MEAN WELL DLP-04 Series DALI Bus Power Supply Owner’s Manual

June 15, 2024
MEAN WELL

MEAN WELL DLP-04 Series DALI Bus Power Supply

MEAN-WELL-DLP-04-Series-DALI-Bus-Power-Supply-PRODUCT

Features

  • Compact size with 2SU(35mm) width(type R)
  • Universal AC input / Full range
  • Withstand 300VAC Surge input for 5 seconds
  • Isolation class I|
  • No load power consumption<0.5W(type L)
  • Protections: Short circuit / Over voltage
  • Cooling by free air convection
  • 3-color LED for status indicator (type R)
  • Installed on DIN rail TS-35/7.5 or 15(type R)
  • 100% full load burn-in test
  • 3 years warranty

Description

  • The DALI Power Supply DLP-04 is a power supply with high efficiency and small size, supplying 240mA for
  • DALI control gears and DALI devices without power supply circuits. The -20~+60°C wide temperature operating range can meet all kinds of applications.
  • It is perfectly suitable for powering up any products labeled with the DALI trademark. with over 35 years of industrial power supply experience, DLP-04 is engineered to be a reliable and safe solution for the DALI bus environment.

Order Name Encoding

SPECIFICATION

MODEL DLP04R DLP04L









OUTPUT

| RATED DC VOLTAGE| 16V
DC VOLTAGE RANGE| 15.3~18.7V
RATED CURRENT| 240mA
GUARANTEED SUPPLY CURRENT| 240mA
MAXIMUM SUPPLY CURRENT| 250mA
RATED POWER| 3.84W
RIPPLE & NOISE **(max.)Note.2| 50mVp-p
SETUP, RISE TIME| 250ms, 50ms/115VAC,230VAC
HOLD UP TIME (Typ.)**| 70ms/230VAC         16ms/115VAC at full load






INPUT

| VOLTAGE RANGE| 90 ~ 264VAC         120 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
AC CURRENT (Typ.)| 0.1A/115VAC         0.06A/230VAC; Model label: 0.4A/100-240VAC
INRUSH CURRENT (Typ.)| COLD START 20A/230VAC
LEAKAGE CURRENT| 0.5mA / 240VAC
NO LOAD POWER CONSUMPTION| Typ. 0.5W| <0.5W



PROTECTION

| SHORT CIRCUIT| Protection type : Constant current limiting, recovers automatically after fault condition is removed


OVER VOLTAGE

| 23.6 ~ 27V
Protection type : Shut off o/p voltage, clamping by zener diode



FUNCTION

| ****


LED DISPLAY

| Green LED: Normal operation| None
Yellow LED: Bus Communication| None
Red LED: Bus short detection| None




ENVIRONMENT

| WORKING TEMP.| -20 ~ +60℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6




SAFETY & EMC

(Note 3)

| SAFETY STANDARDS| BS EN/EN61347-1, BS EN/EN61347-2-11, EAC TP TC 004 approved
DALI STANDARDS| Compliance to IEC62386-101
WITHSTAND VOLTAGE| I/P-O/P:3KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55015, BS EN/EN61547, BS EN/EN61000-3-2,-3, EAC TP TC 020


EMC IMMUNITY

| Compliance to BS EN/EN61000-4-2, 3, 4, 5, 6, 8, 11, BS EN/EN55024, BS EN/EN61000-6-2, BS EN/EN61204-3,

light industry level, EAC TP TC 020



OTHERS

| MTBF| 7018.6K hrs min.     Telcordia SR-332 (Bellcore) ;        625.5K hrs min.      MIL-HDBK-217F (25℃)
DIMENSION| 359054.5mm (WHD)| 1453822mm(LWH)
PACKING| 0.087Kg;96 pcs/9.5Kg/1.04CUFT| 0.084Kg; 60pcs/6Kg/0.48CUFT
NOTE| 1.  All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

3.  The power supply is considered a component that will be installed into the final equipment. The final equipment must be re-confirmed that it still meets EMC directives.

Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

MEAN-WELL-DLP-04-Series-DALI-Bus-Power-Supply-FIG-3

Derating Curve

MEAN-WELL-DLP-04-Series-DALI-Bus-Power-Supply-FIG-4

Output Derating VS Input Voltage

Mechanical Specification

MEAN-WELL-DLP-04-Series-DALI-Bus-Power-Supply-FIG-6

Terminal Pin No. Assignment

Pin No. Assignment Pin No. Assignment
1 DA- 3 AC/L
2 DA+ 4 AC/N

MEAN-WELL-DLP-04-Series-DALI-Bus-Power-Supply-FIG-8

Terminal Pin No. Assignment (TB3) : SWITCHLAB MWX201-75002EB(GRAY)

Pin No. Assignment
1 AC/N
2 AC/L

Terminal Pin No. Assignment (TB4) : SWITCHLAB MWX201-75002B(BLUE)

Pin No. Assignment
1 DA-
2 DA+

Installation Manual

MEAN-WELL-DLP-04-Series-DALI-Bus-Power-Supply-FIG-9 Cautions

  • Central DALI power supply rated at 240mA(DALI standard allows max.250mA).
  • The control interface of a DALI ballast normally sources <2mA, with 64 individual addresses this will source 128mA.

The remaining 112mA can be used to power other DALI controls without an internal power supply such as the DALI GC and DALI SC.

  • DALI signals are not SELV. Therefore the same procedures should be applied as working with mains voltage.
  • Individual DALI circuits must not exceed 240mA.
  • The maximum cable length of the DALI signal wires must not exceed 300m or drop more than 2V on the signal line voltage.

GC and DALI SC

  • DALI signals are not SELV. Therefore the same procedures should be applied as working with mains voltage.
  • Individual DALI circuits must not exceed 240mA.
  • The maximum cable length of the DALI signal wires must not exceed 300m or drop more than 2V on the signal line voltage.

System start-up timing

  1. After external power-on, the timing of a bus power supply shall be as shown in Table 1.
  2. A receiver shall be ready to receive frames within the maximum receiver start-up time specified in Table 1.
  3. A transmitter or a multi-master transmitter shall not start transmissions earlier than the transmitter start-up time specified in Table 1.

Table 1 – Start-up timing

  Minimum Typical Maximum Condition
Bus power supply start-up time     250ms ****

Guaranteed supply current reached

Advanced bus power supply start-up time|  |  | 400ms


Integrated bus power supply start-up time

|  |  | 400msa
 |  | 5s b
Receiver start-up time for externally powered bus units, after the external power cycle|  |  | 450ms e|
Receiver start-up time for externally powered bus units, after bus power down| |  | 100ms| ****




d

U=10V

Receiver start-up time after bus power down for bus-powered bus units|  |  | 1200ms
Transmitter start-up time| 110ms c|  |
Multi-master transmitter start-up time| 110ms|  |
a Applicable if other bus power supplies are allowed in the system

b Applicable if no other bus power supplies are allowed in the system.

c Not applicable for transmitters of bus units that cannot determine the bus state. d Idle state, bus voltage measured at the interface of the bus unit.

e If an external power cycle occurs and the bus power is not available within 350 ms, the 100 ms timing is applicable.

Shows an example of the system start-up timing

MEAN-WELL-DLP-04-Series-DALI-Bus-Power-Supply-FIG-10

  • External power cycle
  • Latest bus power supply start-up
  • Earliest transmitter start-up
  • Latest receiver start-up for externally powered unit
  • Latest receiver start-up for bus-powered unit
  • Bus power down