PeakTech 1096 AC/DC Voltage Tester User Manual
- June 4, 2024
- PeakTech
Table of Contents
PeakTech 1096 AC/DC Voltage Tester
Safety precautions
This product complies with the requirements of the following directives of the
European Union for CE conformity: 2014/30/EU (electromagnetic compatibility),
2014/35/EU (low voltage), 2011/65/EU (RoHS).
Overvoltage category III 1000 V / IV 600 V; pollution degree 2.
CAT I: For signal level, telecommunication, electronic with small transient
overvoltage
CAT II: For local level, appliances, main wall outlets, portable equipment
CAT III: Distribution level, fixed installation, with smaller transient
overvoltages than CAT IV.
CAT IV: Units and installations, which are supplied overhead lines, which are
stand in a risk of persuading of lightning, i.e. main-switches on current
input, overvoltage-diverter, current use counter.
To ensure safe operation of the equipment and eliminate the danger of serious injury due to short circuits (arcing), the following safety precautions must be observed. Damage caused by non-observance of these instructions are excluded from claims of any kind.
- Don’t use this device in high-energy circuits.
- Do not exceed the maximum allowable input voltage of 1000V DC or 1000V AC.
- Under no circumstances exceed the maximum permissible input values (serious risk of injury and/or destruction of the device).
- The specified maximum input voltages should not be exceeded. If it can not be ruled out beyond any doubt that these voltage peaks are exceeded due to the influence of transient disturbances or for other reasons, the measuring voltage must be pre-attenuated accordingly (10: 1).
- Never operate the device unless it is completely closed.
- Check the device and other accessories for possible damage or bare or kinked cables and wires before commissioning. In case of doubt, do not take any measurements.
- Only carry out measuring work in dry clothing, preferably in rubber shoes or on an insulating mat.
- Do not touch the measuring tips of the test leads.
- It is essential to observe warnings on the device.
- Do not expose the device to extreme temperatures, direct sunlight, extreme humidity or moisture.
- Avoid strong vibration.
- Do not operate the device near strong magnetic fields (motors, transformers, etc.).
- Keep hot soldering guns away from the immediate vicinity of the device.
- Before starting the measuring operation, the device should be stabilized to the ambient temperature (important when transporting from cold to warm rooms and vice versa)
- Measure voltages above 120V DC or 50V AC only in accordance with relevant safety regulations. At higher voltages, particularly dangerous electric shocks may occur.
- Lack of battery power can cause inaccurate readings. Electric shocks and physical injuries can be the result.
- If you do not use the device for a long period of time, remove the battery from the battery compartment.
- Periodically clean the case with a damp cloth and a mild detergent. Do not use corrosive abrasives.
- Avoid any proximity to explosive and flammable materials.
- Opening the unit, maintenance and repair work only have to be carried out by qualified service technicians.
- Do not place the device on the workbench or work surface with the front side in order to avoid damage to the controls.
- Do not make any technical changes to the device.
Measuring instruments don’t belong to children’s hands
Cleaning the device
Only clean the device with a damp, lint-free cloth. Use only commercially
available dishwashing liquid. Ensure that no water gets inside the equipment
to prevent possible shorts and damage to the equipment.
Introduction
The new two-pole voltage tester Peaktech 1096 convinces with its versatile functions, which makes it possible to use this voltage tester in many common situations. The LED and the LCD Voltage Indicator makes it easy to measure a voltage at a device or a wire. Furthermore, voltage measurements indicate whether AC or DC voltage is applied to the voltage tester. The L and R LEDs symbolize the left or right hand rotation of the phase to be measured (such as in the three-phase current range). The two-pole voltage tester is also able to perform resistances and continuity tests. The Hold function allows you to “freeze” any reading to make it easier to record the readings. With the two pushbuttons for the low-resistance test, it is possible to check various wires and devices. The profile of the Peaktech 1096 is completed with his features such as the backlight of the LCD screen and the flashlight function, but also with its modern and ergonomic design.
- Modern two pole voltage tester
- Voltage indicator by LED and LCD display
- Resistance and noise resistance measurement
- Illuminated LCD display
- Integrated flashlight
Controls
Operation
The two-pole voltage tester is used to identify live wires and equipment. By
its clear indication of the flashing LED’s and the LCD display, it is easy to
perform various measurements, such as a voltage or resistance measurement.
Note: Keep in mind that with each measurement, your hands and fingers are
behind the Integrated Protective Lip to prevent injury or flashovers.
Voltage measurement
Before each measurement, check the voltage tester for functionality by taking a measurement on a known voltage source. To perform a voltage test, connect the object to be measured with the test probes of the voltage tester. If a voltage higher than 6V is applied, the voltage tester will switch on automatically and show the measured value using the LED’s / LCD display. Furthermore, it is displayed at the same time, whether it is an AC or DC voltage at the measured quantity. At measured voltages above 50VAC / 120VDC. To “freeze” measured values, the hold key can be pressed at any time. If the current value is to be displayed again, the hold key must be pressed a second time.
Single–pole phase test
Note: The single-pole phase test is not suitable for determining the absence of voltage The single-phase test tests whether a phase is live. The voltage tester only signals if a voltage is present above a voltage of 100V AC. This is signaled with the symbol lamp . To obtain a meaningful measurement, it is recommended to perform a two-pole voltage test.
Resistance measurement
Note: Measure resistance only on de-energized conductors.
By pressing and holding (for about 2 seconds) the button for resistance
measurement, the voltage tester is switched on manually and is set directly to
the resistance measurement. To measure the resistance of a device/line, it
have to be connected to the probes. It is possible to measure resistances in
the range between 1Ω and 1999Ω.
After performing the measurement, press the resistance measurement button
again for about 2 seconds to turn off the voltage tester.
Continuity test
Note: Check continuity only on de-energized conductors.
The continuity test makes it possible to check the continuity of a wire or a
device/component. When the passage is detected, the continuity check LED will
illuminate and the beeper will sound.
Rotary field indication
The voltage tester is equipped with a two-pole rotary field indicator. The phase sequence detection is always active. The symbols R or L are always displayed. However, the direction of rotation can only be determined within a three-phase system. Connect the probe “L2” to the presumed phase L2 and the probe “L1” with the presumed phase L1. The voltage and the rotating field direction are over the corresponding LEDs are displayed. “R” means that the putative phase L1 is the actual phase L1 and the presumed phase L2 is the actual phase L2, this results in a right spin field. “L” means the putative phase L1 the actual phase L2 and the suspected phase L2 is the actual phase L1, this results in a left spin field. When rechecking with exchanged probes must have the opposite symbol came on.
Low impedance measurement
This feature is especially useful for testing electrical equipment. Due to the lower internal impedance, the capacitive voltage display is suppressed. The display shows the currently applied voltage. When measuring phase “L1” via earth “PE”, residual current circuit breakers (FI or RCD) can be triggered. To trigger the RCD, simultaneously press the low impedance test buttons during the voltage test. If an RCD with a turn-off characteristic of 10 mA or 30 mA / 230V is installed in the circuit, it will trip.
Replacing the batteries
To ensure that the batteries still provide enough voltage for the measurements, short the probes. If no signal sounds or a battery symbol appears in the display, the batteries must be replaced. Make sure that the voltage tester is not connected to any object. Remove the battery compartment by unscrewing the screw on the bottom of the device (see sample image). Pay attention to the correct polarity when inserting the batteries. After replacing the batteries, close the battery compartment and screw it back in place.
Specification
LED‘s
Voltage range| 12V – 1000V AC/DC
Resolution| ± 12,24,50,120,230, 400,690,1000V AC/DC
Accuracy| Complies with EN 61243-3:2014
Frequency range| 0/40Hz up to 400Hz
Response time| ≤ 1 sec.
Auto power off| ≥ 12V AC/DC
LCD Display
Display| 1999 Counts (3 ½ digits) LCD display with backlight
Voltage range| 6V – 1000V AC/DC
Resolution| 1V AC/DC
Accuracy| ± 3,0% + 5 dgt.
Frequency range| 0/40Hz up to 400Hz
Response time| ≤ 1 sec.
Auto power on| ≥ 6V AC/DC
Voltage detection| Automatic
Polarity detection| Full range
Range detection| Automatic
Internal basic load impedance Peak current| Maximum 3,5mA at 1000V 350kΩ /Is
<3,5mA (no RCD
tripping)
Operation time| ~7kΩ
Peak current| Is = 150mA
RCD tripping| ~ 30mA at 230V
Continuity test| 0 – 400kΩ
Accuracy| Nominal resistance ± 50%
Test current| ≤ 5µA
Resistance measurement| 0Ω – 1999Ω
---|---
Resolution| 1Ω
Accuracy| ± (5% + 10 dgt.) at 20°C
Temperature coefficient| ± 5 dgt./ 10K
Test current| ≤ 30µA
Single – pole phase test| 100V – 1000V AC
Frequency range| 50Hz – 400Hz
Rotary field indication|
Voltage range| 100 … 1000V
Frequency range| 50/60Hz
Measurement principle| Double – pole and contact
electrode
Safety standards| EN 61243-3:2014
Agency approvals| TÜV Rheinland – GS
Overvoltage protection| 1000V AC/DC
Measurement category| CATIII 1000V / CATIV 600V
Protection degree| IP 64
Power supply| 2 x 1,5V ‘‘AAA“ Batteries
Power consumption| Max. 30mA
Temperature range| -10 °C up to 55°C
Humidity| Max. 85% relative humidity
Notification about the Battery Regulation
The delivery of many devices includes batteries, which for example serve to
operate the remote control. There also could be batteries or accumulators
built into the device itself. In connection with the sale of these batteries
or accumulators, we are obliged under the Battery Regulations to notify our
customers of the following:
Please dispose of old batteries at a council collection point or return them
to a local shop at no cost. The disposal in domestic refuse is strictly
forbidden according to the Battery Regulations. You can return used batteries
obtained from us at no charge at the address on the last side in this manual
or by posting with sufficient stamps. Contaminated batteries shall be marked
with a symbol consisting of a crossed-out refuse bin and the chemical symbol
(Cd, Hg or Pb) of the heavy metal which is responsible for the classification
as pollutant:
- “Cd” means cadmium.
- “Hg” means mercury.
- “Pb” stands for lead.
All rights, also for translation, reprinting and copy of this manual or parts
are reserved. Reproduction of all kinds (photocopy, microfilm or other) only
by written permission of the publisher. This manual considers the latest
technical knowing. Technical changings which are in the interest of progress
reserved. We herewith confirm, that the units are calibrated by the factory
according to the specifications as per the technical specifications. We
recommend to calibrate the unit again, after 1 year.
© PeakTech® 07/2021/Lie./Ehr.
PeakTech Prüf- und Messtechnik GmbH – Gerstenstieg 4 – DE-22926 Ahrensburg /
Germany
+49-(0) 4102-97398 80 +49-(0) 4102-97398 99
info@peaktech.de
www.peaktech.de
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>