DELTA DPM-D510 Din Rail Power Meter User Manual

June 14, 2024
Delta

DPM-D510 Din Rail Power Meter

Delta Din-rail Power Meter DPM-D510 User Manual

Specifications

  • Model: DPM-D510
  • Version: 2nd
  • Revision Date: 2023/5/23

Chapter 1: Product Introduction

1.1 Preface

Welcome to the Delta Din-rail Power Meter DPM-D510 User Manual.
This manual provides detailed information on the usage and features
of the DPM-D510.

1.2 Overview

The Delta Din-rail Power Meter DPM-D510 is a high-quality power
meter designed for industrial automation applications. It provides
accurate measurement and monitoring of electrical parameters such
as voltage, current, power, energy, and frequency.

1.3 Safety Precautions

Before using the DPM-D510, please read and follow these safety
precautions:

  • Ensure that the power supply is disconnected before installing
    or servicing the power meter.

  • Do not touch any live electrical components while the power
    meter is connected.

  • Use only the specified power supply voltage and current.

  • Do not expose the power meter to extreme temperatures or
    humidity.

  • Do not use the power meter in explosive or hazardous
    environments.

Chapter 2: Installation

2.1 Mounting

To mount the DPM-D510, follow these steps:

  1. Select a suitable location on the DIN rail to mount the power
    meter.

  2. Slide the power meter onto the DIN rail until it clicks into
    place.

  3. Ensure that the power meter is securely mounted and does not
    move or wobble.

2.2 Wiring

To wire the DPM-D510, follow these steps:

  1. Turn off the power supply to the electrical circuit.

  2. Connect the appropriate wires to the input terminals of the
    power meter.

  3. Tighten the terminal screws to secure the wires in place.

  4. Double-check the wiring connections to ensure they are correct
    and secure.

Chapter 3: Operation

3.1 Power On

To power on the DPM-D510, follow these steps:

  1. Ensure that the power supply to the electrical circuit is
    turned on.

  2. Press the power button on the front panel of the power
    meter.

  3. The display will light up, indicating that the power meter is
    powered on and ready for operation.

3.2 Measurement Display

The DPM-D510 provides a clear and easy-to-read display of the
measured electrical parameters. The display shows values such as
voltage, current, power, energy, and frequency in real-time.

FAQ

Q: Can I use the DPM-D510 in outdoor environments?

A: No, the DPM-D510 is not designed for outdoor use. It should
be installed in a protected indoor environment.

Q: How do I reset the power meter to factory settings?

A: To reset the DPM-D510 to factory settings, press and hold the
reset button on the front panel for 5 seconds. This will restore
all settings to their default values.

Industrial Automation Headquarters
Taiwan: Delta Electronics, Inc. Taoyuan Technology Center No.18, Xinglong Rd., Taoyuan District, Taoyuan City 33068, Taiwan TEL: +886-3-362-6301 / FAX: +886-3-371-6301

Asia
China: Delta Electronics (Shanghai) Co., Ltd. No.182 Minyu Rd., Pudong Shanghai, P.R.C. Post code : 201209 TEL: +86-21-6872-3988 / FAX: +86-21-6872-3996 Customer Service: 400-820-9595
Japan: Delta Electronics (Japan), Inc. Industrial Automation Sales Department 2-1-14 Shibadaimon, Minato-ku Tokyo, Japan 105-0012 TEL: +81-3-5733-1155 / FAX: +81-3-5733-1255
Korea: Delta Electronics (Korea), Inc. 1511, 219, Gasan Digital 1-Ro., Geumcheon-gu, Seoul, 08501 South Korea TEL: +82-2-515-5305 / FAX: +82-2-515-5302
Singapore: Delta Energy Systems (Singapore) Pte Ltd. 4 Kaki Bukit Avenue 1,

05-04, Singapore 417939 TEL: +65-6747-5155 / FAX: +65-6744-9228

India: Delta Electronics (India) Pvt. Ltd. Plot No.43, Sector 35, HSIIDC Gurgaon, PIN 122001, Haryana, India TEL: +91-124-4874900 / FAX: +91-124-4874945
Thailand: Delta Electronics (Thailand) PCL. 909 Soi 9, Moo 4, Bangpoo Industrial Estate (E.P.Z), Pattana 1 Rd., T.Phraksa, A.Muang, Samutprakarn 10280, Thailand TEL: +66-2709-2800 / FAX: +66-2709-2827
Australia: Delta Electronics (Australia) Pty Ltd. Unit 2, Building A, 18-24 Ricketts Road, Mount Waverley, Victoria 3149 Australia Mail: IA.au@deltaww.com TEL: +61-1300-335-823 / +61-3-9543-3720
Americas
USA: Delta Electronics (Americas) Ltd. 5101 Davis Drive, Research Triangle Park, NC 27709, U.S.A. TEL: +1-919-767-3813 / FAX: +1-919-767-3969
Brazil: Delta Electronics Brazil Ltd. Estrada Velha Rio-São Paulo, 5300 Eugênio de Melo – São José dos Campos CEP: 12247-004 – SP – Brazil TEL: +55-12-3932-2300 / FAX: +55-12-3932-237
Mexico: Delta Electronics International Mexico S.A. de C.V. Gustavo Baz No. 309 Edificio E PB 103 Colonia La Loma, CP 54060 Tlalnepantla, Estado de México TEL: +52-55-3603-9200

EMEA
EMEA Headquarters: Delta Electronics (Netherlands) B.V. Sales: Sales.IA.EMEA@deltaww.com Marketing: Marketing.IA.EMEA@deltaww.com Technical Support: iatechnicalsupport@deltaww.com Customer Support: Customer- Support@deltaww.com Service: Service.IA.emea@deltaww.com TEL: +31(0)40 800 3900
BENELUX: Delta Electronics (Netherlands) B.V. Automotive Campus 260, 5708 JZ Helmond, The Netherlands Mail: Sales.IA.Benelux@deltaww.com TEL: +31(0)40 800 3900
DACH: Delta Electronics (Netherlands) B.V. Coesterweg 45, D-59494 Soest, Germany Mail: Sales.IA.DACH@deltaww.com TEL: +49(0)2921 987 0
France: Delta Electronics (France) S.A. ZI du bois Challand 2, 15 rue des Pyrénées, Lisses, 91090 Evry Cedex, France Mail: Sales.IA.FR@deltaww.com TEL: +33(0)1 69 77 82 60
Iberia: Delta Electronics Solutions (Spain) S.L.U Ctra. De Villaverde a Vallecas, 265 1º Dcha Ed. Hormigueras ­ P.I. de Vallecas 28031 Madrid TEL: +34(0)91 223 74 20
Carrer Llacuna 166, 08018 Barcelona, Spain Mail: Sales.IA.Iberia@deltaww.com
Italy: Delta Electronics (Italy) S.r.l. Via Meda 2­22060 Novedrate(CO) Piazza Grazioli 18 00186 Roma Italy Mail: Sales.IA.Italy@deltaww.com TEL: +39 039 8900365
Russia: Delta Energy System LLC Vereyskaya Plaza II, office 112 Vereyskaya str. 17 121357 Moscow Russia Mail: Sales.IA.RU@deltaww.com TEL: +7 495 644 3240
Turkey: Delta Greentech Elektronik San. Ltd. Sti. (Turkey) erifali Mah. Hendem Cad. Kule Sok. No:16-A 34775 Ümraniye ­ stanbul Mail: Sales.IA.Turkey@deltaww.com TEL: + 90 216 499 9910
MEA: Eltek Dubai (Eltek MEA DMCC) OFFICE 2504, 25th Floor, Saba Tower 1, Jumeirah Lakes Towers, Dubai, UAE Mail: Sales.IA.MEA@deltaww.com TEL: +971(0)4 2690148

*We reserve the right to change the information in this catalogue without prior notice.

DPM-093BF20-02 2023/5/23

Digitized Automation for a Changing World
Delta Din-rail Power Meter DPM-D510 User Manual
www.deltaww.com

Delta Din-rail Power Meter DPM-D510 User Manual

Version 1st 2nd

Revision History
Revision The first version was published. Update the specification table in chapter 2.

Date 2022/12/28 2023/5/23

Delta Din-rail Power Meter DPM-D510 User Manual
Table of Contents
Chapter 1 Product Introduction 1.1 Preface …………………………………………………………………………………. 1-2 1.2 Overview ………………………………………………………………………………. 1-2 1.3 Safety Precautions…………………………………………………………………..1-3
Chapter 2 Product Specifications 2.1 Electrical characteristics …………………………………………………………… 2-2 2.2 Communications Specifications ………………………………………………….. 2-3 2.3 Operating the Display………………………………………………………………..2-4
2.1.1 Menu Tree ………………………………………………………………………… 2-5 2.4 Dimensions …………………………………………………………………………….. 2-7
Chapter 3 Installation 3.1 Installation ……………………………………………………………………………. 3-2
3.1.1 Installation Environment ………………………………………………………. 3-2 3.1.2 Danger ……………………………………………………………………………. 3-2 3.1.3 Installation Notes ……………………………………………………………….. 3-6 3.2 Basic Checks ………………………………………………………………………….. 3-7 3.3 Wiring……………………………………………………………………………………3-8 3.3.1 Wiring Diagrams ………………………………………………………………… 3-8 3.3.2 Communication Characteristics……………………………………………… 3-10
Chapter 4 Operation 4.1 General Operation ……………………………………………………………………. 4-2
4.1.1 Read Measurement Data ………………………………………………………. 4-2 4.2 Setups ……………………………………………………………………………………. 4-3
i

4.2.1 Password Setup (PASS) ……………………………………………………….. 4-3 4.2.2 Communication Setup (COM)…………………………………………………. 4-4 4.2.3 Wiring Type (tyPE) ……………………………………………………………… 4-6 4.2.4 VT and CT Setup (VT CT) ……………………………………………………… 4-6 4.2.5 Reset (rSt) ………………………………………………………………………. 4-8 4.2.6 Edit Password (PCHG) …………………………………………………………. 4-9 4.2.7 Meter Information (INFO) …………………………………………………….. 4-9 Chapter 5 Parameters and Funcitons 5.1 Overview of Parameters……………………………………………………………. 5-2 5.2 Modbus Protocol ……………………………………………………………………… 5-7 5.2.1 Supported Modbus Function Code …………………………………………… 5-7 5.2.2 Modbus Communication Protocol …………………………………………….. 5-8 Chapter 6 Error Codes 6.1 Error Codes……………………………………………………………………………. 6-2 Appendix A Accessories A.1 DCTMC Series ………………………………………………………………………….. A-2 A.2 DCTCS Series……………………………………………………………………………A-3 A.3 DCT1000 Series ……………………………………………………………………….. A-4 A.4 DCT2000 Series ……………………………………………………………………….. A-6
ii

1
Chapter1 Product Introduction
Table of Contents
1.1 Preface …………………………………………………………………………………… 1-2 1.2 Overview ………………………………………………………………………………… 1-2 1.3 Safety Precautions …………………………………………………………………… 1-3
1-1

_1

Delta Din-rail Power Meter DPM-D510 User Manual
1.1 Preface
Thank you for choosing this product. This manual provides installation instructions for the DPM-D510 power meter. The multifunction power meter DPM-D510 is an obvious choice for any application in terms of power monitoring and control for sectors such as power system, industrial mining supply company, and public facility. Before using the meter, read this manual carefully to ensure proper use of this meter. After reading the manual, keep it in a convenient location for quick reference. Before you finish reading this manual, observe the following notes. The installation environment must be free of water vapor, corrosive and flammable gas. Follow the instructions on the diagram in this manual for wiring the device. Grounding must be performed correctly and properly according to provisions for related electric work
regulations currently effective in the country. Do not disassemble the meter or alter its wiring when the power is on. When the power is on, do not touch the terminal area to avoid electric shock.
If you still experience issues when using the device, please contact your distributor or our customer service center. As the product is updated and improved, changes to the specifications will be included in the newest version of the manual which you can get by contacting your distributor or downloading it from the Delta Electronics website (http://www.delta.com.tw/ia/).
1.2 Overview
DPM-D510

1-2

Chapter 1 Product Introduction
1.3 Safety Precautions
Installation Notes Install the power meter according to instructions on the manual. Use appropriate personal protective equipment (PPE) and follow safe electrical work practices. Only qualified electrical workers should install this equipment. Such work should be performed only after reading the entire set of installation instructions. Operate the power meter according to instructions on the manual. Neglecting fundamental installation requirements may lead to personal injury as well as damage to electrical equipment or other property. This equipment should be installed in a suitable insulated and fireproof enclosure.
Operation Notes
DO NOT work alone. Before performing visual inspections, tests, or maintenance on this equipment,
disconnect all electric power sources. Always use a properly rated voltage sensing device to confirm that power is off. Replace all devices, doors and covers before turning on power to this equipment. Carefully inspect the work area for tools and objects that may have been left inside
the equipment.
Operation Notes Never short the secondary of a Power Transformer (PT). Never open circuit a Current Transformer (CT) Ensure that the CT secondary winding is fixed securely on the equipment. It may damage the equipment if the secondary winding becomes loose during operation. When used with CTs, make sure the CTs are UL2808 listed in America and Canada and meet or exceed the accuracy specifications for IEC61869-2 class or accepted by authority having jurisdiction (AHJ) in other areas.
Wiring Notes When the measured current is higher than the rated specification for the device, consider using an external current transformer (CT). When the measured voltage is higher than the rated specification for the device, consider using an external potential transformer (PT) (line voltage: 35 to 690V AC L-L or phase voltage: 20 to 400V AC L-N, 3P4W-690Y400 Vac / 3P3W-600 Vac). Connect only one cord to one plug on the quick connector. For the device is accidently unplugged, check the connecting cord and restart.

1_

1-3

_1

Delta Din-rail Power Meter DPM-D510 User Manual
Maintenance and Inspection Notes While cleaning the equipment, be sure to unplug all external power sources first. Use a dry cloth to clean the equipment’s exterior. DO NOT open the equipment or touch the wiring inside to prevent personal injury as well as damage to electrical equipment or other property. DO NOT use aerosol sprays, solvents, or abrasives.

1-4

2
Chapter2 Specifications
Table of Contents
2.1 Electrical Characteristics …………………………………………………………… 2-2 2.2 Communications Specifications ………………………………………………….. 2-3 2.3 Operating the Display………………………………………………………………..2-4
2.1.1 Menu Tree …………………………………………………………………………. 2-5 2.4 Dimensions …………………………………………………………………………….. 2-7
2-1

_2

Delta Din-rail Power Meter DPM-D510 User Manual

2.1 Electrical Characteristics

Measurement Accuracy

Voltage, Electric quantities current

± 0.5%

Real Electric energy

Real power ± 0.5%

Reactive

Power factor

± 1%

Real power

Frequency

± 1%

Reactive power

± 0.5%
± 2% ± 2% ± 2%

Input

1PH2W, 1 CT

3PH3W, connection, 3 CT, 2 PT

Voltage Connection

1PH3W, 2 CT

3PH4W, Y connection, 3 CT, No PT

3PH3W, connection, 3 CT, No PT 3PH4W, Y connection, 3 CT, 3 PT

Rated Voltage

3PH3W, connection, 2 CT, No PT 3PH4W, Y connection, 2 CT, 3 PT Line voltage35 to 690 VAC (L-L) Phase voltage20 to 400 VAC (L-N) MEASUREMENT CAT III Y connection (3P4W)400 Vac (line-to-neutral) / 690 Vac (line-to-line) connection (3P3W)600 Vac (line-to-line)

Rated Current

Nominal : 1 A / 5 A

Range of Current 20mA ~ 6A*
Measurement

Start Current

20mA

Frequency

50 / 60 Hz

Voltage Input

OVERVOLTAGE CAT II

Power

Operating range

100 ~ 240 VAC (maximum power: 4.6 W)

Frequency

Operating frequency

50/60 Hz

Communication RS-485 port

Mechanical Characteristics Environment

Dimension (W x H x D) IP Degree of Protection Ambient operating temperature

Modbus-RTU Baud rate 9600 / 19200 / 38400 bps 90 90 66.7 mm IP20 -20 °C ~ +60°C-4°F ~ +140°F

2-2

Chapter 2 Specifications

Storage temperature

-30 °C ~ +70°C-22°F ~ +158°F

Relative Humidity

5 ~ 95% RH

Altitude

Below 2000 meters

Pollution level

2

*Meet the requirements of IEC62053-22 with accurate range: 50mA~

Screen Type Backlight

LCD White

Display

2_

Electromagnetic Compatibility

Electrostatic Discharge

IEC 61000-4-2

Immunity to Radiated Fields IEC 61000-4-3

Immunity to Fast Transients IEC 61000-4-4

Immunity to Impulse Waves IEC 61000-4-5

Conducted Immunity

IEC 61000-4-6

Immunity to Magnetic Fields IEC 61000-4-8

Immunity to Voltage Dips

IEC 61000-4-11

Radiated Emissions

FCC Part 15 Class A, EN55011 Class A

Conducted Emissions

FCC Part 15 Class A, EN55011 Class A

Harmonics Emissions

IEC 61000-3-2

Flicker Emissions

IEC 61000-3-3

2.2 Communications Specifications

Communications

Communication interface Communication Protocol Baud Rate

RS-485

Modbus-RTU

9600 / 19200 / 38400 bps

2-3

Delta Din-rail Power Meter DPM-D510 User Manual
2.3 Operating the Display
DPM-D510
_2

Home page display:

Parameter V I P
Button overview:

Description
Average voltage L-L: 1PH3W, 3PH3W Average voltage L-N: 1PH2W, 3PH4W
Average current value Total real power

Button BACK Key
UP Key DOWN Key NEXT Key

Basic Mode Go to Menu or return to the previous screen Select item or page Select item or page Go to setting mode

Setting Mode Return to the previous screen without saving the current setting Decrement / Increment the number Decrement / Increment the number Go to setting mode and go to the next setting

2-4

2.3.1 Menu Tree
DPM-D510

Chapter 2 Specifications
2_

Meter Configuration 2-5

Delta Din-rail Power Meter DPM-D510 User Manual
_2
Display (Reversed active/ reactive/ apparent energy are supported by firmware version 1.02 and after.)

Home VLN VLL Current PF/F
2-6

Homepage Phase Voltage Line Voltage Current Power Factor

VT CT rSt
PCHG inFo Addr

Voltage transformer/ current transformer Reset
Change password
Meter information
Communication station no.

Power

Power rate

Active Power

Active Power

Reactive Power Reactive Power

Apparent Power Apparent Power

Energy

Energy

PASS

Password

COM

Communication

tyPE

Connection type

2.4 Dimensions
DPM-D510

bAud Prty Ver dAtE nonE dEF
E

Chapter 2 Specifications
Baud rate Parity Firmware Version Date No reset Reset default values Reset energy values

2_

Unit: mm

Function

PIN

VOLTAGE

CURRENT 2-7

_2

Delta Din-rail Power Meter DPM-D510 User Manual

Rated voltage Control power Rated current
RS-485

V1

V2

20V L-N ~ 400V L-N

V3

35V L-L ~ 690V L-L

Vn

L1/+ 100 ~ 240 Vac
L2/-

I1+

I1-

I2+ –
I2-

I3+

I3-

D+

D-

-7 ~ +12 VDC

Wiring Descriptions

400 mA MAX
1A ~ 5A –

DPM-D510 AC100~240V
250 mA fuse: Either positive or negative charge can be used on L1/+ and L2/-. When using a neutral wire for AC power,
you need to connect the neutral wire to the L2/-. Always use a fuse on L1/+. When using an ungrounded neutral wire to connect to the power, use a fuse on
L2/-. If you are using a Power Transformer (PT) or a Current Transformer (CT), use fuses on the primary and secondary windings. The rated voltage / current of the fuse, breaker, and device should be the same to prevent damage to electrical equipment or other property.
2-8

3 3
Chapter 3 Installation
Table of Contents
3.1 Installation …………………………………………………………………………….. 3-2 3.1.1 Installation Environment ………………………………………………………. 3-2 3.1.2 Danger ……………………………………………………………………………. 3-2 3.1.3 Installation Notes ……………………………………………………………….. 3-6
3.2 Basic Checks …………………………………………………………………………… 3-7 3.3 Wiring ……………………………………………………………………………………. 3-8
3.3.1 Wiring Diagrams ………………………………………………………………… 3-8 3.3.2 Communication Characteristics……………………………………………… 3-10
3-1

Delta Din-rail Power Meter DPM-D510 User Manual

_3

3.1 Installation
3.1.1 Installation Environment
Keep the product in the shipping carton before installation. Store the product properly when it is not to be used for an extended period of time to retain the warranty coverage. Some storage suggestions are listed below. Store the power meter in a clean, dry, and controlled environment. Store DPM-D510 in an ambient temperature range of -30 ~ 70°C (-22 ~ 158°F). Store in a relative humidity range of 5­95%, non-condensing. Do not store the product in a place subjected to corrosive gases or liquids. Place the product on a solid and durable surface. Do not mount the product near heat-radiating elements; or in a location subjected to corrosive gases,
liquids, airborne dust or metallic particles; or where it can be subjected to high levels of electromagnetic radiation.

3.1.2 Danger
EN Danger of electric shock, explosion, and electric arc. FR Risque de choc électrique, d’explosion et d’arc électrique. EN It is strictly forbidden to maintain the power meter by the user him/herself. Current or voltage might be generated on the input terminals of the current or potential transformers. FR Il est strictement interdit d’entretenir le wattmètre par l’utilisateur lui- même. Du courant ou de la tension peut être généré sur les bornes d’entrée des transformateurs de courant ou de potentiel. EN Accessories that come with the product must be used with RS-485 connectors when measuring voltage and functional voltage. These accessories cannot be used with other connectors in substitute. FR Les accessoires fournis avec le produit doivent être utilisés avec des connecteurs RS-485 pour mesurer la tension et la tension fonctionnelle. Ces accessoires ne peuvent pas être utilisés avec d’autres connecteurs en remplacement. EN Installation, repair, and maintenance on this device must be performed by licensed professionals. FR L’installation, la réparation et la maintenance de cet appareil doivent être effectuées par des professionnels agréés. EN Shielded wire should be installed according to instructions from this installation guide with one end grounded. FR Le fil blindé doit être installé conformément aux instructions de ce guide d’installation avec une extrémité mise à la terre. EN Non-compliance with these precautions will result in serious bodily injury or death. FR Le non- respect de ces précautions entraînera de graves blessures corporelles ou la mort. EN Beware of potential hazards. Wear safety equipment properly when operating this device and follow safety standards and related regulations for operating electric equipment.

3-2

Chapter 3 Installation

FR Méfiez-vous des dangers potentiels. Portez un équipement de sécurité correctement lors de l’utilisation de cet appareil et respectez les normes de sécurité et les réglementations relatives à l’utilisation de l’équipement électrique. EN DPM-D510 Multi-functional Power Meter series are used for electric power distribution(electric system) control, suitable for measurement of CATIII system. FR Les séries de wattmètres multifonctionnels DPM-D510 sont utilisées pour le contrôle de la distribution d’énergie électrique (système électrique), adaptées à la mesure du système CATIII. EN Installation of this device should be performed by licensed professionals. Perform operations only after carefully reading this manual. FR L’installation de cet appareil doit être effectuée par des professionnels agréés. Effectuez les opérations uniquement après avoir lu attentivement ce manuel. EN Power parameters for installing and using this device should be within rated specifications tolerated by the device. FR Les paramètres de puissance pour l’installation et l’utilisation de cet appareil doivent être conformes aux spécifications nominales tolérées par l’appareil. EN Do not operate alone. Ne pas opérer seul. EN Using this device with special methods might cause damage to the device’s own self-protective features. FR L’utilisation de cet appareil avec des méthodes spéciales peut endommager ses propres fonctions d’autoprotection. EN Power should be disconnected before installing, checking, or maintaining this device. L’alimentation doit être coupée avant d’installer, de vérifier ou d’entretenir cet appareil. EN Disconnect switch or circuit-breaker to be included in building installation, also suitable location easily reached FR Interrupteur-sectionneur ou disjoncteur à inclure dans l’installation du bâtiment, également un emplacement approprié facilement accessible EN You must use a voltage checking device with the correct rated values to ensure that all power has been disconnected. FR Vous devez utiliser un dispositif de contrôle de tension avec les valeurs nominales correctes pour vous assurer que toute l’alimentation a été coupée. EN Before connecting power, check that all mechanical parts, covers, and doors have been returned to their original states. Make sure there are no parts or tools left inside the device. FR Avant de connecter l’alimentation, vérifiez que toutes les pièces mécaniques, les couvercles et les portes ont été remis dans leur état d’origine. Assurez-vous qu’il ne reste aucune pièce ni aucun outil à l’intérieur de l’appareil. EN When installing or disassembling panels, be careful not to touch a powered bus, and keep away from operating panels to avoid hazards.
3-3

3_

_3

Delta Din-rail Power Meter DPM-D510 User Manual
FR Lors de l’installation ou du démontage des panneaux, veillez à ne pas toucher un bus alimenté et à l’écart des panneaux de commande pour éviter les dangers. EN When using this device, short-circuiting is strictly forbidden for a secondary side of potential transformer. FR Lors de l’utilisation de cet appareil, les courts-circuits sont strictement interdits pour un côté secondaire du transformateur de potentiel. EN When using this device, note that the current transformer must not be under an open circuit. FR Lors de l’utilisation de cet appareil, notez que le transformateur de courant ne doit pas être en circuit ouvert. EN When using this device, make sure the powered bus on the secondary side of the current transformer has been locked and secured to the device to prevent the bus falling during the use, which could damage the device. FR Lorsque vous utilisez cet appareil, assurez-vous que le bus alimenté du côté secondaire du transformateur de courant a été verrouillé et fixé à l’appareil pour éviter que le bus ne tombe pendant l’utilisation, ce qui pourrait endommager l’appareil. EN When using the current transformer with the device, use the UL Listed energy monitoring current sensors that is compliant with CAN/CSA-C22.2 No. 61010-1 /UL 2808 FR Lorsque vous utilisez le transformateur de courant avec l’appareil, utilisez les capteurs de courant de surveillance d’énergie répertoriés UL qui sont conformes à la norme CAN / CSA-C22.2 n ° 61010-1 / UL 2808. EN When measuring current, a current transformer must be used with the device. FR Lors de la mesure du courant, un transformateur de courant doit être utilisé avec l’appareil. EN When the measured voltage exceeds the rated range (line voltage of 35~690V AC L-L, phase voltage: 20~400V AC L-N) for this device, a potential transformer must be used with the device. FR Lorsque la tension mesurée dépasse la plage nominale (tension de ligne de 35 ~ 690V AC L-L, tension de phase: 20 ~ 400V AC L-N) pour cet appareil, un transformateur de potentiel doit être utilisé avec l’appareil. EN This device should be installed in a properly-insulated fire- protection cabinet. FR Cet appareil doit être installé dans une armoire coupe- feu correctement isolée. EN Disconnect all wiring (or power off all other circuits) that may present potentially hazardous voltage levels to the unit when cleaning the power meter. Ensure to use a dry and soft cotton cloth to wipe the surface of the power meter carefully. FR Débranchez tout le câblage (ou éteignez tous les autres circuits) qui peuvent présenter des niveaux de tension potentiellement dangereux pour l’unité lors du nettoyage du wattmètre. Veillez à utiliser un chiffon en coton sec et doux pour essuyer soigneusement la surface du wattmètre. EN Do not disassemble the power meter and contact the internal circuit. Failure to observe this precaution could result in damage to the product and severe bodily injury or loss of life. FR Ne démontez pas le wattmètre et ne contactez pas le circuit interne. Le non-respect de cette précaution peut entraîner des dommages au produit et des blessures corporelles graves ou la mort.
3-4

Chapter 3 Installation

EN Do not use Do not use liquid containing acid and alkali on the power meter. FR Ne pas utiliser N’utilisez pas de liquide contenant de l’acide et des alcalis sur le wattmètre. EN Operate this device according to this manual to prevent improper operation that may cause damage and bodily harm. FR Utilisez cet appareil conformément à ce manuel pour éviter un fonctionnement incorrect qui pourrait causer des dommages et des lésions corporelles. EN This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: FR Cet appareil est conforme à la partie 15 des règles de la FCC. Son fonctionnement est soumis aux deux conditions suivantes: EN (1) this device may not cause harmful interference FR (1) cet appareil ne doit pas provoquer d’interférences nuisibles EN (2) this device must accept any interference received, including interference that may cause undesired operation FR (2) cet appareil doit accepter toute interférence reçue, y compris les interférences pouvant entraîner un fonctionnement indésirable EN This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. FR Cet équipement a été testé et déclaré conforme aux limites d’un appareil numérique de classe A, conformément à la partie 15 des règles de la FCC. Ces limites sont conçues pour fournir une protection raisonnable contre les interférences nuisibles lorsque l’équipement est utilisé dans un environnement commercial. Cet équipement génère, utilise et peut émettre de l’énergie de radiofréquence et, s’il n’est pas installé et utilisé conformément au manuel d’instructions, peut provoquer des interférences nuisibles aux communications radio. Le fonctionnement de cet équipement dans une zone résidentielle est susceptible de provoquer des interférences nuisibles, auquel cas l’utilisateur devra corriger les interférences à ses propres frais. EN To reduce the risk of electric shock, always open or disconnect circuit from power distribution system (or service) or building before installing or servicing current transformers FR Pour réduire le risque de choc électrique, ouvrez ou déconnectez toujours le circuit du système de distribution électrique (ou du service) ou du bâtiment avant d’installer ou d’entretenir des transformateurs de courant EN If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
3-5

3_

Delta Din-rail Power Meter DPM-D510 User Manual
FR si l’équipement est utilisé d’une manière non spécifiée par le fabricant, la protection fournie par l’équipement peut être altérée.

_3

3.1.3 Installation Notes
EN Danger of over-voltage. FR Danger de surtension. EN Insulation tests or high-stress tests on this device are forbidden, as these tests will cause damage to the operating panel. FR Les tests d’isolement ou les tests de contrainte élevée sur cet appareil sont interdits, car ces tests endommageront le panneau de commande. EN Operating without following the instructions of this manual will result in serious bodily injury or death. FR Une utilisation sans suivre les instructions de ce manuel entraînera des blessures graves voire mortelles. EN The installation that the safety of any system incorporating the equipment is the responsibility of the assembler of the system. FR L’installation et la sécurité de tout système incorporant l’équipement est de la responsabilité de l’installateur du système. EN This is open type equipment shall be DIN-Rail mounted in the appropriate final enclosure. FR Cet équipement de type ouvert doit être monté sur rail DIN dans le boîtier final adapté.
Installation Steps Step 1: Use a flathead screwdriver to fit in recess and pull open the fixed plastic plate at the bottom..

Step 2: Install the power meter on the DIN rail in desired location.

3-6

Step 3: Press to lock the plastic plate.

Chapter 3 Installation

3.2 Basic Checks

Items

Contents

Regularly check for mounting looseness where the power meter and device are

connected.

General Check

Prevent foreign objects, such as oil, water, or metal powder entering the device through the ventilation holes. Prevent drill shavings or other debris entering the power meter.

If the power meter is installed at a location with harmful gas or dust, prevent those

materials from entering the power meter.

Insulate the connections at the wiring terminals.

Communications wiring should be done properly to prevent abnormal operations.

Pre-operation Check

Check for the presence of conducive and flammable objects, such as screws or metal

pieces in the power meter.

(not supplied with power)

If electronic devices near to the power meter experience electromagnetic interference,

take steps to reduce the electromagnetic interference.

Check for the correct voltage level for the power supplied to the power meter.

Pre-running Check if the power indicator light is lit.

Check Check if communication between every device is normal.

(supplied with If there is any abnormal response from the power meter, contact your distributor or our

power)

customer service center.

3_

3-7

_3

Delta Din-rail Power Meter DPM-D510 User Manual

3.3 Wiring
3.3.1 Wiring Diagrams
To avoid electric shock, do not change the wiring when the power is on. Install a breaker switch on the power cord for the meter because there is no power switch on the power
meter. When the measured voltage is higher than the rated specification for the device, it is necessary to use an
external potential transformer (PT). When the measured current is higher than the rated specification for the device, it is necessary to use an
external current transformer (CT).

The following table shows the recommended wiring materials.

Connecting Terminals Operating Power/ Voltage
Measurement Current Measurement/ RS-485

Wire Diameters AWG 10­22 AWG 10­22

Screw Turning Torque 5.0 kgf-cm (0.5 N·m) 5.0 kgf-cm (0.5 N·m)

Wire heat resistance > 70°C > 70°C

3-8

Connection Diagrams 3PH3W, connection, 3 CT, No PT

Chapter 3 Installation 3PH3W, connection, 2 CT, No PT

3PH3W, connection, 3 CT, 2 PT

3PH4W, Y connection, 3 CT, No PT

3_

3PH4W, Y connection, 3 CT, 3 PT

3PH4W, Y connection, 2 CT, 3 PT

1PH2W, 1 CT

1PH3W, 2 CT

3-9

Delta Din-rail Power Meter DPM-D510 User Manual

The following table lists the symbols used in the diagram.

Symbol

Description Grounding Current transformer

Terminal block

Voltage transformer

Fuse

_3

3.3.2 Communication Characteristics

Communications Specifications:

Max. Communication 1200 m
Distance

Max. Connection 32
Number

Communication Protocols

Modbus RTU

Function Code

03, 06, 10

Baud Rate Data Length
Parity Stop Bits

9600, 19200, 38400 bps 8-bits None, Odd, Even 1

Use shielded twisted-pair cables for RS485 communication. When connecting multiple devices in series, use the wiring method in the following diagram.

Termina l Resistor
Connect the D+ communication terminal for all devices on the same twisted pair cable. Connect the Dterminals on the other twisted pair cable. Ground the cable shield. Install a terminal resistor on the terminal device as shown.
Use cables with a diameter of 14­20 AWG.

3-10

4
Chapter 4 Operation
Table of Contents
4.1 General Operation ……………………………………………………………………. 4-2 4.1.1 Setting Menu …………………………………………………………………….. 4-2
4.2 Setups ……………………………………………………………………………………. 4-3 4.2.1 Password Setup (PASS)………………………………………………………… 4-3 4.2.2 Communication Setup (COM) …………………………………………………. 4-4 4.2.3 Wiring Type (tyPE) ……………………………………………………………… 4-6 4.2.4 VT and CT Setup (VT CT) ……………………………………………………… 4-6 4.2.5 Reset (rSt) ……………………………………………………………………….. 4-8 4.2.6 Edit Password (PCHG) ………………………………………………………….. 4-9 4.2.7 Meter Information (INFO) ……………………………………………………… 4-9
4-1

Delta Din-rail Power Meter DPM-D510 User Manual

_4

4.1 General Operation
4.1.1 Setting Menu
HOME page (HOME): Values measured by the power meter, including average voltage (Vavg (AVG)), average current (Iavg (AVG)), total real power (Ptot (SUM)).
Phase voltage (VLN): Phase voltage values measured by the power meter, including phase A voltage (VL1N(V)), phase B voltage (VL2N(V)), phase C voltage (VL3N(V)).
Line voltage (VLL): Line voltage values measured by the power meter, including A-B line voltage (VL12(V)), B-C line voltage (VL23(V)), C-A line voltage (VL31(V)).
Electric current page (Current): Electric current measured by the power meter, including phase A current (IL1N(A)), phase B current (IL2N(A)), phase C current (IL3N(A)).
Power factor page (PF/F): Power factors measured by the power meter, including total power factor (PF) and frequency (F(Hz)).
Power page (Power): Values measured by the power meter, including total active power (Ptot(W)), total reactive power (Qtot(var)), and total apparent power (Stot(VA)).
Active power page (Active Power): Active power value measured by the power meter, including active power of phase A (L1N(W)), phase B (L2N(W)) and phase C (L3N(W)).
Reactive power page (VAR): Reactive power value measured by the power meter, including reactive power of phase A (A), phase B (B), phase C (C) and total reactive power (T).
Apparent power page (Apparent Power): Apparent power value measured by the power meter, including apparent power of phase A (L1N(VA)), phase B (L2N(VA)) and phase C (L3N(VA)).
Energy page (Energy): Energy values measured by the power meter, including positive active energy (Wh+), positive reactive energy (var+), positive apparent energy (VA+), reversed active energy (Wh-), reserved reactive energy (var-) and reserved apparent energy (VA-). (Reversed active/ reactive/ apparent energy are supported by firmware version 1.02 and after.) 1. Use UP and DOWN to switch among setting pages. 2. Press BACK to return to the homepage (Home) on other setting pages. 3. Note(1): When on the homepage, press BACK to enter the correct password and enter setting pages. 4. Note(2): Values of positive reactive energy would be displayed with inductance icon, while values of reversed reactive energy would be displayed with capacitance. For values of reversed active energy and apparent energy, a minus sign would be displayed. 5. Note(3): The real-time status of active/ reactive power would be displayed on all measurement display pages with four P-Q quadrants. Inductive and capacitive state would be shown on the PF value display for positive/ reversed reactive energy. Four P-Q quadrants and inductive/ capacitive state would not be displayed when average current is under 20mA. The following figure is shown with a reversed reactive energy value, which the real-time status of active/ reactive power is displayed with a four P-Q quadrant icon.

4-2

Chapter 4 Operation

4.2 Setups
4.2.1 Password Setup (PASS)
Password: before using power meter, you need to enter the password (default 0000) Steps:
1. Press NEXT key till the first digit starts blinking 2. Use UP and DOWN keys to select the first digit of the password 3. Press NEXT key to confirm the selected digit and you can start to set the next digit 4. Repeat steps 2-3 till you complete the setting of the 4 digit password. 5. After you complete the setting of the 4 digit password, press NEXT key to go to the parameter
setting page. *Note 1: if you need to edit the setting you just set, you can press BACK key and the digit will stop blinking. Press NEXT key to reset a new password.

4_

4-3

_4

Delta Din-rail Power Meter DPM-D510 User Manual
4.2.2 Communication Setup (COM)
Address (Addr): device ID; its address setting range is 1-254 (default: 1). Baud Rate (BAud): transmission speed; the setting options are 9600 bps (9.6k) (default), 19200(19.2k)
and 38400 bps (38.4k). Parity setting (Prty): odd and even checking bit for communication; the setting options are None (8n1),
Even (8E1), and Odd (8o1); default: None. Steps:
1. Press NEXT key when the COM icon is displayed to enter the setting menu under COM. 2. Use UP and DOWN keys to select the device ID (Addr), baud rate (bAud) and parity (Prty). 3. When Addr is shown on the display, press NEXT key to confirm the setting and start to use UP and
DOWN keys to select the desired device ID. 4. When bAud is shown on the display, press NEXT key to confirm the setting and start to use UP and
DOWN keys to select the desired baud rate. 5. When Prty is shown on the display, press NEXT key to confirm the setting and start to use UP and
DOWN keys to select the desired parity. 6. In steps 3-5, use UP and DOWN key to choose each digit and press NEXT to confirm the setting.
The setting sequence for the three-digit number of device ID is hundreds digit tens digit units digit; you are allowed to set only one digit at a time.
*Note: You can go back to the previous setting item by pressing BACK key anytime, whether you have completed or canceled the setting.

4-4

Chapter 4 Operation
4_
4-5

Delta Din-rail Power Meter DPM-D510 User Manual

_4

4.2.3 Wiring Type (tyPE)
Connection types: options are one-phase two-wire (1P2W), one-phase three-wire (1P3W), three-phase three-wire (3P3W), and three-phase four-wire (3P4W); default: three-phase four-wire (3P4W).
Steps: 1. Press NEXT key when the tyPE icon is shown on the left side of the display, then the previous
connection type setting would be displayed (13P234W icon). Press NEXT to configure the setting.
2. Press UP and DOWN keys to select the desired connection type. 3. Press NEXT key to confirm the setting. *Note: You can go back to the previous setting item by pressing BACK key anytime, whether you have completed or canceled the setting.

4.2.4 VT and CT Setup (VT CT)
VT number (VT): The number of voltage transformers that is currently being used. Options are 0 (0VT), 2(2VT) and 3(3VT). The default is 3.
CT number (CT): The number of current transformers that is currently being used. Options are 1 (1VT), 2(2VT) and 3(3VT). The default is 3
VT ratio (VT Pri / VT SEC): Volt for the primary-side current transformer, ranging from 1 to 9999 V; default: 1 V. Volt for the secondary-side current transformer, ranging from 1 to 9999 V; default: 1 V.
CT ratio (CT Pri / CT SEC): Ampere for the primary-side current transformer, ranging from 1 to 9999 A; default: 5 A. Ampere for the secondary-side current transformer, selecting between 1A and 5A; default: 5A.
4-6

Chapter 4 Operation
Steps: 1. When VT CT is shown on the display, press NEXT key to enter the setting menu under VT CT and VT would be shown on the display. 2. Use UP and DOWN keys to select the number of VT (VT no.) and CT (CT no.), VT ratio (VT Pri / VT SEC), CT ratio (CT Pri / CT SEC). 3. Press NEXT when VT no. is displayed. When the option starts blinking, you can use UP and DOWN keys to select the number of voltage transformers you need. 4. Press NEXT when CT no. is displayed. When the option starts blinking, you can use UP and DOWN keys to select the number of current transformers you need. 5. Press NEXT when VT Pri or VT SEC is displayed. When the option starts blinking, you can use UP and DOWN keys to select the desired VT ratio. 6. Press NEXT when CT Pri or CT SEC. is displayed. When the option starts blinking, you can use UP and DOWN keys to select the desired CT ratio.
7. In steps 3-5, you are allowed to set only one digit at a time by using UP and DOWN key to choose each digit and press NEXT to confirm the setting.
*Note: You can go back to the previous setting item by pressing BACK key anytime, whether you have completed or canceled the setting.

4_

4-7

Delta Din-rail Power Meter DPM-D510 User Manual

_4

4.2.5 Reset (rSt)
No action (nonE): do not reset. Restore to defaults (dEF): restore the power meter parameters to default settings. Reset the energy value: Reset the accumulated value of electric energy (PH) on the meter to zero. Steps:
1. Press NEXT key till the option starts blinking. 2. Use UP and DOWN keys to select the reset options. 3. Press NEXT key to confirm the setting. Note: You can go back to the previous setting item by pressing BACK key anytime, whether you have completed or canceled the setting.

4-8

Chapter 4 Operation
4.2.6 Edit Password (PCHG)
Edit the password (default 0000) Steps:
1. Press NEXT key till the first digit starts blinking 2. Use UP and DOWN keys to select the first digit of the password 3. Press NEXT key to confirm the setting and start to set the next digital input. 4. Repeat steps 2-3 till you complete the setting of the 4 digit password. 5. Press NEXT key to confirm the setting. Note: You can go back to the previous setting item by pressing BACK key anytime, whether you have completed or canceled the setting.
4_
4.2.7 Meter Information (INFO)
Firmware version (VEr): M.XX (M is the version number. Before mass production = 0; after mass production >=1)
Firmware release date (dAtE): MMDD (MM=month; DD= day)
4-9

Delta Din-rail Power Meter DPM-D510 User Manual

_4
4-10

5
Chapter 5 Parameters and Functions
Table of Contents
5.1 Overview of Parameters ……………………………………………………………. 5-2 5.2 Modbus Communication ……………………………………………………………. 5-7
5.2.1 Supported Modbus Function Codes ………………………………………….. 5-7 5.2.2 Modbus Communication Protocol …………………………………………….. 5-8
5-1

_5

Delta Din-rail Power Meter DPM-D510 User Manual

5.1 Overview of Parameters

Modbus
Address
Modicom Hex
Format

Item

Range

Data Type

Unit

Data Size (byte)

Read (R) / Write (W)

0. System Parameters: 0001 ­ 00FF

5 40006 Meter Constant

3200

uint P/kWh 2

R

6 40007 Meter Model

0: None 19DPM-510

word

2

R

7 40008

Day: 0­65535

Total running time of

8

40009 the meter

Hour: 00­23

Minute: 00­59

uint Day 2

R

Hour,

byte

2

R

Minute

9 40010 Firmware version 0.00 ­ 9.99

uint

2

R

Year: 00­99 A 40011 Firmware release
Month: 1­12

date

B 40012

Date: 1­31

Year,

byte

2

R

Month

word Date 2

R

C 40013
Power system D 40014
configuration

03P4W 13P3W 21P2W 31P3W

Reserved word

2

R/W

E 40015 Primary CT (A)

1 ­ 9999

uint A

2

R/W

0: 1A F 40016 Secondary CT (A)
1: 5A

word A

2

R/W

10 40017 Primary PT

1 ­ 9999

uint V

2

R/W

11 40018 Secondary PT

1 ­ 9999

uint V

2

R/W

5-2

Chapter 5 Parameters and Functions

Transformer 12 40019
quantities

0: 3CT3PT 1: 3CT2PT 2: 3CT0PT 3: 2CT3PT 4: 2CT2PT 5: 2CT0PT 6: 1CT3PT 71CT2PT 81CT0PT

word

2

R/W

13 40020

Reserved

14 40021 Timeout

1 ­ 99

word Second 2

R/W

15 40022

Reserved

16 40023 Baud Rate

0: 9600 1: 19200 2: 38400

word bps 2

R/W

17 40024 Communication mode 1: RTU

word

2

R/W

18 40025 Data bit

0: 8

word bit

2

R/W

19 40026 Stop bit

0: None 1: Even 2: Odd

word

2

R/W

1A 40027 Stop bit

0: 1

word bit

2

R/W

1B 40028 Modbus address

0 ­ 254

word

2

R/W

0: None

1C 40029 Reset

1: Reset to factory default

word

2

W

2: Reset energy value

1. Meter Parameters: 0100 ­ 01FF

100 40257 Phase A voltage
101 40258

0.000 ­ 99999.999

float V

4

R

102 40259 Phase B voltage
103 40260

0.000 ­ 99999.999

float V

4

R

104 40261 Phase C voltage
105 40262

0.000 ­ 99999.999

float V

4

R

_5

5-3

_5

Delta Din-rail Power Meter DPM-D510 User Manual

106 40263 Average phase 107 40264 voltage

0.000 ­ 99999.999

108 40265 A­B line voltage
109 40266

0.000 ­ 99999.999

10A 40267 B­C line voltage
10B 40268

0.000 ­ 99999.999

10C 40269 C­A line voltage
10D 40270

0.000 ­ 99999.999

10E 40271 Average line voltage 0.000 ­ 99999.999
10F 40272

110 40273 Phase A voltage 111 40274 unbalance

0.00 ­ 99.99

112 40275 Phase B voltage 113 40276 unbalance

0.00 ­ 99.99

114 40277 Phase C voltage 115 40278 unbalance

0.00 ­ 99.99

116 40279 Phase voltage 117 40280 unbalance

0.00 ­ 99.99

118 40281 A­B line voltage 119 40282 unbalance

0.00 ­ 99.99

11A 40283 B­C line voltage 11B 40284 unbalance

0.00 ­ 99.99

11C 40285 C­A line voltage 11D 40286 unbalance

0.00 ­ 99.99

11E 40287 Line voltage 11F 40288 unbalance

0.00 ­ 99.99

120 40289 Phase A current
121 40290

0.000 ­ 99999.999

122 40291 Phase B current
123 40292

0.000 ­ 99999.999

124 40293 Phase C current

0.000 ­ 99999.999

5-4

float V

4

R

float V

4

R

float V

4

R

float V

4

R

float V

4

R

float %

4

R

float %

4

R

float %

4

R

float %

4

R

float %

4

R

float %

4

R

float %

4

R

float %

4

R

float A

4

R

float A

4

R

float A

4

R

Chapter 5 Parameters and Functions

125 40294

126 40295 Three­phase average 0.000 ­ 99999.999
127 40296 current

float A

4

R

128 40297 Neutral line current 0.000 ­ 99999.999
129 40298

float A

4

R

12A 40299 Phase A current 12B 40300 unbalance

0.00 ­ 99.99

float %

4

R

12C 40301 Phase B current 12D 40302 unbalance

0.00 ­ 99.99

float %

4

R

12E 40303 Phase C current 12F 40304 unbalance

0.00 ­ 99.99

float %

4

R

130 40305 Current unbalance 0.00 ­ 99.99
131 40306

float %

4

R

132 40307 Total power factor
133 40308

-0.00000 ­ 1.00000 float
(positive: lag; negative: lead)

4

R

134 40309 Power factor of phase -0.00000 ­ 1.00000

float

135 40310 A

(positive: lag; negative: lead)

4

R

136 40311 Power factor of phase -0.00000 ­ 1.00000

float

137 40312 B

(positive: lag; negative: lead)

4

R

138 40313 Power factor of phase -0.00000 ­ 1.00000

float

139 40314 C

(positive: lag; negative: lead)

4

R

13A 40315 Total displacement -0.00000 ­ 1.00000

float

13B 40316 power factor

(positive: lag; negative: lead)

4

R

13C 40317 Total displacement

-0.00000 ­ 1.00000

power factor of phase

float

13D 40318 A

(positive: lag; negative: lead)

4

R

13E 40319 Total displacement

-0.00000 ­ 1.00000

power factor of phase

float

13F 40320 B

(positive: lag; negative: lead)

4

R

140 40321 Total displacement -0.00000 ­ 1.00000

power factor of phase

float

(positive: lag; negative: lead)

141 40322 C

4

R

_5

5-5

Delta Din-rail Power Meter DPM-D510 User Manual

_5

142 40323 Frequency
143 40324

0.0000 ­ 99.9999

float Hz

4

R

144 40325 Total instantaneous 0.000 ­ 99999.999
145 40326 active power

float kW 4

R

146 40327 Instantaneous active 0.000 ­ 99999.999
147 40328 power of phase A

float kW 4

R

148 40329 Instantaneous active 0.000 ­ 99999.999
149 40330 power of phase B

float kW 4

R

14A 40331 Instantaneous active 0.000 ­ 99999.999
14B 40332 power of phase C

float kW 4

R

14C 40333 Total instantaneous 0.000 ­ 99999.999
14D 40334 reactive power

float kVAR 4

R

14E 40335 Instantaneous
reactive power of 14F 40336
phase A

0.000 ­ 99999.999

float kVAR 4

R

150 40337 Instantaneous
reactive power of 151 40338
phase B

0.000 ­ 99999.999

float kVAR 4

R

152 40339 Instantaneous
reactive power of 153 40340
phase C

0.000 ­ 99999.999

float kVAR 4

R

154 40341 Instantaneous 155 40342 apparent power

0.000 ­ 99999.999

float kVA 4

R

156 40343 Instantaneous
apparent power of 0.000 ­ 99999.999 157 40344
phase A

float kVA 4

R

158 40345 Instantaneous
apparent power of 0.000 ­ 99999.999 159 40346
phase B

float kVA 4

R

15A 40347 Instantaneous
apparent power of 0.000 ­ 99999.999 15B 40348
phase C

float kVA 4

R

15C 40349 Active energy of three 0x00000000 ­ 0xFFFFFFFF unit kWh 4

R

5-6

Chapter 5 Parameters and Functions

15D 40350 – phase delivered

15E 40351 Active energy of three

– phase received

(Supported by

0x00000000 ­ 0xFFFFFFFF unit kWh 4

R

15F 40352 firmware version 1.02

and after)

160 40353 Reactive energy of

three – phase 161 40354
delivered

0x00000000 ­ 0xFFFFFFFF unit kVARh 4

R

162 40355 Reactive energy of

three – phase

received

0x00000000 ­ 0xFFFFFFFF unit kVARh 4

R

163 40356 (Supported by

firmware version 1.02

and after)

164 40357 Apparent energy of

three – phase 165 40358
delivered

0x00000000 ­ 0xFFFFFFFF unit kVAh 4

R

166 40359 Apparent energy of

three – phase

received

0x00000000 ­ 0xFFFFFFFF unit kVAh 4

R

167 40360 (Supported by

firmware version 1.02

and after)

_5

5.2 Modbus Communication

5.2.1 Supported Modbus Function Codes

Function Code
0x03 0x06 0xFE

Modbus Name
Read Holding Registers Preset Single Registers Read Data Log

Description
Read the contents of read location Preset the contents of written location Read the contents of data log

When the protocol is Modbus RTU, the maximum address to be gathered with a single Modbus block read is 50 for function code 0x3, and the maximum address is 49 for function code 0x10. The function code 0xFE can be used only when the protocol is Modbus RTU.

5-7

Delta Din-rail Power Meter DPM-D510 User Manual

5.2.2 Modbus Communication Protocol
Modbus RTU mode is adopted with Modbus Master sending out the Request, in which the Function Code uses 0x03 to request response from Slave to correspond to values in Modbus address. In Response, Modbus Slave responds to the values of Modbus address in the Master request. The packet format of IEEE754 is used for the address of floating point numbers that corresponds to the register values found in table 5.2, using 2’s complement packet format. The format are as follows:

Low Word

High Word

High Byte Low Byte High Byte Low Byte

The packet formats (2’s complement) for the address of integers that corresponds to the register values found in table 5.2 are shown in the example below.

Read

_5

5-8

Chapter 5 Parameters and Functions
Write:

Example: For Modbus Master, such as PLC or data collector, it uses Modbus protocol to get the value of CT setting (Register address 0x000E) on the power meter (Modbus Slave) (Slave address 0x1). The register value is 1000. The packet format for Request sent out by Modbus Master (PLC or data collector) is as follows:

_5

The packet format for Response responded by Modbus Slave (power meter) is as follows: 5-9

Delta Din-rail Power Meter DPM-D510 User Manual

_5

After receiving response from the power meter, Modbus Master acquires the value of currents from the primary-side current transformer (register address 0x000E), which is 1000 (0x3E8).

Should Modbus Slave (power meter) receive an abnormal Request, the format of the abnormal packet responded and the error codes are as follows.

Error Code 0x01 0x02 0x03
0x04

Error Name Illegal Function Illegal Data Address Illegal Data Value
Slave Device Failure

Description The function code is illegal. The data address is illegal to read or write. The data format is incorrect, such as wrong data length. Slave cannot execute the command.

Slave Response

Slave Address

Function Code

Exception Code

0x01 0x83 0x1 CRC

5-10

6
Chapter 6 Error Codes
Table of Contents
6.1 Error Codes …………………………………………………………………………….. 6-2
6-1

Delta Din-rail Power Meter DPM-D510 User Manual

6.1 Error Codes
When an error occurs during operation, the power monitor sends an error code through Modbus. The following table lists the error codes and causes.

Error Code 0x01 0x02 0x03 0x04

Name Illegal function Illegal data address Illegal data value Slave device failure

Description Incorrect function code Incorrect data address to read or write Incorrect data format (for example, data length) Slave cannot execute the command.

_6

6-2

1A2
Appendix A Accessories
Table of Contents
A.1 DCTMC Series …………………………………………………………………………..A-2 A.2 DCTCS Series ……………………………………………………………………………A-3 A.3 DCT1000 Series ………………………………………………………………………..A-4 A.4 DCT2000 Series ………………………………………………………………………..A-6
A-1

Delta Din-rail Power Meter DPM-D510 User Manual

When measured current is higher than the rated specification for the device, use of an external current transformer (CT) is necessary. Choose the proper CT from the table below to install.
A.1 DCTMC Series

Model Number

Measurement Accuracy

Primary Current

Secondary Current

Rated Burden
(VA)

External Dimension*1
(mm)

Size of Opening*1
(mm)

DCT-MC010-5 DCT-MC020-5

1.0% 0.5%

100A 200A

5A

1.5

806038

20*30.5

5A

3.75

DCT-MC030-5

0.5%

300A

5A

5

9874.543

42*42

DCT-MC040-5

0.5%

400A

5A

7.5

DCT-MC050-5

0.5%

500A

5A

DCT-MC060-5

0.5%

600A

5A

5

12710345

51*61

10

*1: See the following table for detailed information on the external dimensions and sizes of opening.

Toroidal Current Transformer Model Number

Dimension (mm)

DCT-MC010-5 DCT-MC020-5

External Dimension80 x 60 x 38 Size of Opening20 x 30.5

DCT-MC030-5

_A

External Dimension98 x 74.5 x 43

Size of Opening42 x 42

DCT-MC040-5

DCT-MC050-5 DCT-MC060-5

External Dimension127 x 103 x 45 Size of Opening51 x 61

A-2

Appendix A Accesories

A.2 DCTCS Series

Model Type

Measurement Accuracy

Primary Current

Secondary Current

Rated Burden
(VA)

External Dimension*1
(mm)

Size of Opening*1
(mm)

DCT-CS010-5

1%

100A

5A

1000

DCT-CS020-5

1%

200A

5A

1000 66.849.834.2 23.8*25.2

DCT-CS030-5

1%

300A

5A

1000

DCT-CS040-5

1%

400A

5A

1000

DCT-CS050-5

1%

500A

5A

1000

856942.5

36.5*36.5

DCT-CS060-5

1%

600A

5A

1000

*1: See the following table for detailed information on the external dimensions and sizes of opening.

Small Size Toroidal Current Transformer Model

Dimension (Unit: mm)

DCT-CS010-5 DCT-CS020-5 External Dimension66.8 x 49.8 x 34.2
Size of Opening23.8 x 25.2 DCT-CS030-5
A_
DCT-CS040-5 DCT-CS050-5 External Dimension85 x 69 x 42.5
Size of Opening36.5 x 36.5 DCT-CS060-5

A-3

Delta Din-rail Power Meter DPM-D510 User Manual

A.3 DCT1000 Series
Electromagnetic Compatibility: CE-marking, IEC61869-2.

Model Number

Measurement Accuracy

Primary Current

Secondary Current

Rated Burden
(VA)

External Dimension*1
(mm)

Size of Opening*1
(mm)

DCT-S301C

1.0%

100 A

5 A

1.5

DCT-S211C

0.5%

200 A

5 A

1

90 x 40 x 111

21 x 32

DCT-S221C

0.5%

300 A

5 A

1.5

DCT-S231C

0.5%

400 A

5 A

2.5

DCT-S241C

0.5%

500 A

5 A

2.5

DCT-S251C

0.5%

600 A

5 A

2.5

116.5 x 52 x 147 50 x 80

DCT-S261C

0.5%

750 A

5 A

2.5

DCT-S271C

0.5%

1000 A

5 A

5

DCT-S281C

0.5%

1500 A

5 A

146.5 x 51.6 x

7.5

80 x 122

198

DCT-S291C

0.5%

2000 A

5 A

10

DCT-S2A1C

0.5%

2500 A

5 A

15

186.5 x 52 x 252 81 x 160.5

_A

DCT-S2B1C

0.5%

3000 A

5 A

20

*1: See the following table for detailed information on the external dimensions and sizes of opening.

A-4

Appendix A Accesories

Model Number DCT-S301C
DCT-S211C

External Dimension: 90 x 40 x 111 Size of Opening: 21 x 32

DCT-S221C

Dimension (mm)

DCT-S231C

DCT-S241C DCT-S251C

External Dimension: 116.5 x 52 x 147 Size of Opening: 50 x 80

DCT-S261C

DCT-S271C

External Dimension: 146.5 x 51.6 x 198 Size of Opening: 80 x 122

DCT-S281C
A_

DCT-S291C

External Dimension: 186.5 x 52 x 252 Size of Opening: 81 x 160.5

DCT-S2A1C

DCT-S2B1C

A-5

Delta Din-rail Power Meter DPM-D510 User Manual

A.4 DCT2000 Series

Electromagnetic Compatibility: UL, UL2808.

Model Number

Measurement Primary Secondary Rated Burden

Accuracy Current Current

(VA)

External Dimension*1
(mm)

Size of Opening*1 (mm)

DCT-S201B

1.0%

100 A

5 A

1

DCT-S211B

0.5%

200 A

5 A

1

90 x 40 x 110

20 x 30

DCT-S221B

0.5%

300 A

5 A

1.5

DCT-S231B

0.5%

400 A

5 A

1.5

DCT-S241B

0.5%

500 A

5 A

2.5

DCT-S251B DCT-S261B

0.5% 0.5%

600 A

5 A

750 A

5 A

2.5 115 x 57 x 158
2.5

50 x 80

DCT-S2C1B

0.5%

800 A

5 A

3.75

DCT-S271B

0.5%

1000 A

5 A

5

*1: See the following table for detailed information on the external dimensions and sizes of opening.

Model Number

DCT-S201B

External Dimension: 90 x 40 x 110

Size of Opening:

_A

20 x 30

DCT-S211B

Dimension (mm)

DCT-S221B

A-6

Model Number

DCT-S231B DCT-S241B DCT-S251B

External Dimension: 115 x 57 x 158 Size of Opening: 50 x 80

DCT-S261B

DCT-S2C1B

DCT-S271B

Appendix A Accesories Dimension (mm)

A_

A-7

Delta Din-rail Power Meter DPM-D510 User Manual MEMO
_A
A-8

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals