HYPERLITE CES-LS-HERO-100W UFO LED High Bay Light Instruction Manual

June 14, 2024
HYPERLITE

HYPERLITE CES-LS-HERO-100W UFO LED A0

RELIABLE SOLID BRIGHT

LED HIGH BAY LIGHT

HERO Series

Certification:

FEATURES & SPECIFICATIONS

Performance Data

| CES-LS-HERO-100W| CES-LS-HERO-150W| CES-LS-HERO-200W| CES- LS-HERO-250W
---|---|---|---|---
General| Lumens| 14000 lm| 21000 lm| 28000 lm|

35000 lm

Efficacy

| 140 lm/W
CCT|

4000K, 5000K

Beam angle

| 120°
CRI|

80

Life span

| >50,000 hours
Color finish|

Black, White

Electrical

|

Power

| 100W| 150W| 200W| 250W
Input voltage|

AC120-277V

Dimming

| 1 – 10V
Power factor|

0.9

Temperature

| -22°F-113°F(-30°C to 45°C) |

-22°F-104°F(-30°C to 40°C)

Physical & Listing

|

Compatible accessories

|

1-10V Dimmer, Reflector (Need additional purchase)

Mounting

|

Hook

Listing

| UL, cUL
IP rating|

IP 65

Warranty

|

5 Years

PACKAGING INFORMATION

Model

| Wattage| Qty/Ctn| Net Weight| Gross Weight| CTN Size
---|---|---|---|---|---
CES-LS-HERO-100W| 100W| 1| 5.2 ± 1 lbs| 6.4 ± 1 lbs|

11.8″11.8″7.1″

CES-LS-HERO-150W

|

150W

|

7.7 ± 1 lbs

|

9.8 ± 1 lbs

|

13.0″13.0″7.6″

CES-LS-HERO-200W

|

200W

|

9.0 ± 1 lbs

|

10.4 ± 1 lbs

CES-LS-HERO-250W

|

250W

120° DISTRIBUTION

100W/14000lm 53.0fc

| 150W/21000lm 76.7fc| 200W/28000lm 101.2fc| 250W/35000lm 141.3fc| 10ft
---|---|---|---|---
100W/14000lm 13.2fc| 150W/21000lm 19.1fc| 200W/28000lm 25.3fc| 250W/35000lm 35.3fc|

20ft

100W/14000lm 7.4fc

| 150W/21000lm 11.7fc| 200W/28000lm 14.2fc| 250W/35000lm 19.9fc| 26ft
100W/14000lm 4.3fc| 150W/21000lm 6.6fc| 200W28000lm 8.2fc| 250W35000lm 12.7fc|

33ft

100W/14000lm 2.3fc

| 150W/21000lm 3.3fc| 200W/28000lm 4.2fc| 250W/35000lm 6.5fc|

46ft

HYPERLITE LED Luminaire

Industrial LED High Bay Lighting

(HERO Series)

Features
  • UL&CUL No E483348 Suitable for Wet Locations.
  • IP65 Rated Ingress Protection.

ATTENTION

BEFORE YOU INSTALL
Read these instructions completely and carefully

WARNING

RISK OF ELECTRIC SHOCK

  • Turn power off before inspection, installation or removal.
  • Properly ground electrical enclosure.
  • Follow all NEC and local codes.
  • Use only UL or IEC approved wire for input/output connections.

Save These Instructions

Use only in the manner intended by the manufacturer.
If you have any questions, contact the manufacturer.

Prepare Electrical Wiring

Electrical Requirements
The LED driver must be supplied with 120-277 VAC, 50/60 Hz per product label and connected to an individual properly grounded branch circuit, protected by a 15 or 20 ampere circuit breaker.

Grounding Instructions
The grounding and bonding of the overall system shall be done in accordance with National Electric Code (NEC) Article 600 and local codes.

Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

HYPERLITE CES-LS-HERO-100W UFO LED A6

  1. Wall
  2. Drill the hole
  3. Expansion screw & Hook
  4. Chain
  5. Hook
  6. Lamp
  7. Fix the hook
  8. Connect
  9. Dimming
  10. (Pink) DIM-
  11. (Purple) DIM+
INSTALLATION

1. Please check that the plug is in good condition. Install the lamp and plug it into the socket. Than you can test the light fixture.

2.Please connect the input wire in correct way, Black or Brown wire is L, White or Blue wire is N, Green or Green-yellow wire is ground connection. Please also make sure the wire connection is fixed perfectly before using.

Suspension Mounting

Announcements:

  1. This equipment is only for professional installation. Non-professional personnel shall not remove or install the equipment.
  2. Please read the instruction manual before installation and keep it for future reference.
  3. To avoid damage, falling, electric shock or fire, please do not modify the lamp or replace accessories without confirming with the supplier.
  4. Maintenance/installation and replacement the lamps , please confirm to cut off the power supply, and the lamps have set up a cooling. Please make sure the lamps and has been properly installed before processing power.
  5. Ensure the accurate and reliable connection.
  6. Ensure that the product around the vent, the lamp cannot violate any fire prevention regulations when using.

▲ Working Environment

▲ Warehouse

FOOTCANDLE LIGHT GUIDE

Footcandles are the most common unit of measure used by lighting professionals to calculate light levels in businesses and outdoor spaces. A footcandle is defined the illuminance on a one square foot surface from a uniform source of light. The Illuminating Engineering Society (IES) recommends the following footcandle levels to ensure adequate illumination and safety for occupants. Below is a guideline for common areas to assist in achieving appropriate light levels with the greatest energy-effciency.

Building Area & Task| Average Maintained Footcandles (Horizontal) (FC)| Range of Maintained Footcandles (Horizontal) (FC)| Average Maintained Footcandles (Vertical) (FC)| Range of Maintained Footcandles (Vertical) (FC)| Comments
---|---|---|---|---|---
WAREHOUSING & STORAGE
Bulky Items—Large Labels| 10| | 5| |
Small Items—Small Labels| 30| | 15| |
Cold Storage| 30-40| 10-30| 10| 5-15|
Open Warehouse| 30-40| 10-30| | |
Warehouse w/Aisles| 30-40| 10-30| 10| 5-15|
COMMERCIAL OFFICE
Open Office | 40| 30-50| | | @30” Above Finished Floor (AFF)
Private Office | 40| 30-50| | | @30” AFF
Conference Room| 30| | | | Matte surface reflectance for the table 40% recommended
Restroom| 18| 75-30| | |
Lunch & Break Room| 15| 5-20 | | |
EDUCATIONAL (SCHOOLS)
Classroom| 40| 30-50| | | @30” AFF
Gymnasium| | | | |
Class I (Pro or Div. 1 College) | 125| | 30| |
Class II (Div. 2 or 3 College) | 80| | 20| |
Class III (High School)| 50| | 150| |
Class IV (Elementary)| 30| | 100| |
Auditorium| 75| 3-10| 5| 2.5-10|
Corridor| 25| 10-40| | |

▲ This guide is a collaborative effort of Energy Trust of Oregon and the Lighting Design Lab, Seattle, Washington.

Building Area & Task| Average Maintained Footcandles (Horizontal) (FC)| Range of Maintained Footcandles (Horizontal) (FC)| Average Maintained Footcandles (Vertical) (FC)| Range of Maintained Footcandles (Vertical) (FC)| Comments
---|---|---|---|---|---
INDUSTRIAL/MANUFACTURING
Assembly| | | | |
Simple (Large Item)| 30| | 15| 15-60|
Difficult (fine) | 100| 10-30| 10| 50-200|
Component Manufacturing| | | | |
Large| 30| 10-30| 30| 15-60|
Medium| 70-80| 25-100| 50| 25-100|
EXTERIOR
Parking (Covered)| 5| | | | 1FC min, 10:1 Max to Min Uniformity
Parking (Open) (Medium Activity)| | | | |
Lighting Zone 3 (Urban)| 1.5| 75-3| 0.8| 0.4-1.6|
Lighting Zone 2 (suburban)| 1| 0.5-2| 0.6| 0.3-1.2|
Gas Station Canopy| 12.5| 10-15| | |
Safety (Building Exterior)| 1| 0.5-2| | | If security is an issueraise average level to 3
RETAIL
General Retail (Ambient)| | 50| | |
Department Store| 40| 220-80| 15| 7.5-30|
Perimeter| | | 75| 35-150|
Accent Lighting (Displays) | | | | | 3-10 times greater than ambient light levels
AUTOMOTIVE
Showroom| 70-80| 25-100| 10| 7.5-30|
Service Area| 50| 25-10| 30| 15-30|
Sales Lot (Exterior)| | | | |
Lighting Zone 3 (Urban) | 20| 10-40| 20| 10-40|
Lighting Zone 2 (Suburban) | 15| 7..5-30| 15| 7.5-30|
GROCERY
Circulation| 20| 10-40| 7.5| 3.5-15|
General Retail| 70-80| 25-100| 20| 10-40|
Perimeter| | | 50| 25-100|
BANKING
ATM| 20| 10-40| 15| | Vertical at face of ATM

NOTES:

  • This guide is based on information gathered from the IES ‘The Lighting Handbookʼ 10th Edition. It is highly recommended that all lighting professionals refer to the full IES guide when specifying lighting projects.
  • At least half of users are in the 25 – 65 age range .
  • Horizontal—horizontal plane that average maintained foot-candles are measured.
  • Vertical—vertical plane the average maintained foot-candles are measured.
  • It is the responsibility of the to determine and provide appropriate lighting levels for each space.
WIRING DIAGRAM OF DIMMER

Dimmer Without Load
The light power supply is not powered by dimmer, This kind of connection mode is dimmer without load, which don’t need to consider load power and load current, only need to consider less than effective optical current 200mA. According to each 0/1-10v adjustable light power signal current of 10mA conservative estimates there are up to 20 dimming power sources can be connected in parallel.

HYPERLITE CES-LS-HERO-100W UFO LED A8a

  1. AC 120-277V
  2. Pink DIM-
  3. Purple DIM+
  4. DIMMER 1-10V or 0-10V

Dimmer With Load

  1. The light power supply is powered by the dimmer. The light is the load of the dimmer power supply. It is necessary to consider the load power and load current. The maximum effective load of the dimmer is 800W and the current is 10A.
  2. When Ac120-277V input, effective power is 800W, current is 10A; When Ac120-277V input Effective power is 400W, current is 10A.
  3. The following is the number of dimmable power supply in parallel of two input voltages.
    – When Ac120-277V input: 800W/100W=8pcs, 10A/2A=5pcs, take the minimum value, so it can Parallel 5 dimming power supply.
    – When Ac120-277V input: 400W/100W=4pcs, 10A/2A=5pcs, take the minimum value, so it can Parallel 4 dimming power supply.

HYPERLITE CES-LS-HERO-100W UFO LED A8b

  1. Pink DIM
  2. Purple DIM+
  3. AC120-277V
  4. DIMMER 1-10V or 0-10V

LED High Bay Light

| |
---|---|---
Hero Black Series| Hero White Series|

Radar Series

| |
Saturn Series| Saturn Series|

Ray Series

LED Wall Pack Light

| |
---|---|---
Space Series| Oval Series|

Wall. E Series

LED Area Light

| LED Canopy Light| LED Flood Light
---|---|---
| |

Hope Series

| Vega Series| Mars Series
LED Grow Light| Vapor Tight Light|

Temporary Work Light

| |
Groplanner O Series| Capsule Series|

Hive Series

More products…

A good & brand new product. Congrats! Enjoy brighter life now.

Feel free to contact us
Email: service@hi-hyperlite.com
Toll-free number: +1(855) 688 7879

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals