overcurrent protection Power Factor THDi Efficiency Max efficiency EU efficiency Protection DC reverse polarity protection Short circuit protection Output over current protection Surge protection Ground fault monitoring Integrated AFCI (DC arc-fault circuit protection) Protection class / Over voltage category Integrated DC switch

S5-EH1P3K-L

S5-EH1P3.6K-L

3kW

3.6kW

3kVA

3.6kVA

3kVA

3.6kVA

1/N/PE

230 V

187-265 V

50 Hz

45-55 Hz

15.0 A

18.5 A

65A 10us

65A 10us

16.0A

20.0A

0.99 (0.8 leading – 0.8 lagging)

<2%

97.1% >96.5%

Yes Yes Yes DC Type / AC Type Yes Yes (Activation required) I / II(PV), II(battery), III(AC) Yes

.89.

Technical Data General data Dimensions(W/H/D) Weight Topology Operation temperature range Ingress protection Noise emission Cooling concept Max.operation altitude Active anti-islanding method
Grid connection standard
Safty/EMC standard Features DC connection AC connection Display Communication Warranty

9. Specifications

S5-EH1P3K-L

S5-EH1P3.6K-L

333505249mm 18.3kg
non-isolated
-25+60 IP65
<20 dB (A)
Natural convection 3000m
Active frequency shifting G98 or G99, VDE-AR-N 4105 / VDE V 0124, EN 50549-1,
VDE 0126 / UTE C 15 / VFR:2019, RD 1699 / RD 244 / UNE 206006 / UNE 206007-1, CEI 0-21, C10/11,
NRS 097-2-1, TOR, EIFS 2018.2, IEC 62116, IEC 61727, IEC 60068, IEC 61683, EN 50530, MEA, PEA
IEC/EN 62109-1/-2, EN 61000-6-2/-3

MC4 connector Quick connection plug 7.0″LCD color screen display RS485, Optional:Wi-Fi, GPRS 5 years standard (extand to 20 years)

.90.

9. Specifications

Technical Data Input DC (PV side) Recommended max. PV power Max. input voltage Rated voltage Start-up voltage MPPT voltage range Full load MPPT voltage range Max. input current Max. short circuit current Max. inverter backfeed current to the array MPPT number/Max input strings number Battery Battery Type Battery Voltage range Battery Capacity Maximum Charging Power Maximum Charge/discharge current Communication Output AC(Back-up) Rated output power Max. apparent output power Back-up switch time Rated output voltage Rated frequency Rated output current THDv(@linear load) Input AC (Grid side) Input voltage range Max. input current Frequency range

S5-EH1P4.6K-L

S5-EH1P5K-L

8000W 155-520V

600V 330V 120V 90-520V
15.0A/15.0A 22.5A/22.5A
0A 2/2

8000W 170-520V

Li-ion / Lead-acid 42 – 58V
50 – 2000Ah 5kW 100A CAN

5kW 7 kVA, 10SEC
<20ms 1/N/PE, 230 V
50Hz 22.0 A <2%

31.5 A

187-265V 45-55 Hz

34.5 A

.91.

9. Specifications

Technical Data Output AC(Grid side) Rated output power Rated apparent output power Max. apparent output power Operation phase Rated grid voltage The grid voltage range Rated grid frequency AC grid frequency range Rated grid output current Inrush current Max. output fault current Max. output overcurrent protection Power Factor THDi Efficiency Max efficiency EU efficiency Protection DC reverse polarity protection Short circuit protection Output over current protection Surge protection Ground fault monitoring Integrated AFCI (DC arc-fault circuit protection) Protection class / Over voltage category Integrated DC switch

S5-EH1P4.6K-L

S5-EH1P5K-L

4.6kW

5kW

4.6kVA

5kVA

4.6kVA

5kVA

1/N/PE

230 V

187-265 V

50 Hz

45-55 Hz

21.0 A

25.0 A

65A 10us

65A 10us

22.0A

26.0A

0.99 (0.8 leading – 0.8 lagging)

<2%

97.1% >96.5%

Yes Yes Yes DC Type / AC Type Yes Yes (Activation required) I / II(PV), II(battery), III(AC) Yes

.92.

9. Specifications

Technical Data General data Dimensions(W/H/D) Weight Topology Operation temperature range Ingress protection Noise emission Cooling concept Max.operation altitude Active anti-islanding method
Grid connection standard
Safty/EMC standard Features DC connection AC connection Display Communication Warranty

S5-EH1P4.6K-L

S5-EH1P5K-L

333505249mm 18.3kg
non-isolated
-25+60 IP65
<20 dB (A)
Natural convection 3000m
Active frequency shifting G98 or G99, VDE-AR-N 4105 / VDE V 0124, EN 50549-1,
VDE 0126 / UTE C 15 / VFR:2019, RD 1699 / RD 244 / UNE 206006 / UNE 206007-1, CEI 0-21, C10/11,
NRS 097-2-1, TOR, EIFS 2018.2, IEC 62116, IEC 61727, IEC 60068, IEC 61683, EN 50530, MEA, PEA
IEC/EN 62109-1/-2, EN 61000-6-2/-3

MC4 connector Quick connection plug 7.0″LCD color screen display RS485, Optional:Wi-Fi, GPRS 5 years standard (extand to 20 years)

.93.

9. Specifications

Technical Data Input DC (PV side) Recommended max. PV power Max. input voltage Rated voltage Start-up voltage MPPT voltage range Full load MPPT voltage range Max. input current Max. short circuit current Max. inverter backfeed current to the array MPPT number/Max input strings number Battery Battery Type Battery Voltage range Battery Capacity Maximum Charging Power Maximum Charge/discharge current Communication Output AC(Back-up) Rated output power Max. apparent output power Back-up switch time Rated output voltage Rated frequency Rated output current THDv(@linear load) Input AC (Grid side) Input voltage range Max. input current Frequency range

S5-EH1P6K-L
8000W 600V 330V 120V 90-520V 200-520V 15.0A/15.0A 22.5A/22.5A
0A 2/2
Li-ion / Lead-acid 42 – 58V
50 – 2000Ah 5kW 100A CAN
5kW 7 kVA, 10SEC
<20ms 1/N/PE, 230 V
50Hz 22.0 A <2%
187-265V 34.5 A
45-55 Hz

.94.

9. Specifications

Technical Data Output AC(Grid side) Rated output power Rated apparent output power Max. apparent output power Operation phase Rated grid voltage The grid voltage range Rated grid frequency AC grid frequency range Rated grid output current Inrush current Max. output fault current Max. output overcurrent protection Power Factor THDi Efficiency Max efficiency EU efficiency Protection DC reverse polarity protection Short circuit protection Output over current protection Surge protection Ground fault monitoring Integrated AFCI (DC arc-fault circuit protection) Protection class / Over voltage category Integrated DC switch

S5-EH1P6K-L
6kW 6kVA 6kVA 1/N/PE 230 V 187-265 V 50 Hz 45-55 Hz 30.0 A 65A 10us 65A 10us 31.0A >0.99 (0.8 leading – 0.8 lagging) <2%

97.1% >96.5%
Yes Yes Yes DC Type / AC Type Yes Yes (Activation required) I / II(PV), II(battery), III(AC) Yes

.95.

Technical Data General data Dimensions(W/H/D) Weight Topology Operation temperature range Ingress protection Noise emission Cooling concept Max.operation altitude Active anti-islanding method
Grid connection standard
Safty/EMC standard Features DC connection AC connection Display Communication Warranty

9. Specifications
S5-EH1P6K-L
333505249mm 18.3kg
non-isolated -25+60
IP65 <20 dB (A) Natural convection
3000m Active frequency shifting G98 or G99, VDE-AR-N 4105 / VDE V 0124, EN 50549-1, VDE 0126 / UTE C 15 / VFR:2019, RD 1699 / RD 244 / UNE 206006 / UNE 206007-1, CEI 0-21, C10/11, NRS 097-2-1, TOR, EIFS 2018.2, IEC 62116, IEC 61727, IEC 60068, IEC 61683, EN 50530, MEA, PEA IEC/EN 62109-1/-2, EN 61000-6-2/-3
MC4 connector Quick connection plug 7.0″LCD color screen display RS485, Optional:Wi-Fi, GPRS 5 years standard (extand to 20 years)

.96.

10. Appendix
10.1 Advanced Settings
NOTE: The following sections have restricted access. Only authorized personnel are allowed to modify the settings. Please contact Solis service team for XXXX password.
NOTE: The standard code selection “4777_A”, “4777_B”, “4777_C” and “4777-N” already have preset default settings as required by AS/NZS 4777.2:2020. Unless specially required, customers do not need to gain access to the following sections or modify any settings inside.
Setting Path: Advanced Setting -> Password: XXXX -> STD.Mode Settings There are several grid code related settings under STD.Mode Settings.
10.1.1 Working Mode Set
Solis AU version inverters have the following working mode settings: 1. NULL 2. P Mode Settings 3.Q Mode Settings 1. NULL Description: Inverter will not be under any working mode. 2. P Mode Settings This P Mode Settings include 1 working mode: Volt-Watt 2.1 Volt-Watt Description: Inverter will change the active output power based on grid voltage.
.97.

10. Appendix

Maximum Power Level,P/S rated(%)

120 100
80

60 40 20

0

Inverter Voltage,V

Vw1 Vw2

Status: Enable/Disable (Note: This is used to enable or disable the Volt-Watt mode) Voltage 1: 207V P-Limit 1: 100% Voltage 2: 220V P-Limit 2: 100% Voltage 3 (Vw1): 235-255V (Default: 4777-A(253V); 4777-B(250V);4777-C(253V);4777-N(242V)) P-Limit 3: 100% Voltage 4 (Vw2): 240-265V (Default: 4777-A(260V); 4777-B(260V);4777-C(260V);4777-N(250V)) P-Limit 4: 0%-20% (Default: 20% for 4777-A; 4777-B; 4777-C; 4777-N)
3. Q Mode Settings This Q Mode Settings include 5 working modes: Disable, Volt-Var, Fixed-PF, Reac-Power, P-factor 3.1 Disable Description: This mode will disable the reactive power response working modes 3.2 Volt-Var Description: Inverter will change the reactive output power based on grid voltage.

.98.

10. Appendix

Reactive Power Level, Q/S rated(%)

Supplying

60

50

40 30

20

10

0

Vv1

Vv2

-10

Vv3

Vv4

-20

-30

-40

-50

-60 Absorbing

Inverter Voltage, V

Voltage 1 (Vv1): 180-230V (Default: 4777-A(207V); 4777-B(205V);4777-C(215V);4777-N(207V)) Voltage 2(Vv2) : 180-230V (Default: 4777-A(220V); 4777-B(220V);4777-C(230V);4777-N(220V)) Voltage 3(Vv3) : 230-265V (Default: 4777-A(240V); 4777-B(235V);4777-C(240V);4777-N(235V)) Voltage 4(Vv4) : 230-265V (Default: 4777-A(258V); 4777-B(255V);4777-C(255V);4777-N(244V)) Leading(Supplying) : +30~+60% (Default: 4777-A(+44%); 4777-B(+30%);4777-C(+44%);4777-N(+60%)) Lagging(Absorbing) : -30%~-60% (Default: 4777-A(-60%); 4777-B(-40%);4777-C(-60%);4777-N(-60%))

.99.

10. Appendix
3.3 Fixed PF Description: This mode is to set a fixed power factor output Range: -0.8~+0.8 Default: 1
3.4 Reac-Power Description: This mode is to set a fixed reactive power output Range:-60%~+60% Default: 0%
3.5 Power-PF Description: This mode is not required in Australia.
10.1.2 Power Rate Limit
To set the power rate limits for increase and decrease in power level per minute. Wgra+: 5-100%, Default:16% Wgra-: 5-100%, Default:16%
10.1.3 Freq Derate Set
To set the frequency response limits for response to a decrease/increase in frequency. OVF_Start(F_ULCO): 50.1Hz~50.5Hz (Default: 4777-A(50.25Hz), 4777-B(50.15Hz), 4777-C(50.5Hz), 4777-N(50.2Hz)) OVF_Stop(F_Pmin): 51Hz~53Hz (Default: 4777-A(52Hz), 4777-B(52Hz), 4777-C(53Hz), 4777-N(52Hz)) UNF_Start(F_LLCO): 49.5Hz~49.9Hz (Default: 4777-A(49.75Hz), 4777-B(49.85Hz), 4777-C(49.5Hz), 4777-N(49.8Hz)) UNF_Stop(F_Pmax): 47Hz~49Hz (Default: 4777-A(48Hz), 4777-B(48Hz), 4777-C(47Hz), 4777-N(48Hz))
10.1.4 10mins Voltage Set
To set the 10mins average protection limit. Range: 244V to 258V Default: 4777-A (258V); 4777-B(258V); 4777-C(258V); 4777-N(249V)
10.1.5 DRM Settings
“DRM ON/OFF” is used to enabled or disable the functionality of the DRM port. “DRM3” and “DRM7” are used to define the reactive power absorption for DRM3 and DRM7. Range: 0~- 60%
.100.

10. Appendix

10.2 Built-In DC Isolator Specification

A DC-PV2 switch , complied to AS60947.3:2018 ,within the inverter, is used as isolating device. Please check below ratings.

DC switch brand Model PV category Ue Ie Ui Uimp Icw Icm I(make)/Ic(break) Complied standard

Beijing People GHX5-32P DC-PV2 1100V 30A 1500V 8000V 700A 1400A 120A AS 60947.3

.101.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals