REGENCY CV40E-NG11 Modern Gas Fireplace NYV 40 Instruction Manual

June 14, 2024
Regency

REGENCY CV40E-NG11 Modern Gas Fireplace NYV 40

REGENCY-CV40E-NG11-Modern-Gas-Fireplace-NYV-4

Product Information

This product is the San Francisco Bay CB40E-NG1, a single-sided fireplace manufactured by Regency Fire. It comes in two models, CV40E-NG11 and CV40E- LP11. This fireplace is designed to provide warmth and ambiance to your living space.

It is important to note that this appliance should only be installed and serviced by a qualified installer, service agency, or the gas supplier. Failure to do so may result in serious injury, death, or property damage.

The appliance has been tested and approved by FPI Fireplace Products International Ltd., located in Delta, BC Canada.

One of the key safety features of this fireplace is a barrier provided to reduce the risk of burns from the hot viewing glass. This barrier must be installed for the protection of children and other at-risk individuals.

Product Usage Instructions

Warning: The glass of the fireplace gets hot during operation. Do not touch it until it has cooled down. Never allow children to touch the glass.

Keep the burner and control compartment clean for optimal performance. Refer to the installation and operating instructions that accompany the appliance for detailed guidance on cleaning and maintenance.

If you are using the appliance in CPI (continuous pilot mode), it is important to follow these instructions:

  1. The on-demand pilot features a seven-day safety timer.
  2. Each time the appliance is turned off, the seven-day timer starts again.
  3. The pilot light will remain lit until it is manually shut off if there is no call for heat for five full days.

To relight the pilot after the seven-day inactivity period, simply press the on/off button on the remote control transmitter from on to off and back to on. Once the pilot has re-established operation, normal functionality will resume.

Note: If you are not using the CPI mode, there is no requirement to do anything with the IPI/CPI mode on the remote control transmitter.

For any further information or assistance, please refer to the complete owner’s and installation manual provided with the product.

City Series® Zero Clearance Direct Vent Gas Fireplace

Owners & Installation Manual

San Francisco Bay CB40E-NG1
Installation video

STYLE Single sided

MODEL CV40E-NG11 / CV40E-LP11

http://bit.ly/2vjpzmr
www.regency-fire.com

Warning Fire or explosion Hazard failure to follow safety warnings exactly could result in serious injury, death, or property damage.
– Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

– WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance.
· Do not touch any electrical switch: do not use any phone in your building. Leave the building immediately.
· Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s instructions.
· If you cannot reach your gas supplier, call the fire department.

– Installation and service must be performed by a qualified installer, service agency or the gas supplier.

Tested by :

Certified to/Certifié pour: CSA 2.17-2017 ANSI Z21.88-2019 CSA 2.33-2019

Installer: Please complete the details on the back cover and leave this manual with the homeowner. Homeowner: Please keep these instructions for future reference.

919-927g

FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4

06.12.23

To the New Owner:

Congratulations! You are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The City Series are hand crafted appliances and have been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch. The CV40E City Series has been approved by Intertek for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your Regency® Fireplace.
Front

! DANGER

!

HOT GLASS WILL CAUSE BURNS

DO NOT TOUCH GLASS UNTIL COOLED

NEVER ALLOW CHILDREN TO TOUCH GLASS

A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and must be installed for the protection of children and other at risk individuals.
CAUTION:
HOT WHILE IN OPERATION. DO NOT TOUCH. SEVERE BURNS MAY RESULT. KEEP CHILDREN, CLOTHING, FURNITURE, GASOLINE, AND ANY OTHER LIQUIDS WITH FLAMMABLE VAPOURS AWAY.

KEEP BURNER AND CONTROL COMPARTMENT CLEAN.

SEE INSTALLATION AND OPERATING INSTRUCTIONS ACCOMPANYING

APPLIANCE.

920-408

L’écran pare-étincel contact accidentel a enfants et des perso
ATTENTIO
Risque de brûlure Ne pas toucher l’a Ne pas laisser les vêtements, les me à distance de l’app S’assurer que le b Voir les instruction l’appareil.

920-408

On Demand Pilot (seven day safety timer)
Import4Ian.3snt4tru.7icntfioonrmPlaatteion if using the appliance in CPI (continuous pilot mode) only

This pilot This

aolipgnphlFvg4yltir.ioea3aairnwnp4pacp.ihtn6ehligigceeliassdaesaraivsfene- PatgfnhrreoooternuFoCalttfaesPnmaidIddeecg(scoast2onasunttsreiatynfiampnsucptuoeeelouinmauestnssxffcicuspteehtlilelewaosddltehl)swvebserteihwetnhesittdhhtclahioehmywetsiiestn”somOionfsnpnpitneeDharaceaecCimtft”uiileavoardeinsntsy”dio.n ”pIfICoItPAhsliael- iot2uitgos,Plneaaesi5rnssm.a1yfa4eon.tu4eyr,nfrtteehaLmetauofborteelello.wcwohinnictghrowl tirllasnhsumtitdtoewr. n

the

gas

valve

completely

by

extinguishing

the

Instruction Plate

Each timEeacthheamppaliinanbcuernsehrasllhbuetasrdaowCnla,sms aIInIBuamllyarokrintghrwoiuthghletthteerscaolnl farocmontthraestthinegrmboasctkagtr,otuhneds,elovceantedday timer starts again.

adjacent to the controlling device or in an equally conspicuous position where the instruction can be easily read.

The seven day inactivity timer is controlled within the circuit board. Therefore, if in CPI mode and when the pilot light is extinguished after seven straight days

of inactiAviptyri,l t2h2e/1C4P:ICsreetatitnegd odnratfht e remote control transmitter will remain in the “CPI” (continuous pilot) position. Therefore, all that is required to relight the

pilot woDulodubbeletosidperedss the on/off button on the remote control transmitter from “on” to “off” and back to “on”. Once the pilot has re- established operation will

resume Masatneorriaml:aSl.yTnhtheereticisPnaoperer quirement to do anything with the IPI/CPI mode on the remote control transmitter. If the unSCitiozlneoer5:v.eA9rs6g5so”heWoswaxns5inl.o7na1gr”twHaosrskeven full days without a call for heat, the pilot will remain lit until it is manually shut- off.

If the unit is being operated in IPI (intermittent pilot) mode, neither the above instructions nor the seven day timer will apply.

See the instructions in this manual and on the Lighting Instructions plate on the appliance to light or re-light the pilot.

2 | CV40E-11 City Series

MANUFACTURED MOBILE HOME REQUIREMENTS

INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE This Regency® product has been tested and listed by Intertek as a Direct Vent Wall Furnace to the following standards: to Vented Gas Fireplace Heaters ANSI Z21.88 · CSA 2.33 and Gas-fired Appliances for Use at High Altitudes CSA 2.17-2017. This Direct Vent System Appliance must be installed in accordance with the manufacturer’s installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada. This appliance installation must comply with the manufacturer’s installation instructions and local codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A., and the current CSA B149.1 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada. This Regency® mobile/manufactured home listed appliance comes factory equipped with four 1/4″ diameter holes located near each corner of the base. Fasten the fireplace in place using screw, inserted through the holes. This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as applicable to local codes. See the “Wiring Diagram” section. The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1. This appliance may only be installed in an aftermarket permanently located, manufactured home (U.S.A only) or mobile home, where not prohibited by local codes. This appliance can only be used with the type of gas indicated on the rating plate. This appliance is not convertible for use with other cases, unless a certified kit is used. Ensure that structural members are not cut or weakened during installation.
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible fore use with other gases, unless a certified kit is used.
CV40E-11 City Series | 3

Safety decal

This is a copy of the label that accompanies Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review. The safety label is located on the front inside base of the unit, visible when the outer front panel is removed.
NOTE: Regency® units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
Copy of Safety Decal

Duplicate S/N

484

C #: 4001172

Listed/Nom: VENTED GAS FIREPLACE HEATERS / APPAREIL DE CHAUFFAGE AU GAZ À ÉVACUATION. Certified to/Certifié : ANSI Z21.88-2019 · CSA-2.33-2019
CSA 2.17-2017 MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE.
Refer to Intertek’s Directory of Building Products for detailed information. Pour plus de détails, se reporter au Répertoire des produits de construction de Intertek.

DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE Serial No./ No de série
484

NATURAL GAS: Model: CV40E-NG11/CB40E-NG11

Minimum supply pressure 5.0″ WC/C.E. (1.25kPa)

Manifold pressure – High 3.8″ WC/C.E. (0.94kPa)

Manifold pressure – Low 1.1″ WC/C.E. (0.27 kPa)

Orifice size

42 DMS

Maximum input

28,500 Btu/h (8.33 kW)

Minimum input

15,500 Btu/h (4.54 kW)

Altitude

0-4500 ft/pi (0-1372 m)

PROPANE GAS: Model: CV40E-LP11/CB40E-LP11

Minimum supply pressure 11″

WC/C.E. (2.73 kPa)

Manifold pressure – High 10.5″ WC/C.E. (2.62 kPa)

Manifold pressure – Low 2.9″ WC/C.E. (0.72 kPa)

Orifice size

53 DMS

Maximum input

28,500 Btu/h (8.35kW)

Minimum input

15,500 Btu/h (4.54 kW)

Altitude

0-4500 ft/pi (0-1372 m)

APPAREIL FONCTIONNANT AU GAZ NATUREL Modèle CV40E-NG11/CB40E-NG11 Pression d’alimentation minimale Pression de sortie (manifold) – Haute Pression de sortie (manifold) – Basse Taille de l’orifice Débit calorifique maximal Débit calorifique minimal Altitude
APPAREIL FONCTIONNANT AU GAZ PROPANE Modèle CV40E-LP11/CB40E-LP11 Pression d’alimentation minimale Pression de sortie (manifold) – Haute Pression de sortie (manifold) – Basse Taille de l’orifice Débit calorifique maximal Débit calorifique minimal Altitude

Minimum Clearances to Combustibles / Dégagements minimaux par rapport aux matériaux combustibles

Min. 120in²
D C

B F
A

E

DOOR SEAL: Please check that the door is
properly sealed

Side Walls / Murs latéraux

A 8.5″ (216 mm)

Ceiling / Plafond

B

37-1/2″ (953 mm)

Min. Mantel Height /Hteur Min

Manteau

C 9″ (229 mm) with 12″ mantel

Max. Mantel Depth/Profondeur Max

Manteau

D 12″ (305 mm)

Alcove Width/Largeur Alcôve

E 84″ (1524 mm)

Alcove Depth/Profondeur Alcôve

F 36″ (2134 mm)

(See Instruction Manual for detailed instructions) (Voir manuel pour plus de détails)

This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1, or Natural Gas and Propane Installation Code, CSA B149.1.

This appliance must be installed in accordance with the Standard CAN/CSA Z240 MH, Mobile Housing, in Canada, or with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the

United States, or when such a standard is not applicable, ANSI/NCSBCS A225.1/NFPA 501A, Manufactured Home Installations Standard or ANSI A119.2 ou NFPA 501C Standard for Recreational Vehicles

This appliance is only for use with the type(s) of gas indicated on the rating plate and may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by

local codes. See owner’s manual for details. This appliance is supplied with a conversion kit.

L’appareil doit être installé conformément aux codes et règlements locaux, ou, en l’absence de tels règlements, selon les codes d’installation National Fuel Gas Code ANSI Z223.1, ou CSA-B149.1 Natural Gas and

Propane Installation Code en vigueur.

L’appareil doit être installé conformément à la norme CAN/CSA-Z240, Série MM, Maisons mobiles ou CAN/CSA-Z240 VC, Véhicules de camping, ou la norme 24 CFR Part 3280, Manufactured Home Construction

and Safety Standard. Si ces normes ne sont pas applicables, veuillez vous référer à la norme ANSI/NCSBCS A225.1/NFPA 501A, Manufactured Home Installations Standard, ou ANSI A119.2 ou NFPA 501C

Standard for Recreational Vehicles.

Cet appareil doit être utilisé uniquement avec les types de gaz indiqués sur la plaque signalétique et peut être installé dans une maison préfabriquée (É.-U. seulement) ou mobile installée à demeure si les règlements

For Use Only with Barrier CV40E – 1 sided (Part # 940-435/P) & CB40E 3 sided (Part # 940-438/P,940-439/P,940-440/P) Follow installation instructions. FPI Fireplace Products International Ltd.

Utiliser uniquement avec l’écran CV40E -1 face (n°940-435/P) & CB40E – 3 faces (n°940-438/P,940-439/P,940-440/P) . Suivre les instructions d’installation.

Delta, BC, Canada

FOR USE WITH GLASS DOORS CERTIFIED WITH THE APPLIANCE ONLY À UTILISER AVEC LES PORTES VITRÉES HOMOLOGUÉES POUR L’APPAREIL

Electrical supply / Alimentation électrique 115VAC, 1.5 A, 60Hz.

Part No. 946-556 Heatwave Kit may be used. Le système Heatwave (pièce n°946-556) peut être utilisé.

VENTED GAS FIREPLACE – NOT FOR USE WITH SOLID FUELS. CATEGORY I.

FOYER AU GAZ À ÉVACUATION – NE PAS UTILISER AVEC UN COMBUSTIBLE SOLIDE. CATÉGORIE I.

Made in Canada/ Fabriqué au Canada

Model/Modèle :

CV40E-NG11

CV40E-LP11

CB40E-NG11

CB40E-LP11

EP5011169

CANADIAN ENERGY PERFORMANCE VERIFIED
RENDEMENT ÉNERGÉTIQUE
VÉRIFIÉ

CSA P.4.1 Fireplace Efficiency (FE) /Efficacité énergétique des foyers (EEF) CSA P.4.1 Natural Gas / Gaz naturel 55.23% Propane Gas / Gaz propane 56.06%

919-929b

FagonarsdPCSMtaifoarzhiretletoettepe:u#rarSir:ai:trllai:ctmeenuosseft dMb (9BeianF1lsaid9sltecoah- k9cnea2heot9uCn1bsbo0geym0rt%etmasy,)openi9nlxuw.cs1mtee8aapbl”lltWetahwrtihoxoonarf6t.1is9i8n”dHicDateedcaaslbeLinogcparitniteodnred.
MaOsscatc. h1u5s/1et8t:s. Created draft
Nov. 05/18: New Serial # ForNothve20S/1ta8t:e of AMddaessdaecfhfiucsieentctsie, sfalesxpibelreR/D conJnaenct2o3r/s1s9h:all notRexecveAed-3R6einmcohdeesliendlednegctahl. + added ETL logo at the bottom
Sept. 7/22: Rev B – Updated standards + wording For the State of Massachusetts, the appliances individual manual shut-off must be a t-handle type valve.

Remove barrier glass from unit (refer to manual) lift out the outer liner base glass once the glass has been removed the rating plate will be attached to a small black chain as seen below.
DO NOT REMOVE DECAL FROM UNIT

The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed.

CV40E-11 City Series | 5

dimensions
CV40E Dimensions

Ø

6

3 4

171mm

Ø 4″ 102mm

21

7 8

556mm

40 ”

1016mm

46

1 4

“”

1175mm

11

7 16

291mm

7

1 4

183mm

Gas Line Entry

18

11 16

475mm

17

11 16

449mm

2” (51mm)

3-1/2” (89mm)

13” (330mm)

200mm

7 8

7

949mm

3 8

37

879mm

5 8

382mm

1 16

34

15

849mm

7 16

33

648mm

25 196″

267mm

1 2

10

43″ 1091mm
Note: Electrical connection on left hand side of the appliance. A metal receptacle box is supplied/installed with the appliance to make all 120 volt electrical connections.
Note: Height Dimension may vary depending on the height of the leveling legs. Dimensions will appear as (inches)” / (metric)mm throughout this manual. The inches are rounded to the nearest 1/16″ when converted, when greater accuracy is required, use the metric dimensions.
Note: These units are non-load bearing.
ALL PICTURES / DIAGRAMS SHOWN THROUGHOUT THIS MANUAL ARE FOR ILLUSTRATION PURPOSES ONLY. ACTUAL PRODUCT MAY VARY DUE TO PRODUCT ENHANCEMENTS.
6 | CV40E-11 City Series

Gas Installation Checklist

dimensions

This general checklist does not contain all pertinent installation details or specifics and does not supersede the guidelines in this manual. Your Regency dealer/installer should use it in conjunction with manual instructions. Please follow all local codes and jurisdictions in authority.

Customer:

Date Installed:

Install Address: Serial No: Model No:

Location of Fireplace: Installer:

Site Requirements

YES NO

If applicable, are the insulation, vapour barrier, and drywall present if installed on an outside wall or chase?
Does the area have a solid continuous base to support the unit? Will the area accommodate the size of the applliance and all clearances? Are the gas and electrical roughed into the area where the unit is being installed?
In City & Grandview series cool wall applications, is the chase enclosure sealed to prevent heat from escaping? All hot air from the unit must exit via the mandatory ventilation openings. In City & Grandview applications, Is the chase enclosure vented with the mandatory heat ventilation openings? See manual for details. If applicable, is the masonry/factory built freplace in its original condition with no modifications?
If applicable, have the hearth requirements been met?
Unit Setup

YES NO

If applicable, are the standoffs and top nailing flange extensions installed and at the correct depth to accommodate finishing material? See manual for details. If applicable, is the fireplace level and secured, meeting framing clearances? See manual for details. If applicable, is the unit converted to top or rear vent per manual instructions, and the insulation discarded?
Venting

YES NO

Are the venting components approved for the unit installed? Does the venting configuration comply with venting diagrams? Is venting installed and secured, and are clearances for the vent pipe and termination cap maintained? If applicable, was a 1/4″ rise maintained for every foot of horizontal run? Was the termination installed and sealed? Is the direct vent termination at the highest point in the vent assembly? If applicable, are both chimney liners continuous from flue collars to termination? Electrical and Wiring

YES NO

Is the appliance connected to the household’s 110/120v per local codes? Check local codes for receptacle placement. Were the connections in the fireplace tested with a circuit tester? Is the appliance properly grounded? If applicable, is the supplied electrical/gang box affixed to the wall to facilitate the mounting of the receiver/battery box ? Gas

YES NO

Does the supply pressure meet the requirements shown on the rating plate? Was a conversion performed? Was a leak check performed and manifold pressures verified? Is the shut-off valve installed and easily accessible to the customer?

CV40E-11 City Series | 7

installation
Finishing If applicable, is only noncombustible material installed in the noncombustible areas? Do clearances meet installation and manual requirements? Do the mantels and/or projections comply with the installation manual? If applicable, was the solid fuel fireplace warning plate installed? Appliance Media Setup Do commands from the remote or wall switch light the pilot and main burner? Are the burner media/log set, glass door, and screen installed per instructions in the manual? Was the air shutter on the proper setting after running the unit for 20 minutes? If applicable, were the surround and trims installed according to the manual? Was the operation of the fan, lights (if installed), and flame modulation checked? Customer Tutorial and Presentation Is the customer confident operating the new gas appliance and aware of all the features on the remote? Confirm that the rating and lighting plates are attached to the appliance. Do not remove. Was the customer informed of the location of the rating and lighting plates? Was accessing unit controls in a power outage explained to the customer? Are the model and serial numbers and the date of installation of the unit written in the manual and on the checklist? Were the warranty and unit registration reviewed with the customer? Comments:

YES NO YES NO YES NO

8 | CV40E-11 City Series

Important Message
SAVE THESE INSTRUCTIONS
City Line Direct Vent Fireplaces must be installed in accordance with these instructions. Carefully read all the instructions in this manual first. Consult the “authority having jurisdiction” to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fireplace is installed in compliance with manufacturer’s instructions and all applicable codes.
Before You Start
Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following:
INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.

CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME AREA AS THE APPLIANCE. TODDLERS, YOUNG CHILDREN AND OTHERS MAY BE SUSCEPTIBLE TO ACCIDENTAL CONTACT BURNS. A PHYSICAL BARRIERS IS RECOMMENDED IF THERE ARE AT RISK INDIVIDUAL IN THE HOUSE. TO RESTRICT ACCESS TO A FIREPLACE OR STOVE, INSTALL AN ADJUSTABLE SAFETY GATE TO KEEP TODDLERS, YOUNG CHILDREN AND OTHER AT RISK INDIVIDUALS OUT OF THE ROOM AND AWAY FROM HOT SURFACES.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
A BARRIER DESIGNED TO REDUCE THE RISK OF BURNS FROM THE HOT VIEWING GLASS IS PROVIDED WITH THIS APPLIANCE AND SHALL BE INSTALLED FOR THE PROTECTION OF CHILDREN AND OTHER AT-RISK INDIVIDUALS.

owner’s information
WE RECOMMEND REMOVING THE GLASS WITH THE GLASS VACUUM HOLDERS SUPPLIED BY THE MANUFACTURER. LOWER THE GLASS TO REST IN A SAFE PLACE. THIS IS TO PREVENT DAMAGE TO THE GLASS EDGES. EXTRA CARE MUST BE TAKEN WHEN REMOVING/INSTALLING THE GLASS. BREAKAGE OR DAMAGE TO THE EDGE OF THE GLASS WHICH OCCURS AS A RESULT OF CARELESS HANDLING WILL NOT BE COVERED UNDER WARRANTY.

WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.

ANY SAFETY SCREEN, GUARD, OR BARRIER REMOVED FOR SERVICING THE APPLIANCE, MUST BE REPLACED PRIOR TO OPERATING THE APPLIANCE.

IF THE BARRIER BECOMES DAMAGED, THE BARRIER SHALL BE REPLACED WITH THE MANUFACTURER’S BARRIER FOR THIS APPLIANCE.

CV40E-11 City Series | 9

owner’s information
General Safety Information
1. The appliance installation must conform with local codes or, in the absence of local codes, with the current Canadian or National Gas Codes, CSA B149.1 or ANSI Z223.1 Installation Codes.
2. See general construction and assembly instructions. The appliance and vent should be enclosed.
3. This appliance must be connected to the specified vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fitted as per Venting instructions.
4. Inspect the venting system annually for blockage and any signs of deterioration.
5. Venting terminals shall not be recessed into a wall or siding.
6. Any safety glass removed for servicing must be replaced prior to operating the appliance.
7. To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fireplace.
8. Wear gloves and safety glasses for protection while doing required maintenance.
9. Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination.
10. Under no circumstances should this appliance be modified. Parts that have to be removed for servicing should be replaced prior to operating this appliance.
11. Installation and any repairs to this appliance should be done by a qualified service person. A professional service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.
12. Do not slam shut or strike the glass door.
13. Under no circumstances should any solid fuels (wood, paper, cardboard, coal, etc.) be used in this appliance.
14. The appliance area must be kept clear and free of combustible materials (gases and other flammable vapours and liquids).
10 | CV40E-11 City Series

owner’s information

Lighting Procedure
IMPORTANT: The remote control system supplied with this appliance has several options for starting/operating the appliance using the battery holder and ON/OFF key on the hand held transmitter. Prior to operating this appliance, please read the remote control operating instructions (packaged with remote control) to understand how to operate this remote control system.
1. Ensure the battery holder switch is in the Remote position and / or wall mounted battery holder (if equipped) is in the position.
2. Press and release the ON/OFF button on the remote handheld transmitter (see Diagram 1). An audible beep should be heard from the receiver. If not using the remote, the unit can also be turned on by sliding the battery holder switch to the position (if equipped).

Note: The first try for ignition will last approximately 60 seconds. If there is no flame ignition (rectification) the board will stop sparking for approximately 35 seconds. After wait time , the board will start second try for ignition by sparking for approximately 60 seconds . If there is still no positive ignition the board will go into lock out.
The system will need to be reset as follows:
a) Turn the system off by pressing the ON/OFF button on the remote. b) Wait 5 minutes then repeat from step 2.
Shutdown Procedure
1. Press the ON/OFF button on the remote

2. If service is to be performed- you must disconnect power and shut off gas to the unit.

ON/OFF

Button

Diagram 1

  • Remote shown in Manual Mode on Hi

3. After approximately 4 seconds the spark ignition system will spark for 60 seconds to light the pilot.

4. The unit will turn on.

  • Not offered on all models. Continuous Pilot/Intermittent Pilot (CPI/IPI) selection See remote control instructions for details.

On Demand Pilot (seven day safety timer)
Important information if using the appliance in CPI (continuous pilot mode) only
This appliance is a ProFlame 2 system fitted with the “On Demand” Pilot, a safety feature which will shut down the gas valve completely by extinguishing the pilot light in the event of a continuous full seven days of inactivity. This only applies if the CPI (continuous pilot) switch is in the “on” position in your remote control transmitter.
Each time the main burner shuts down, manually or through the call from the thermostat, the seven day timer starts again.
The seven day inactivity timer is controlled within the circuit board. Therefore, if in CPI mode and when the pilot light is extinguished after seven straight days of inactivity, the CPI setting on the remote control transmitter will remain in the “CPI” (continuous pilot) position. Therefore, all that is required to relight the pilot would be to press the on/off button on the remote control transmitter from “on” to “off” and back to “on”. Once the pilot has re-established operation will resume as normal. There is no requirement to do anything with the IPI/CPI mode on the remote control transmitter. If the unit never goes as long as seven full days without a call for heat, the pilot will remain lit until it is manually shut-off.
If the unit is being operated in IPI (intermittent pilot) mode, neither the above instructions nor the seven day timer will apply.
See the instructions in this manual and on the Lighting Instructions plate on the appliance to light or re-light the pilot.
CV40E-11 City Series | 11

owner’s information

Copy of the Lighting Plate Instructions

FOR YOUR SAFETY READ BEFORE LIGHTING POUR VOTRE SÉCURITÉ ­ À LIRE AVANT LA MISE EN MARCHE
This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Natural Gas and Propane Installation Codes, CSA B149.1. Cet appareil doit être installé conformément aux codes locaux, s’il y a lieu. En l’absence de tels codes, suivre le National Fuel Gas Code, ANSI Z223.1/NFPA 54, ou les Natural Gas and Propane Installation Codes, CSA B149.1.
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to the owner’s information manual provided with this appliance. For assistance or additional information consult a qualified installer, service agency or gas supplier.
AVERTISSEMENT : Quiconque ne respecte pas scrupuleusement les instructions de la présente notice risque de déclencher un incendie ou une explosion pouvant entraîner des dégâts matériels ou des blessures pouvant être mortelles. Tout défaut d’installation, de réglage, de modification, de service ou d’entretien peut entraîner des blessures ou des dommages matériels. Reportez-vous au manuel d’utilisation fourni avec cet équipement. Pour obtenir de l’aide ou des informations complémentaires, consulter un installateur ou un service d’entretien qualifié, ou le fournisseur de gaz.
A) This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.
B) BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS – Do not try to light any appliance. – Do not touch any electric switch, do not use any phone in your building. – Immediately call your gas supplier from a neighbours phone. Follow the gas supplier’s instructions. – If you cannot reach your gas supplier, call the fire department. C) Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and replace any part of the control system and any gas control which has been underwater.
A) Cet appareil est muni d’un dispositif d’allumage qui allume automatiquement la veilleuse. Ne tentez pas d’allumer la veilleuse manuellement.
B) AVANT LA MISE EN MARCHE, reniflez tout autour de l’appareil pour déceler une odeur de gaz. Reniflez au niveau du plancher, car certains gaz sont plus lourds que l’air et peuvent s’accumuler au niveau du sol.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
· Ne tentez pas d’allumer l’appareil · Ne touchez à aucun interrupteur; n’utilisez pas de téléphones se trouvant dans le bâtiment. · Appelez immédiatement votre fournisseur de gaz depuis un téléphone extérieur. Suivez les instructions du fournisseur. · Si vous ne pouvez pas rejoindre le fournisseur, appelez le service incendie.
C) N’utilisez pas cet appareil s’il a été plongé dans l’eau, même partiellement. Faites inspecter l’appareil par un technicien qualifié et remplacez tout élément du système de contrôle ou de commande qui a été plongé dans l’eau.
CAUTION: Hot while in operation. Do not touch. Severe burns may result. Due to high surface temperatures keep children, clothing and furniture, gasoline and other liquids having flammable vapors away. Keep burner and control compartment clean. See installation and operating instructions accompanying appliance.
ATTENTION : Surfaces chaudes lorsque l’appareil est en marche. Ne pas toucher. Risque de brûlures graves. En raison des températures élevées, les enfants, les vêtements et le mobilier, le carburant et tout autre liquide aux vapeurs inflammables doivent être tenus éloignés de l’appareil. Nettoyer régulièrement le brûleur et le compartiment des commandes. Voir les consignes d’installation et d’utilisation fournies avec l’appareil.

LIGHTING INSTRUCTIONS / CONSIGNES D’ALLUMAGE

  1. Ensure the Main switch is in the ON position and/or the wall mounted battery holder (if equipped) is in the position.

  2. Press and release the ON/OFF button on the remote handheld transmitter. An audible beep should be heard from the receiver. If not using the remote, the unit can also be turned on by sliding the battery holder switch to the position (if equipped).

  3. After approximately 4 seconds the spark ignition system will spark for 60 seconds to light the main burner.

  4. The unit will turn on. Note: The first attempt to ignition will last approximately 60 seconds. If there is no flame ignition (rectification) the board will stop sparking for approximately 35 seconds. After this wait time, the board will start a second try for ignition by sparking for approximately 60 seconds. If there is still no positive ignition after the second attempt the board will go into lock out. The system will need to be reset as follows (after going into lock out mode):
    a) Wait 5 minutes – turn the system off by pressing the ON/OFF button on the remote. b) After approximately 2 seconds press the ON/OFF button again. c) Unit will repeat step 2.

  5. S’assurer que le commutateur principal est en position ON et/ou que le bloc-piles mural (le cas échéant) est en position . 2) Appuyer sur la touche ON/OFF de la télécommande puis relâcher. Un bip sonore retentira depuis le récepteur. Si vous n’utilisez pas
    la télécommande, l’appareil peut également être allumé en faisant glisser le commutateur du bloc-piles sur la position (le cas échéant). 3) Après environ 4 secondes, le système d’allumage produira une étincelle pendant 60 secondes pour allumer le brûleur principal. 4) L’appareil s’allumera. Remarque : Au premier allumage, le système tente d’allumer les flammes pendant 60 secondes. Si l’essai est infructueux, le système fera une pause de 35 secondes. C’est ce qu’on appelle l’étape de rectification. Ce délai écoulé, le système tente à nouveau d’allumer les flammes en produisant des étincelles pendant 60 secondes. Si les flammes ne s’allument toujours pas, le système se met en mode verrouillage.
    Il faut alors le réinitialiser en suivant les étapes ci-dessous (pour le déverrouiller) : a) Attendre 5 minutes et éteindre l’appareil en appuyant sur la touche ON/OFF de la télécommande. b) Attendre 2 secondes et appuyer encore une fois sur la touche ON/OFF. c) L’appareil répètera l’étape 2.
    TO TURN OFF GAS APPLIANCE / POUR ÉTEINDRE UN APPAREIL AU GAZ

  6. Press the ON/OFF button on the remote. 2) If service is to be performed­you must disconnect power and shut off gas to the unit. 1) Appuyer sur la touche ON/OFF de la télécommande. 2) Lors de l’entretien de l’appareil, vous devez débrancher l’alimentation électrique et couper le gaz alimentant l’appareil.
    DO NOT REMOVE THIS INSTRUCTION PLATE
    NE PAS ENLEVER CETTE ÉTIQUETTE D’INSTRUCTIONS

919-649

12 | CV40E-11 City Series

Proflame II Remote Control Operating Instructions

owner’s information

IMPORTANT:The Proflame Transmitter 2 is an integrated part of the

Proflame 2 System, which consists of these elements:

·

Proflame 2 Transmitter, to be used in conjunction with:

·

Integrated Fireplaces Control (Proflame 2 IFC)

The Proflame 2 Transmitter provides for controlling the following hearth

appliance functions:

Main Burner On/Off

Main Burner flame modulation (6 levels)

Choice of standing or intermittent pilot (CPI/IPI)

Thermostat and Smart thermostat functions

Accent light modulation (6 levels)**

Split flow valve**

Comfort Fan speed modulation (6 levels)**

** This feature is not available on all models.

TECHNICAL DATA REMOTE CONTROL

Supply Voltage

4.5V (three 1.5V AAA batteries)

Ambient temperature ratings
Radio Frequency

0 – 50oC (32 – 122oF) 315 MHZ

WARNING:THETRANSMITTER AND RECEIVER ARE RADIO FREQUENCY DEVICES. PLACING THE RECEIVER IN OR NEAR METAL MAY SEVERELY REDUCETHE SIGNAL RANGE.

The Proflame Transmitter uses a streamline design with a simple button layout and informative LCD display (Fig. 1). A Mode Key is provided to index between the features and a Thermostat Key is used to turn on/off or index through Thermostat functions (Fig. 1 & 2). Additionally, a Key Lock feature is provided (Fig. 22).

ATTENTION!
– Turn “OFF” the main gas supply of the appliance during installation or maintenance of the Receiver device.
– Turn “OFF” main gas supply to the appliance prior to removing or reinserting the batteries.

– In case of remote control malfunction, turn off the IFC device using the “ON/OFF” main switch.

– For installation / maintenance, switch off the IFC device removing main power supply plug.

Figure 1: Proflame Transmitter

OPERATING PROCEDURE
Pairing the remote control to remote receiver/battery holder (if required)
Power the receiver. Press the ”PRG” button located on the top right hand corner of receiver/battery holder, see the receiver instruction (). The Receiver will “beep” three (3) times to indicate that it is ready to synchronize with a Transmitter. Install the 3 AAA type batteries in the Transmitter battery bay, located on the base of the Transmitter. (Fig. 3) With the batteries already installed in the Transmitter, push the On button. The Receiver will “beep” four times to indicate the Transmitter’s command is accepted and sets to the particular code of that Transmitter. The system is now initialized.
(
) The receiver may be independent or integral to the IFC hearth appliance control module. The receiver instruction may not be independent when part of the IFC.

Figure 2: Transmitter LCD Display

Figure 3: Battery Compartment
CV40E-11 City Series | 13

owner’s information

Temperature indication Display

Remote-Flame Control

With the system in the “OFF” position, press the Thermostat Key and the Mode Key at the same time. Look at the LCD screen on the transmitter to verify that a C or F is visible to the right of the room temperature display (Figures 4 & 5).

The proflame has six (6) flame levels. With the system on, and the flame level at the maximum in the appliance, pressing the Down Arrow Key once will reduce the flame height by one step until the flame is turned off. The Up Arrow Key will increase the flame height each time it is pressed. If the Up Arrow Key is pressed while the system is on but the flame is off, the flame will come on in the high position. ( Fig. 7 & 8 ) A single “beep” will confirm reception of the command.

Figure 4: Remote Control display in Farenheit.

Figure 5: Remote Control display in Celsius.

Fig. 7

Turn on the Appliance
With the system OFF, press the ON/ OFF Key on the Transmitter. The Transmitter display will show some other active Icons on the screen. At the same time the Receiver wil activate the appliance. A single “beep” from the Receiver will confirm reception of the command.

Fig. 8
Room Thermostat (Transmitter Operation)

Figure 6: Remote Control display
Turn off the Appliance
With the system ON, press the ON/OFF Key on the Transmitter. The Transmitter LCD display will only show the room temperature (Fig. 6). At the same time the Receiver will turn off the appliance. A single “beep” from the Receiver confirms reception of the command.

The Remote Control can operate as a room thermostat. The thermostat can be set to a desired temperature to control the comfort level in a room. To activate this function, press the Thermostat Key (Fig. 1). The Lcd display on the Transmitter will change to show that the room thermostat is “ON” and the set temperature is now displayed (Fig. 9). To adjust the set temperature, press the Up or Down Arrow Keys until the desired set temperature is displayed on the LCD screen of the Transmitter.

14 | CV40E-11 City Series

Figure 9

Figure 10

owner’s information

Smart Thermostat (Transmitter Operation)

Remote dimmer control (Light)**

The Smart Thermostat function adjusts the flame height in accordance to the difference between the set point temperature and the actual room temperatures. As the room temperature gets closer to the set point the Smart Function will modulate the flame down. To activate this function, press the Thermostat Key (Fig. 1) until the word “SMART” appears to the right of the temperature bulb graphic (Fig. 11). To adjust the set temperature, press the Up or Down Arrow Keys until the desidered set temperature is displayed on the LCD screen of the Transmitter (Fig. 12). Note. When Smart Thermostat is activated, manual flame height adjustment is disabled.

The auxiliary function controls the AUX power outlet by the dimmable light control. To activate this function use the Mode Key (fig. 1) to index to the AUX icon (fig. 15 & 16). The intensity of the output can be adjusted through six (6) levels. Use the Up/Down Arrow Keys (fig.1) adjust the output level (fig. 16). A single “beep” will confirm reception of the command.
Note: This function is available only with the IFC Control Module.

Figure 15

Figure 16

Figure 11: Smart Flame Function

Figure 12

Split Flow control**

Fan Speed Control**
If the appliance is equipped with a hot air circulating fan, the speed of the fan can be controlled by the Proflame system. The fan speed can be adjusted through six (6) speeds.To activate this function use the Mode Key (fig.1) to index to the fan control icon (Fig. 13). Use the Up/Down Arrow Keys (fig.1) to turn on, off or adjust the fan speed (fig. 14). A single “beep” will confirm reception of the command.

The secondary burner is controlled by the split Flow. To activate this function use the Mode Key (fig. 1) to index to the SPLIT FLOW mode icon (fig. 17 & 18). Pressing the Up Arrow Key will activate the secondary burner. Pressing the Down Arrow Key will turn the secondary burner off. A single “beep” will confirm the reception of the command.

Figure 13

Figure 14

Figure 17

Figure 18

CV40E-11 City Series | 15

owner’s information

Continuous Pilot/Intermittent Pilot (CPI/IPI) selection
Note: Power vent models do not have a Continuous Pilot option.
With the system in “OFF” position press the Mode Key (fig. 1) to index to the CPI mode icon (fig. 19 & 20). Pressing the Up Arrow Key will activate the Continuous Pilot Ignition mode (CPI). Pressing the Down Arrow Key will return to IPI. A single “beep” will confirm the reception of the command.

5. “Clr” will remove the mode by using the up or down arrow while still holding both buttons (icon will disappear once removed, or icon will show up again once added).
6. Use the “Mode” button to move to the next function. 7. “Set” will add that mode by using the up or down arrow while still
holding both buttons (icon will disappear once removed, or icon will show up again once added) Use the “Mode” button to move to the next function. Note: You should never program out the fan (if installed) or CPI/IPI
mode on the remote.
KEY LOCK
This function will lock the keys to avoid unsupervised operation. To activate this function, press the MODE and UP Keys at the same time (fig. 21). To de- activate this function, press the MODE and UP Keys at the same time.

Figure 19

Figure 20

CPI/IPI SWITCH

This appliances comes equipped with a CPI/IPI switch. The function of both the CPI/IPI switch are as follows: Continuous pilot (CPI) – A pilot that when in operation, is intended to remain continuously ignited until it is manually interrupted. Intermittent pilot (IPI) – A pilot that is automatically ignited when an appliance is called on to operate and which remains continuously ignited during each period of main burner operation. The pilot is automatically extinguished when each main burner operating cycle is completed. The mode of the fireplace is easily changed from an intermittent pilot ignition system (IPI) to a continuous pilot ignition system (CPI) by using remote control as noted above. The benefits of having as CPI are as follows: -Keeps venting primed for trouble free start-up under colder weather conditions or inversions. -Keeps the unit glass warm, which decreases the amount of condensation on start-up -Provides owners with flexibility to choose a traditional continuous pilot. The primary benefit of having the IPI function is a significant savings on fuel as the pilot will only run when there is a call for heat.
Thermostat Icon: If the thermostat icon is not present on the remote transmitter, follow instructions noted below 1.Take one or all batteries out (removing one battery will work). 2. Press and hold down the Thermostat button on the remote. 3. Reinstall the 3rd battery while still holding thermostat button down. 4. If you see “Set” the thermostat option is now enabled. If you see “Clr”
the thermostat option is now disabled 5. Repeat the procedure if you did not see the “Set” or “Clr” to remove
or add the option back to the remote.
Enable all other functions if not present on the remote transmitter, follow instructions noted below: 1. Remove one battery or all batteries (removing one battery will work). 2. Press and hold both the ON/OFF and the MODE button at the same time . 3. Reinstall the 3rd battery while still holding both buttons (keep holding
buttons once 3rd battery is installed, then release the mode button only. 4.The screen will show either “Clr” or “Set” with the 1st mode being
your option to disable or enable.

Figure 21
LOW BATTERY POWER DETECTION Transmitter
The life span of the remote control batteries depends on various factors: quality of the batteries used, the number of ignitions of the appliance, the number of changes to the room thermostat set point, etc. When the Transmitter batteries are low, a Battery Icon will appear on the LCD display of the Transmitter (Fig. 22) before all battery power is lost. When the batteries are replaced this Icon will disappear.
Figure 22

16 | CV40E-11 City Series

owner’s information

Proflame II Battery Holder Battery Replacement & Battery Pack up if 120 Volt Power is lost

How to replace/add the batteries on battery holder (Proflame 2).

Note : If a wall switch cover plate is installed, first remove cover plate by removing 2 small phillips head screws

STEP 1

Move both the left/right slides as shown below.

The battery compartment will be pushed out slightly, to allow to easily extract it

STEP 2

Extract the battery compartment from the remote receiver/battery holder

Replace 4 x AA batteries and insert the battery compartment back into remote receiver/battery holder

STEP 3

Keeping the battery compartment pressed in, close the left slide

Close the right slide

STEP 4 Reinstall wall cover plate with 2 Phillips head screws.

CV40E-11 City Series | 17

owner’s information

Inner Glass Panel (Firebox Glass) Installation / Removal

To watch the firebox installation video click here. Note: glass panels must be installed to operate fireplace

WARNING: GLASS HANDLING

Press glass vacuum clamps in open position firmly onto surface of glass. Bring handles together to close.

We recommend using the glass vacuum holders supplied by the manufacturer. Lower the glass to rest in a safe place, this is to prevent damage to the glass edges. Extra care must be taken when removing/installing the glass. Breakage or damage to the edge of the glass which occurs as a result of careless handling will not be covered under warranty.

· We recommend handling the glass with supplied vacuum clamps
· When removing glass­prepare a soft, scratch resistant surface to place the glass
· Never clean or remove hot glass Note: The suction cups may leave a round film on the glass when used. Ensure that the glass is cleaned using a fireplace glass cleaner prior to operating the appliance.

Open

Closed

Important: Prior to installing the inner glass, ensure that there is no media present in the bottom channel as this can cause damage to the glass. Remove any media from bottom channel prior to installing the glass.

1. Remove outer safety glass panels if previously installed­see instructions in this manual.
2. Remove outer panels installed in units – see panel removal section in this manual.
3. Ensure all 7 front clamps are in the open position to allow clearance for the glass.

Handle front panel with supplied vacuum clamps
5. To remove the glass panels–always remove the side panel(s) (for 3 sided units) before removing the front panel.
6. Reverse steps to remove glass.

Open 7 clamps prior to placing front glass panel
4. Lift up the front panel using the supplied vacuum clamps and position into the lower front channel­ensure the front panel is accurately centered–with the front panel in position–secure in place by closing the 3 lower clamps and 4 upper clamps.
18 | CV40E-11 City Series

owner’s information

Outer Safety Glass Panel (Barrier Glass) Installation / Removal

To watch the safety barrier glass installation video click here.

Note: safety glass panels must be installed to operate fireplace

WARNING: GLASS HANDLING
We recommend using the glass vacuum holders supplied by the manufacturer. Lower the glass to rest in a safe place, this is to prevent damage to the glass edges. Extra care must be taken when removing/installing the glass. Breakage or damage to the edge of the glass which occurs as a result of careless handling will not be covered under warranty.

3. Tilt the top of the glass panel inward and lift up and underneath the upper front panel of the outside frame. Hook the glass panel onto the pins and also onto the two angle adjustment brackets located on the frame in two locations as shown in the diagram below.
Note: The front frame upper panel is shown as transparent to better illustrate the install (this area is not visible when installing glass).

· We recommend handling the glass with supplied vacuum clamps
· When removing glass­prepare a soft, scratch resistant surface to place the glass
· Never clean or remove hot glass Note: The suction cups may leave a round film on the glass when used. Ensure that the glass is cleaned using a fireplace glass cleaner prior to operating the appliance.

The outer glass safety panel to be installed during the initial installation after the unit is in the final position.
Note: The outer safety panel comes with plastic corners to protect these against damage. These should be kept in place until such time the outer safety panels are installed. Ensure these are removed prior to operating the appliance. Keep the plastic corners in a safe place if ever removing the outer panels for servicing.
1. Carefully remove glass safety panels from packaging. Press glass vacuum clamp in open position firmly onto surface of glass. Bring handles together to close.

Pins on body of unit

Open

Closed

Angle adjustment brackets

Note: If the outer safety glass panel does not sit at 90º and angles too far inward or outward, remove the glass panel and adjust the screw of the panel angle bracket. Turn the panel angle bracket screw in 1/4 increments–reinstall panel to check.

NOTE: Inner glass panel shown in image – depicting proper handling of glass.
2. Using the supplied vacuum clamps, lift the large front glass panel and position it front and centre by manoeuvering up and underneath the front of the unit frame.

Panel angle bracket–to adjust, turn screw:
Clockwise = bring panel in
Counter clockwise= bring panel out
CV40E-11 City Series | 19

owner’s information

Maintenance Instructions

1. Always turn off the gas valve before cleaning. For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacuuming at least once a year. When cleaning the logs, use a soft clean paint brush as the logs are fragile and easily damaged.

by having excessive lateral runs, too many elbows, and exterior portions of the system being exposed to cold weather.
4. Inspect joints, to verify that no pipe sections or fittings have been disturbed, and consequently loosened. Also check mechanical supports such as Wall Straps, or plumbers’ tape for rigidity.

2. Clean appliance and door with a damp cloth (never when unit is hot). Never use an abrasive cleaner. The glass should be cleaned with a gas fireplace glass cleaner. The glass should be cleaned when it starts looking cloudy.
3. The fireplace is finished in a heat resistant paint and should only be refinished with heat resistant paint. Regency® uses StoveBright Paint – Metallic Black #6309.

Log Replacement
The unit should never be used with broken logs. Turn off the gas valve and allow the unit to cool before opening door and carefully remove the logs. (The pilot light generates enough heat to burn someone.) If for any reason a log should need replacement, you must use the proper replacement log. The position of these logs must be as shown in the diagrams under Log Installation.

4. Make a periodic check of burner for proper position and condition. Visually check the flame of the burner periodically, making sure the flames are steady; not lifting or floating. If there is a problem, call a qualified service person.
5. The appliance and venting system must be inspected before use, and at least annually, by a qualified field service person, to ensure that the flow of combustion and ventilation air is not obstructed.
Note: Never operate the appliance without the glass properly secured in place.

Note: Improper positioning of logs may create carbon build-up and will severely alter the unit’s performance which is not covered under warranty.
Glass Gasket
If the glass gasket requires replacement use a tadpole glass gasket (Part

846-696).

Glass

6. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace nay part of the control system and any gas control which has been under water.
7. In the event this appliance has been serviced check that the vent-air system has been properly resealed & reinstalled in accordance with the manufacturer’s instructions.
8. Verify operation after servicing.

General Vent Maintenance

Conduct an inspection of the venting system semiannually. Recommended areas to inspect as follows:
1. Check the Venting System for corrosion in areas that are exposed to the elements. These will appear as rust spots or streaks, and in extreme cases, holes. These components should be replaced immediately.

Your Regency® fireplace is supplied with high temperature 5mm Tempered outer glass & 5mmCeramic inner glass. If your glass requires cleaning, we recommend using an approved glass cleaner available at all authorized dealers. Do not use abrasive materials.
CAUTION & WARNINGS:

  • Do not clean when the glass is hot. The use of substitute glass will void all
    product warranties.
    Care must be taken to avoid breakage of
    the glass.
  • Do not strike or abuse the glass. Do not operate this fireplace without the
    glass front or with a cracked or broken glass front.
    Wear gloves when removing damaged or broken glass. * Replacement of the glass panels should be done by a licensed or qualified service per son.

2. Remove the Cap, and shine a flashlight down the Vent. Remove any bird nests, or other foreign material.

3. Check for evidences of excessive condensation, such as water droplets forming in the inner liner, and subsequently dripping out the joints, Continuous condensation can cause corrosion of caps, pipe, and fittings. It may be caused

20 | CV40E-11 City Series

Glass Replacement

In the event that you break your glass by impact, purchase your replacement from an authorized Regency dealer only. Replacement glass is shipped already installed into the door frame. Reinstall as per Glass Installation in the “Glass Installation” section.
REPLACEMENT GLASS:
CV40E Outer Safety Glass- Tempered (Part# 940-435/P) Inner Glass – Ceramic (Part# 940-434/P)

MA Code – CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10

installer’sreiqnufoirremmaetinotns

(2) Revise 10.8.3 by adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1. Detailed instructions for the installation of the venting system design or the venting system components; and

2. A complete parts list for the venting system design or venting system.

(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipmentat the completion of the installation.
CV40E-11 City Series | 21

installer’s information

Locating Your Gas Fireplace

Unit Assembly Prior to Installation

1. When selecting a location for your fireplace, ensure that the clearances are met.
2. The appliance must be installed on a flat, solid, continuous surface For example a wood, metal or concrete floor or in a raised (on the wall) application. The appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.
3. The CV40E Direct Vent Gas Fireplace can be installed in a recessed position or framed out into the room as in A, B, C, D. See Diagram 1.

Before you start
The CV40E has 6 standoffs, 2 on each side and 2 at the back that need assembly before installation. WARNING! Risk of Fire! Comply with all minimum clearances.
Side and Back Standoff Assembly CV40E The standoffs are shipped in a flat position and must be folded into shape and attached. Take each standoff off the unit by removing one screw and bend into the correct shape. Slot the 2 tabs of the stand off into the slots in the unit and attach the other end with one screw.

A) Flat on Wall-CV40E

Standoff locations

CV40E

Diagram 1
B) Flat on Wall Corner-CV40E C) Recessed into Wall/Alcove-CV40E D) Corner- CV40E

Nailing Strips CV40E
Nailing strips are shipped folded flat against the unit. Fold nailing strips out 90º before installing unit. Secure nailing strips to framing using wood or metal screws.

4. For bedroom installations, check with local codes before installation. This appliance is offered with a remote control.
5. The CV40E Direct Vent Gas Fireplace is approved for alcove installations, see “Clearances” section for details.
6. We recommend that you plan your installation on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have an authorized inspector, dealer, or installer review your plans before installation.
Note: For vent terminations refer to “Exterior Vent Termination Locations” section.

Nailing strips

22 | CV40E-11 City Series

Levelling Bolts
There are four levelling bolts – two on each side that can be adjusted if required.

installer’sreiqnufoirremmaetinotns

Levelling bolts

Access Panel Removal The front access panel may be removed for ease of hooking up gas and electrical. Once complete ensure that the access panel is reinstalled prior to any finishing. The CV40E has 4 screws to remove access cover. See locations in diagrams to the right.
4 screws

CV40E-11 City Series | 23

installer’s information

General Safety Information
1. The appliance installation must conform with local codes or, in the absence of local codes, with the current Canadian or National Gas Codes, CSA B149.1 or ANSI Z223.1 Installation Codes.
2. See general construction and assembly instructions. The appliance and vent should be enclosed.
3. This appliance must be connected to the specified vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fitted as per Venting instructions.
4. Inspect the venting system annually for blockage and any signs of deterioration.
5. Venting terminals shall not be recessed into a wall or siding.
6. Any safety glass removed for servicing must be replaced prior to operating the appliance.
7. To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fireplace.
8. Wear gloves and safety glasses for protection while doing required maintenance.
9. Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination.
10. Under no circumstances should this appliance be modified. Parts that have to be removed for servicing should be replaced prior to operating this appliance.
11. Installation and any repairs to this appliance should be done by a qualified service person. A professional service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.
12. Do not slam shut or strike the glass door.
13. Under no circumstances should any solid fuels (wood, paper, cardboard, coal, etc.) be used in this appliance.
14. The appliance area must be kept clear and free of combustible materials, (gases and other flammable vapours and liquids).

Installation Checklist
1. Locate appliance. Refer to the following sections: a) Locating Your Fireplace b) Clearances c) Combustible Mantel Clearances d) Framing & Finishing e) Venting. See the “Venting Introduction” to “Venting Arrangements” sections.
2. Assemble Standoffs. Refer to the “Unit Assembly Prior to Installation” section. (NOTE: must be done before installing unit into fireplace.)
3. Install vent. See the “Horizontal Installations” to “Installation Procedures” sections.
4. Wire 120 volt AC power to the supplied receptacle box located on lower left hand side of appliance. The Duplex receptacle and receptacle cover are also included and will be located in the manual package. Note: This heater does not require 120 volt AC supply for operation of the burner but is highly recommended as a primary power source to eliminate the need for 4 AA batteries. Batteries should only be used as a secondary power source when power is lost within the home. 120 Volt AC power is also required for operation of the lights.
5. Install junction box supplied with appliance. Install remote battery box inside of junction box. Hook battery box to wire marked receiver. This will enable operation of the burner. If 120 Volt AC power was brought to appliance, batteries are not required.
Note: The wire harness (marked receiver) is located near the gas valve and will need to be routed to the exterior of the fireplace from either the left or right hand side of the appliance prior finishing.
6. Make gas connections. Test the pilot. Must be as per diagram. Refer to the “Gas Line Installation” & “Pilot Adjustment” sections.
7. Install standard and optional features. Refer to the following sections where applicable:
a. Safety Glass b. Firebox (inner) glass c. Log Set d. Fireglass e. Ceramic stones or other approved media f. Painted, enamel or glass panels (panels
required) g. Optional Framing Kit h. Heatwave Kit

Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly and operation fully explained to customer.
This includes:
1. Clocking the appliance to ensure the correct firing rate (rate noted on label 28,500 Btu/h NG/LP) after burning appliance for 15 minutes.
2. If required, adjusting the primary air to ensure that the flame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
Heatwave Duct System Optional kit
The HeatWave Air Duct Kit increases the effectiveness of your fireplace by dispersing warm air from the fireplace to remote locations in the same room or other rooms in your home.
Up to two kits may be installed on the fireplace.
Please Note: One adaptor kit #656-995 must be used with each 946-556.
The HeatWave Duct Kit has different clearance and framing requirements, check the HeatWave manual for details.
Note: If using the optional heat wave kit, this does not reduce the size of the ventilation opening The ventilation opening must be a minimum 120 square inches regardless.

8. Plug 3 prong plug for the lights into the receptacle. The 3 prong plug will be located near the gas valve on the appliance.

9. Final check.

! WARNING: Cancer and Reproductive Harm www.P65Warnings.ca.gov 919-874

24Part # -|919-8C74V40E-11 City Series

Description: Prop. 65 Short form label

Date:

May 30/18

Colour:

Black font on white

Size:

5″W x 0.7″H

Ventilation Openings
Regency’s patented Cool Wall system releases warmth at ceiling level. This system reduces excessive radiant heat in front of the fireplace so you can enjoy your fireplace more often. · Design your own chase vent solution to suit your home · Use optional front or left & right side chase vent grills · Release warmth into the room discreetly
Ventilation Opening Locations
The following are examples of how the ventilation openings may be placed above the fireplace. The air travelling through the heat exchanger is heated by the fireplace and then directed out the back of the fireplace. The combined warmed air is then vented back into the room.
If using the optional heat wave kit, this does not reduce the size of the ventilation opening. The ventilation opening(s) must be a minimum 120 square inches regardless.
Front Exit
The ventilation opening may be placed in front ensuring it meets the 120 square inch opening & is located 0-3″ (76mm) from the enclosure ceiling.

installer’sreiqnufoirremmaetinotns
Top Exit The ventilation opening may be short of the ceiling as shown below. Minimum opening height must be 1-1/2″ (38 mm) measured from top of enclosure to the ceiling and must be in open in front and both sides to meet the minimum 120 square inches free open air requirement.

SIde Exit (Left/Right)
Ventilation openings, when placed on both sides, must be of the same size. They must be have an equal split (50/50) free air opening to balance air flow. A ventilation opening may never be on one side only. The ventilation openings cannot be any smaller than 6″ (152mm) wide to equal the total area of 120 square inches of free open area. Example: 6″ (152mm) wide x 10″ (254 mm) High = 60 square inches per side of free open area. A second ventilation grill is installed on the other side to =100%.
The ventilation openings must be located 0-3″ from the enclosure ceiling.

The ventilation opening may be fully open at the top of the enclosure. This type of ventilation opening would be used when the top of the enclosure is not visible from above and where the ceiling within the room is higher than normal. When creating this type of ventilation opening, measures should be into place to avoid having objects of any type falling or be thrown into the ventilation opening. Mesh screen or other preventative measures should be put into place.

The ventilation opening may be placed on top ensuring it meets the 120 square inch opening. This type of ventilation opening would be used when the top of the enclosure is visible from above and where the ceiling within the room is higher than normal.

CV40E-11 City Series | 25

m

c

3

installer’s information

Chase Enclosure

(1073 mm)

When choosing to install the ventilation openings from the front or both sides, The top of the ventilation opening cannot be any lower than 0-3″ from the top of the chase enclosure for all installations. Minimum height of enclosure from base of appliance is 63″. A minimum 120in2 opening in the enclosure is required to maintain safe operating temperatures. This can be achieved in a number of ways including the examples shown in this manual.

IMPORTANT:

Exterior wall/Alcove enclosure: When installing into an exterior cavity or alcove enclosure (ceiling, back and sides), regardless of where appliance is

placed within the home, requires the use of either drywall or other means such as plywood, wood studs, etc. to prevent heat from escaping anywhere above

/Itnhtreorungahltchh(e1aes0nec2:loWmsuhrmeenoixnths1eta1rllt4ihnagmnatsmhaen)rienqtuerirneadl

grill / chase

ventilation opening. framing installation ,regardless

of

where

appliance

is

placed

within

the

home,

requires

the

use

of

either

drywall or other means such as plywood, on the rear wall of the chase to eliminate heat escaping into the rear wall cavity. If the chase is extended to the

ceiling ,the ceiling will also need to be finished in a manner to prevent heat escaping into floor joist/attic space.

One of the following methods must be used to prevent the heat from escaping. a. If choosing drywall, ensure that the drywall is butt up tight with no gaps. b. Plywood, wood studs, etc. installed tightly with no gaps.

As this appliance has been designed with all hot air escaping through the chase enclosure ventilation/grill openings only, if hot air is trapped as a result of the hot air escaping through joints, crevasses, open studs, or other openings within the enclosure above, this will change the clearances within the enclosure causing the enclosure to overheat. It is vital that all the hot air from within the enclosure exits through the ventilation openings only. Ensure that the ventilation openings are made as such to prevent debris, objects from falling into the enclosure. Warning: DO NOT cover or place objects in front of the ventilation opening air outlet(s).

Max 3″ (76 mm)

Stud

Top of chase enclosure
Ceiling

M40in”i(m1u0m161m20ms)qC. hinacsheoVpeennting

Stud

Max 3″ (76 mm)

Stud

Ceiling ToTpopofocfhcahsaeseenecnlocslousruere
M40in”im(1u0m161m20msq) .CihnachseoVpeennting

Stud

In the example above, the ceiling does not meet the requirement as it is higher than the specified minimum. Top of chase enclosure is sealed off to meet the 0-3 (76 mm) requirement.

26 | CV40E-11 City Series

installation

Clearances

The clearances listed below are minimum distances unless otherwise stated.
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

Clearance: Single Sided A: From Floor A1 : Mantel Height (min.) B: Sidewall (on one side) C: Enclosure Width (min.) D: Mantel Depth (max.) E: Alcove Width F: Alcove Depth

Dimension Min. 0″
8-1/2″ (216mm) 46-3/4″ (1187mm)
84″ (2134mm) 36″ (914mm)

Measured From: Bottom of Fireplace Opening Top of Fireplace Opening Side of Fireplace Opening Minimum inside dimensions
Side wall to side wall (min.) Front of Unit

Flue Clearances to Combustibles

Horizontal – Top

3″ (76mm)

Horizontal – Side

2″ (51mm)

Horizontal – Bottom

2″ (51mm)

Vertical

2″ (51mm)

Passing through wall/ floor/ceiling – when firestop is used.

1-1/2″ (38mm)

G: To Enclosure Ceiling (min/max)

0-3″ (0-76mm)

H: Convection Air outlet

120 sq. inches (min)

I: Enclosure Depth (min.)

19″ (483mm)

J: Opening Height

15-1/16″ (383mm)

K: To Ceiling (min) All 3 sides

1-1/2″ (38mm)

L: Chase Enclosure (min.)

63″ (1600mm)

M: Clearance to sprinkler head (Min.)

36″ (914mm)

Hearth

0″

** See mantel clearances chart in this manual

From top of enclosure * Top/front or side of enclosure Minimum inside dimensions Bottom/Top of Fireplace Opening To Top of Ceiling From base of unit/floor Perpendicular from chase grill No hearth required

  • A minimum of 120 square inches of open area, not lower than 3″ (76 mm) from top of enclosure, required for all installations — this can be achieved by having an open area in front, both sides, and/or above as shown in the four diagrams on the next page.

E F
Alcove
The HeatWave Duct Kit has different clearance and framing requirements, check the HeatWave manual for details.
Caution Requirements The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be recessed into combustible construction.

ML
Chase grill

Sprinkler

Side View

WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not adhered to. It is of greatest importance that this fireplace
and vent system be installed only in accordance with these instructions.
CV40E-11 City Series | 27

installation
Clearances
K H

I L
A1
A

C
D J B

Floor to ceiling with top ventilation opening

G H
I

L

A1

H

H

G

H

C D
J

B A

Low framing with ventilation opening in front/2 sides or top

G H
I
A1 L
A

H G
H
C D
J
B

G H

H G
H

L

I

A1

A

C D J
B

Full framing with low ventilation opening in front or 2 sides

Full framing with ventilation opening in front or 2 sides

Note: The ventilation opening may only be placed above, on both sides and in front as shown above. Ventilation grills can never be placed behind the appliance.
28 | CV40E-11 City Series

installation
Optional Flush Front Chase Vent Installation – Part #657-991 (White)
This optional flush front chase vent grill is designed so that only the grills are exposed. The 4 flanges in front which secure the chase vent grill to the stud work is covered by the drywall to give a seamless look.
Framed opening must be between 4″ (102 mm) and 4.5″ (114 mm) tall, and at least 42.25″(1073 mm) wide to accommodate the chase vent. The top of the chase vent opening must be 3″ or less from the top of the
chase enclosure.
Min 42.25″ (1073 mm)
Opening for vent 4″-4.5″
(102 mm x 114 mm)

3 (76 mm)

(1016 mm)

Finish edges of drywall

with trim or Finish edges ocf doryrwnall er

bead.

Edge finish with trim or corner bead.
Edge finish must not decrease

must not decrease opening area below 130in (3.25″ x 40″) or (83 mm x 1016 mm)

opening area below

130in (3.25” x 40”)

or (83mm x 106mm)

Drywall

Header Stud

3 (76 mm)

(1016 mm)

CV40E-11 City Series | 29

installation

Frame opening for vent (See Vent Framing Clearances Page)

Screw Chase vent to Framing

Use at least 3 sets of screws

to keep the vent flat against framing

Drywall

Frame wall with finishing material

If necessary, mark where the
chase vent is located before fixing drywall in place

Cut hole in finishing material around inside of chase vent. Finish edges around opening

30 | CV40E-11 City Series

installation
Optional Front Grill Installation – Part #656-991 (Black)
This optional grill meets the requirement of the 120 square inches required for the enclosure in all installations and is designed to keep the enclosure cool. In this application, both the flange and screws to secure the grills are exposed as this grill is designed to be installed after the finished facing has been placed on the wall. To install the front grill – frame an opening of 4-3/8” H x 39-1/8” W (111mmm H x 994mm W). The finished facing material should be attached and be the same size as the framed opening to eliminate gaps. Install the grill and secure in place with one screw on either side, installed from the front.

C A
B

DIMENSIONS
A 39-1/8” (994mm) B 4-3/8” (111mm) C Maximum 3” (76mm) from top of enclo-
sure.

Secure with screws from the front through the sides.

Optional Side Grill Installation – Part # 656-992 (Set of 2/Black)

These optional grills meet the requirement of the 120 square inches required for the enclosure in all installations and are designed to keep the enclosure cool. In this application, both the flange and screws to secure the grills are exposed as this grill is designed to be installed after the finished facing has been placed on the wall. To install the side grills – frame an opening of 8-5/16” H x 8-5/16” W (211mm H x 211mm W). The finished facing material should be attached and be the same size as the framed opening to eliminate gaps. Install the grill and secure in place with one screw on either side, installed from the front through the louvers. Repeat steps to install the second grill to the other side of the chase.

A

A

B

B

DIMENSIONS

C

C

A

Maximum 3” (76mm) from top of enclo-

sure.

B

8-5/16” (211mm)

C

8-5/16” (211mm)

Unit may not be exactly as shown, but the drawing dipicts the process.

Secure with screws through louvers to the sides.
CV40E-11 City Series | 31

installation
Mantel Clearances
Combustible mantel clearances from top of front facing are shown in the diagram on the right.

14 12 10 8 6 4 2 26

20

1/2″ (13 mm) Drywall, wood,

wood panel, etc.

10 12″ (305 mm)

0
To Bottom of Fireplace Opening 15-1/16″
(383 mm)

9″ (229 m) 5-1/8″ (130 mm)
Top of Fireplace Opening

Mantel Leg Clearances
Combustible mantel leg clearances as per diagram: CV40E
MANTEL LEG

12″ 7″ 4″ 2″

Allowable mantel leg projection

8-1/2″

32 | CV40E-11 City Series

Framing Dimensions

NOTE: Framing may be constructed of combustible material (ie. 2 x 4) and does not require steel studs.

Framing Dimensions A B
C

D E
F
G

Description
Framing Height Framing Width Framing Depth Minimum Height to Combustibles Corner Wall Depth Corner Facing Wall Width Vent Centerline Height

CV40E
37-3/8″ (949mm) 46-3/4″ (1187mm)
19″ (483mm) 63″(1600mm) 55″ (1396mm) 77-3/4″ (1974mm) 56-1/4″ (1429mm)

Note: A combined minimum of 120 square inches of open area is required for the convection air outlet to cool the enclosure. Ensure clearances for Convection Air Outlets are met. See clearances CV40E (single sided) in this manual as there are different methods as to how this can be achieved.

Maximum material dimensions 2″ x 4″ for wood studs in front. Studs behind and to the side can be either
2” x 4” or 2” x 6”.

installation

Note: Wood header on edge
may be 2” x 4” or 2” x 6”.

Note: This appliance must be installed on a solid surface such as a plywood floor which must be the full width and depth of the appliance.

  • The framing depth/width does not take into account dry wall/wood or similar materials against the back /side wall. The framing depth will need to change based on the thickness of the material (example: B – 46 3/4″ framing width +1/2″ drywall = 47 3/4″) (example: C – 19″ framing depth +1/2″ drywall = 19 1/2″)
    CV40E-11 City Series | 33

installation
Wall Board/Drywall Installation
WARNING! Risk of Fire! Comply with all minimum clearances to combustibles as specified.
Finishing Instructions It is important to follow the framing and finishing instructions to ensure proper placement of fireplace into the surrounding framing/finishing materials. Wall board materials 1/2 in. thick are specified in this installation manual to properly align with the optional finishing methods offered with this appliance. The CV40E may be finished to the appliance opening with 1/2 inch thick drywall. · Ensure that the back and side clearances are maintained.
WARNING! Risk of Fire! Maintain specified air space clearances to combustibles. Inadequate air space could cause overheating and fire.
DO NOT use screws more than 3/4 inch in length on the lower access cover panel. Longer screws may penetrate gas line or damage valve or electrical components. Note: It is acceptable to use a high temperature silicone sealant to adhere drywall to lower access cover panel.
The appliance is designed to be used with 1/2 in. wall sheathing materials such as drywall, plywood, wood composites, or non-combustible materials. Thicker materials may be used. Refer to facing and finishing details in this manual.
Facing Material · Facing and/or finishing materials must never overhang into the glass opening. · Facing materials may be combustible or non-combustible
WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum clearances. Comply with all minimum clearances to combustibles as specified in this manual. Overlapping materials could ignite and will interfere with proper operation.
PAINTING If desired finishing includes a painted wall, 100% acrylic latex, oil-based or standard acrylic paints may be used. Follow paint manufacturer’s instructions for paint and primer application.

[99mm]

7 8

3

[73mm]

7 8

2

1″ [25mm]

3″ [73mm] SCREWS ONLY IN SHADED AREA

3″ [76mm]

34 | CV40E-11 City Series

installation

Framing and Finishing Inset Installations
1. Frame in the enclosure for the unit with framing material.

Note: When constructing the framed opening ensure there is access to install the gas lines,electrical. Also the wiring harness must be wall mounted using the receptacle provided with the appliance. The wiring harness will be located on the right hand side of the appliance if facing the unit from the front. This must be done prior to any finishing.
2. For exterior walls, insulate the enclosure to the same degree as the rest of the house, apply vapour barrier and drywall, as per local installation codes. (Do not insulate the fireplace itself).

**Combustible material

Do not place any materials where glass is located

WARNING: Failure to insulate and add vapor barriers to the inside of the exterior wall will result in operational and performance problems including, but not limited to: excessive condensation on glass doors, poor flame package, carbon, blue flames etc. These are not product related issues.
Note that in all applications while there is a zero clearance to combustibles to the unit, all clearances to combustibles from the venting inside the chase still applies. Please see venting clearances in the specific product manual.

**Combustible material

3. IMPORTANT:
Exterior wall/Alcove enclosure: When installing into an exterior cavity or alcove enclosure (ceiling, back and sides), regardless of where appliance is placed within the home, requires the use of either drywall or other means such as plywood, wood studs, etc. to prevent heat from escaping anywhere above /though the enclosure other than the required grill/ ventilation openings.
Internal chase: When installing as an internal chase framing installation, regardless of where appliance is placed within the home, requires the use of either drywall or other means such as plywood, on the rear wall of the chase to eliminate heat escaping into the rear wall cavity. If the chase is extended to the ceiling ,the ceiling will also need to be finished in a manner to prevent heat escaping into floor joist/attic space. One of the following methods must be used to prevent the heat from escaping :
a. If choosing drywall, ensure that the drywall is butt up tight with no gaps. b. Plywood, wood studs, etc. installed tightly with no gaps. As this appliance has been designed with all hot air escaping through the chase enclosure ventilation / grill openings only, if hot air is trapped as a result of the hot air escaping through joints, crevasses, open studs, or other openings within the enclosure above, this will change the clearances within the enclosure causing the enclosure to overheat. It is vital that all the hot air from within the enclosure exits through the ventilation openings only. Ensure that the ventilation openings are made as such to prevent debris, objects from falling into the enclosure.
4. Combustible material (drywall,wood, wood panels, etc.) may be brought up to the appliance (top,bottom and sides).

Drywall guide
Diagram 1 – Loosen 4 screws and lift off lower drywall guide
Note: an offset screwdriver is provided with the appliance for ease of removal/installation.

5. Ensure that the material being used does not encroach anywhere in the area of the glass. This would cause dangerous operating conditions.

6. This appliance comes with a 1/2″ lip at top and bottom to hide the ends of the drywall. The 1/2″ side and bottom lip supplied with the appliance can alternatively be removed (see Diagram 1) and replaced with J Style Trim or Metal Corner Bead purchased at your local hardware store to cover cut/ exposed edges of the combustible facing material or any other finishing materials being used. 4 screws secure the bottom lip — see Diagram 1. These will be hidden so the outer panels will need to be removed to access the screws. See outer panel removal in this manual.

CV40E-11 City Series | 35

installation

TVCBR4e0 TcyepsicsaleIndstainllsto Wall

CB40 Typical Installs

Maximum TV Recess

TV Flush with Hearth

MAXIMUM TV RECESS MAFXLIUMSUHMTTVVWRIETCHEHSESARTHFLUSH TV WITH HEARTH

Max 3″ (76 mm)
To Top of Enclosure

TMo TaopxTMoo3fTa”Eonx(pc73loo6f”sEum(nr7ecm6losm)urem)

Max 3″ (76 mm)
To Top of Enclosure

120in2 min
Chase vent opening

Cha1s2eC0vhiean1ns22etm0ovipeinnne2ntmionpignening

120in2 min
Chase vent opening

Max 4 5/8″ (117 mm)
TV recess with drywall up against unit Max. 2 x 4 stud
Max 5 1/8″ (130 mm)
Mantle
Max 36″ (914 mm)
Hearth

12″ min (305 mm) 17.5″(445 mm) min
(includes 1/2″ drywall) 12″ min (305 mm)
17.5″(445 mm) min (includes 1/2″ drywall)

Max 4 5/8″ (117 mm)
TV recess with drywall up againMstauxn.it2 x 4 stud Max. 2 x 4 stud Header Stud

MaMxan5tle1/p8″eSn(c1eret3rwa0stemmumunsi)tt

not more

than 1/2″ (13 mm).

Adhere to “No Screw”

zones painted on unit.

Max 36″
Hearth

(Ga9slu1ae4ncamalntmebrn)eautisveed.

Max. 2 x 4 stud
Header Stud Screws must not
penetrate unit more than 1/2″ (13 mm). Adhere to “No Screw” zones painted on unit. Glue can be used
as an alternative.

4 5/8″ (117 mm) maximum TV recess using 1/2″ (13 mm) drywall CB40E shown

4 5/8″ (117 mFlumsh) mwaaxllimTVurmecTeVssruecseinsgs 1/2″ (13 mm) drywall Flush wall TV recess using 1/2″ (13 mm) drywall using 1/2″ (13 mm) drywall CB40E shown

36 | CV40E-11 City Series

Exterior Vent Termination Locations

installation

Minimum Clearance Requirements
A Clearance above grade, veranda, porch, deck, or balcony
B Clearance to window or door that may be opened C Clearance to permanently closed window D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61cm)
from the center line of the terminal (check with the local code)

Canada1 12″(30cm) 12″(30cm)

  • 18″(46cm)

USA2 12″(30cm) 9″ (23cm)

  • 18″(46cm)

E Clearance to unventilated soffit F Clearance to outside corner: with AstroCap Termination Cap.
Clearance to outside corner: with all other approved Termination Caps. G Clearance to inside corner: with AstroCap Termination Cap
Clearance to inside corner: with all other approved Termination Caps. H Clearance to each side of center line extended above meter/regulator assembly J Clearance to service regulator vent outlet K Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance L Clearance to a mechanical air supply inlet

3′ (91cm) above if within 10′ (3m) horizontally.

20″(51cm) 6″(15cm) 14″(36cm) 6″(15cm) 12″(30cm) 36″(90cm)a 36″(90cm) 12″(30cm) 72″(1.8m)

20″(51cm) 6″(15cm) 14″(36cm) 6″(12cm) 12″(30cm)

    • 9″ (23cm) 36″(90cm)b

M Clearance above paved sidewalk or a paved driveway located on public property

84″(2.1m)

N Clearance under veranda, porch, deck, or balcony

12″(30cm)

1 In accordance with current CSA B149.1, Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings

Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor

  • a

Clearance in accordance with local 3 feet (91cm) within a height of 15

installation codes and the requirements of the gas feet (4.5m) above the meter / regulator assembly

supplier

b 3 feet (91cm) above – if within 10 feet (3m) horizontally

CV40E-11 City Series | 37

installation

4″ x 6-5/8″ Rigid Pipe Cross Reference Chart
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI. Note: Olympia Ventis DV is only approved for certain models. See list of approved models in cross-reference chart.

Description

Simpson Direct Vent Pro®

*Selkirk Direct TempTM

*American Metal Products® Amerivent Direct

*Metal-FabTM Sure Seal

*Security Secure- Vent®

*ICC Excel Direct

Olympia Ventis DV

6″ Pipe Length-Galvanized

46DVA-06

4DT-6

N/A

4D6

SV4L6

TC-4DL6

VDV-0406

6″ Pipe Length-Black

46DVA-06B

4DT-6B

N/A

4D6B

SV4LB6

TC-4DL6B

VDVB-0406

7″ Pipe Length-Galvanized

N/A

N/A

4D7

N/A

N/A

N/A

N/A

7″ Pipe Length-Black

N/A

N/A

4D7B

N/A

N/A

N/A

N/A

9″ Pipe Length-Galvanized

46DVA-09

4DT-9

N/A

N/A

N/A

TC-4DL9

VDV-0409

9″ Pipe Length-Black

46DVA-09B

4DT-9B

N/A

N/A

N/A

TC-4DL9B

VDVB-0409

12″ Pipe Length-Galvanized

46DVA-12

4DT-12

4D12

4D12

SV4L12

TC-4DL1

VDV-0412

12″ Pipe Length-Black

46DVA-12B

4DT-12B

4D12B

4D12B

SV4LB12

TC-4DL1B

VDVB-0412

18″ Pipe Length-Galvanized

46DVA-18

4DT-18

4D18

4D18

SV4LA

TC-4DL18

VDV-0418

18″ Pipe Length-Black

46DVA-18B

4DT-18B

4D18B

4D18B

SV4LA

TC-4DL18B

VDVB-0418

24″ Pipe Length-Galvanized

46DVA-24

4DT-24

4D24

4D24

SV4L24

TC-4DL2

VDV-0424

24″ Pipe Length-Black

46DVA-24B

4DT-24B

4D24B

4D24B

SV4LB24

TC-4DL2B

VDVB-0424

36″ Pipe Length-Galvanized

46DVA-36

4DT-36

4D36

4D36

SV4L36

TC-4DL3

VDV-0436

36″ Pipe Length-Black

46DVA-36B

4DT-36B

4D36B

4D36B

SV4LB36

TC-4DL3B

VDVCB-0436

48″ Pipe Length-Galvanized

46DVA-48

4DT-48

4D48

4D48

SV4L48

TC-4DL4

VDV-0448

48″ Pipe Length-Black

46DVA-48B

4DT-48B

4D48B

4D48B

SV4LB48

TC-4DL4B

VDVB-0448

60″ Pipe Length-Galvanized

46DVA-60

4DT-60

N/A

N/A

N/A

N/A

N/A

60″ Pipe Length-Black

46DVA-60B

4DT-60B

N/A

N/A

N/A

N/A

N/A

Adjustable Length 3″-10″-Galvanized N/A

N/A

Adjustable Length 3″-10″-Black

N/A

N/A

Adjustable Length 7″-Galvanized

N/A

N/A

Adjustable Length 7″-Black

N/A

N/A

Extension Pipe 8-1/2″-Galvanized

46DVA-08A

N/A

Extension Pipe 8-1/2″-Black

46DVA-08AB

N/A

Adjustable Length 12″-Galvanized N/A

N/A

Adjustable Length 12″-Black

N/A

N/A

Extension Pipe 16″-Galvanized

46DVA-16A

N/A

Extension Pipe 16″-Black

46DVA-16AB

N/A

N/A N/A 4D7A 4D7AB N/A N/A 4D12A 4D12A N/A N/A

4DAL 4DALB N/A N/A N/A N/A N/A N/A N/A N/A

N/A

TC-4DLT

N/A

N/A

TC-4DLTB

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

SV4LA12

TC-4dLSI

N/A

SV4LBA12

TC-4dLSIB

N/A

N/A

N/A

N/A

N/A

N/A

N/A

45º Elbow-Galvanized 45º Elbow-Black 45º Elbow Swivel-Galvanized 45º Elbow Swivel-Black 90º Elbow-Galvanized 90º Elbow-Black 90º Elbow, Swivel-Galvanized 90º Elbow, Swivel-Black 90º Starter Elbow, Swivel-Galvanized Adaptor*

46DVA-E45 46DVA-E45B See 46DVA-E45 See 46DVA-E45B 46DVA-E90 46DVA-E90B See 46DVA-E90 See 46DVA-E90B N/A N/A

4DT-EL45 4DT-EL45B N/A N/A 4DT-EL90S 4DT-EL90SB N/A N/A N/A N/A

4D45L 4DT-EL45B N/A N/A 4DT-EL90S 4DT-EL90SB N/A N/A N/A N/A

Ceiling Support

N/A

Cathedral Support Box

46DVA-CS

Wall Support/Band

46DVA-WS

Offset Support

46DVA-ES

Wall Thimble-Black

46DVA-WT

Wall Thimble Cover/Ceiling Support 46DVA-DC

Firestop Spacer

46DVA-FS

Trim Plate-Black

N/A

  • Not available from Regency

38 | CV40E-11 City Series

4DT-CS 4DT-CSS 4DT-WS/B 4DT-OS 4DT-WT N/A 4DT-FS 4DT-TP

4DSP 4DRSB 4DWS N/A 4DWT N/A 4DFSP 4DFPB

N/A N/A 4D45L 4D45LB N/A N/A 4D90L 4D90LB 4D90A 4D90L
4DFSP 4DRS 4DWS N/A 4DWT N/A 4DFS 4DcP

N/A N/A SV4E45 SV4EB45 N/A SV4EBR90-1 SV4E90-1 SV4EB90-1 N/A N/A
SV4SD SV4CSB SV4BM SV4SU SV4RSM SV4PF SV4BF SV4LA

TE-4DE45 TE-4DE45B N/A N/A TE-4DE90 TE-4DE90B N/A N/A N/A N/A
TM4-RDS TM4-SDS TM-SWS TM-SOS N/A N/A TM-4CS TM-4TP

VDV-EL0445 VDVB-EL0445 N/A N/A VDV-EL0445 VDVB-EL0445 N/A N/A N/A VDV-UAA04
VDV-SCR04 VDV-CSS04 VDV-WS04 N/A VDV-WPT04 N/A VDV-FS04 VDV-WTC04

installation

Description

Simpson Direct Vent Pro®

Attic Insulation Shield 12″

46DVA-IS

Attic Insulation Shield – Cold Climates 36″ 46DVA-KHA

*Selkirk Direct TempTM
N/A N/A

*American Metal Products® Amerivent Direct
4DAIS12
4DAIS12

*Metal-FabTM Sure Seal
DDIS N/A

*Security Secure- Vent®
SV4RSA N/A

*ICC Excel Direct

Olympia Ventis DV

N/A TM-4AS

VDV-AIS04 N/A

Basic Horizontal Termination Kit (A) N/A

Horizontal Termination Kit (B)

N/A

Vertical Termination Kit

N/A

4DT-HKA 4DT-HKB 4DT-VKC

4DHTK2 4DHTK1 4DHTK

4DHTKA 4DHTKB 4DHTK

SV-SHK SV-HK SV-FK

TM4-HTK TM4-HTK N/A

VDV-KW04 VDV-K04 N/A

High Wind Vertical Cap High Wind Horizontal Cap
Horizontal Square Termination Cap Vertical Termination Cap Storm Collar

46DVA-VCH N/A
46DVA-HC 46DVA-VC 46DVA-SC

N/A N/A
4DT-HHC 4DT-HVC 4DT-SC

N/A N/A
4DHC 4DVC 4DSC

N/A N/A
4DHT 4DVT 4DSC

N/A N/A
SV4CHC-1 SV4CGV-1 SV4FC

TM-4VT TM-4DHT
TM-4HT N/A TM-SC

VDV-VCHW04 N/A
VDV-HC04 N/A VDV-SC04

Flashing – Flat Roof Adjustable Flashing 0/12-6/12 Adjustable Flashing 6/12-12/12
Vinyl Siding Standoff Vinyl Siding Shield Plate
Snorkel Termination 14″ Snorkel Termination 36″

46DVA-FF 46DVA-F6 46DVA-F12
46DVA-VSS N/A
46DVA-SNK14 N/A

N/A 4DT-ST14 4DT-ST36
4DT-VS 4DT-VSP
N/A N/A

N/A 4D12S 4D36S
N/A N/A
N/A N/A

N/A 4DF 4DF12
4DVS N/A
N/A N/A

N/A SV4STC14 SV4STC36
SV4VS SV4VS
N/A N/A

N/A TF-4FA TF-4FB
TM-VSS N/A
TM-4ST14 TM-4ST36

N/A VDV-F0406 VDV-SSO
N/A N/A
N/A N/A

Wall Firestop

46DVA-WFS

N/A

N/A

  • Not available from Regency

N/A

N/A

TM-4TR

VDV-FS04

FPI 946-506/P **510-994 640-530/P

Vent Guard (Optional) for AstroCap Rigid Pipe Adaptor (Must use with all rigid piping) Riser Vent Terminal

946-205 946-208/P 946-523/P 946-206

Vinyl Siding Shield for Riser Vent Terminal Vent Guard (Optional) for Riser Vent Terminal AstroCap Horizontal Cap Vinyl Siding Standoff for AstroCap

Note: When using Metal-Fab Sure Seal Rigid Piping – please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).

Offset Pipe Selection: Use this table to determine offset pipe lengths.

Pipe Length (L)

4″ x 6-5/8″ Venting

Run (X)

Rise (Y)

0″ (0mm)

4-7/8″ (124mm)

13-7/8″ (340mm)

6″ (152mm)

8″ (203mm)

16-1/2″ (419mm)

9″ (229mm)

10-1/8″ (257mm)

18-5/8″ (473mm)

12″ (305mm)

12-1/4″ (311mm)

20-3/4″ (527mm)

24″ (610mm)

20-5/8″ (524mm)

29-1/8″ (740mm)

36″ (914mm)

29″ (737mm)

37-1/2″ (953mm)

48″ (1219mm)

37-7/16″ (951mm)

45-15/16″ (1167mm)

For specific instructions on venting components – visit the manufacturers website listed below.
Simpson Direct Vent Pro: www.duravent.com Selkirk Direct-Temp: www.selkirkcorp.com American Metal Products: www.americanmetalproducts.com Metal-Fab Sure Seal: www.mtlfab.com Security Secure Vent: www.securitychimneys.com Industrial Chimney Company: www.icc-rsf.com Olympia Ventis DV: www.olympiachimney.com

Note: Horizontal runs of vent must be level, or have a 1/4″ rise for every 1 foot of run towards the termination. Never allow the vent to run downward – this could cause high temperatures and may present a possible fire hazard.

CV40E-11 City Series | 39

installation
Vent Restrictor Position
Vent restriction is required for certain venting installations, see the diagrams in the “Venting Arrangements” section to determine if they are required for your installation. The Vent Restrictor plate is packed in the instruction manual package. To set the vent restriction as indicated in the venting arrangements diagrams, refer to the following instructions; 1. Remove the safety glass and firebox glass – see instructions in this manual. 2. Remove the screws that hold the vent restrictor plate in place (see Diagram 1) 3. Adjust the vent restrictor plate to the required vent restrictor position as per the diagrams shown. 4. Once the vent restrictor plate is in the required position, secure with screws.
Vent Restrictor Positions
Set 0 (Full open) Factory set

Screw locations

Set 1 (Vent restrictor at 2″)

Vent restrictor location – inside top of firebox
Diagram 1

Set 2 (Vent restrictor at 1.75″) Set 3 (Vent restrictor at 1.5″) 40 | CV40E-11 City Series

installation
Venting Introduction
The CV40E uses the “balanced flue” technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney. Note: These flue pipes must not be connected to any other appliance. The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it’s own separate vent system. Common vent systems are prohibited.
Venting Arrangement for Horizontal Terminations (Rigid/Flex Pipe)
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o (two 45o elbows equal one 90o elbow). Note: Must use optional rigid pipe adapter (Part# 510-994) when using Rigid Pipe Venting Systems.
56-1/4″ (1429mm)
VENT RESTRICTOR SETTING: Vent restrictor factory set at Set 0. Refer to the “Vent Restrictor Position” section for details on how to change the vent restrictor from the factory setting of Set 0 to Set 2 if required. Note: For horizontal terminations the Regency Direct Vent Flex System may be used for installations with a maximum
continuous vent length of up to 10 feet. If longer runs are required, rigid pipe must be used. · Maintain clearances to combustibles as listed in “Clearances” section · Horizontal vent must be supported every 3 feet. · Firestops are required at each floor level and whenever passing through a wall. · A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes. · Flex system can only be used up to 10 feet – otherwise rigid venting must be used.
CV40E-11 City Series | 41

installation

Horizontal Termination – 4″ X 6-5/8″ Venting (Flex Vent Systems)

Minimum Vent Clearances to Combustibles

  • Clearances noted below must be maintained; except when passing through a wall, ceiling or at the termination where the use of a firestop or wall thimble reduces clearance to 1″ (25mm).

Horizontal Top* Horizontal Side Horizontal Bottom Vertical Vent

3″ (76mm)* 2 ” (51mm) 2″ (51mm) 2″ (51mm)

Below are the recommended framing dimensions (inside measurements) for the 4″ x 6-5/8″ rigid vent terminations – for use with a firestop or wall thimble.

Recommended Framed Opening Size

Vent Size

Framing Size

4″ x 6 – 5/8″ 10″ x 10″

1. Locate the unit in the framing, rough in the gas (preferably on the right side of the unit). Locate the centerline of the termination and mark wall accordingly. Cut an square hole in the wall – see chart (inside dimension).
Note: If installing termination on a siding covered wall, a vinyl siding standoff or vinyl furring strips must be used to ensure that the termination is not recessed into the siding.

Outside Wall

Furring Strips
2. Level the fireplace and fasten it to the framing using nails or screws through the nailing strips.
3. Assemble the vent assembly by applying Mill Pac to the inner flue collar of the termination and slipping the inner flex liner over it at least 1-3/8″ (35mm). Fasten with the 3 screws (drilling pilot holes will make this easier). Apply Mill-Pac to the outer flex pipe and slip it over the outer flue collar of the vent terminal at least 1-3/8″(35mm) and fasten with the 3 screws.

NOTE: Horizontal sections must be supported at intervals not exceeding 3 feet (0.9 meter). (Flame picture and performance will be affected by sags in the liner).

ASTROCAP DIMENSIONS (946-523/P)

4. Separate the 2 halves of the wall thimble and securely fasten the one with the tabs to the outside wall making sure that the tabs are on top and bottom. Fasten the other thimble half to the inside wall. The thimble halves slip inside each other and can be adjusted for 2 x 4 or 2 x 6 walls.
5. Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up (there are markings on the cap indicating which way is up). This will position the termination cap with proper down slope for draining water. Fasten the cap to the outer wall with the 4 supplied screws.
6. Pull the centre inner and outer flex liner out enough to slip over the flue collars of the fireplace. (You may wish to cut the liner shorter to make it more workable.) Do not bend liner more than 90o. The liners must slip over the collars a minimum of 1-3/8″.

11″ (294mm)

11″ (294mm)
of hole CL

56-1/4″ (1429mm) Min.

7. Apply Mill Pac over the fireplace inner flue collar and slip the inner flex liner down over it and attach with 3 supplied screws.

8. Do the same with the outer flue collar and outer flex liner.
9. Apply a bead of silicone between the thimble and termination and around the outer edge of the terminal at the wall in order to keep the water out.

NOTE: A minimum of 1′ (305mm) vertical off the top of the unit is required before any horizontal runs can start.

IMPORTANT: Do not locate termination hood where excessive snow or ice buildup may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.

2″ x 4″ or 2″ x 6″

Screws (3 per connection)

4″ (102mm) dia. flue pipe with spring spacer

Termination Cap

6-7/8″ (173mm) dia. air intake
Wall Thimble 2 pieces (10″ (254mm)
Outer Diameter)

Screws (4 per connection)

42 | CV40E-11 City Series

installation
Horizontal Terminations – Flex Vent 4″ x 6-7/8″
These venting systems, in combination with the CV40E/CB40E Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by Warnock Hersey/ Intertek. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in “Exterior Vent Termination Locations” section.
Regency® Direct Vent (Flex) System Termination Kits include all the parts needed to install the CV40E/CB40E using a flexible vent.

FPI Kit # Length Contains:

946-513 2 Feet #946-515 4 Feet #946-516 10 Feet

1. 6-7/8″ flexible outer liner (Kit length) 2. 4″ flexible inner liner (Kit length) 3. spring spacers 4. thimble 5. AstroCap termination cap
6. screws 7. tube of Mill Pac 8. plated screws 9. S.S. screws #8 x 1-1/2″ drill point

Notes:
1. Liner sections should be continuous without any joints or seams.
2. Only Flex pipe purchased from Regency® may be used for Flex installations
3. Horizontal vent must be supported every 3 feet.
4. Regency® Direct Vent System (Flex) is only approved for horizontal terminations.
5. Flex system can only be used up to a maximum continuous vent length of up to 10 feet. If longer runs are required, rigid pipe must be used.

CV40E-11 City Series | 43

installation
Horizontal Terminations – Rigid Pipe 4″ x 6-5/8″
The minimum components required for a basic horizontal termination are:
1 Horizontal Termination Cap 1 Rigid Pipe Adaptor (510-994) 1 Wall Thimble 1 Length of pipe to suit wall thickness
(see chart)
Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap. For siding other than vinyl furring strips may be used, instead of the vinyl siding standoff, to create a level surface to mount the vent terminal. The Terminal must not be recessed into siding. Measure the wall thickness including furring strips.
If a Vinyl Siding Standoff is required (it must be used with vinyl siding), measure to outside surface of wall without siding and add 2 inches.

Flat Wall Installation

Wall Thickness (inches)
4″ – 5-1/2″ 7″ – 8-1/2″ 10″ – 11-1/2″ 9″ – 14-1/2′ 15″ – 23-1/2″

Vent Length Required (inches) 6″ 9″ 12″
11″ – 14-5/8″ Adj. Pipe 17″ – 24″ Adj. Pipe

Horizontal Termination Cap Vinyl Siding Standoff (Optional)
Wall Thimble Adj.Pipe Length 90o Elbow
Pipe Length Rigid Pipe Adapter

WARNING:
Do not combine venting components from different venting systems.
Use of the the AstroCapTM and FPI Riser is acceptable with all systems.

This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with Duravent Direct-Vent, Selkirk Direct-Temp, Ameri Vent Direct Venting, ICC Excel Direct, Olympia Chimney and Security Secure Vent systems. Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not
affect the Intertek WHI listing of components.

When using Rigid Vent other than Simpson Dura-Vent, 3 screws must be used to secure rigid pipe to adaptor.

The FPI AstroCapTM and FPI Riser Vent terminal are certified for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent, American Metal Products Ameri Vent Direct Vent, Security Secure Vent®, ICC Excel, Selkirk Direct-Temp and Olympia Chimney. AstroCapTM is a proprietary trademark
of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.

44 | CV40E-11 City Series

installation
Horizontal Terminations – Rigid/Flex Pipe 4″ x 6-5/8″
The diagrams below shows examples of horizontal termination arrangements using one, two, or three 90o elbows (two 45o elbows equal one 90o elbow)
1. A maximum of three 90o elbows are permitted.
2. Minimum distance between elbows is 1 ft. (305mm).
· Maintain clearances to combustibles as listed in the “Clearances” section. · Horizontal vent must be supported every 3 feet. · Firestops are required at each floor level and whenever passing through a wall. · Must use optional rigid pipe adaptor (Part# 510-994) when using rigid pipe vent systems. · A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes. · Flex system can only be used up to 10 feet – otherwise rigid venting must be used.

Horizontal Venting with Two (2) 90o Elbows

One 90o elbow = Two 45o elbows.

Option V

H + H1

A) 1′ Min. 2′ Max.

B) 2′ Min. 4′ Max.

C) 3′ Min. 5′ Max.

D) 4′ Min. 6′ Max.

E) 5′ Min. 7′ Max.

F)

6′ Min. 8′ Max.

Restrictor Set 0 – Factory Setting

With these options, maximum total pipe length is 30 feet with minimum of 6 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.

Horizontal Venting with Three (3) 90o Elbows

One 90o elbow = Two 45o elbows.

Option V

H V + V1

A) 1′ Min. 1′ Max. 2′ Min.

B) 1′ Min. 2′ Max. 3′ Min.

C) 2′ Min. 2′ Max. 5′ Min.

D) 3′ Min. 2′ Max. 7′ Min.

E) 4′ Min. 3 Max. 9′ Min.

F) 5′ Min. 4′ Max. 10′ Min.

G) 6′ Min. 5′ Max. 11′ Min.

H) 7′ Min. 6′ Max. 12′ Min.

Restrictor Set 0 – Factory Setting

H + H1 2′ Max. 3′ Max. 4′ Max. 5′ Max. 6′ Max. 7′ Max. 8′ Max. 9′ Max.

With these options, max. total pipe length is 30 feet with min. of 12 feet total vertical and max. 9 feet total horizontal.
Please note min. 1 foot between 90o elbows is required.

CV40E-11 City Series | 45

installation

DuraVent Horizontal
Terminations
Install the vent system according to the manufacturer’s instructions included with the components.

  1. Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the unit. Rough in the gas preferably on the right side of the unit and the electrical (junction block is on the left side) on the left.
  2. Direct Vent pipe and fittings are designed with special twist-lock connections to connect the venting system to the appliance flue outlet. A twist-lock appliance adaptor is an available option that must be used in conjunction with the Simpson Dura-Vent Direct Vent system.
  3. Put a bead of Mill-Pac inside the outer section of the adapter and on the inner collar. Slip the adapter over the existing inner and outer flue collar and fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier). Level the fireplace and fasten it to the framing using nails or screws through the nailing strips.
  4. Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.
    Note: a) Twist-lock procedure: Four indentations, located on the female ends of pipes and fittings, are designed to slide straight onto the male ends of adjacent pipes and fittings, by orienting the four pipe indentations so they match and slide in to the four entry slots on the male ends, Diagram 1. Push the pipe sections completely together, then twistlock one section clockwise approximately one-quarter turn, until the two sections are fully locked. The female locking lugs will not be visible from the outside, on the Black Pipe or fittings. They may be located by examining the inside of the female ends.

b) Horizontal runs of vent must be supported every three feet. Wall straps are available for this purpose.
5) Mark the wall for a 10″ x 10″ square hole. The center of the square hole should line up with the centerline of the horizontal pipe. Cut and frame the 10 inch square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of non-combustible material, i.e. masonry block or concrete, a 7″(178mm) dia. (7-1/2″(191mm) dia. for flex) hole is acceptable.
Diagram 2
Note: a) The horizontal run of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fire.
b) The location of the horizontal vent termination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. For External Vent Terminal Locations, see the “Exterior Vent Termination Locations” section.
c) Snorkel Terminations: For installations requiring a vertical rise on the exterior of the building, 14-inch and 36inch tall Snorkel Terminations are available, as well as the standard Riser Vent. Follow the same installation procedures as used for standard Horizontal Termination. NEVER install the snorkel upside down.

56-1/4″ (1429mm)

Note: Riser Vent is only for use in above grade terminations.
Diagram 3a
*Diagrams 3 & 4: As specified in CSA B149.1 Installation Code. Local codes or regulations may require different clearances.
Below Grade Installation If the Snorkel Termination must be installed below grade, i.e. basement application, proper drainage must be provided to prevent water from entering the Snorkel Termination. Refer to Diagram 4. Do not attempt to enclose the Snorkel within the wall, or any other type of enclosure.

Diagram 4

Diagram 1
NOTE: For best results and optimum performance with each approved venting system, it is highly recommended to apply “Mill-Pac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty.

NOTE: For Snorkel terminations in ABOVE grade installations, follow national or local code requirements.
6) The arrow on the vent cap should be pointing up. Insure that the 1-1/2″ clearances to combustible materials are maintained (Diagram 4). Install the termination cap. The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.

46 | CV40E-11 City Series

installation
Venting Arrangement for Vertical Terminations – Straight Vertical Venting and/or with a Max. of Two (2) 90o Elbows (1 – 90o = 2 – 45o)

The shaded area in the diagram shows all allowable combinations
of straight vertical and offset to vertical terminations, using two 90o elbows, with Rigid Pipe Venting Systems.

Two 45o elbows equal to one 90o elbow.

· Vent must be supported at offsets.

40

· Minimum distance between elbows is 1 ft. (305mm).

38

· Maintain clearances to combustibles as listed in the

“Clearances” section.

36

· Horizontal vent must be supported every 3 feet.
34
· Firestops are required at each floor level and whenever passing through a wall.
32
· Must use optional rigid pipe adaptor (Part# 510-994) when using rigid pipe vent systems.
30
· Refer to the “Vent Restrictor Position” section for details on how to change the vent restrictor from the factory setting 28 of Set 0 through to Set 3 if required.

26

0

Horizontal (Feet)

2

4

6

8

10

12

14

16

18

20

Maximum: 37 ft. (11.2m)

Vent Restrictor on Set 3

24

22

Vertical Height (Feet)
Maximum: 27 ft. (8.2m)

20

Vent Restrictor on Set 2

18

16

14

12
Vent Restrictor on Set 1 10

Min. 56-1/4″ (1429mm)
Minimum 8’6″ (2.6m)

8

  • 6

4

2

0
*Minimum length of pipe between elbows 12″ (305mm)

CV40E-11 City Series | 47

installation

Vertical terminations – Rigid Pipe 4″ x 6-5/8″

The minimum components required for a basic vertical termination are:
1 Vertical Termination Cap 1 Rigid Pipe Adaptor (510-994) 1 Ceiling Firestop 1 Flashing 1 Storm Collar 1 Length of pipe to suit wall thickness
(see chart)
Galvanized pipe is desirable above the roofline due to its higher corrosion resistance. Continue to add pipe sections through the flashing until the height of the vent cap meets the minimum height requirements specified in table below or local codes. Note that for steep roof pitches, the vertical height must be increased. A poor draft, or down drafting can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the vent height may solve the problem.

Roof Pitch

Minimum Vent Height

Feet

flat to 7/12

2

over 7/12 to 8/12 2

over 8/12 to 9/12 2

over 9/12 to 10/12 2.5

over 10/12 to 11/12 3.25

over 11/12 to 12/12 4

over 12/12 to 14/12 5

over 14/12 to 16/12 6

over 16/12 to 18/12 7

over 18/12 to 20/12 7.5

over 20/12 to 21/12 8

Meters 0.61 0.61 0.61 0.76 0.99 1.22 1.52 1.83 2.13 2.29 2.44

Vertical Terminal Storm Collar Flashing Ceiling Firestop
Pipe Length Rigid Pipe Adapter

WARNING:
Do not combine venting components from different venting systems.
Use of the the AstroCapTM and FPI Riser is acceptable with all systems. This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with Duravent Direct-Vent, Selkirk Direct-Temp, Ameri Vent Direct Venting, ICC Excel Direct, Olympia Chimney, and Security Secure Vent systems. Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not affect the Intertek WHI listing of components.

When using Rigid Vent other than Simpson Dura-Vent, 3 screws must be used to secure rigid pipe to adaptor.

The FPI AstroCapTM and FPI Riser Vent terminal are certified for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent, American Metal Products Ameri Vent Direct Vent, Security Secure Vent®, ICC Excel, Selkirk Direct-Temp and Olympia Chimney. AstroCapTM is a proprietary trademark
of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.

48 | CV40E-11 City Series

Vertical Terminations – Rigid Pipe 4″ x 6-5/8″

· Two 45o elbows equal to one 90o elbow. Maximum of six 45o elbows allowed. · Vent must be supported at offsets. · Minimum distance between elbows is 1 ft. (305mm). · Maintain clearances to combustibles as listed in the “Clearances” section. · Horizontal vent must be supported every 3 feet. · Firestops are required at each floor level and whenever passing through a wall. · Must use optional rigid pipe adaptor (Part# 510-994) when using rigid pipe vent systems

Vertical Venting with Three (3) 90o Elbows

One 90o elbow = Two 45o elbows.

Option
A) B) C) D)

V
1′ Min. 2′ Min. 3′ Min. 4′ Min.

H + H1 2′ Max 3′ Max 4′ Max 5′ Max

V + V1 3′ Min. 4′ Min. 6′ Min. 7′ Min.

With these options, max. total pipe length is 30 feet with min. of 10 feet total vertical and max. 8 feet total horizontal.

E)

5′ Min. 6′ Max 8′ Min.

F)

6′ Min. 7′ Max 9′ Min.

G) 7′ Min. 8′ Max 10′ Min.

Lengths do not include elbow

indicated

Please note min. 1 foot between 90o elbows is required.

Restrictor Set 0 – Factory Setting

V1 H1

installation

H

V

CV40E-11 City Series | 49

installation

DuraVent Vertical Termination – 4″ X 6-5/8″ Venting (Rigid Vent Systems)

4. Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow connections are in the fully twist-locked position and sealed.

1. Maintain the 1-1/2″ clearances (air spaces) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafter, or other nearby combustible surfaces. Do not pack air spaces with insulation. Check “Venting” Sections for the maximum vertical rise of the venting system and the maximum horizontal offset limitations.
2. Set the gas appliance in its desired location. Drop a plumb bob down from the ceiling to the position of the appliance flue exit, and mark the location where the vent will penetrate the ceiling. Drill a small hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where the vent will penetrate the roof.
3. A Firestop spacer must be installed in the floor or ceiling of every level. To install the Firestop spacer in a flat ceiling or wall, Diagram 1 cut a 10 inch square hole. Frame the hole as shown in Diagram 2 and install the firestop.
Note: All vertical terminations are vented using 4″ x 6-5/8″ venting and rigid pipe adaptor #510-994.

Diagram 4

NOTE: For best results and optimum performance with each approved venting system, it is highly recommended to apply “Mill-Pac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty.
5. Cut a hole in the roof centered on the small drilled hole placed in the roof in Step 2. The hole should be of sufficient size to meet the minimum requirements for clearance to combustibles of 1-1/2″. Slip the flashing under the shingles (shingles should overlap half the flashing) as per Diagram 3.

Roof Pitch

Minimum Vent Height

Feet

flat to 7/12

2

over 7/12 to 8/12 2

over 8/12 to 9/12 2

over 9/12 to 10/12 2.5

over 10/12 to 11/12 3.25

over 11/12 to 12/12 4

Meters 0.61 0.61 0.61 0.76 0.99 1.22

over 12/12 to 14/12 5

1.52

over 14/12 to 16/12 6

1.83

over 16/12 to 18/12 7

2.13

over 18/12 to 20/12 7.5

2.29

over 20/12 to 21/12 8

2.44

7. Ensure vent is vertical and secure the base of the flashing to the roof with roofing rails, slide storm collar over the pipe section and seal with a mastic.

Diagram 3
Diagram 3: The upper half of the flashing is installed under the roofing material and not nailed down until the chimney is installed. This allows for small
adjustments.
6. Continue to assemble pipe lengths.

8. Install the vertical termination cap by twistlocking it.
Note: Any closets or storage spaces, which the vent passes through must be enclosed.

Diagram 2
50 | CV40E-11 City Series

Note: If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3 feet, to avoid excessive stress on the elbows, and possible separation. Wall straps are
available for this purpose.
Galvanized pipe is desirable above the roofline due to its higher corrosion resistance. Continue to add pipe sections through the flashing until the height of the vent cap meets the minimum height requirements specified in Dia. 4 or local codes. Note that for steep roof pitches, the vert

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals