nVent RAYCHEM RayClic-LE Lighted End Seal Kit Instruction Manual

June 10, 2024
nVent RAYCHEM

RayClic Connection System
RayClic-LE Lighted End Seal Kit Installation Instructions

APPROVALS

| 718K Pipe Heating Cable
---|---
| 877Z De-Icing and Snow Melting
| Not UL Listed with XL-Trace Edge
heating cable for buried piping
| For HWAT and IceStop only
Hazardous Locations: For IceStop (GM-XT) only
Class I, Div. 2, Groups A, B, C, D

KIT CONTENTS

Item Qty Description
A 1 Lighted end seal
B 1 Pipe mounting bracket
C 2 Plastic cable ties
D 1 Clip
E 1 Cable lubricant

nVent RAYCHEM RayClic-LE Lighted End Seal Kit - KIT
CONTENTS

WARNING:
This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully  follow all the installation instructions.

  • To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of nVent, agency certifications, and national electrical codes, ground fault equipment protection must be used. Arcing may not be stopped by conventional circuit breakers.
  • Bus wires will short if they contact each other. Keep bus wires separated.
  • Keep components and heating cable ends dry before and during installation.
  • The black heating cable core is conductive and can short. It must be properly insulated and kept dry.
  • Component approvals and performance are based on the use of nVent-specified parts only. Do not use substitute parts or vinyl electrical tape.
  • Leave these instructions with end user for reference and future use.

If you experience difficulty during installation, refer to the “Troubleshooting Guide” on page 5.

Lighted End Seal Installation

nVent RAYCHEM RayClic-LE Lighted End Seal Kit - Installation
1nVent RAYCHEM RayClic-LE Lighted End
Seal Kit - Installation 2nVent
RAYCHEM RayClic-LE Lighted End Seal Kit - Installation 3

Roof Installation

nVent RAYCHEM RayClic-LE Lighted End Seal Kit - Roof 1

Troubleshooting Guide

PROBLEM SOLUTION
Braid clips are missing. The braid clips are attached to the cardboard

packing insert under the lid. The braid clips must be  used to ensure a ground connection. If clips are missing or lost, call nVent at (800) 545‑6258.
Mounting bracket is missing.| A pipe mounting bracket is supplied with the Power Connection, Powered Splice, Powered Tee and  Lighted End Seal kits. A wall mounting bracket or additional pipe mounting bracket may be  ordered using one of the catalog numbers listed under “Optional Accessories” on the front page of  these instructions when you place your order.
Connector does not snap onto bracket.| The bracket has two sets of attachment clips. Fold up the four outer clips for the Power  Connection and Lighted End Seal kit. Fold up only the center clips for the Powered Splice and
Powered Tee kits.
Heating cable type not mentioned.| nVent RAYCHEM RayClic connection kits are approved for use only with HWAT, XL-Trace Edge, and IceStop heating cables. Do not use with other heating cables.
Braid clip does not fit.| Be sure the clip is installed on the metal braid, not on the outer jacket.
Heating cable does not have aluminum wrap.| Only HWAT heating cables have the aluminum wrap under the braid. Skip the aluminum wrap  removal step for XL- Trace Edge and IceStop heating cables.
Heating cable cannot be inserted into connector.| Check for the following:
• Apply lubricant to heating cable primary (white) jacket.
• Outer jacket strip length is 3 1/8 inches.
• Braid clip is installed on top of the metal braid, not on the outer jacket.
• Braid is pulled back over braid clip.
• For HWAT, 1 inch of braid is removed.
• Sealing nut is loose (but not removed).
• Connection screws are loose.
Lid does not close.| Be sure all screws are fully tightened before closing the lid.
Heating cable cannot be removed.| The power connection and end seal are designed to be installed only once; the heating cable cannot be removed once installed.
Additional nVent RAYCHEM RayClic-E and RayClic-LE end seals can be ordered from nVent.
Light does not come on.| • Verify there is voltage present.
• Verify the cable guide is screwed down completely.
• If the light still does not function, the RayClic-LE cannot be repaired and must be replaced.

nVent RAYCHEM RayClic-LE Lighted End Seal Kit - Roof 2

North America
Tel +1.800.545.6258
Fax +1.800.527.5703
thermal.info@nVent.com| Europe, Middle East, Africa
Tel +32.16.213.511
Fax +32.16.213.604
thermal.info@nVent.com
---|---
Asia Pacific
Tel +86.21.2412.1688
Fax +86.21.5426.3167
cn.thermal.info@nVent.com| Latin America
Tel +1.713.868.4800
Fax +1.713.868.2333
thermal.info@nVent.com

©2021 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.
RAYCHEM-IM-H53514-FTCP-EN-2111
nVent.com/RAYCHEM