Goodman GPHH3 3.5 Ton Horizontal Packaged Air Conditioner Instruction Manual

June 14, 2024
Goodman

INSTALLATION INSTRUCTIONS FOR SELF-CONTAINED
PACKAGE AIR CONDITIONERS AND HEAT PumpP UNITS
PC/PH 13.4 SEER2 “H” SERIES WiTH R-410A

GPHH3 3.5 Ton Horizontal Packaged Air Conditioner

Goodman GPHH3 3.5 Ton Horizontal Packaged Air
Conditioner

RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
*NOTE: PLEASE CONTACT YOUR DISTRIBUTOR OR OUR WEBSITE FOR THE APPLICABLE SPECIFICATION SHEETS REFERRED TO IN THIS MANUAL.
These installation instructions cover the outdoor installation of self contained package air conditioner and heating units.
See the Specification Sheets applicable to your model for information regarding accessories.
WARNING
ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE OR REPAIR(HEREINAFTER, “SERVICE”) THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT. THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROGEDURES. IF YOU SERVIGE THIS UNIT, YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHIGH MAY RESULT. IN ADDITION, IN JURISDICTIONS THAT REQUIRE ONE OR MORE LIGENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT. IMPROPER INSTALLATION, ADJUSTMENT, SERVIGING OR REPAIR OF THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST, SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

To THE INSTALLER

Carefully read all instructions for the installation prior to installing unit. Make sure each step or procedure is understood and any special considerations are taken into account before starting installation. Assemble all tools, hardware and supplies needed to complete the installation. Some items may need to be purchased locally. After deciding where to install unit, closely look the location over – both the inside and outside of home. Note any potential obstacles or problems that might be encountered as noted in this manual. Choose a more suitable location if necessary.
IMPORTANT NOTE: IF A CRANKCASE HEATER IS USED, THE UNIT SHOULD BE ENERGIZED 24 HOURS PRIOR TO COMPRESSOR START UP TO ENSURE CRANKCASE HEATER HAS SUFFICIENTLY WARMED THE COMPRESSOR. COMPRESSOR DAMAGE MAY OCCUR IF THIS STEP IS NOT FOLLOWED.
Before using this manual, check the serial plate for proper model identification.
The installation and servicing of this equipment must be performed by qualified, experienced technicians only.

SHIPPING INSPECTION

CHECKING PRODUCT RECEIVED
Upon receiving the unit, inspect it for damage from shipment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company. Check the unit model number, specifications, electrical characteristics and accessories to determine if they are correct. In the event an incorrect unit is shipped, it must be returned to the supplier and must NOT be installed. The manufacturer assumes no responsibility for installation of incorrectly shipped units.
MessAGE To THE HOMEOWNER
These instructions are addressed primarily to the installer; however, useful maintenance information is included and should be kept, after installation, for future reference.

REPLACEMENT PARTS

ORDERING PARTS
When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate. Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact:
HOMEOWNER SUPPORT
GOODMAN MANUFACTURING COMPANY, L.P.
19001 KERMIER ROAD
WALLER, TEXAS 77484
855-770-5678

IMPORTANT SAFETY INSTRUCTIONS

Recognize Safety Symbols, Words, and Labels
The following symbols and labels are used throughout this manual to indicate immediate or potential hazards. It is the owner’s responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of serious personal injury or death, property damage and/or product damage.
WARNING
Do NOT CONNECT TO OR USE ANY DEVICE THAT IS NOT DESIGN
CERTIFIED BY THE MANUFACTURER FOR USE WITH THIS UNIT. SERIOUS PROPERTY DAMAGE, PERSONAL INJURY, REDUGED UNIT PERFORMANGE AND/OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF SUCH NON-APPROVED DEVICES.
WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
CONNECTING UNIT DUCT WORK TO UNAUTHORIZED HEAT PRODUCING DEVIGES SUCH AS A FIREPLAGE INSERT, STOVE, ETC. MAY RESULT IN PROPERTY DAMAGE, FIRE, GARBON MONOXIDE POISONING, EXPLOSION, PERSONAL INJURY OR DEATH.
WARNING
THIS PRODUCT GONTAINS OR PRODUGES A GHEMIGAL OR GHEMICALS WHIGH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANGER, BIRTH DETEGTS OR OTHER REPRODUCTIVE HARM.
WARNING
To AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO NOT USE THIS UNIT IF ANY PART HAS BEEN UNDER WATER. [MMEDIATELY GALL A QUALIFIED SERVIGE TECHNIGIAN TO INSPEGT THE FURNAGE AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN UNDER WATER.
WARNING
THIS UNIT MUST NOT BE USED AS A “CONSTRUCTION HEATER” DURING THE FINISHING PHASES OF CONSTRUCTION ON A NEW STRUCTURE. THIS TYPE OF USE MAY RESULT IN PREMATURE FAILURE OF THE UNIT DUE TO EXTREMELY LOW RETURN AIR TEMPERATURE AND EXPOSURE TO CORROSIVE OR VERY DIRTY ATMOSPHERES.
WARNING
To PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH, DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS IN THE VIGINITY OF THIS APPLIANCE.

CODES AND REGULATIONS

G ENERAL
The PC & PH series air conditioners and heat pumps are designed for OUTDOOR USE ONLY. This series is available in cooling Capacities of 2, 2 2, 3, 3 ¥, 4 and 5 nominal tons of cooling. Optional field installed heat kits are available in 5,8,10,15 and 20 KW. The units can be easily installed in manufactured or modular homes with existing high- static duct work. The units can also be easily converted to accommodate a plenum for normal or low-static applications. The PC & PH series are self contained packaged units so the only connections needed for installation are the supply and return ducts, the line and low voltage wiring and drain connection. Rated performance is achieved after 20 hours of operation. Rated performance is delivered at the specified airflow. See outdoor unit specification sheet for split system models or product specification sheet for packaged and light commercial models. Specification sheets can be found at www.goodmanmfg.com for Goodman® brand products or www.amana-hac.com for Amana® brand products. Within either website, please select the residential or commercial products menu and then select the submenu for the type of product to be installed, such as air conditioners or heat pumps, to access a list of product pages that each contain links to that model’s specification sheet.
The information on the rating plate is in compliance with the FTC & DOE rating for single phase units. The three phase units in this series are not covered under the DOE certified program. The efficiency ratings of these units are a product of thermal efficiency determined under continuous operating conditions independent of any installed system.
EPA REGULATIONS
IMPORTANT: THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY (EPA) HAS ISSUED VARIOUS REGULATIONS REGARDING THE INTRODUCTION AND DISPOSAL OF REFRIGERANTS IN THIS UNIT. FAILURE TO FOLLOW THESE REGULATIONS MAY HARM THE ENVIRONMENT AND CAN LEAD TO THE IMPOSITION OF SUBSTANTIAL FINES. BECAUSE REGULATIONS MAY VARY DUE TO PASSAGE OF NEW LAWS, WE SUGGEST A CERTIFIED TECHNICIAN PERFORM ANY WORK DONE ON THIS UNIT. SHOULD YOU HAVE ANY QUESTIONS PLEASE CONTACT THE LOCAL OFFICE OF THE EPA.
NATIONAL CODES
This product is designed and manufactured to permit installation in accordance with National Codes.
It is the installer’s responsibility to install the product in accordance with National Codes and/or prevailing local codes and regulations.

MAJOR COMPONENTS

GENERAL
The unit includes a hermetically sealed refrigerating system (consisting of a compressor, condenser coil, evaporator coil with flowrator), an indoor blower, a condenser fan and all necessary internal electrical wiring. The heat pump also includes a reversing valve, solenoid, defrost thermostat and control and loss of charge protection. The system is factory- evacuated, charged and performance tested. Refrigerant amount and type are indicated on rating plate.

INSTALLATION

PRE-INSTALLATION CHECKPOINTS
Before attempting any installation, the following points should be considered:

  • Structural strength of supporting members
  • Clearances and provision for servicing
  • Power supply and wiring
  • Air duct connections
  • Drain facilities and connections
  • Location may be on any four sides of a home, manufactured or modular, to minimize noise

CLEARANCE
The unit is designed to be located outside the building with unobstructed condenser air inlet and discharge. Additionally, the unit must be situated to permit access for service and installation. Condenser air enters from three sides. Air discharges upward from the top of the unit. Refrigerant gauge connections are made on the right side of the unit as you face the compressor compartment. Electrical connections can be made either on the right or left sides of the unit. The best and most common application is for the unit to be located 10” from wall (4” minimum) with the connection side facing the wall. This “close to the wall” application minimizes exposed wiring.
Close to the wall application assures free, unobstructed air to the other two sides. In more confined application spaces, such as corners provide a minimum 10″ clearance on all air inlet sides. Allow 18″ minimum for service access to the compressor compartment and controls. The top of the unit should be completely unobstructed. If units are to be located under an overhang, there should be a minimum of 36″ clearance and provisions made to deflect the warm discharge air out from the overhang.
LocaTtion
Consider the affect of outdoor fan noise on conditioned space and any adjacent occupied space. It is recommended that the unit be placed so that condenser air discharge does not blow toward windows less than 25 feet away.
The unit should be set on a solid, level foundation – preferably a concrete slab at least 4 inches thick. The slab should be above ground level and surrounded by a graveled area for good drainage. Any slab used as a unit’s foundation should not adjoin the building as it is possible that sound and vibration may be transmitted to the structure. For rooftop installation, steel or treated wood beams should be used as unit support for load distribution.
Heat pumps require special location consideration in areas of heavy snow accumulation and/or areas with prolonged continuous subfreezing temperatures. Heat pump unit bases have holes under the outdoor coil to permit drainage of defrost water accumulation. The unit must be situated to permit free unobstructed drainage of the defrost water and ice. A minimum 2” clearance under the outdoor coil is required in the milder climates.
OuTsIDE SLAB INSTALLATION (FIGURE 1)

  1. The unit must be mounted on a solid, level foundation.
  2. Select a location that will minimize the length of the supply and return ducts.
  3. Select a location where external water drainage cannot collect around the unit.
  4. Consideration should also be given to shade, appearance and noise.Goodman GPHH3 3.5 Ton Horizontal Packaged Air Conditioner - parts

ROOFTOP INSTALLATION (FIGURE 2)

  1. Before locating the unit on the roof, make sure that the strength of the roof and beams is adequate to support the weight involved. (See specification sheet for weight of units.) This is very important and the installer’s responsibility.
  2. Make proper consideration for the weather—tight integrity of the roof and proper drainage of condensate.
  3. To ensure proper condensate drainage, unit must be installed in a level position.
  4. Consideration should also be given to shade, appearance and noise.

WARNING
DO NOT, UNDER ANY GIRCUMSTANGES, GONNECT RETURN DUGTWORK TO ANY OTHER HEAT PRODUCING DEVIGES SUCH AS A FIREPLACE INSERT, STOVE, ETC. UNAUTHORIZED USE OF SUGH DEVICES MAY RESULT IN PROPERTY DAMAGE, FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PERSONAL INJURY OR DEATH.

DUCTING

Ducting work should be fabricated by the installing contractor in accordance with local codes. Industry manuals may be used as a guide when sizing and designing the duct system- such as NESCA (National Environmental Systems Contractors Association, 1501 Wilson Blvd., Arlington, Virginia 22209).
The unit should be placed as close as possible to the space to be air- conditioned allowing clearance dimensions as indicated. Ducts should run as directly as possible to supply and retum outlets. Use of non-flammable weatherproof flexible connectors on both supply and retum connections at the unit to reduce noise transmission is recommended.
Itis preferable to install the unit on the roof of the structure if the registers or diffusers are located in the wall or ceiling. A slab installation is recommended when the registers are low on the wall or in the floor.
CONNECTING THE RETURN AND SuppLY FLEXIBLE DucT IN MANUFACTURED OR MoDULAR HOUSING APPLICATION The return and supply fittings are to be attached at the unit to a suitable square to round duct converter. Your distributor has a factory designed square to round converter transition. The model #s of these kits are as follows: Small Chassis 275″ SQRPCH102, Large and Extra Large Chassis 32.5.” and 36” SQRPCH103 (See Specification Sheets for Dimension details). The SQRPCH101 has 14” duct collar on supply and 16” duct collar (equivalent diameter, opening is oval) on the return. The SQRPCH102 and SQRPCH103 have 14” duct collar on supply and 18” duct collar (equivalent diameter, opening is oval) on the return. The collars are to  be slipped into the openings, and the flanges bent around the converter. The square to round converter is attached to the flanges of the square duct openings. The flexible duct is then clamped on to the collars. Once the duct is affixed to the unit, seal the collars and flanges with a proper waterproof sealant (See Figure 3).
It is strongly encouraged to use appropriately sized ducts based upon the CFM for your application (unit’s CFM). If duct sizing through industry manuals or air duct calculators require larger ducts than converter openings, run larger duct size up to unit converter openings and reduce with a reducer duct fitting or transition right at the unit.

MINIMUM FILTER SIZE

NOMINAL SIZE (INCHES)| NOMINAL AREA (SQ. FT.)
10×20| 1.4
14×20| 1.9
14×25| 2.4
15×20| 2.1
16×20| 2.2
16×25| 2.8
20×20| 2.8
20×25| 3.5
25×25| 4.3

TASLE 1Goodman GPHH3 3.5 Ton Horizontal Packaged Air Conditioner -
parts2 PLENUM APPLICATION
A suitable plenum or square duct must be constructed. The duct cross-sectional area should be determined by industry duct sizing manuals or air duct calculators.
On ductwork exposed to outside air conditions of temperature and humidity, use an insulation with a good K factor, and a vapor barrier. Industry practices should be followed. Balancing dampers are recommended for each branch duct in the supply system. Ductwork should be properly supported from the unit.
NOTE: PROPER SEALING OF ALL DUCT WORK AND AIR HANDLING COMPARTMENTS IS EXTREMELY IMPORTANT TO OVERALL UNIT EFFICIENCY.
FILTERS
Filters are not provided with unit, and must be supplied and installed in the return duct system by the installer. A field installed filter grille is recommended for easy and convenient access to the filters for periodic inspection and cleaning. Filters must have adequate face area for the rated quantity of the unit. See air delivery tables (Figure 4) for recommended filter size.
PIPING
CoONDENSATE DRAIN
The condensate drain connection of the evaporator is a half coupling of %” N.P.T. A trap must be provided to have Proper condensate drainage. Goodman
GPHH3 3.5 Ton Horizontal Packaged Air Conditioner -
parts3Install condensate drain trap as shown. Use % drain connection size or larger. Do not operate without trap. Unit must be level or slightly inclined toward drain.
WIRING
CAUTION
To AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE ONLY COPPER CONDUGTORS.
All wiring should be made in accordance with the National Electrical Code. The local Power Company should be consulted to determine the availability of sufficient power to operate the unit. The voltage, frequency, and phase at the power supply should be checked to make sure it corresponds to the unit’s RATED VOLTAGE REQUIREMENT.
Install a branch circuit fused disconnect near the unit, in accordance with the N.E.C. or local codes. Wire sizes and overcurrent protection should be determined from the unit nameplate ampacity and in accordance with Table 4 (page 7) or the N.E.C. Under no circumstances should wiring be sized smaller than is recommended by either of these two sources.
Fuses smaller than that recommended on the wiring diagrams could result in unnecessary fuse failure or service calls. The use of protective devices of larger size than indicated could result in extensive damage to the equipment. The manufacturer bears no responsibility for damage caused to equipment as result of the use of larger than is recommended size protective devices.
All units have undergone a run test prior to packaging for shipment. This equipment has been started at minimum rated voltage and checked for satisfactory operation. Do not attempt to operate this unit if the voltage is not within the minimum and maximum voltages shown on nameplate.
All exterior wiring must be within approved weatherproof conduit. The unit must be permanently grounded in accordance with local codes, or in absence of local codes, with N.E.C ANSI/ NFPA NO. 70-1984 or latest edition by using ground lug in the control box.
Fuses or HACR type circuit breakers may be used where codes permit. Goodman
GPHH3 3.5 Ton Horizontal Packaged Air Conditioner -
parts4NOTE: SOME SINGLE PHASE UNITS ARE EQUIPPED WITH A SINGLE POLE CONTACTOR. CAUTION MUST BE EXERCISED WHEN SERVICING AS ONLY ONE LEG OF THE POWER SUPPLY IS BROKEN WITH THE CONTACTOR.
To wire the unit, make the following high and low voltage connections.
WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
HicH VoLTAGE WIRING: (SEE FIGURE 6)
Single Phase – Two leads should be connected to terminals L1 & L2 in the electrical control section, using wire sizes specified in wiring table.
Low VoLTAGe WIRING: (SEE FIGURE 6)
a. Air Conditioners – Connect 24V wires from the thermostat to the comesponding wires in the control box using No. 18AWG as follows:

LEAD THERMOSTAT
Red R (24V)
Green G (Fan)
Yellow Y (Cool)
White W1 (Heat)*
Brown W2 (Heat)*

TABLE 2
b. Heat Pumps – Connect 24V wires from the thermostat to the comresponding wires in the control box using No. 18AWG as follows:

TERMINAL THERMOSTAT
Red R (24V)
Green G (Fan)
Orange O (Rev. Valve)
White W1 (Heat, 2nd)*
Brown W2 (Heat 3rd)*
Yellow Y (Cool)
C (Blue) C (Common)

*OPTIONAL FIELD INSTALLED HEAT CONNECTIONS
TaBLE 3
INTERNAL WIRING:
A diagram detailing the internal wiring of this unit is located on the electrical box cover. If any of the original wire supplied with the appliance must be replaced, the wire gauge and insulation must be the same as the original wiring.
Transformer is wired for 230 volts on the 208 / 230 models. See wiring diagram for 208 volt wiring.

BRANCH CIRCUIT AMPACITY 15 20 25 30 35 40 45 50
SUPPLY WIRE LENGTH – FEET
200 6 4 4 4 3 3 2 2
150 8 6 6 4 4 4 3 3
100 10 8 8 6 6 6 4 4
50 14 12 10 10 8 8 6 6

TABLE 4

  1. For branch circuit wiring (main power supply to unit disconnect), the minimum wire size for the length of the run can be determined from Table 4 using the circuit ampacity found on the unit rating plate. From the unit disconnect to unit, the smallest wire size allowable in Table 4 may be used for the ampacity, as the Disconnect must be in sight of the unit.
  2. Wire size based on 60° C rated wire insulation and 30° C Ambient Temperature (86° F).
  3. For more than 3 conductors in a raceway or cable, see the N.E.C. for derating the ampacity of each conductor.

OPERATION

START-UP PROCEDURE AND CHECKLIST
Begin with power tumed off at all disconnects.
WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

  1. Turn thermostat system switch to “Cool,” and fan switch to “Auto” and turn temperature setting as high as it will go.

  2. Inspect all registers and set them to the normal open position.

  3. Turn on the electrical supply at the disconnect.

  4. Turn the fan switch to the “ON” position. The blower should operate after a 10 second delay.

  5. Turn the fan switch to “Auto” position. The blower should stop after a 60 second delay.

  6. Slowly lower the cooling temperature until the unit starts. The compressor, blower and fan should now be operating. Allow the unit to run 10 minutes, make sure cool air is being supplied by the unit.

  7. Turn the temperature setting to the highest position, stopping the unit. The indoor blower will continue to run for 60 seconds.

  8. Turn the thermostat system switch to “OFF” and disconnect all power when servicing the unit.
    WARNING
    HIGH VOLTAGE!
    ** DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
    HeaTt Pump START-UP PROCEDURE**

  9. Check the cooling mode for the heat pump in the same manner as above. The reversing valve is energized when the thermostat is placed in the cooling position. A clicking sound should be noticeable from the reversing valve. By lowering the temperature setting to call for cooling, the contractor is energized. The compressor, blower and fan should then be running. After the cooling mode is checked out, turn the thermostat system switch to “OFF”.

  10. Turn the thermostat system switch to “HEAT” and fan switch to “AUTO”.

  11. Slowly raise the heating temperature setting. When the heating first stage makes contact, stop raising the temperature setting. The compressor, blower and fan should now be running with the reversing valve in the de-energized (heating) position. After giving the unit time to settle out, make sure the unit is supplying heated air.

  12. If the out door ambient is above 80°F, the unit may trip on its high pressure cut out when on heating. The compressor should stop. The heating cycle must be thoroughly checked, so postpone the test to another day when conditions are more suitable but-DO NOT FAILTOTEST.

  13. If the out door ambient is low and the unit operates properly on the heating cycle, you may check the pressure cutout operation by blocking off the indoor return air until the unit trips. If unit operates properly in the heating cycle, raise the temperature setting until the heating second stage makes contact. Supplemental resistance heat, if installed should now come on. Make sure it operates properly.
    NOTE: IF OUTDOOR THERMOSTATS ARE INSTALLED THE OUTDOOR AMBIENT MUST BE BELOW THE SET POINT OF THESE THERMOSTATS FOR THE HEATERS TO OPERATE. IT MAY BE NECESSARY TO JUMPER THESE THERMOSTATS TO CHECK HEATER OPERATION IF OUTDOOR AMBIENT IS MILD.

  14. For thermostats with emergency heat switch, return to step 11. The emergency heat switch is located at the bottom of the thermostat. Move the switch to emergency heat. The heat pump will stop, the blower will continue to run, all heaters will come on and the thermostat emergency heat light will come on.

  15. If checking the unit in the wintertime, when the outdoor coil is cold enough to actuate the defrost control, observe at least one defrost cycle to make sure the unit defrosts completely.Goodman GPHH3 3.5 Ton Horizontal Packaged Air Conditioner - parts5 FINAL SYSTEM CHECKS

  16. Check to see if all supply and retum air grilles are adjusted and the air distribution system is balanced for the best compromise between heating and cooling.

  17. Check for air leaks in the ductwork.

  18. See Sections on Air Flow Measurement and Adjustment and Checking Charge.

  19. Make sure the unit is free of “rattles”, and the tubing in the unit is free from excessive vibration. Also make sure tubes or lines are not rubbing against each other or sheet metal surfaces or edges. If so, correct the trouble.

  20. Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use.

  21. Be sure the Owner is instructed on the unit operation, filter, servicing, correct thermostat operation, etc.

  22. The foregoing “Start-up Procedure and Check List” is recommended to serve as an indication that the unit will operate normally.

COMPONENTS

  1. Contactor – This control is activated (closed) by the room thermostat for both heating and cooling. The contactor has a 24V coil and supplies power to the compressor and outdoor fan motor.

  2. Crankcase Heater – This item is “ON” whenever power is supplied to the unit and the crankcase heater thermostat is closed. Crankcase heater thermostat closes at 67° and opens at 85°. It warms the compressor crankcase thereby preventing liquid migration and subsequent compressor damage. The insert type heater is self regulating. It is connected electrically to the contactor L1 and L2 terminals.

  3. Condenser Motor – This item is activated by the contactor during heating and cooling, except during defrost and emergency heat operation.

  4. Compressor – This item is activated by the contactor for heating and cooling, except during emergency heat. Itis protected by an internal overload.

  5. Contactor Relay – This control is activated by the thermostat (24V coil) and supplies power to the contactor.

  6. Defrost Control – The Defrost control provides time/ temperature initiation and termination of the defrost cycle. When a Defrost cycle is initiated, the defrost control shifts the reversing valve to “cooling” mode, stops the outdoor fan and brings on supplemental heat. Normally, a Defrost cycle will take only 2-3 minutes unless system is low on charge or outdoor conditions are severe. (Windy and cold.) The defrost control also provides for a 3 minute off cycle compressor delay.

  7. Outdoor Thermostat – These optional controls are used to prevent full electric heater operation at varying outdoor ambient (0° F-to 45° F). They are normally open above their set points and closed below to permit staging of indoor supplement heater operation. If the outdoor ambient temperature is below 0° F (-18° C) with 50% or higher RH, an outdoor thermostat (OT) must be installed and set at (0°) on the dial. Failure to comply with this requirement may result in damage to the product which may not be covered by the manufacturer’s warranty.

  8. Reversing Valve Coil – This coil is activated by the themostat, in the cooling mode and during defrost. It positions the reversing valve pilot valve for cooling operation.

  9. Indoor Blower Motor – Units with EEM Motors The EEM model indoor blower motor is activated by the room thermostat by cooling/HEATING or fan ON position. The motor is energized by a 24 volt control signal (from thermostat Y, G or W) for EEM motors. EEM motors are constant torque motors with very low power consumption.
    (See Air Flow Measurement and Adjustment for speed adjustment instructions).

  10. Blower Interlock Relay – This relay is used to energize the blower during the electric heat operation. Some room thermostats do not energize the motor during electric heat. This relay insures blower operation when the room thermostat energizes heat. This relay has a 240 volt coil and an 8 amp contact relay. This relay is energized by the electric heat kit sequencer.

EXPLANATION AND GUIDANCE (HEAT PUMP)

  1. The heat pump is a relatively simple device. It operates exactly as a Summer Air Conditioner unit when itis on the cooling cycle. Therefore, all the charts and data for service that apply to summer air conditioning apply to the heat pump when it is on the cooling cycle, and most apply on the heating cycle except that “condenser” becomes “evaporator”, “evaporator” becomes “condenser”, “cooling” becomes “heating”.

When the heat pump is on the heating cycle, it is necessary to redirect the refrigerant flow through the refrigerant circuit external to the compressor. This is accomplished with a reversing valve. Thus, the hot discharge vapor from the compressor is directed to the indoor coil (evaporator on the cooling cycle) where the heat is removed, and the vapor condenses to liquid. It then goes through the expansion device to the outdoor coil (condenser on the cooling cycle) where the liquid is evaporated, and the vapor goes to the
compressor.
When the solenoid valve coil is operated either from heating to cooling or vice versa, the piston in the reversing valve to the low pressure (high pressure) reverse positions in the reversing valve.
Figure 7 shows a schematic of a heat pump on the cooling cycle and the heating cycle. In addition to a reversing valve, a heat pump is equipped with an expansion device and check valve for the indoor coil, and similar equipment for the outdoor coil. It is also provided with a defrost control system. The expansion devices are flowrator distributors and perform the same function on the heating cycle as on the cooling cycle. The flowrator distributors also act as check valves to allow for the reverse of refrigerant flow.
When the heat pump is on the heating cycle, the outdoor coil is functioning as an evaporator. The temperature of the refrigerant in the outdoor coil must be below the temperature of the outdoor air in order to extract heat from the air. Thus, the greater the difference in the outdoor temperature and the outdoor coil temperature, the greater the heating capacity of the heat pump. This phenomenon is a characteristic of a heat pump. Itis a good practice to provide supplementary heat for all heat pump installations in areas where the temperature drops below 45° F. It is also a good practice to provide sufficient supplementary heat to handle the entire heating requirement should there be a component failure of the heat pump, such as a compressor, or refrigerant leak, etc.
Since the temperature of the liquid refrigerant in the outdoor coil on the heating cycle is generally below freezing point, frost forms on the surfaces of the outdoor coil under certain weather conditions of temperature and relative humidity. Therefore, it is necessary to reverse the flow of the refrigerant to provide hot gas in the outdoor coil to melt the frost accumulation. This is accomplished by reversing the heat pump to the cooling cycle. At the same time, the outdoor fan stops to hasten the temperature rise of the outdoor coil and lessen the time required for defrosting. The indoor blower continues to run and the supplementary heaters are energized.

DEFROST CONTROL

During operation the power to the circuit board is controlled by a temperature sensor, which is clamped to a feeder tube entering the outdoor coil. Defrost timing periods of 30,60 and 90 minutes may be selected by setting the circuit board jumper to 30, 60 and 90 respectively. Accumulation of time for the timing period selected starts when the sensor closes (approximately 34 + 5°F), and when the wall thermostat calls for heat. At the end of the timing period, the unit’s defrost cycle will be initiated provided the sensor remains closed. When the sensor opens (approximately 60°F), the defrost cycle is terminated and the timing period is reset. If the defrost cycle is not terminated due to the sensor temperature, a twelve minute override interrupts the unit’s defrost period.

SUGGESTED FIELD TESTING ITROUBLE SHOOTING

  1. Run unit in the heating mode (room thermostat calling for heat).
  2. Check unit for proper charge. NOTE: Bands of frost on the condenser coil indicate low refrigerant charge.
  3. Shut off power to unit.
  4. Disconnect outdoor fan by removing the outdoor fan motor wire from “DF2” on defrost control.
  5. Restart unit and allow frost to accumulate.
  6. After a few minutes of operation, the unit’s defrost themmostat should close. To verify this, check for 24 volts between “DFT” and “C” on board. If the temperature at the thermostat is less than 28° F and the thermostat is open, replace the unit’s defrost thermostat, as it is defective.
  7. When the unit’s defrost thermostat has closed, short the test pins on the defrost board until the reversing valve shifts, indicating defrost. This should take up to 22 seconds depending on what timing period the control is set on. After defrost initiation, the short must instantly be removed or the unit’s defrost period will only last 3 seconds.
  8. The control is shipped from the factory with the compressor delay option selected. This will de-energize the compressor contactor for 30 seconds on defrost initiation and defrost termination. If the jumper is set to Normal, the compressor will continue to run during defrost initiation and defrost termination. The control will also ignore the low pressure switch connected to R-PS1 and PS2 for 5 minutes upon defrost initiation and 5 minutes after defrost termination.
  9. After the unit’s defrost thermostat has terminated, check the defrost thermostat for 24 volts between “DFT” and “C”. The reading should indicate 0 volts (open sensor).
  10. Shut off power to unit.
  11. Replace outdoor fan motor lead to terminal “DF2” on defrost board and turn on power.

AIR FLOW MEASUREMENT AND ADJUSTMENT

After reviewing section on DUCTING, proceed with airflow measurements and adjustments. Unit’s blower curves (in Specification Sheets) are based on external static pressure (ESP, in. of W.C.). The duct openings on the unit are considered internal static pressure, so as long as ESP is maintained, the unit will deliver the proper air up to the maximum static pressure listed for the CFM required by the application (i.e. home, building, etc.).
In general 400 CFM per ton of cooling capacity is a rule of thumb. Some applications depending on the sensible and latent capacity requirements may need only 350 CFM or up to 425 CFM per ton. Check condition space load requirements (from load calculations) and equipment expanded ratings data to match CFM and capacity.
After unit is set and ducted, verify ESP with a 1” inclined manometer with pitot tubes or a Magnahelic gauge and confirm CFM to blower curves in the specification sheets. All units have multiple speed blower motors. If factory selected speed is not utilized, the speed tap can be changed. Never run CFM below 350 CFM per ton, evaporator freezing or poor unit performance is possible.
TOTAL EXTERNAL STATIC PRESSURE

  1. Using a digital manometer measure the static pressure of the retum duct at the inlet of the unit (Negative Pressure).Goodman GPHH3 3.5 Ton Horizontal Packaged Air Conditioner - parts6

  2. Measure the static pressure of the supply duct (Positive Pressure).

  3. Add the two readings together.
    NOTE: BOTH READINGS MAY BE TAKEN SIMULTANEOUSLY AND READ DIRECTLY ON THE MANOMETER IF SO DESIRED.

  4. Consult proper table for quantity of air.

If the external static pressure exceeds the minimum or maximum allowable statics, check for closed dampers, dirty filter, undersized or poorly laid out ductwork.
ADJUSTING SPEED TAP FOR INDOOR BLOWER MOTOR
EEM MOTOR
The blower motor speed for the EEM motor is controlled by three 24V low voltage leads: green, yellow, and white. The green lead sets the speed for fan-only mode. The yellow lead sets the speed for cooling and heat pump heating mode (if applicable). The white lead sets the speed for electric heat mode (emergency heat and second stage heat, if applicable).
The leads are factory connected as follows: Green to T1, Yellow to T2, and White to T3. T1 is the low speed setting and is dedicated to fan-only mode. T2 is medium speed cooling and T3 is medium speed heating. T4 is high speed cooling and T5 is high speed heating. To adjust the blower speed, move the yellow and/or white wires to T4 and T5.
NOTE: IF MORE THAN ONE LEAD IS ENERGIZED AT THE SAME TIME, THE MOTOR WILL USE THE HIGHER SPEED SETTING.
NOTE: PCH3 anD PHH3 UNITS ARE RATED FOR A maximum E.S.P. oF 0.8 EXCEPT WHEN USING A 20Kw ELECTRIC HEATER. (THE MAXIMUM STATIC FOR 20 kKW ELECTRIC HEAT Is 0.5 E.S.P.) WHEN THESE UNITS ARE INSTALLED IN THE 0.5 – 0.8 E.S.P. RANGE, THE WHITE LEAD (ELECTRIC HEAT) MUST BE MOVED TO T5 FOR PROPER OPERATION OF THE ELECTRIC HEATERS.
See CFM vs ESP tables in this manual.
Refrigerant Charge Check (Units with Fixed Orifice Devices)
After completing airflow measurements and adjustments the unit’s refrigerant charge must be checked. All package units with fixed orifice devices are charged using the super heat method at the compressor suction line. After superheat is adjusted it is recommended to check unit sub-cooling at the condenser coil liquid line out. For charge adjustments, see superheat and subcooling charts shown for each model.
SUPERHEAT CAN BE DETERMINED AS FOLLOWS:

SUPERHEAT

CHECKING SUPERHEAT
Refrigerant gas is considered superheated whenever its temperature is higher than the saturation temperature corresponding to its pressure. The degree of superheat equals the degrees of temperature increase above the saturation temperature at existing pressure. See Temperature – Pressure Chart.

  1. Run system at least 10 minutes to allow pressure to stabilize.
  2. Temporarily install thermometer on suction (large) line near compressor with adequate contact and insulate for best possible reading.
  3. Refer to the superheat table provided for proper system superheat. Add charge to lower superheat or recover charge to raise superheat.

Superheat Formula = Suct. Line Temp. – Sat. Suct. Temp.

Ambient Condenser Inlet Temp (°F Drybulb) Return Air Temp. (°F Drybulb)
65 70
100
95
90
85
80
75 10
70 10
65 13
60 17

EXAMPLE:
a. Suction Pressure = 143
b. Corresponding Temp. °F. = 50
c. Thermometer on Suction Line = 59°F
To obtain the degrees temperature of superheat, subtract 50.0 from 59.0°F. The difference is 9° Superheat. The 9° Superheat would fall in the * range of allowable superheat.
SUPERHEAT = SUCTION LINE TEMP – SAT. SUCTION TEMP.
SUBCOOLING = SAT. LINE TEMP – LIQUID LINE TEMP.
CHECKING SUBCOOLING
Refrigerant liquid is considered subcooled when its temperature is lower than the saturation temperature corresponding to its pressure. The degree of subcooling equals the degrees of temperature decrease below the saturation temperature at the existing pressure.

  1. Attach an accurate thermometer or preferably a thermocouple type temperature tester to the liquid line close to the pressure switch.
  2. Install a high side pressure gauge on the liquid access fitting.
  3. Record the gauge pressure and the temperature of the line.
  4. Compare the hi-pressure reading to the “Required Liquid Line Temperature” chart. Find the hi-pressure value on the left column. Follow that line right to the column under the design subcooling value. Where the two intersect is the required liquid line temperature. Alternately you can convert the liquid line pressure gauge reading to temperature by finding the gauge reading in Temperature – Pressure Chart and reading to the left, find the temperature in the °F. Column.
  5. The difference between the thermometer reading and pressure to temperature conversion is the amount of subcooling.

Subcooling Formula = Sat. Liquid Temp. – Liquid Line Temp.
EXAMPLE:
a. Liquid Line Pressure = 417
b. Corresponding Temp. °F. = 120°
c. Thermometer on Liquid line = 109°F.
To obtain the amount of subcooling, subtract 109°F from 120°F. The difference is 11° subcooling. See the specification sheet or technical information manual for the design subcooling range for your unit.

*PC

Design superheat @ 95 °F outdoor ambient temperature
Models| Superheat ± 2°F
PCH32441| 12
PCH33041| 12
PCH33641| 9
PCH34241| 12
PCH34841| 6
PCH36041| 8
*PH

Design superheat @ 95 °F outdoor ambient temperature
Models| Superheat ± 2°F
PHH32441| 5
PHH33041| 5
PHH33641| 6
PHH34241| 7
PHH34841| 12
PHH36041| 8

ELECTRIC HEAT INSTALLATION & ADJUSTMENT

This series of electric cooling and heat pump package equipment is designed to accept a field installed electric heat kit. The unit is equipped to easily install the HKR/HKP Series Electric Heat Kit. Full Installation Instructions are included in this kit. Please use this document for guidance in field equipping the package unit with electric heat.
Choose the heat kit that fits the application for the specific installation. Permanently mark the unit’s nameplate with the model being installed. High and low voltage connections are detailed in the heat kit instructions.
Indoor Blower motor speed tap selection may need to be modified to accommodate normal continuous operation to prevent a nuisance trip.
See following table.

PCH/PHH3(24-60) Models (0 – 0.5 E.S.P.)

Unit Model Number| Electric Heat KW
5| 8| 10| 15| 20
[PCH/PHH]32441| T3| T3| T3| NA| NA
[PCH/PHH]33041
| T3| T3| T3| s| NA
[PCH/PHH]33641| T3| T3| T3| s| NA
[PCH/PHH]34241
| T3| T3| T3| s| s
[PCH/PHH]34841| T3| T3| T3| iS5| T3
[PCH/PHH]36041
| T3| T3| T3| TS| T3
PCH/PHH3(24-60) Models (0.5-0.8 E.5.P.)

Unit Model Number| Electric Heat KW
5| 8| 10| 15| 20
[PCH/PHH]32441| TS| TS| TS| TS| NA
[PCH/PHH]33041
| T5| T5| T5| s| NA
[PCH/PHH]33641~| T5| T5| T5| TS| NA
[
PCH/PHH]34241| T5| T5| T5| s| NA
[PCH/PHH]34841| T5| T5| T5| TS| NA
[PCH/PHH]36041
| T5| T5| T5| TS| NA

T1 – Fan Only, T2 – Normal Speed Cooling T3 – Normal Speed Heating T4 – High Speed Cooling, T5 – High Speed Cooling

MAINTENANCE

WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

The Self Contained Package Air Conditioner and Heat Pump should operate for many years without excessive service calls if the unit is installed properly. However it is recommended that the homeowner inspect the unit before a seasonal start up. The coils should be free of debris so adequate airflow is achieved. The return and supply registers should be free of any obstructions. The filters should be cleaned or replaced. These few steps will help to keep the product up time to a maximum. The Troubleshooting Chart
(on page 16) should help in identifying problems if the unit does not operate properly.

SERVICE

THE FOLLOWING INFORMATION IS FOR USE BY QUALIFIED SERVICE AGENCY ONLY: OTHERS SHOULD NOT ATTEMPT TO SERVICE THIS EQUIPMENT.
Common Causes of Unsatisfactory Operation of Heat Pump on the Heating Cycle.

Inadequate Air Volume Through Indoor Coil
When a heat pump is in the heating cycle, the indoor coil is functioning as a condenser. The return air filter must always be clean, and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure, and high pressure cut out.
Outside Air Into Return Duct
Do not introduce cold outside air into the return duct of a heat pump installation. Do not allow air entering the indoor coil to drop below 65°F. Air below this temperature will cause low discharge pressure, thus low suction pressure, and excessive defrost cycling resulting in low heating output. It may also cause false defrosting.
Undercharge
An undercharged heat pump on the heating cycle will cause low discharge pressure resulting in low suction pressure and frost accumulation on the outdoor coil.
Poor “Terminating” Sensor Contact
The unit’s defrost terminating sensor must make good thermal contact with the outdoor coil tubing. Poor contact may not terminate the unit’s defrost cycle quickly enough to prevent the unit from cutting out on high discharge pressure.

Malfunctioning Reversing Valve
This may be due to:

  1. Solenoid not energized – In order to determine if the solenoid is energized, touch the nut that holds the solenoid cover in place with a screwdriver. If the nut magnetically holds the screwdriver, the solenoid is energized and the unit is in the cooling cycle.
  2. No voltage at unit’s solenoid – Check unit voltage. If no voltage, check wiring circuit.
  3. Valve will not shift:
    a. Undercharged – check for leaks;
    b. Valve Body Damaged – Replace valve;
    c. Unit Properly Charged – If it is on the heating cycle, raise the discharge pressure by restricting airflow through the indoor coil. If the valve does not shift, tap it lightly on both ends with a screwdriver handle. Do Not Tap The Valve Body. If the unit is on the cooling cycle, raise the discharge pressure by restricting airflow through the outdoor coil. If the valve does not shift after the above attempts, cut the unit off and wait until the discharge and suction pressure equalize, and repeat above steps. If the valve does not shift, replace it.

PCH/PHH3[24-36]41 BLOWER PERFORMANCE
PCH/PHH3[24-36]41 BLOWER PERFORMANCE

Model Speed Volts E.S.P. (In. of H,0)
0.1 0.2 0.3 0.4
*PCH32441** T1 230 CFM
Watts 74 85 96
T2/T3 230 CFM 922
Watts 74 85 96
T4/T5 230 CFM 1231
Watts 168 180 193
*PHH32441** T1 230 CFM
Watts 69 80 91
T2/T3 230 CFM 1057
Watts 112 123 135
T4/T5 230 CFM 1224
Watts 158 170 180
*PCH33041** T1 230 CFM
Watts 97 109 122
T2/T3 230 CFM 1123
Watts 123 136 148
T4/T5 230 CFM 1462
Watts 241 253 266
*PHH33041** T1 230 CFM
Watts 91 102 114
T2/T3 230 CFM 1190
Watts 147 159 170
T4/T5 230 CFM 1396
Watts 221 233 244
*PCH33641** T1 230 CFM
Watts 132 144 156
T2/T3 230 CFM 1261
Watts 131 144 157
T4/T5 230 CFM 1577
Watts 277 290 302
*PHH33641** T1 230 CFM
Watts 132 144 156
T2/T3 230 CFM 1364
Watts 213 225 237
T4/T5 230 CFM 1543
Watts 284 296 308

PCH/PHH3[42-60]41 BLOWER PERFORMANCE
PCH/PHH3[42-60]41 BLOWER PERFORMANCE

Model Speed Volts E.S.P. (In. of H,0)
0.1 0.2 0.3 0.4
*PHH36041** T1 230 CFM
Watts 146 158 174
T2/T3 230 CFM 1410
Watts 222 236 250
T4/T5 230 CFM 1637
Watts 331 348 361
*PCH36041** T1 230 CFM
Watts 118 130 142
T2/T3 230 CFM 1441
Watts 246 258 271
T4/T5 230 CFM 1610
Watts 321 332 344
*PHH34841** T1 230 CFM
Watts 179 190 203
T2/T3 230 CFM 1711
Watts 330 341 358
T4/T5 230 CFM 2002
Watts 498 521 516
*PCH34841** T1 230 CFM
Watts 179 190 203
T2/T3 230 CFM 1785
Watts 381 394 407
T4/T5 230 CFM 2002
Watts 498 521 516
*PHH34241** T1 230 CFM
Watts 168 175 183
T2/T3 230 CFM 1793
Watts 363 371 379
T4/T5 230 CFM 1919
Watts 449 457 465
*PCH34241** T1 230 CFM
Watts 168 175 183
T2/T3 230 CFM 1931
Watts 449 457 462
T4/T5 230 CFM 2013
Watts 502 511 523

NOTES

  1. Data shown is dry coil. Wet coil pressure drop is approx
  2. Data shown does not include fiter pressure drop, approx. 0.08″ H20.
  3. Reduce airflow by 2% for 208V operation

TROUBLESHOOTING CHART

WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

PACKAGE UNITS – HEAT PUMP AND AC UNITS
HOMEOWNER’S RouTINE MAINTENANCE RECOMMENDATIONS We strongly recommend a bi- annual maintenance checkup be performed by a qualified service agency before the heating and cooling seasons begin.

WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. REPLACE OR CLEAN FILTER
IMPORTANT NOTE: NEVER OPERATE UNIT WITHOUT A FILTER INSTALLED AS DUST AND LINT WILL BUILD UP ON INTERNAL PARTS RESULTING IN LOSS OF EFFICIENCY, EQUIPMENT DAMAGE AND POSSIBLE FIRE.
A RETURN AIR FILTER IS NOT SUPPLIED WITH THIS UNIT; HOWEVER, THERE MUST BE A MEANS OF FILTERING THE RETURN AIR. AN INDOOR AIR FILTER MUST BE USED WITH YOUR COMFORT SYSTEM. A PROPERLY MAINTAINED FILTER WILL KEEP THE INDOOR COIL OF YOUR COMFORT SYSTEM CLEAN. A DIRTY COIL COULD CAUSE POOR OPERATION AND/OR SEVERE EQUIPMENT DAMAGE.

The installer of your unit can tell you where your filter(s) are and how to clean or replace them.
Check your return filter(s) at least once every two months.
When they are dirty, replace or clean as required. Disposable type filters should be replaced. Reusable type filters may be cleaned.
NOTE: REUSABLE TYPE FILTERS SHOULD BE WASHED WITH WARM WATER, DRIED COMPLETELY AND SPRAYED WITH AN ADHESIVE ACCORDING TO THE MANUFACTURERS RECOMMENDATIONS.
You may want to ask your dealer about high efficiency filters. High efficiency filters are available in both electronic and non-electronic types. These filters can do a better job of catching small airborne particles.
Improper filter maintenance is the most common cause of inadequate heating or cooling performance. Filters should be cleaned (permanent) or replaced (disposable) every two months or as required. When replacing a filter, it must be
replaced with a filter of the same type and size and always make certain the air flow arrows on the filter point in the proper direction.
CONDENSER AND EVAPORATOR MoOTORS
The bearings on the air circulating blower motor and condenser motor are permanently lubricated and require no further lubrication.
COMPRESSOR
The compressor motor is hermetically sealed and does not require additional oiling.

ALumiNum INDOOR CoiL CLEANING (QUALIFIED SERVICER ONLY)
This unit is equipped with an aluminum tube evaporator coil. The safest way to clean the evaporator coil is to simply flush the coil with water. This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum tube residential cooling coils.
An alternate cleaning method is to use one of the products listed in the technical publication TP-109 (shipped in the literature bag with the unit) to clean the coils. The cleaners listed are the only agents deemed safe and approved for use to clean round tube aluminum coils. TP-109 is available on the web site in Partner Link > Service Toolkit.
NOTE: ENSURE COILS ARE RINSED WELL AFTER USE OF ANY CHEMICAL CLEANERS.
ANNUAL INSPECTION (QUALIFIED SERVICER ONLY)
Your package unit should be inspected by a qualified installer, or service agency at least twice every year. This check should be performed before the heating and cooling seasons begin. This will ensure that the system is performing properly and safely. Repair as necessary.

  • Check physical support of the unit. Ensure it is sound without any sagging, cracks, or gaps, around the base.
  • Check for obvious signs of deterioration of the unit.
  • Check both condenser and evaporator coil to make sure each are clean.
  • Return Air Connection. Check for physical soundness and ensure that the connection is firmly sealed to the package unit casing.
  • Wiring. Check wires for damage. Check electrical connections for tightness and/or corrosion.
  • Filters. Check that filters are clean and in the proper placement in the unit or duct system.
  • Louvers. Inspect air inlet louvers inside the heat exchanger compartments. Ensure the area is clean and free of dirt and debris.

BEFORE CALLING YOUR SERVICER

  • Check the thermostat to confirm that it is properly set.
  • Check the disconnect switch near the unit to confirm thatitis closed.
  • Check the electrical panel for tripped circuit breakers or failed fuses. Reset the circuit breakers or replace fuses as necessary.
  • Check for blockage of the indoor air inlets and outlets.
  • Confirm that they are open and have not been blocked by objects (rugs, curtains or furniture).
  • Check for obstructions on the unit. Confirm that it has not been covered on the sides or the top. Remove any obstruction that can be safely removed. If the unit is covered with dirt or debris, call a qualified servicer to clean it.
  • Check the filter. If it is dirty, clean or replace it.

START-UP CHECKLIST

Goodman GPHH3 3.5 Ton Horizontal Packaged Air Conditioner -
parts7

THIS PAGE IS LEFT INTENTIONALLY BLANK.

CUSTOMER FEEDBACK
We are very interested in all product comments. Please fill out the feedback form on one of the following links:
Goodman® Brand Products: (http://www.goodmanmfg.com/about/contact-us).
Amana® Brand Products: (http://www.amana-hac.com/about-us/contact-us).
You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page.

|
---|---

<https://www.goodmanmfg.com/about/contact-us>

|

<http://www.amana-hac.com/about-us/contact-us>  

PRODUCT REGISTRATION
Thank you for your recent purchase. Though not required to get the protection of the standard warranty, registering your product is a relatively short process, and entitles you to additional warranty protection, except that failure by California and Quebec residents to register their product does not diminish their warranty rights.
For Product Registration, please register as follows:
Goodman® Brand products: (https://www.goodmanmfg.com/product-registration).
Amana® Brand products: (http://www.amana-hac.com/product-registration).
You can also scan the QR code on the right for the product brand you purchased to be directed to the Product Registration page.

Goodman GPHH3 3.5 Ton Horizontal Packaged Air Conditioner - QR
code3|
---|---

<https://www.goodmanmfg.com/product-registration>

|

<http://www.amana-hac.com/product-registration>  

Goodman GPHH3 3.5 Ton Horizontal Packaged Air Conditioner - QR
codeIOG-3022~IOG-3022~072021~8
All information contained herein is subject to change without notice.
19001 Kermier Rd. Waller, TX 77484
www.goodmanmfg.com
www.amana-hac.com
© 2021 Goodman Manufacturing Company, L.P.
Amana- registered trademark of Maytag Corporation o s related companies and is used under license. All ights reserved

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals